Course in
BUILDING ELECTRICAL SYSTEMS DESIGN & DRAFTING
Prepared By Eng : AMJED OSMAN ELSAYED MOHAMED
E‐mail:
[email protected]
INTRODUCTION design of the electrical installation in building used to be simple and straight forward . Such installations
generally
included electrical service from an electricity board company , power distribution within the building for sockets (receptacles ), air conditioniong and other electrical loads , lighting and few specialty system such as fire alram and telephone .
Eng : Amjed Osman
Building Electrical Design
Generation , transmission and distributions of electrical energy
Eng : Amjed Osman
Building Electrical Design
Transmission of Electricity From power station to consumer
Power Station
High Voltage Distribution
Generation Primary Transmission
Secondary Transmission
11kV, 17kV,
330kV,
60kV,
11kV,
22kV, 23kV
500kV
132kV
33kV
Yard transformer
Regional Substation
Zone Substation
Eng : Amjed Osman
240/415V
Distribution Substation
Building Electrical Design
Distribution of Power High Voltage and low voltage distribution system Consumer 1 and 2: 230V two wire Consumer 3 : 230/400V three wire
Bulk Supply Consumer
Consumer 4 : 230/400V four wire
1
2
3
4
Delta/Star transformer
Line 1(A) Line 2(B)
Three phase, high voltage distribution
Line 3(C) Neutral
Three Phase Star System
Three phase four wire distribution low voltage 230/400V
Eng : Amjed Osman
Building Electrical Design 5
Types of phase:‐ There are 3 phase types: 1. Red phase or phase (A) 2. Yellow phase or phase (B) 3. Blue phase or phase (C)
Phase system: There are 3 types of phase system : 1. One ø system or 1 phase system 2. Tow ø system or 2 phase system 3.Three ø system or 3 phase system
Eng : Amjed Osman
Building Electrical Design
Eng : Amjed Osman
Building Electrical Design
ELECTRICAL CODES AND STANDARDS: Electrical codes :‐ the principles used in electrical design and installation are know as electrical codes.
Examples : UK‐ UAE‐ QATAR‐ OMAN‐ SUDAN:‐ UK, UAE, Qatar ,Oman, Sudan follow B.S (British standards) know IEC(International Electrotechnical Commission)
USA‐KSA:‐ USA,KSA follow NEC codes (National electrical codes) which is chapter no 70 in NFPA book (National fire protection association )
European countries: European countries follow IEC standards (international electrical technical commission ). Eng : Amjed Osman
Building Electrical Design
Voltages and codes around the world U.K → U.K follow B.S codes (also know as IEE regulation ) Normal voltages
230/400V 50Hz.
USA→ USA follow NEC (NFPA 70) Normal voltage
110/220 220/380
60Hz 60Hz
KSA→ KSA follow NEC (NFPA 70) Before 2010 KSA was having 2 voltages 127/220 V 60Hz 220/380 V 60 Hz In 2010 the ministry of electricity decided that new project after 2010 will have only one voltage through out KSA 220/380 60Hz Eng : Amjed Osman
Building Electrical Design
Voltages and codes around the world UAE → UAE follow B.S
Normal voltage
230/400v 50 Hz
SUDAN → Sudan follow B.S
Normal voltage
240/415v 50 Hz
Qatar → Qatar follow B.S
Normal voltage 240/415v
50Hz Eng : Amjed Osman
Building Electrical Design
SWITCH used for on or off purpose of small equipment like light – ceiling fan
–exhaust fan - socket – water heaters – washing machine – cooking range- window and split A/C – small water pumps.etc
Rating of switch : the maximum current which can flow through switch safety without any damages for switch is know as rating of switch
Eng : Amjed Osman
Building Electrical Design
Standard Rating of Switch 5A 10 A 15 A 20 A 25 A 30A or 32 A
Note In Gulf we used 10 A switch for light only In Gulf we used 20 A switch for W/H – W/M etc Eng : Amjed Osman
Building Electrical Design
Types of Switch One way switch
Two way switch
Intermediate switch
Eng : Amjed Osman
Building Electrical Design
One way switch
Eng : Amjed Osman
Building Electrical Design
Two way switch
Eng : Amjed Osman
Building Electrical Design
Intermediate switch
Eng : Amjed Osman
Building Electrical Design
back box In Gulf they are 2 standard back box size 1. 3×3 2. 6×3
Gang : represents no. of switch in back box 1 Gang
2 gang
3 gang
Eng : Amjed Osman
Building Electrical Design
Gang four gang 4G
five gang 5G
Eng : Amjed Osman
six gang 6G
Building Electrical Design
Sockets Types of S/O in BS (Sudan , Oman, Qatar, UAE ) 3pin → 13A general s/o → 15A s/o for A/C → 45A flex outlet for W/H , W/M , C/R
K.S.A : S/Os in NEC standard are know as receptacles Receptacles → 15A/20A , 220 V Receptacles →15A or 20A , 127 V
Eng : Amjed Osman
Building Electrical Design
Sockets Other classification
1. Single S/O outlet : The back box has only one s/o inside .the back box size is used 3×3.
2.Double or twin S/O outlet : The back box has two s/o , the back box size is used 6×3
3.Shaver outlet : (110_ 220 v)
Eng : Amjed Osman
Building Electrical Design
Radial circuit
Eng : Amjed Osman
Building Electrical Design
Ring circuit
Eng : Amjed Osman
Building Electrical Design
flex outlet
Eng : Amjed Osman
Building Electrical Design
CILEING ROSE
WIRES AND CABLES: Wire : conductor + insulation (small size) Cables : conductor + insulation + sheath (large size ) Bare conductor : only conductor (no insulation). Ex, over
head lines in Sudan
Units of wires and cables mm² → Sudan and B.S countries (UAE, K.SA,Qatar) OR AWG →(American Wire Gnage ) mm² : it is cross sectional area of conductor without
insulation Eng : Amjed Osman
Building Electrical Design
AWG
Eng : Amjed Osman
Building Electrical Design
Equivalent of mm² to AWG MM²
AWG
REMARK
1.0 mm²
18 AWG
AWG For KSA
1.5 mm²
16 AWG
AWG For KSA
2.5 mm²
14 AWG
AWG For KSA
4 mm²
12 AWG
AWG For KSA
6 mm²
10 AWG
AWG For KSA
10 mm²
8 AWG
AWG For KSA
16 mm²
6 AWG
AWG For KSA
25 mm²
4 AWG
AWG For KSA
35 mm²
2 AWG
AWG For KSA
50 mm²
1 1/0 AWG
AWG For KSA
70 mm²
2/0 AWG
AWG For KSA
95 mm²
3/0 AWG
AWG For KSA
120 mm²
4/0 AWG
AWG For KSA
150 mm²
250 kc MIL
AWG For KSA
185 mm²
350 kc MIL
AWG For KSA
240 mm²
400 kc MIL
AWG For KSA
300 mm²
500 kc MIL
AWG For KSA
Eng : Amjed Osman
Building Electrical Design
CORE OF CABLES Core (c) represents the numbers of conductors in the cable , there are two types of the cable based on the cores of cables
1. Single core cable (1c)
2. Multi core cable (a) 2 core cable (2c)
Eng : Amjed Osman
Building Electrical Design
CORE OF CABLES (b) Three core cable (3c)
(c)Four core cable (4c)
(d)3 ½ core or 3.5 core
Eng : Amjed Osman
Building Electrical Design
Run of cable:Run of cable represents the no .of single core or multi core Always the earth is separate run and 1c only . no multi core for earth
wire We prefer multi core cables above 6mm², avoid single cables above 6mm² 1.5 mm² → single core (1c) 2.5 mm² → single core (1c) 4 mm² → single core (1c) 6 mm² → single core (1c) 10 mm² → (2c ,3c , 4c, 3.5c) 16 mm² → (2c ,3c , 4c, 3.5c) 25 mm² → (2c ,3c , 4c, 3.5c) : : 300 mm² → (2c,3c , 4c, 3.5c) Eng : Amjed Osman
Building Electrical Design
Earth wire sizing Earth wire is dependent on phase size Wire or cable size for phase and N
Earth wire or cable size
1.0mm²
1.0 mm²
1.5 mm²
1.5 mm²
2.5 mm²
2.5 mm²
4 mm²
4 mm²
6 mm²
6 mm²
10 mm²
10 mm²
16 mm²
16 mm²
25 mm²
16 mm²
35 mm²
25 mm²
50 mm²
25 mm²
70 mm²
35 mm²
95 mm²
50 mm²
120 mm²
70 mm²
150 mm²
95 mm²
185 mm²
95 mm²
240 mm²
120 mm²
300 mm²
150 mm²
Eng : Amjed Osman
Building Electrical Design
Conductor materials
1. Copper (cu)
2. Aluminum (al)
Eng : Amjed Osman
Building Electrical Design
Insulation materials 1. PVC :(Poly-Viny Chloride) PVC insulated wires are used for smaller loads like light , fans , s/o , w/m , w/h , c/r They can with stand up to 60 C,
2. LSOH : Low Smoke zero Holagen LSOH insulated wires are used for smaller loads like lights , fans , s/o , w/h , w/m . c/r . Eng : Amjed Osman
Building Electrical Design
Insulation materials XLPE : cross linked polyethylene XLPE insulated cables are used as main
feeder cable (service wire) for DB OR SMDB OR MCC OR T/F etc. and for heavy mechanical load like chiller – AHU – Boilers XLPE cables can with stand up to 90º c
FR : Fire Retardant or MICC (Mincal Insulated Cable Conductor ) FR cable are professed for emergency load like lights fire fighting pumps , emergency lights ,fire alarms cables Eng : Amjed Osman
Building Electrical Design
Types power cable : 1.Un armoured cable
2. Armoured cable SWA (Steel Wire Armour ) b) AWA (Aluminum Wire Armour) c) SSA (Steel Strip Armour ) a)
d) ASA (Aluminum Strip Armour)
Eng : Amjed Osman
Building Electrical Design
Voltage classification H.V → High Voltage (above 1000 v) M.V → Medium Voltage (250 to 1000v) L.V → Low Voltage (30 to 250 v) ELV → Extra Low Voltage (voltage less
than 30 ac or 54 v dc) Grade of cable means the with stand voltage whether the cable is for LV or MV or HV. Eng : Amjed Osman
Building Electrical Design
Color codes of cable PHASE
In sudan or gulf New color code countries in europe
Phase (A) or (1)
Red
Brown
Phase (B) or (2)
Yellow
Black
Phase (C) or (3)
Blue
Grey
Neutral
Black
Blue
Earth
Green or Y/G
Y/G
Eng : Amjed Osman
Building Electrical Design
Final representation of cables 1×4c×10mm² ,XLPE/SWA/PVC.Cu,0.6/1kv + 1×1c×10mm², pvc /pvc ,cu Y/G
1 → run 4c→ core 10mm²→size XLPE → insulation SWA→ armour PVC→ sheath Cu → conductor material 0.6/1kv → M.V /L.V grade Earth 1 → run 1c→ core 10mm²→ size PVC → insulation PVC→ sheath Cu → conductor material Y/G → Earth Eng : Amjed Osman
Building Electrical Design
Electrical faults Types of electrical faults Over load Short circuit Earth –fault or shock Over voltage Under voltage Eng : Amjed Osman
Building Electrical Design
1. Over load Over load mean current more than rated current of equipment Ex : 10 A rated switch 2A→ safe 6A→ safe 10A→ safe 11A→ un safe (over load current) When over load current passes then the s/w gets damage.
Eng : Amjed Osman
Building Electrical Design
2. Short circuit When any phase of neutral or any two phase meet
each other then infinite current flows through them. Usually thousands of current in 1 ms (KA of current in 1ms ), this increase the temperature is know as short- circuit condition
Eng : Amjed Osman
Building Electrical Design
3.Earth – fault or shock When any phase meet earth wire or any conducting materials eg
(metals – human body – water – etc. ) some a mount of current passes in to ground through the earth wire or any conducting material This current passing to earth from phase wire is know as earth – leakage current and the fault is know as earth – fault . Good conductor
Bad conductor
Silver (best)
wood
Cu and AL
Rubber
All metals expect few semi‐ conductor
Plastic – paper – glass
Human body
porcelain
Water
Air Eng : Amjed Osman
Building Electrical Design
Summary P – N → Short circuit P – P → Short circuit P – E or human body → earth fault –
shock N – E or human body → No effect E – human body → No effect
Eng : Amjed Osman
Building Electrical Design
Productive devices The devices which protected from electrical faults are knows as protective devices Types of protective devices 1. Fuse → protective from over load only 2. Circuit breaker → protects from over load and s.c faults 3. RCB or ELCB or GFCI→ protects from earth faults or shock 4. RCBO or RCCB → protects from over load , s.c and earth faults 5. UVR (Under Voltage Relay)→ protects from under voltage Eng : Amjed Osman
Building Electrical Design
Circuit Breaker : The CB is protective devices which can be operated manually and automatically it trips in case of over load and short‐ circuit condition
5 A to 40 A MCB (Miniature circuit breaker )
50 A to 600 A MCCB (Modulate Case circuit breaker ) 800 A to 3500 A ACB (Air Circuit Breaker)
Eng : Amjed Osman
Building Electrical Design
Standard of C.B (A)
Type of C.B
5
MCB
10
MCB
15
MCB
20
MCB
25
MCB
30 or 32
MCB
40
MCB
50
MCCB
60 or 63
MCCB
80
MCCB
100
MCCB
125
MCCB
150
MCCB
200
MCCB
225
MCCB
250
MCCB
300
MCCB
400
MCCB
500
MCCB
600
MCCB
800
ACB
1000
ACB
1250
ACB
1500
ACB
2000
ACB
2500
ACB
3000
ACB
3500
ACB
Eng : Amjed Osman
Building Electrical Design
Standard short – circuit rating of C.B 1. 6KA 2. 10KA 3. 16KA 4. 25KA 5. 35KA 6. 50KA Eng : Amjed Osman
Building Electrical Design
TYPES OF C.B 1.MCB → Miniature Circuit Breaker 2.MCCB→ Modulate Case Circuit Breaker 3.ACB → Air Circuit Breaker
other breaker used in H.V (power plants and s/s ) 4.VCB → Vacuum C.B 5. OCB → Oil C.B 6. SF6 Eng : Amjed Osman
Building Electrical Design
Types of MCB B curve MCB
C curve MCB
D curve MCB
Eng : Amjed Osman
Building Electrical Design
Types of MCB
Eng : Amjed Osman
Building Electrical Design
Application of B,C,D curve MCB
1. B curve MCB is preferred for lighting circuit. 2. C curve MCB is preferred for small heavy like W/H – W/M – C/R 3.D curve MCB is preferred for machine like (backing machine ).
Eng : Amjed Osman
Building Electrical Design
MCCB(Modulate Case circuit breaker ) Rating 50 to 600A
Types of MCCB 1. Adjustable MCCB here we can set the tripping value normally
2. Fixed or un adjustable MCCB
Eng : Amjed Osman
Building Electrical Design
ACB : Air Circuit Breaker Rating 800 to 3500A 1.Motorized with drawable ACB : Here the start and stop push buttons are operated by a motor which is required to be energized and after it is off we can with draw the ACB to avoid are flash
2.Motorized non_ with draw able ACB Here the start and stop push buttons are operated by a motor which is required to be energized and after it is off/on we need to with raw ACB Eng : Amjed Osman
Building Electrical Design
RCD or ELCB or GFCI B.S (Sudan and UAE,Qatar)
→RCD (Residual Current Devices )
→ELCB (Earth Leakage Circuit Breaker)
NEC (KSA)
→ GFCI : Ground fault Circuit Breaker Eng : Amjed Osman
Building Electrical Design
Working principle of RCD The RCD continuously monitors the current difference
between phase and neutral . if the leakage current is equal to sensitivity of RCD then the RCD is trip Recommended sensitivity of RCD : For lights use 100 mA RCD (0.1A) For sockets use 30 mA RCD (0.03A) For W/H- W/M- C/R use 30 mA (0.03A) For A/C use 100mA RCD (0.1A) For under water lighting use 10mA RCD (0.001A) Note: the RCD is provide with a test buttons to verity that RCD is working propyl
Eng : Amjed Osman
Building Electrical Design
Working principle of RCD No .of poles : Since neutral is compulsory in RCD we have
1. Two poles RCD
2. Four poles RCD
Eng : Amjed Osman
Building Electrical Design
RCCB or RCBO : RCCB
Residual Current Circuit Breaker
RCBO
Residual CB with over current protection (over load & S.C) Note RCCB or RCBO protects from all 3 faults (over load , S.C and earth
fault)Since this technology is now they are very less used
Eng : Amjed Osman
Building Electrical Design
RCCB or RCBO Ex : (C 40A - 100ma
- 10KA)
C → type of RCBO 40 A→ rating of RCBO 100mA → sensitivity of MCBO 10KA→ short- circuit rating Note In UAE they have both CB and RCD for all lights and W/H. S/O , A/C In Qatar RCD are minatory for S/O , W/H , W/M only not require for lights and A/C. In KSA RCD are not used GFCI are minatory only for equipment inside bath room and kitchen. Eng : Amjed Osman
Building Electrical Design
Isolator or disconnect switch (D/S): Isolator or D/S is not a protective devices is it doesn’t trip in case of
any fault it is only meant for on and off purpose It can look similar to CB with handle side handle or rotary handle Note In sudan and B.S countries the isolator is used as main breaker knows as (main isolator ) inside the DB or final DB Always install D/S near to every heavy mechanical equipment such as chiller , AHU , Motor and pumps , lights for maintains and repair purpose
Eng : Amjed Osman
Building Electrical Design
STANDARD ISOLATOR RATING 1. 20 A 2. 25 A 3. 30 A 4. 40 A 5. 50 A 6. 60 A 7. 80 A 8. 100 A 9. 125 A 10. 150 A 11. 220 A 12. 225 A 13. 250 A 14. 300 A 15. 350 A 16. 400 A 17. 500 A
18. 19. 20. 21. 22. 23. 24. 25 26
600 A 800 A 1000 A 1250 A 1500 A 2000 A 2500 A 3000 A 3500 A
Eng : Amjed Osman
Building Electrical Design
DB (NEC)
Eng : Amjed Osman
Building Electrical Design
DB (B.S)
Eng : Amjed Osman
Building Electrical Design
DB (B.S)
SMDB
Eng : Amjed Osman
Building Electrical Design
STANDARD ISOLATOR RATING NO .OF POLES FOR ISOLATOR DB:
2P
4P
No.of poles D/S near the heavy mechanical equipment SPN for single phase equipment
TPN for three phase equipment Eng : Amjed Osman
Building Electrical Design
Wires and cables insulation methods Majorly the wires of cables are said to be installed in two methods Cable in air No
(2) Cable in ground
1
Methods for cable in Air Free in Air
2
conduit
3 4 5
Cable trunking Cable tray Cable ladder
Methods for cable in ground Directly buried or directly laid under ground cable Duct bank or electrical ducts Cable tranch
Eng : Amjed Osman
Building Electrical Design
Conduit: (electrical pipe) Material of conduit PVC
Metallic
GI/GS→ Galvanized Iron/
Galvanized Steel Eng : Amjed Osman
Building Electrical Design
Conduit: (electrical pipe) Material of conduit : EMT→ Electrical Metallic Tubes RGS/RGI →Rigid Galvanized Steel/
Rigid Galvanized Iron Note PVC conduits are used as connected conduit inside the wall , slabs ,
and floor screed. GI/GS or RGI/RGS are used as exposed conduits or the wall , or slab in India and B.S countries (Qatar , UAE ,Oman) EMT conduits are used as exposed conduits on the wall or slab in KSA Eng : Amjed Osman
Building Electrical Design
Standard size of conduits ½ ´´ → 16 mm ¾´´ → 20 mm 1´´ → 25mm 1¼´´→ 32 mm 2´´ → 50 mm 3´´ → 75 mm 4´´ → 100 mm Note ½ ´´ conduits are not recommended ¾´´ (20 mm) 0r 1´´ (25 mm) conduit can be use for wiring
lighting 1´´ (25 mm) or (32mm) conduit can be used for wiring of s/o , w/h , w/m , c/r , pumps and low current system like fire alarms wires , CCTV telephone and TV wires. Eng : Amjed Osman
Building Electrical Design
Conduits accessories Coupler : coupler used to join 2conduts
Bends : In gulf countries bends are made
at site in the same coduit using PVC bending
Eng : Amjed Osman
Building Electrical Design
circular JB is fixed near to every light point , ceiling and exhaust and smoke electors
Types of JB circular JB One way
two way through
two way angle
two way U
three way
four way
Eng : Amjed Osman
Building Electrical Design
Junction box octagonal JB
back bax : are used for s/o flex outlet etc
adapter : use for fixing conduit to the back box
Eng : Amjed Osman
Building Electrical Design
Standard mounting heights of wiring accessories All switches → 1250 mm AFFL (After Finish Floor
Level) Light , fan , w/h , w/m . Sockets →450 mm AFFL Tel/sockets →450 mm AFFL Sockets in kitchen → 250 mm above kitchen plat form s/o for w/h , w/m , A/C , near the equipment
Eng : Amjed Osman
Building Electrical Design
Standard mounting heights of wiring accessories
Eng : Amjed Osman
Building Electrical Design
conduiting laying of conduit is knows as coduiting there are three stages for conduiting
Conduiting in slab
Eng : Amjed Osman
Building Electrical Design
Conduiting in wall
Eng : Amjed Osman
Building Electrical Design
Conduiting in floor
Eng : Amjed Osman
Building Electrical Design
Cable trunking Cable trunking is used to carry branch of wires (many wires )
Materials' : 1. PVC cable trunking 2. Metallic cable trunking
Eng : Amjed Osman
Building Electrical Design
Standard size of cable trunking 1. 50mm ×50mm (5cm×5cm) 2. 100mm ×100mm (10cm×10cm) 3. 150mm ×150mm (15cm×15cm) 4. 200mm ×200mm (20cm×20cm) 5. 250mm ×250mm (25cm×25cm) 6. 300mm ×300mm (30cm×30cm) 7. 400mm ×400mm (40cm×40cm) 8. 500mm ×500mm (50cm×50cm) Note: other combination are also available ex : 300mm×100mm Eng : Amjed Osman
Building Electrical Design
Installation methods of cable trunking The cable trunking can be installed is three method as per
requirements On the surface of the wall
Hanging from slab
Under floor trunking
Eng : Amjed Osman
Building Electrical Design
CABLE TRAY Cable tray is used to carry heavy cable
Types of cable tray:
1. Perforated cable tray : is preferred for carraying power cables
2. Plain cable tray : can be used for low current system like TV , CCTV ,FF
Eng : Amjed Osman
Building Electrical Design
Materials of cable tray 1. No PVC 2. Metallic (a) Galvanized cable tray
(b) Hot dip galvanized cable
Eng : Amjed Osman
Building Electrical Design
Standard cable tray size 50mm ×50mm (5cm×5cm) 150mm ×150mm (15cm×15cm) 200mm ×100mm (20cm×10cm) 250mm ×100mm (25cm×10cm) 300mm ×100mm (30cm×10cm) 400mm ×100mm (40cm×10cm) 500mm ×100mm (50cm×10cm) 600mm×100mm (60cm×10cm) 800mm×100mm (80cm×10cm) 900mm×100mm (90cm×10cm) Note: if more than 900mm cable tray is required then use two cable tray parally
1) 2) 3) 4) 5) 6) 7) 8) 9) 10)
Eng : Amjed Osman
Building Electrical Design
Cable tray installation Cable tray can be installed in three methods : 1. On the surface of wall
2. Hanging from cable
3.Floor mounted (on the floor ) Eng : Amjed Osman
Building Electrical Design
Cable laying methods on cable tray There are three methods of cable laying on cable tray Flat formation – touching Flat formation – spacing Trefoil formation (only for single core cables )
Eng : Amjed Osman
Building Electrical Design
Cable ladder Cable ladder are preferred only for vertical installation only in
electrical shaft or riser
Cable installation in ground :
there are three methods of cable tray installation in ground 1.Directly buried or directly laid under ground 2.Duct bank or electrical duct 3.Cable trench Eng : Amjed Osman
Building Electrical Design
Cable installation in ground 1.Directly buried or directly laid under ground
Eng : Amjed Osman
Building Electrical Design
2.Duct bank or electrical duct
Eng : Amjed Osman
Building Electrical Design
3.Cable trench
Eng : Amjed Osman
Building Electrical Design
Coordination with mechanical system 1. HAVC (Heating Ventilation and Air Conditioning ) 2. Plumbing
water supply b) drainage 3. Fire fighting 4. Conveyors like ,lifts scalolar 5. Swimming pool. a)
Eng : Amjed Osman
Building Electrical Design
Types of HVAC system 1.
Window A/C
2. Split A/C
Eng : Amjed Osman
Building Electrical Design
3.VRV or VRF system
Eng : Amjed Osman
Building Electrical Design
4. Package A/C
Eng : Amjed Osman
Building Electrical Design
5. Central A/C – VAV system
Eng : Amjed Osman
Building Electrical Design
6. Chilled water system
Eng : Amjed Osman
Building Electrical Design
Plumbing system 1. Water supply
2. Drainage system
Eng : Amjed Osman
Building Electrical Design
Fire fighting system
Duty and stand by pumps Eng : Amjed Osman
Building Electrical Design
Plumbing system Lift : The installation works of lift etc is done by separate contractor know as lift contractor The elect.engineer has to provide a D/S inside the lift room for supply to the lift system Summing pool : are usually done by separate contractor knows as swimming pool contractor . Sometimes the elec. Engineer has to supply electricity to under water lights which is done at voltage not greater than 30 v a.c the lights shall be provide with 10ma RCD. Eng : Amjed Osman
Building Electrical Design
Panel board An enclosure with protection devices such as C.B and
RCD knows as panel board . Ex : DB – SMDB – MCC – MDB (All are panel board) Switch gear : a panel board including instruments is knows as switch gear. Ex : MDB – MCC
Eng : Amjed Osman
Building Electrical Design
MCC (motor control center ) MCC is a panel board to which major mechanical motors
or loads are connected. MCC has measuring indicating remote start indicates. Ex : MCC panel has ammeter voltmeter frequency meter power factor meter , phase indicators motor run off trip indicating lamps auto , manual selector switch CB and motor starters with remote terminal blocks.
Eng : Amjed Osman
Building Electrical Design
Panel board The panel board and switch gear (DB- SMDB – MDB –
MCC ) are manufactured in separate factories knows as switch gear manufacturing company and these panel boards are delivered at site for installation Well – know switch gear companys : 1. ABB 2. Schneider electric 3. Mitsubishi 4. Merlin gerin 5. Siemens 6. L&T Eng : Amjed Osman
Building Electrical Design
Bus duct system Note : bus duct has a housing with bus bar insulated , bus bar is used
to carry current of very high ratings , ex : above 600A only
STANDARD BUS DUCT RATING: 600A 800A 1000A 1230A 1500A 2000A 2500A 3000A 3500A Bus way or bus duct riser : is used for power distribution inside the
high building for each house
Eng : Amjed Osman
Building Electrical Design
IP PROTECTION IP →Ingress Protection or International Protection IP is the number assigned to the electrical equipment and motors installed outside the building or in wall areas to protection from water and dust and object No 0 1 2 3 4 5 6 7 8
Protection form object and Protection form water dust Not protect Not protect Hand protect Vertical water Finger protect 15º Tool protect 60º Wire protect Splashing of water Dust protect Low jets of water Complete protect High jets of water Immession Complete submersible Eng : Amjed Osman
Building Electrical Design
TRANSFORMES Types of transformer 1. steps up transformer 2. step down transformer
Types base on phase system single phase three phase Types of transformer base on poling oil cooled transformer air cooled transformer Eng : Amjed Osman
Building Electrical Design
TRANSFORMES Note: for indoor transformer use air cooled transformer for outdoor transformer use oil cooled transformer in gulf countries the transformer are indoor type
installed in separate room ex substation room or transformer room oil cooled transformer are not referred inside the building . air cooled transformer are used inside building unit of transformer is KVA Eng : Amjed Osman
Building Electrical Design
TRANSFORMES
STANDARD RATING OF TRANSFORMER 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16)
50 KVA 60KVA 80KVA 100KVA 150KVA 250KVA 315KVA 500KVA 630KVA 800KVA 1000KVA 1500KVA 2000KVA 2500KVA 3000KVA 3500KVA Eng : Amjed Osman
Building Electrical Design
TRANSFORMES Need of transformer Gulf countries Transformer is not require for building whose
total max demand less than 400kva If the total max demand is greater than 400kVA then we require transformer Max permit transformer size 2500kVA Sometimes is 3000kVA Eng : Amjed Osman
Building Electrical Design
TRANSFORMES Steps to calculate the transformer size :
1.Consider Total max demand of MDB = KW 2.Total max demand of MDB in KVA = KW/cosø = KVA 3.Add 10% as future load Total max demand with future load in KVA = kVA ×1.10 4. Transformer size = Total max demand with future load in KVA Transformer load (90%)
Then select the standard size
Eng : Amjed Osman
Building Electrical Design
TRANSFORMES Ex : calculate the Transformer size for project inside whose max demand is
100kw Solution : Total max demand of MDB = 100 KW 1.Total max demand of MDB in KVA = KW/cosø = 100/0.8=125KVA 2. Add 10% as future load 3. Total max demand with future load in KVA =125 kVA ×1.10=137.5KVA 4. Transformer size = Total max demand with future load in KVA Transformer load (90%) = 137.5Kva/.90 = 157.7Kva Standard T/F size = 250KVA / air cooled 11kv/440v / indoor T/F Y/▲ / z% = 5% 3ø, 4 wires 50 Hz Eng : Amjed Osman
Building Electrical Design
Capacitor bank Types of load: 1.Resistive load: current is in phase with voltage 2.Inductive load: current lags voltage 3.Capacitive load: current leads voltage Phase angle: angle between voltage and current Note: All loads in our daily life are resistive – inductive loads, ex (tube light,bulb, motor and pumps ,w/h, w/m , r/c). Hence capacitor bank are required which are connected to MDB ,which improves the over all power factor of the system . Sudan PF = 0.80 (low PF) Final PF = 0.98 or 0.96 (improve p.f) Eng : Amjed Osman
Building Electrical Design
Capacitor bank Note Capacitor bank is not require for single phase equipment or for
small project Capacitor bank required for project involving three phase equipment or here phase motors or MCC panels and this capacitor bank is connected to MDB. Unity of capacitor bank: KVAR (Kilo – Volt – Ampere – Reactive)
Formula to calculate capacitor bank:
Capacitor bank (KVAR) Max demand of MDB in KW {tan(cos-¹ø1) – tan (cos-¹ø2)} Where Ø1 → initial power factor = 0.8 Ø2 → final power factor = 0.98 Eng : Amjed Osman
Building Electrical Design
Capacitor bank Types of capacitor bank:
1.Fixed capacitor bank 2.APFC (Automatic Power Factor Corrector) APFC: in this types the capacitor are automatic , they become on and off depending on the load Ex: If full load then all capacitor are on If half load then few capacitor are on If no load then very few capacitor on
Eng : Amjed Osman
Building Electrical Design
standard capacitor bank 1. 10 KVAR 2. 15 KVAR 3. 20 KVAR 4. 25 KVAR 5. 35 KVAR 6. 40 KVAR 7. 50 KVAR 8. 75 KVAR 9. 100 KVAR 10. 125 KVAR 11. 135 KVAR 12. 150 KVAR 13. 175 KVAR 14. 200 KVAR 15 225 KVAR 16. 275 KVAR
17. 18. 19. 20. 21.
300 KVAR 375 KVAR 420 KVAR 540 KVAR 750 KVAR
Eng : Amjed Osman
Building Electrical Design
Capacitor bank
Eng : Amjed Osman
Building Electrical Design
EMERGENCY BACK UP SYSTEM UPS / Inverter
(Un interrupted Power Supply)
DG (Disel Generator )
or stand by generator
Eng : Amjed Osman
Building Electrical Design
UPS / Inverter UPS →Un interrupted Power Supply
Eng : Amjed Osman
Building Electrical Design
UPS / Inverter UPS is used for back up of electronic equipment ,ex(computer, CCTV) Inverter is used for back up of electrical and electronic equipment's Ex → electrical (fans – lights - w/m ) Ex → electronic (computer – CCTV ) Unit of UPS/Inverter → KVA (Kilo – Volt – Ampere ) Eng : Amjed Osman
Building Electrical Design
Standard of UPS /Inverter 1. 0.5 KVA 2. 085 KVA 3 1 KVA 4. 1.4 KVA 5. 2 KVA 6. 3 KVA 7. 3.5 KVA 8. 5 KVA 9. 7.5 KVA 10. 10 KVA 11. 20 KVA 12. 25 KVA 13. 30 KVA 14. 40 KVA 15. 50 KVA 16. 65 KVA 17. 80 KVA 18. 100 KVA
Eng : Amjed Osman
Building Electrical Design
UPS / Inverter Step to calculate UPS/inverter size:
1.Calculate the total load in KW 2.Calculate the total load in KVA 3. UPS/Inverter size = total load in KVA UPS/Inverter loading = total load in KVA 0.80 (80% or 85% loading) 4. select the standard size
Eng : Amjed Osman
Building Electrical Design
UPS / Inverter Wattages of load: 1. Tube lights = 40 w 2. Ceiling fans = 80 w 3. Computer
(a)CRT computer = 300 w (b)LCD computer = 200 w (c)LED computer = 160 w 4. printer = 200 w 5. router = 50 w 6. (6) EPBAX = 50 w 7. (7) CCTV = 50 w Eng : Amjed Osman
Building Electrical Design
Diesel generator The diesel generator can be connected in two methods
1.C.O.S (Change Over Switch ) manually operated switching 2. A.T.S (Auto Transfer Switch ) automatic switching Units of generator → KVA
Eng : Amjed Osman
Building Electrical Design
C.O.S (Change Over Switch ) manually operated
Eng : Amjed Osman
Building Electrical Design
A.T.S (Auto Transfer Switch ) automatic switching
Eng : Amjed Osman
Building Electrical Design
Diesel generator Standard generator size 1. 10 KVA 2. 20 KVA 3. 30 KVA 4. 40 KVA 5. 50 KVA 6. 63 KVA 7. 75 KVA 8. 100 KVA 9. 125 KVA 10. 132 KVA 11. 160 KVA 12. 200 KVA 13. 225 KVA 14. 250 KVA 15. 300 KVA
16. 400 KVA 17. 500 KVA 18. 600 KVA 19. 630 KVA 20. 750 KVA 21. 800 KVA 22. 1000 KVA 23. 1250 KVA 24. 1500 KVA 25. 1800 KVA 26. 2000 KVA 27. 2500 KVA
Eng : Amjed Osman
Building Electrical Design
Diesel generator Step to calculate generator size:
1. Calculate the total load in kw = (SMDB Comm) 2. Total load in KVA = kw /cosø = KVA 3. Generator size = = total load in KVA generator loading (0.80) 4. Select the standard generator size
Eng : Amjed Osman
Building Electrical Design
Electrical instruments (testing and commission): 1. Voltmeter 2. Ammeter 3. Energy meter or Kwh meter 4. P.F meter 5. Frequency 6. Phase indicators 7. Multi meter Eng : Amjed Osman
Building Electrical Design
Earthing and lighting protection system Earthing : connection of wire to the ground is knows as
earthing Types of earthing conductor: 1.Earth continuity conductor (ECC) or protection earth conductor 2.Main earth conductor 3.Equipment bonding conductor 1.Earth continuity conductor (ECC) or protection earth conductor: The earth wire passing to final loads and DB to SMDB or MDB is knows as ECC. 2.Main earth conductor: The earth wire connected to ground is knows as main earth conductor usually it is connected to MDB. Eng : Amjed Osman
Building Electrical Design
Earthing and lighting protection system 3.Equipmential bonding conductor
Every metallic part in the electrical installation shall be connected to ground (earth)
Eng : Amjed Osman
Building Electrical Design
Earthing and lighting protection system Types of earth pits:
1.Pipe earthing
Eng : Amjed Osman
Building Electrical Design
Earthing and lighting protection system 2. Electrode earthing
Eng : Amjed Osman
Building Electrical Design
Lighting protection system lighting protection system is building above 15 meter
Eng : Amjed Osman
Building Electrical Design
Lighting protection system
Eng : Amjed Osman
Building Electrical Design
lighting system lamp → any device which gives light is knows as lamp types of lamp:
1.Incandescent lamps
2.Fluorescent lamps a) CFL (compact Fluorescent lamps) b)tube
Eng : Amjed Osman
Building Electrical Design
Types of lamp 3.Mercury vapor lamps 4.Metal halide lamps
5.HPS(High Pressure Sodium)
6.Halogen lamps Eng : Amjed Osman
Building Electrical Design
Types of lamp Note: Incandescent lamps are not recommended as their efficiency is very low (high input current , low output current For indoor purpose the best lamps are fluorescent lampsas their efficiency is very good (less input current or power high out put light The M.V lamps and metal ,HPS lamps are preferred for out door street light. Lamp input: is measured in watts Ex : tube light(40w,36w) or CFL (24w , 36w) Lamp output: lamp output is measured in lumens . Eng : Amjed Osman
Building Electrical Design
Luminaire or lighting fixture Lamp fixed on a frame or reflectors is knows as luminaire Illumination:
The lumen output of any luminaire falling on asq.meter room area is knows as illumination It is measured is 1.Lux (Lx) if the room dimensions are in meter 2.Foot candle (F.C) if the room dimension are in feets Relation between LUX and F.C: 1 LUX = 0.1 F.C 1F.C = 10 LUX Eng : Amjed Osman
Building Electrical Design
Recommended lux level for different rooms by IENSNA IENSNA: Illumination Engineer Society North America
Bedroom = 50 lux = 5 FC Hall = 150 lux = 15 FC Kitchen = 300 lux = 30 FC Bathroom =100 lux = 10 FC Coefficient of utilization (Cu): The Cu depends on the reflection factors of ceiling wall and floor colors . also it depends on the work plane height Note: for manual calculation consider cu = 45%
Eng : Amjed Osman
Building Electrical Design
Lamp lumen factor (LLF) Lamp lumen factor (LLF) or lumen loss factor(LLF)
or maintenance factor (MF): Ex : tube light (40 w) Today → 2450 lumens After 3 years→ less than 2450 lumens The LLF depends on cleaning of luminaire Note For manual calculation for 3 years maintence consider LLF= 0.67 Eng : Amjed Osman
Building Electrical Design
Formula Formula to calculate no.of luminaire in room:
No.of lamps
=
(lux or FC)× room area ( luminaire )×(lumens ×cu × LLF)
Cu = .45 LLF = 0.67
Eng : Amjed Osman
Building Electrical Design
Arrangement of luminaire: (x=2x) X → distance from wall to luminaire 2X→distance between luminaire to luminaire
Eng : Amjed Osman
Building Electrical Design