Digital PID Controller: Digital control system offers many advantages over their analog counterparts. The PID controller in the continuous-data domain is described by
The proportional constant KP is implemented digitally by a constant gain KP. Since a digital computer or processor has finite word length, the constant KP cannot be realized with infinite resolution. The numerical integration rule that can be used to digitally approximate the integral controller KI/s is Trapezoidal rule of integration The time derivative of a function f(t) at t = kT can be approximated by the Backward difference rule, using the values of f(t) measured at t = kT and (k -1)T. A difference Equation model of PID Controller is
where
For programming convenience let here Y(z) and E(z) are the output and input of the PID controller in the z domain
Where Y(z) and E(z) are the output and input of the PID controller. Then
Y(Z)=(a0+ a1Z-1+ a2Z-2)
and
E(Z)=(1 - Z -1) M (Z)
using the inverse Z-transformation, Y(K)=a0m(K)+a1m(K-1)+a2m(K-2) m(K)=e(K) + m(K-1) the above two equations are implanted in the programming. Advantages : 1. The advantage of Digital controller over a analog control are higher immunity to environmental
changes such as temperature and ageing components. 2. More Advanced control algorithms such as adaptive control and non-linear control implemented. 3. The ability to redesign the controller by changing the software(rather than hardware). 4. Digital control can be used to achieve power efficiency optimization.
can be