PLUMBING FIXTURES
PIPES AND FITTINGS
0.375 m
Min. distance of water closet center to side wall
3/8"
Min. NPS of fixture supply pipe for toilet
0.75 m
Min. distance of water closet center to water closet center
1/2"
Min. NPS of fixture supply pipe for shower
0.30 m
Min. distance of urinal center to side wall
1/2"
Min. NPS of fixture supply pipe for kitchen sink
0.60 m
Min. distance of urinal center to urinal center
1/2"
Min. NPS of fixture supply pipe for bathtub
Min. distance of bidet center to side wall
3/8"
Min. NPS of fixture supply pipe for bidet
Min. distance of bidet center to bidet center
3/8"
Min. fixture supply pipe diameter for tank type water closet.
0.375 m 0.75 m 2%
Min. slope of shower receptor
3"
4%
Max. slope of shower receptor
1.5"
559 mm 0.60 sq.m.
Min. fixture drain size for a water closet Min. fixture drain size for a bathtub
Min. height of threshold for shower wide door
0.05m (2”)
Min. depth of water seal for trap
Min. interior area of shower compartment
0.10m (4”)
Max. depth of water seal for trap
Min. spacing of drains for gang shower
51 mm
Min. height of a water seal for each fixture trap.
32" or 0.80 m
Mounting height of wall hung lavatory from the FFL
51 mm
Min. water seal depth or outlet diameter of grease trap
36" or 0.90 m
Max. mounting height of toilet grab bars from FFL
102 mm
Max. height of a water seal for each fixture trap.
19"
Max. mounting height of tissue paper holder from FFL
38 mm (1 ½”)
4.9 m
Min. trap diameter for a bathtub
51 mm (2")
Min. trap diameter for a shower stall.
51 mm (2")
Min. size of waste branch for a shower stall.
3" 38 mm (1 ½”)
Min. size of trap and waste branch for a pedestal urinal.
0.90 m
Min. extension of the VSTR above an openable window.
Min. size of trap or branch for a bidet.
0.90 m
Min. distance of vent away from any lot line, alley and street boundary lines.
3m
Min. horizontal distance of any VSTR from a roof deck used for other purposes aside from protection from weather.
4.6 m
Min. length of any branch requiring separate venting.
10
Min. number of stories served by a waste stack requiring a parallel vent stack.
6.10 m
Max. distance of any under floor clean-out from any access door, crawl space, or crawl hole
1 ½”
Vent pipe size for lavatories, drinking fountain
1 ½”
Vent pipe size sink
0.16 m
Diameter of drum trap
0.20 m
Min. length of a drum trap
0.32 m
Max. length of a drum trap
0.75 m
Max. spacing of waste outlets of one trap that serve three single compartment sinks
0.60 m
Max. length of the tailpiece from any fixture.
25 mm
Min. diameter of pipe sleeve
75 mm
Min. pipe sleeve for 64mm diameter uPVC pipe
32 mm (1 ¼”)
Min. diameter of an individual vent
1.5 m (5’)
Max. distance of vent from trap seal
150 mm
Min. extension of the VSTR above the roof
2.10 m
Min. vertical extension of VSTR from any roof deck where it is protruded
300 mm
Min. extension of VSTR above any other vertical surface.
150 mm (6")
Min. height of a branch vent above the fixture it is venting
152 mm 0.30 m
Min. height of vent above the highest level rim of the fixtures served before offsetting horizontally. Min. distance of the VSTR from any openable window.
1”
Vent pipe size for shower, laundry, slop sinks
3”
Vent pipe size for water closet
15 m 1.5 m (or less)
Max. length requirement to have a clean-outs Length of horizontal drain which does not require a clean-out unless such line is serving sinks or urinal
38 mm
Size of cleanout for pipe size of 38 mm ∅
38 mm
Size of cleanout for pipe size of 51 mm ∅
64 mm
Size of cleanout for pipe size of 64 mm ∅
76 mm
Size of cleanout for pipe size of 64 mm ∅
102 mm or larger
Size of cleanout for pipe size of 89 mm ∅
305 mm
Min. front clearance of clean-out 51 mm or less
450 mm
Max. front clearance of clean-out 51 mm or more
450 mm 750 mm
300 mm
Min. vertical clearance of clean-out in under floor piping extended to or above floor finish or extended outside the building Min. horizontal clearance of clean-out in under floor piping extended to or above floor finish or extended outside the building Min. distance of water piping from any regulating equipment, water heater, conditioning tanks, and similar equipment requiring union fittings.
3 m (10')
Max. spacing of pipe supports at intervals.
26 gauge
Min. Gauge of galvanized sheet used for downspouts.
Fixture Unit FU
7.5 gal. per minute or 1 cubic ft. per minute
SEPTIC TANK Min. width of a septic tank. Min. length of a septic tank. Min. liquid depth for a septic tank. Max. liquid depth for septic tank.
1/8 Bend
A type of pipe fitting for a Yoke Vent.
4 – 5 ft 45˚
1/8 bend elbow
60˚
1/6 bend elbow
2%
Min. slope of horizontal drainage pipe
1%
Min. slope for pipe with more than 102 mm diameter
¼” : 1ft or 6mm : 300mm
Length of house sewer from the inner face of the foundation wall of a building to the junction with another sewer.
Slope requirement for a house drain.
0.90 m 1.50 mts. 0.60 m 1.80 mts.
Minimum width of a septic tank. Minimum length of a septic tank. Minimum liquid depth for a septic tank.
1 cum.
Minimum capacity, in cubic meters, of the
Maximum liquid depth for septic tank.
secondary compartment of a septic tank. 508 mm.
1.50 mts
Minimum dimension of a manhole access to a septic tank. Minimum length of the secondary compartment of a septic tank with a capacity of more than 6 cubic meters.
15.20 mts.
Minimum distance of a water supply well from a septic tank.
45.70 mts.
Minimum distance of a water supply well from a seepage pit or cesspool.
30.50 mts.
Minimum distance of a water supply well from a disposal field.
3
Minimum head of water, in meters, required for each section of plumbing for water test. How many days, at least, shall be given before any plumbing work inspection is done after written notice for inspection.
3
15 minutes
8%
300mm
7.48 gals 7.5 gals 4.34 psi
Minimum time, in minutes, required for water to stay in the system or pipes for a water test without any leaks to satisfy said testing. Minimum lead content in percent for pipes and fittings safe for humans. Minimum vertical distance from the bottom of water pipes to the top of sewer or drain pipe if laid in the same trench on top of the other. 1 cubic foot of water contains 1 cubic foot of water contains If the water riser is 3.0 meter in height, what will be the minimum pressure of the water
inside that pipe? Schedule 40 & 80
Manufactured schedule for uPVC pipes
12
A self-closing basin faucet needs how many psi (pressure) to be efficient
30gal.
How many gallons do an average daily consumption of a Bathtub?