FIRE RESISTANT CABLES

LOW VOLTAGE

600/1000 V

FP400 BS7846 CABLE CHARACTERISTICS

TEMPERATURE RANGE -25 to +90°C

Bending radius Circular conductor r=6D Shaped conductor r=8D

MECHANICAL IMPACT Very good

FIRE PERFORMANCE BSEN50265-2-1 BSEN50266-2-4

FLEXIBILTY Rigid

HALOGEN FREE BSEN50267-2-1

LOW SMOKE EMISSIONS BSEN50268-2

FIRE RESISTANT BS6387 Category CWZ

KEY APPLICATIONS Essential safety circuits associated with fire detection, alarm and evacuation and particularly for power supplies to building equipment, used in fire-fighting and control such as sprinkler pumps, smoke extractors, fire lifts, fire shutters and control dampers.

CABLE DESCRIPTION Conductor: Plain annealed copper stranded (class 2) conductor for ease of handling. Primary Insulation: Mineral ceramic (Mica/Glass) fire resistant tape. Secondary Insulation:

90°C cross - linked insulation.

Old Existing Core Identification: oo red-black ooo red-yellow-blue oooo black-red-yellow-blue New Harmonised Core Identification: oo brown-blue ooo brown-black-grey oooo blue-brown-black-grey 7-48 cores white with printed numbers Bedding: Extruded LSOH bedding compound. Armour: Single layer of galvanised steel wires. Sheath: Robust LSOH sheath. Colour - black. Other colours to special order

Old Existing Core Colours

New Harmonised Core Colours

FP400/05/04

FIRE RESISTANT CABLES

LOW VOLTAGE

600/1000 V

FP400 BS7846 Nominal cross sectional area mm ²

Approximate overall diameter mm

Approximate diameter under armour mm

Nominal diameter of armour wires mm

Approximate cable weight kg/km

Maximum conductor resistance at 20°C ohms/km

Current rating DC or Single phase AC Clipped direct Amps

Current rating DC or Single phase AC Free Air Amps

Volt drop DC

Volt drop Single phase AC

mV/A/m

mV/A/m

27 36 49 62 85 110 146 180 219 279 338 392 451 515 637 698 787

29 39 52 66 90 115 152 188 228 291 354 410 472 539 636 732 847

31 19 12 7.9 4.7 2.9 1.85 1.35 0.98 0.67 0.49 0.39 0.31 0.25 0.195 0.155 0.12

31 19 12 7.9 4.7 2.9 1.9 1.35 1 0.69 0.52 0.42 0.35 0.29 0.24 0.21 0.19

27 * 36 * 49 *

29 * 39 * 52 *

31 19 12

31 19 12

27 * 36 * 49 *

29 * 39 * 52 *

31 19 12

31 19 12

27 * 36 *

29 * 39 *

31 19

31 19

27 * 36 *

29 * 39 *

31 19

31 19

27 * 36 *

29 * 39 *

31 19

31 19

Two core 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

12.9 14.1 15.2 16.4 18.6 21.4 23.7 27.2 28 30.7 35.3 36.6 39.3 44.2 48 51.8 55.9

8.3 9.6 10.6 12 14 15.9 18.3 20.9 21.2 23.7 27.3 28.4 30.9 34.4 38 41.6 45.3

0.9 0.9 0.9 0.9 0.9 0.9 1.25 1.6 1.6 1.6 2 2 2 2.5 2.5 2.5 2.5

310 380 450 530 630 920 1200 1600 2000 2400 3300 3800 4400 5700 7200 8300 10500

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047

Seven core 1.5 2.5 4

16.4 18.3 20.8

11.8 13.7 15.3

0.9 0.9 1.25

500 640 910

12.1 7.41 4.61 Twelve core

1.5 2.5 4

21.2 24.0 27.3

15.7 18.3 20.9

1.25 1.25 1.6

850 1090 1550

12.1 7.41 4.61

Nineteen core 1.5 2.5

24.2 28.6

18.5 22.0

1.25 1.6

1120 1650

12.1 7.41

Twenty-seven core 1.5 2.5

29.4 33.4

22.8 26.6

1.6 1 .6

1650 2150

12.1 7.41

Thirty-seven core 1.5 2.5

32.2 36.7

25.6 29.9

1.6 1.6

2000 2650

12.1 7.41

Circular conductor <= 35mm² Shaped conductor >= 50mm² Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations *The tabulated rating is as a two core cable and may be used where the number of cores carrying current does not exceed the square root of the total number of cores.

FP400/05/04

FIRE RESISTANT CABLES

LOW VOLTAGE

600/1000 V

FP400 BS7846 Nominal cross sectional area mm ²

Approximate overall diameter

Nominal diameter of armour wires mm

Approximate cable weight

mm

Approximate diameter under armour mm

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

13.4 14.8 16.1 17.4 20.3 22.8 27.4 29.2 33.0 37.0 40.6 43.8 48.0 52.0 57.1 63.0 69.5

8.8 10.2 11.5 12.8 14.8 17.1 20.8 22.4 26.2 30.0 32.4 35.4 38.4 42.2 46.9 52.6 58.7

0.9 0.9 0.9 0.9 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 2.5 2.5

340 430 510 620 930 1210 1800 2100 2600 3400 4500 5500 6900 8200 10200 12200 15000

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 +400

14.3 16 17.3 19.6 21.8 24.6 29.1 32.2 35.0 40.2 44.0 48.4 52.5 57.1 62.7 69.6 78.0

9.7 11.4 12.7 14.1 16.3 18.9 22.5 25.4 28.0 32.0 35.6 38.8 42.7 46.9 52.3 58.8 65.3

0.9 0.9 0.9 1.25 1.25 1.25 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.15

390 490 590 830 1040 1370 2100 2500 3200 4500 5600 7200 8500 10300 12800 15600 20400

kg/km

Maximum conductor resistance at 20°C ohms/km

Short circuit rating (1 sec) of conductor

Current rating Three phase AC Free Air Amps

Volt drop Three phase AC

KA

Current rating Three phase AC Clipped direct Amps

0.20 0.35 0.57 0.86 1.4 2.2 3.6 5.0 7.1 10.0 13.6 17.2 21.4 26.5 34.3 42.9 57.2

23 31 42 53 73 94 124 154 187 238 389 335 386 441 520 599 673

25 33 44 56 78 99 131 162 197 251 304 353 406 463 546 628 728

27 16 10 6.8 4.0 2.5 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.185 0.165

0.20 0.35 0.57 0.86 1.4 2.2 3.6 5.0 7.1 10.0 13.6 17.2 21.4 26.5 34.3 42.9 57.2

23 31 42 53 73 94 124 154 187 238 289 335 386 441 520 599 673

25 33 44 56 78 99 131 162 197 251 304 353 406 463 546 628 728

27 16 10 6.8 4.0 2.5 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.185 0.165

mV/A/m

Three core 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 Four core 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Circular conductor <= 35mm² Shaped conductor >= 50mm²

FP400/05/04