• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
1 ats eim cne nUEt oVs BCry N oS - mo Q idVD nRl X IVFS
1-1
Specifications TECHNICAL SPECIFICATIONS
Capacity
1 1
Power Input (50Hz)
FXDQ40NBVE
FXDQ50NBVE
FXDQ63NBVE
7.1
Cooling
kW
4.5
5.6
Heating
kW
5.0
6.3
8.0
Cooling
kW
0.160
0.165
0.181
Heating
kW
0.147
0.152
0.168
Power Input (60Hz)
Cooling
kW
0.182
0.185
0.192
Heating
kW
0.168
0.170
0.179
Casing
Material
Dimensions
Unit
Galvanised steel plate Height
mm
200
200
200
Width
mm
900
900
1,100
mm
620
620
620
kg
27
28
31
3
3
3
Depth Weight
Unit
Heat Exchanger
Dimensions
Nr of Rows Fin Pitch
mm
1.5
1.5
1.5
Face Area
m²
0.176
0.176
0.227
12
12
Nr of Stages Fan
Type
Air Flow Rate
Cooling
Fan
12
Sirocco fan High high m³/min
10.5
12.5
16.5
High
m³/min
9.5
11.0
14.5
Low
m³/min
8.5
10.0
13.0
External static pressure
High
Pa
44
44
44
Standard
Pa
15
15
15
Motor
Output (high)
W
62
130
130
Sound Pressure
High high dBA
34
35
36
High
dBA
32
33
34
Low
dBA
30
31
32
Drive Cooling
Piping connections
Direct drive
Liquid (OD)
Type
Flare connection
Gas
Type Diameter
mm
Drain
Diameter
mm
Diameter
mm
6.35
6.35
12.7
Sound absorbing insulation Air Filter
12.7 VP20 (I.D. 20/O.D. 26) Foamed polyethylene Removable/washable/Mildew proof
Refrigerant control
Electronic expansion valve
Temperature control
Microprocessor thermostat for cooling and heating
Safety devices
Fuse Fan motor thermal protector
Standard Accessories
Standard Accessories
Operation manual Installation manual Drain hose Sealing pads Clamps Washer Insulation for fitting Clamp metal Washer fixing plate Screws for duct flanges Air filter Product Quality Certificate
1
9.52
Flare connection
• VRV Systems • Indoor Units
15.9
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
1 1-1
Specifications TECHNICAL SPECIFICATIONS
Notes
FXDQ40NBVE
FXDQ50NBVE
FXDQ63NBVE
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19×CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7,5m (horizontal) Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m (horizontal) Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. External static pressure is changeable to set by the remote control; this pressure means : high static pressure standard static pressure.
3 1 1
The operation sound levels are conversion values in anechoic chamber. In practice, sound levels tend to be higher than the specified values due to ambient noise or reflection. When the suction place is changed to bottom suction, sound level will increase
1-2 ELECTRICAL SPECIFICATIONS (50HZ) Power Supply
FXDQ40NBVE
Name
Voltage range
FXDQ63NBVE
VE
Phase
Current
FXDQ50NBVE
1~
Frequency
Hz
Voltage
V
Minimum circuit amps (MCA)
A
50
50
50
220-240 1.0
1.0
1.1
Maximum fuse amps (MFA) A
15
15
15
Full load amps (FLA)
A
0.8
0.8
0.9
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage range variation between phases is 2%. MCA/MFA : MCA = 1.25 x FLA MFA is smaller than or equal to 4 x FLA Next lower standard fuse rating minimum 15A Select wire size based on the MCA Instead of a fuse, use a circuit breaker
1-3 ELECTRICAL SPECIFICATIONS (60HZ) Power Supply
FXDQ40NBVE
Name
Voltage range Notes
FXDQ63NBVE
VE
Phase
Current
FXDQ50NBVE
1~
Frequency
Hz
60
60
60
Voltage
V
220
220
220
Minimum circuit amps (MCA)
A
1.1
1.3
1.4
Maximum fuse amps (MFA) A
15
15
15
Full load amps (FLA)
A
0.9
1.0
1.1
Minimum
V
-10%
Maximum
V
+10% Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage range variation between phases is 2%. MCA/MFA : MCA = 1.25 x FLA MFA is smaller than or equal to 4 x FLA Next lower standard fuse rating minimum 15A Select wire size based on the MCA Instead of a fuse, use a circuit breaker
• VRV Systems • Indoor Units
2
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
2
Safety device settings
FXDQ20,25,32PB FXDQ40,50,63NB
1 2
3
Kit name
FXDQ20PB
FXDQ25PB
PC boad (A1P) fuse
FXDQ32PB
FXDQ40NB
FXDQ50NB
FXDQ63NB
250V 5A OFF: 250V 5A 5°C OFF ON: 83 15°C ON
Fan motor thermal protector
4D060926
• VRV Systems • Indoor Units
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
3
Options
3
FXDQ20,25,32PB FXDQ40,50,63NB
1
Individual control systems FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE
Kit name Wired remote control
FXDQ40NBVE FXDQ50NBVE BRC1D52
H/P
BRC4C65
C/O
BRC4C66
Simplified remote control
BRC2C51
Remote control for hotel use
BRC3A61
Infrared remote control
3
FXDQ63NBVE
Centralized control system FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE
Kit name
FXDQ40NBVE FXDQ50NBVE
Central remote control
DCS302CA51
Unified on/off control
DCS301BA51
Schedule timer
DST301BA51
FXDQ63NBVE
Other options FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE
Kit name
FXDQ40NBVE FXDQ50NBVE
Adapter for wiring
KRP1B56
Wiring adapter for electrical appendices (1)
KRP2A53
Wiring adapter for electrical appendices (2)
KRP4A54
Remote sensor
KRCS01-1B
Installation box for adapter PCB. Electrical box with earth terminal
FXDQ63NBVE
KBP1BA101
2 blocks
KJB212AA
3 blocks
KJB311AA
Noise filter (for electromagnetic interface use only)
DST301BA51
External control adapter for outdoor unit (must be installed on indoor units)
DTA104A53
Insulation kit for high humidity
KDT25N32
KDT25N50
KDT25N63
4D060939
• VRV Systems • Indoor Units
4
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
4
Capacity tables
4-1
Cooling capacity tables
FXDQ40,50,63NB TC: Total capacity;kW – SHC: Sensible capacity;kW
1 4
Unit size 40
50
63
Outdoor Nominal air temp. capacity °CDB 4.5 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0 5.6 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0 7.1 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0
14.0WB 20.0DB TC SHC 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8
16.0WB 23.0DB TC SHC 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3
18.0WB 26.0DB TC SHC 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8
Indoor air temperature 19.0WB 27.0DB TC SHC 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9
20.0WB 28.0DB TC SHC 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.7 3.2 4.7 3.2 4.6 3.2 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 5.9 4.0 5.8 4.0 5.7 3.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.5 4.8 7.4 4.8 7.2 4.7
22.0WB 30.0DB TC SHC 5.4 3.3 5.4 3.3 5.4 3.3 5.4 3.3 5.4 3.3 5.4 3.3 5.4 3.3 5.3 3.3 5.2 3.3 5.2 3.2 5.1 3.2 5.0 3.2 4.9 3.2 4.9 3.1 4.8 3.1 4.7 3.1 6.7 4.2 6.7 4.2 6.7 4.2 6.7 4.2 6.7 4.2 6.7 4.2 6.7 4.2 6.6 4.2 6.5 4.1 6.4 4.1 6.3 4.0 6.2 4.0 6.1 4.0 6.0 3.9 5.9 3.9 5.8 3.9 8.5 5.1 8.5 5.1 8.5 5.1 8.5 5.1 8.5 5.1 8.5 5.1 8.5 5.1 8.4 5.1 8.3 5.0 8.1 5.0 8.0 4.9 7.9 4.9 7.8 4.8 7.7 4.8 7.5 4.7 7.4 4.7
24.0WB 32.0DB TC SHC 5.9 3.5 5.8 3.5 5.8 3.5 5.7 3.5 5.6 3.4 5.5 3.4 5.5 3.4 5.4 3.3 5.3 3.3 5.3 3.3 5.2 3.3 5.1 3.2 5.0 3.2 5.0 3.2 4.9 3.1 4.8 3.1 7.4 4.1 7.3 4.1 7.2 4.1 7.1 4.0 7.0 4.0 6.9 4.0 6.8 4.0 6.7 3.9 6.6 3.9 6.6 3.9 6.5 3.8 6.4 3.8 6.3 3.8 6.2 3.7 6.1 3.7 6.0 3.7 9.3 5.7 9.2 5.6 9.1 5.5 9.0 5.4 8.8 5.4 8.7 5.3 8.7 5.3 8.5 5.2 8.4 5.1 8.3 5.1 8.2 5.0 8.1 4.9 7.9 4.9 7.8 4.8 7.7 4.8 7.6 4.7 ED39226A
5
• VRV Systems • Indoor Units
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
4
Capacity tables
4-2
Heating capacity tables
3
FXDQ40,50,63NB
Unit Size
Nominal capacity
40
5.0
50
6.3
63
8.0
Outdoor air temperature °CDB °CWB -19.8 -20.0 -18.8 -19.0 -16.7 -17.0 -14.7 -15.0 -12.6 -13.0 -10.5 -11.0 -9.5 -10.0 -8.5 -9.1 -7.0 -7.6 -5.0 -5.6 -3.0 -3.7 0.0 -0.7 3.0 2.2 5.0 4.1 7.0 6.0 9.0 7.9 11.0 9.8 13.0 11.8 15.0 13.7 -19.8 -20.0 -18.8 -19.0 -16.7 -17.0 -14.7 -15.0 -12.6 -13.0 -10.5 -11.0 -9.5 -10.0 -8.5 -9.1 -7.0 -7.6 -5.0 -5.6 -3.0 -3.7 0.0 -0.7 3.0 2.2 5.0 4.1 7.0 6.0 9.0 7.9 11.0 9.8 13.0 11.8 15.0 13.7 -19.8 -20.0 -18.8 -19.0 -16.7 -17.0 -14.7 -15.0 -12.6 -13.0 -10.5 -11.0 -9.5 -10.0 -8.5 -9.1 -7.0 -7.6 -5.0 -5.6 -3.0 -3.7 0.0 -0.7 3.0 2.2 5.0 4.1 7.0 6.0 9.0 7.9 11.0 9.8 13.0 11.8 15.0 13.7
16.0 kW 3.0 3.0 3.2 3.4 3.6 3.7 3.8 3.9 4.0 4.2 4.4 4.7 4.9 5.1 5.2 5.4 5.6 5.6 5.6 3.7 3.8 4.1 4.3 4.5 4.7 4.8 4.9 5.1 5.3 5.5 5.9 6.2 6.4 6.6 6.8 7.0 7.1 7.1 4.7 4.9 5.1 5.4 5.7 6.0 6.1 6.3 6.5 6.8 7.0 7.5 7.9 8.1 8.4 8.7 8.9 9.0 9.0
18.0 kW 2.9 3.0 3.2 3.4 3.6 3.7 3.8 3.9 4.0 4.2 4.4 4.6 4.9 5.1 5.2 5.3 5.3 5.3 5.3 3.7 3.8 4.0 4.3 4.5 4.7 4.8 4.9 5.1 5.3 5.5 5.9 6.2 6.4 6.6 6.7 6.7 6.7 6.7 4.7 4.9 5.1 5.4 5.7 6.0 6.1 6.3 6.5 6.7 7.0 7.4 7.8 8.1 8.4 8.5 8.5 8.5 8.5
Indoor air temperature °CDB 20.0 21.0 kW kW 2.9 2.9 3.0 3.0 3.2 3.2 3.4 3.4 3.6 3.5 3.7 3.7 3.8 3.8 3.9 3.9 4.0 4.0 4.2 4.2 4.4 4.4 4.6 4.6 4.9 4.8 5.0 4.8 5.0 4.8 5.0 4.8 5.0 4.8 5.0 4.8 5.0 4.8 3.7 3.7 3.8 3.8 4.0 4.0 4.3 4.2 4.5 4.5 4.7 4.7 4.8 4.8 4.9 4.9 5.1 5.1 5.3 5.3 5.5 5.5 5.8 5.8 6.2 6.1 6.3 6.1 6.3 6.1 6.3 6.1 6.3 6.1 6.3 6.1 6.3 6.1 4.7 4.7 4.8 4.8 5.1 5.1 5.4 5.4 5.7 5.7 6.0 6.0 6.1 6.1 6.2 6.2 6.4 6.4 6.7 6.7 7.0 7.0 7.4 7.4 7.8 7.7 8.0 7.7 8.0 7.7 8.0 7.7 8.0 7.7 8.0 7.7 8.0 7.7
22.0 kW 2.9 3.0 3.2 3.4 3.5 3.7 3.8 3.9 4.0 4.2 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 3.7 3.8 4.0 4.2 4.5 4.7 4.8 4.9 5.1 5.3 5.5 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 4.7 4.8 5.1 5.4 5.7 6.0 6.1 6.2 6.4 6.7 7.0 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5
24.0 kW 2.9 3.0 3.2 3.4 3.5 3.7 3.8 3.9 4.0 4.2 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.7 3.8 4.0 4.2 4.5 4.7 4.8 4.9 5.1 5.3 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.7 4.8 5.1 5.4 5.7 5.9 6.1 6.2 6.4 6.7 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
1 4
ED39226A
• VRV Systems • Indoor Units
6
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing
FXDQ40,50NB
300
50 or more
20 or more
900
500 (Suspension bolt pitch)
620
5
620
300 or more (Service space)
900
20 or more
300 or more (Service space of installation box for adaptor PCB)
20 or more
1
Ceiling A (Service space)
300
20-M5 Holes (All around)
100 160 180
50 170
100 23
30 33
18 - M4 Holes (All around)
Allow view A Inspection door (Ceiling opening) 50 20 10
63
47 90
90
Adjustable (0~600)
130
200 170 153 80
90
880 860 4 x P150 = 600
550
300 or less
Suspension bolt 4 - M8 ~ M10 12.5 21 57.5
60
(All around) 22 - Ø 4.7 hole 8 x P100 = 800 940 (Suspension bolt pitch)
280 330
150 100 90 80
7 x P100 = 700 780 800 820 (In case of back-suction)
Nr 1 2 3 4 5 6 7 8 9 10 11
200 180 160 100
20 - M5 Holes (All around)
10 20 50
7 x P100 = 700 780 800 820 (In case of bottom-suction)
130 100 90 80
Part name Liquid pipe connection port Gas pipe connection port Drain pipe connection port Drain hose (Accessory) Control box Transmission wiring connection Power supply connection Suspension bracket Inspection door Socket for drain Air filter (Accessory)
Description ø 6.4 Flare connection ø 12.7 Flare connection IVP20 (O.D. ø 26 / I.D. ø 20) I.D. ø 25 (Outlet)
NOTES
1
2 3
In case of back-suction, mount chamber cover to bottom side of the unit. In case of bottom-suction, mount chamber cover to back side of the unit. Location of unit’s name plate: control box cover. Mount the air filter at the suction side. (Select its color (gravity method) 50% or more). It can not be equipped with air filter (accessory) when connecting duct to suction side. 3D045494B
FXDQ63NB 300 or more (Service space) 50 or more
900
20 or more
20 or more
620
300
620
500 (Suspension bolt pitch)
1100
20 or more
300 or more (Service space of installation box for adaptor PCB)
Ceiling A
300
280 330
100 160 180
50 170
100 23
30 33
18 - M4 Holes (All around)
Allow view A Inspection door (Ceiling opening)
20-M5 Holes (All around)
50 20 10
63
47 90
130
Adjustable (0~600)
550
300 or less 1080 1060 6 x P150 = 900
200 170 153 80
12.5 21 57.5
Suspension bolt 4 - M8 ~ M10
(Service space)
60
(All around) 26 - Ø 4.7 hole 10 x P100 = 1000 1140 (Suspension bolt pitch)
150 100 90 80
9 x P100 = 900 980 1000 1020 (In case of back-suction)
10 20 50
200 180 160 100
20 - M5 Holes (All around)
9 x P100 = 900 980 1000 1020 (In case of bottom-suction)
130 100 90 80
Nr 1 2 3 4 5 6 7 8 9 10 11
Part name Liquid pipe connection port Gas pipe connection port Drain pipe connection port Drain hose (Accessory) Control box Transmission wiring connection Power supply connection Suspension bracket Inspection door Socket for drain Air filter (Accessory)
Description ø 6.4 Flare connection ø 12.7 Flare connection VP20 (O.D. ø 26 / I.D. ø 20) I.D. ø 25 (Outlet)
NOTES
1
2 3
In case of back-suction, mount chamber cover to bottom side of the unit. In case of bottom-suction, mount chamber cover to back side of the unit. Location of unit’s name plate: control box cover. Mount the air filter at the suction side. (Select its color (gravity method) 50% or more). It can not be equipped with air filter (accessory) when connecting duct to suction side. 3D045496C
7
• VRV Systems • Indoor Units
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
5
Dimensional drawing & centre of gravity
5-2
Centre of gravity
3
FXDQ40,50NB
1 5
4D043886J
FXDQ63NB
4D043887H
• VRV Systems • Indoor Units
8
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
6
Piping diagram
FXDQ20,25,32PB FXDQ40,50,63NB
1
Gas side
6
Liquid side
Electronic expansion valve
Filter
Filter
Fan
Indoor heat exchanger
4D060927
9
• VRV Systems • Indoor Units
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
7
Wiring diagram
7-1
Wiring diagram
3
FXDQ20,25,32PB FXDQ40,50,63NB
1 7
POWER SUPPLY Note: 3 Input from outside Note: 1 Transmission wiring central remote control
Wired remote control
Control box A1P C1 F1U HAP
Printed circuit board Capacitor (M1F) Fuse (F5A, 250V) Light emitting diode (service monitor-green) Magnetic relay (M1P) Motor (indoor fan) Motor (drain pump) Thermal protector (M1F embedded)
KPR M1F M1P Q1M
: Terminal ,
R1T R2T R3T S1L T1R V1TR X1M X2M Y1E
Colors:
Thermistor (air) Thermistor (coil - 1) Thermistor (coil - 2) Float switch Transformer (220V/22V) Phase control circuit Terminal block Terminal block Electronic expansion valve
BLK:
Black
Z1C•Z2C R1T SS1 X16A X18A
ORG:
Noise filter (ferrite core) Wired remote control Thermistor (air) Selector switch (main/sub) Connector for optional parts Connector (adapter for wiring) Connector (wiring adapter for electrical appendices)
Orange
WHT:
White
YLW:
Yellow
: Connector
BLU:
Blue
PNK:
Pink
: Field wiring
GRY:
Gray
PRP:
Purple
GRN:
Green
RED:
Red 3D060547
NOTES
1 2 3
In case of using central remote control, connect it to the unit in accordance with the attached installation manual. Remote control model varies according to the combination system, confirm enineering materials and catalogs, etc. before connecting. When connecting the input wires from outside, forced off or on/off control operation can be selected by remote control. In details, refer to the installation manual attached to the unit.
• VRV Systems • Indoor Units
10
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
8
Sound data
8-1
Sound pressure spectrum
1 8
Octave band sound pressure level dB(0dB=0.0002µbar)
FXDQ50NB Octave band sound pressure level dB(0dB=0.0002µbar)
FXDQ40NB
Approximate threshold hearing for continuous noise
Approximate threshold hearing for continuous noise
Octave band center frequency (Hz)
Octave band center frequency (Hz)
4D060948
4D060949
NOTE
2
3 4
NOTE
Scale Over All (dB): HH (B, G, N is already rectified) A 34.0 C 39.0 Operating conditons: • Power source: 220~240V 50Hz / 220V 60Hz • Cooling: Return air temperature: 27°C DB, 19°C WB Outdoor temperature: 35°C DB, 24 °C WD • Heating: Return air temperature: 20°C DB, 15°C WB Outdoor temperature: 7°C DB, 6°C WB Measuring place: Anechoic chamber Location of microphone 2m
1m
Duct
Duct Suction
L 30.0 37.0
1 2
3 4
Microphone
5
Octave band sound pressure level dB(0dB=0.0002µbar)
Approximate threshold hearing for continuous noise
Octave band center frequency (Hz)
4D060950 NOTE
2
3 4
Scale Over All (dB): HH (B, G, N is already rectified) A 36.0 C 42.0 Operating conditons: • Power source: 220~240V 50Hz / 220V 60Hz • Cooling: Return air temperature: 27°C DB, 19°C WB Outdoor temperature: 35°C DB, 24 °C WD • Heating: Return air temperature: 20°C DB, 15°C WB Outdoor temperature: 7°C DB, 6°C WB Measuring place: Anechoic chamber Location of microphone 2m
1m
Duct
Duct Suction
Air flow rate H 34.0 40.5
L 32.0 39.0
1,5m
Discharge
Microphone
5
11
2m
1m
Duct
Duct Suction
Air flow rate H 33.0 39.0
L 31.0 38.0
Microphone
The operation condition is external static pressure 15 Pa. Operation noise differ with operation and ambient conditions.
FXDQ63NB
1
Scale Over All (dB): HH (B, G, N is already rectified) A 35.0 C 40.0 Operating conditons: • Power source: 220~240V 50Hz / 220V 60Hz • Cooling: Return air temperature: 27°C DB, 19°C WB Outdoor temperature: 35°C DB, 24 °C WD • Heating: Return air temperature: 20°C DB, 15°C WB Outdoor temperature: 7°C DB, 6°C WB Measuring place: Anechoic chamber Location of microphone
Discharge
1,5m
Discharge
Air flow rate H 32.0 38.0
1,5m
1
The operation condition is external static pressure 15 Pa. Operation noise differ with operation and ambient conditions.
• VRV Systems • Indoor Units
5
The operation condition is external static pressure 15 Pa. Operation noise differ with operation and ambient conditions.
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
Fan characteristics
3D046299C
50
4
40
(mmH2O)
6
60
6
5
50
3
High (standard ESP)
3
40
e it of er lim sure Low tic presP) sta h ES (hig
te f ex it o lim ssure ) pp er ic pre rd ESP U tat da s tan (s
2
1
al it of extern Lower limessure static pr ESP) (standard
2
20
1
10 (Pa)
7
8
9 10 11 12 Air flow rate (m3/min)
High (high ESP)
tern
x of e mit e er li ssur Lowatic preSP) st igh E (h
13
(mmH2O)
(mmH2O)
NOTES
al
8
9
al
3
extern Lower limit ofre static pressu ) (standard ESP
10 11 12 13 Air flow rate (m3/min)
1
14 15 (mmH2O)
NOTES
The remote control can be used to switch between “high” and “low”.
1
The remote control can be used to switch between “high” and “low”.
2
The air flow is set to “standard” before leaving the factory. It is possible to switch between “standard ESP” and “high ESP” via the remote control.
2
The air flow is set to “standard” before leaving the factory. It is possible to switch between “standard ESP” and “high ESP” via the remote control.
FXDQ63NB
3D046301C
(mmH2O) 7
6
60
6
5
50
Up sta per li (hig tic pre mit of h ES ssur exte P) e rnal
(Pa) 70
External static pressure
(mmH2O) 7
3
40
20
1
10
5
High (high ESP)
4
30
2
High (standard ESP) nal xter of e limit ssure Low r e ) Upp tic pre rd ESP (high ESP) sta anda (st
3
rnal
te of e x r limit re Lowetic pressu sta h ESP) (hig
2 1
rnal
Low (standard ESP)
(mmH2O)
9
5
1
4
1
2 Low (high ESP)
Low (standard ESP)
3
4
High (standard ESP)
30
al xtern
l rna
Low (standard ESP)
(Pa)
(mmH2O) 7
4
30
10
1
(Pa) 70
4
Low (high ESP)
20
2
(mmH2O) 7
l
3
5
High (high ESP)
3D046300C
U s ppe (sta tatic p r limit nda res of rd sure ext ESP ern a )
5
(mmH2O) 6
Up sta per lim (hightic press it of exte ESP) ure rnal
(Pa) 60
External static pressure
(mmH2O) 6
FXDQ50NB
Up sta per limit (hightic pressu of extern ESP) re al
FXDQ40NB
External static pressure
9
(Pa) 11 12
13
Lower limit of exte static pressure (standard ESP)
14 15 16 17 18 Air flow rate (m3/min)
19
(mmH2O)
NOTES
1
The remote control can be used to switch between “high” and “low”.
2
The air flow is set to “standard” before leaving the factory. It is possible to switch between “standard ESP” and “high ESP” via the remote control.
• VRV Systems • Indoor Units
12
• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NBVE
9
Fan characteristics
1 9
13
• VRV Systems • Indoor Units