Ceiling Mounted Duct - Daikin

  • June 2020
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Ceiling Mounted Duct - Daikin as PDF for free.

More details

  • Words: 8,124
  • Pages: 27
EDUS 39 - 600 - F4

FXMQ-M Ceiling Mounted Duct Type

AMERICAS

EDUS39-600-F4

FXMQ-M Ceiling Mounted Duct Type 1. 2. 3. 4. 5. 6. 7.

Features ......................................................................................................2 Specifications ..............................................................................................3 Dimensions .................................................................................................4 Piping Diagrams..........................................................................................6 Wiring Diagrams..........................................................................................7 Electric Characteristics................................................................................8 Capacity Tables ..........................................................................................9 7.1 Cooling Capacity .......................................................................................... 9 7.2 Heating Capacity ........................................................................................ 10

8. Fan Performances.....................................................................................11 9. Sound Levels ............................................................................................12 10.Installation .................................................................................................13 11.Accessories...............................................................................................25

FXMQ-M

1

Features

EDUS39-600-F4

1. Features The Ceiling-Mounted Duct Type is a new addition to the VRV indoor units lineup that provides greater flexibility to satisfy individual air-conditioning needs even in a broad area. „ Increased allowable external static pressure accommodates greater flexibility in duct design and application. Ceiling-Mounted Duct Type FXMQ30M FXMQ36M FXMQ48M

30 type

2

36, 48 type

FXMQ-M

EDUS39-600-F4

Specifications

2. Specifications Ceiling Mounted Duct Type FXMQ30MVJU

FXMQ36MVJU

FXMQ48MVJU

Cooling Capacity1

Model Btu/h

30,000

36,000

48,000

Heating Capacity2

Btu/h

34,000

40,000

54,000

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

15-3/8 × 28-3/8 × 27-1/8” ( 390.5 x 720.7 x 689 mm)

15-3/8 × 43-3/4 × 27-1/8” ( 390.5 x 1111.2 x 689 mm)

15-3/8 × 43-3/4 × 27-1/8” ( 390.5 x 1111.2 x 689 mm)

3 × 16 × 13

3 ×16 ×13

3 ×16 ×13

1.95

3.43

3.43

D11/2D3AA1VE

2D11/2D3AG1VE

2D11/2D3AF1VE Sirocco Fan

Casing / Color Dimensions: (H × W × D) Coil (Cross Fin Coil)

in (mm)

Rows × Stages × FPI Face Area

ft²

Model Type Fan

Sirocco Fan

Sirocco Fan

Motor Output

kW

0.15

0.27

0.43

Air Flow Rate (H/L)

cfm

690/565

1,020/810

1,270/1,020

External Static Pressure4

in. Wg

0.66-0.43

0.71-0.43

1.0-0.72

Direct Drive

Direct Drive

Direct Drive

Microprocessor Thermostat for Cooling and Heating

Microprocessor Thermostat for Cooling and Heating

Microprocessor Thermostat for Cooling and Heating

Sound Absorbing Thermal Insulation Material

Glass Fiber

Glass Fiber

Glass Fiber

Air Filter5

See Note 5

See Note 5

See Note 5

Drive Temperature Control

Piping Connections

Liquid Pipes

in / mm

φ3/8” / 9.5 mm (Flare Connection)

φ3/8” / 9.5 mm (Flare Connection)

φ3/8” / 9.5 mm (Flare Connection)

Gas Pipes

in / mm

φ5/8” / 15.8 mm (Flare Connection)

φ5/8” / 15.8 mm (Flare Connection)

φ5/8” / 15.8 mm (Flare Connection)

in / mm

VP25 External Dia. 1-1/4 Internal Dia. 1

VP25 External Dia. 1-1/4 Internal Dia. 1

Dia. 1-1/4 ( External Internal Dia. 1 )

Drain Pipe

(

)

(

VP25

)

Machine Weight (Mass)

Lbs

99

139

144

Sound Level (H/L)6

dBA

45/41

45/41

48/45

Safety Devices

Fuse, Thermal Fuse for Fan Motor

Fuse, Thermal Fuse for Fan Motor

Fuse, Thermal Fuse for Fan Motor

Refrigerant Control

Electronic Expansion Valve

Electronic Expansion Valve

Electronic Expansion Valve

R-410A Series

R-410A Series

R-410A Series

Operation Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws.

Operation Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws.

Operation Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws.

Connectable outdoor unit Standard Accessories Drawing No.

C:3D042685

Notes: 1. Nominal cooling capacities are based on the following conditions: Return air temperature: 80°FDB, 67°FWB Outdoor temperature: 95°FDB Equivalent ref. piping length: 25 ft / 7.5 m (Horizontal) 2. Nominal heating capacities are based on the following conditions: Return air temperature: 70°FDB. Outdoor temperature: 47°FDB, 43°FWB Equivalent ref. piping length: 25 ft / 7.5m (Horizontal) 3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. 4. The airflow is set to STANDARD before leaving the factory. It is possible to switch between STANDARD ESP and HIGH ESP by changing the terminals in the electrical box. Refer to the fan curves for actual fan performance. 5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method (gravity method) 50% or more. 6. Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation, these values are normally somewhat higher as a result of installation conditions. 7. Refer to page 8 for Power Input.

FXMQ-M

3

Dimensions

EDUS39-600-F4

3. Dimensions 3D042508

FXMQ30MVJU

4

FXMQ-M

EDUS39-600-F4

Dimensions

3D042512

FXMQ36MVJU FXMQ48MVJU

FXMQ-M

5

Piping Diagrams

EDUS39-600-F4

4. Piping Diagrams

Gas piping connection port

Heat exchanger

R3T

R1T Fan

R2T Liquid piping connection port

Filter

Electronic Filter expansion valve

J:DU220-602J

R1T : Thermistor for suction air temperature R2T : Thermistor for liquid line temperature R3T : Thermistor for gas line temperature

6

Capacity

Gas

Liquid

30/36/48M

φ 5/8

φ 3/8

FXMQ-M

EDUS39-600-F4

Wiring Diagrams

5. Wiring Diagrams 3D043176A

FXMQ30M/36M/48MVJU

FXMQ-M

7

Electric Characteristics

EDUS39-600-F4

6. Electric Characteristics

8

FXMQ-M

EDUS39-600-F4

Capacity Tables

7. Capacity Tables 7.1

Cooling Capacity

FXMQ-M Cooling capacity Indoor Air Temp. °FWB Unit size

Outdoor air temp. °FDB

30

36

48

75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103

61

64

67

70

72

75

TC

SHC

TC

SHC

TC

SHC

TC

SHC

TC

SHC

TC

SHC

MBh

MBh

MBh

MBh

MBh

MBh

MBh

MBh

MBh

MBh

MBh

MBh

23.7 23.7 23.7 23.7 23.7 23.7 23.7 23.7 28.4 28.4 28.4 28.4 28.4 28.4 28.4 28.4 37.9 37.9 37.9 37.9 37.9 37.9 37.9 37.9

17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 23.5 23.5 23.5 23.5 23.5 23.5 23.5 23.5 30.6 30.6 30.6 30.6 30.6 30.6 30.6 30.6

26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 32.2 32.2 32.2 32.2 32.2 32.2 32.2 32.2 42.9 42.9 42.9 42.9 42.9 42.9 42.9 42.9

18.8 18.8 18.8 18.8 18.8 18.8 18.8 18.8 25.1 25.1 25.1 25.1 25.1 25.1 25.1 25.1 32.7 32.7 32.7 32.7 32.7 32.7 32.7 32.7

30.0 30.0 30.0 30.0 30.0 30.0 30.0 30.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 48.0 48.0 48.0 48.0 48.0 48.0 48.0 48.0

19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 26.3 26.3 26.3 26.3 26.3 26.3 26.3 26.3 34.4 34.4 34.4 34.4 34.4 34.4 34.4 34.4

33.2 33.2 33.2 33.0 32.4 31.8 31.3 30.7 39.8 39.8 39.8 39.5 38.9 38.2 37.5 26.9 53.1 53.1 53.1 52.7 51.8 50.8 50.0 49.1

20.2 20.2 20.2 20.3 20.1 20.1 19.9 19.6 27.1 27.1 27.1 27.1 27.1 27.1 27.0 26.9 35.6 35.6 35.6 35.6 35.2 35.1 35.0 34.6

35.1 34.5 33.9 33.4 32.8 32.2 31.7 31.1 42.1 41.4 40.7 40.0 39.4 38.7 38.0 37.3 56.1 55.2 54.3 53.4 52.5 51.6 50.7 49.8

20.2 20.1 19.8 19.7 19.5 19.3 19.3 19.3 27.1 27.0 26.7 26.4 26.2 25.9 25.7 25.4 35.6 35.5 35.2 34.7 34.4 34.0 33.7 33.4

35.7 35.1 34.5 34.0 33.4 32.9 32.3 31.7 42.8 42.1 41.5 40.8 40.1 39.4 38.8 38.1 57.1 56.2 55.3 54.4 53.5 52.6 51.7 50.8

19.0 18.8 18.7 18.7 18.7 18.7 18.6 18.4 25.8 25.4 25.2 24.9 24.7 24.4 24.2 24.0 34.0 33.7 33.4 33.1 32.6 32.3 32.0 31.7

TC : Total capacity ; kW SHC : Sensible heat capacity ; kW

Refer to Outdoor Unit Capacity Tables for the actual performance data of each indoor and outdoor unit combination.

FXMQ-M

9

Capacity Tables

7.2

EDUS39-600-F4

Heating Capacity

FXMQ-M Heating Capacity Indoor Air Temp. °FDB Indoor unit

Outdoor Air Temp. °FDB

30

36

48

22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0

°FWB 20.0 24.0 28.0 32.0 36.0 40.0 43.0 47.0 50.0 53.0 56.0 20.0 24.0 28.0 32.0 36.0 40.0 43.0 47.0 50.0 53.0 56.0 20.0 24.0 28.0 32.0 36.0 40.0 43.0 47.0 50.0 53.0 56.0

62

65

68

70

72

75

TC

TC

TC

TC

TC

TC

MBh

MBh

MBh

MBh

MBh

MBh

29.2 30.6 32.0 33.3 34.7 36.1 37.2 38.6 38.7 38.7 38.7 35.0 36.7 38.4 40.0 41.7 43.4 44.6 46.3 46.5 46.5 46.5 46.7 48.9 51.1 53.4 55.6 57.8 59.5 61.7 62.0 62.0 62.0

29.1 30.5 31.9 33.3 34.7 36.1 36.9 36.9 36.9 36.9 36.9 35.0 36.6 38.3 40.0 41.6 43.3 44.2 44.2 44.2 44.2 44.2 46.6 48.8 51.1 53.3 55.5 57.7 59.0 59.0 59.0 59.0 59.0

29.1 30.5 31.9 33.2 34.6 35.0 35.0 35.0 35.0 35.0 35.0 34.9 36.6 38.2 39.9 41.6 42.0 42.0 42.0 42.0 42.0 42.0 46.5 48.7 51.0 53.2 53.2 56.0 58.0 56.0 56.0 56.0 56.0

29.0 30.4 31.8 33.2 34.0 34.0 34.0 34.0 34.0 34.0 34.0 34.8 36.5 38.2 39.8 40.0 40.0 40.0 40.0 40.0 40.0 40.0 46.5 48.7 50.9 53.1 54.0 54.0 54.0 54.0 54.0 54.0 54.0

29.0 30.4 31.8 32.5 32.5 32.5 32.5 32.5 32.5 32.5 32.5 34.8 36.5 38.1 39.0 39.0 39.0 39.0 39.0 39.0 39.0 39.0 46.4 48.6 50.8 52.0 52.0 52.0 52.0 52.0 52.0 52.0 52.0

28.9 30.3 30.6 30.6 30.6 30.6 30.6 30.6 30.6 30.6 30.6 34.7 36.4 36.8 36.8 36.8 36.8 36.8 36.8 36.8 36.8 36.8 46.3 48.5 49.0 49.0 49.0 49.0 49.0 49.0 49.0 49.0 49.0

Refer to Outdoor Unit Capacity Tables for the actual performance data of each indoor and outdoor unit combination.

10

FXMQ-M

EDUS39-600-F4

Fan Performances

8. Fan Performances FXMQ30MVJU

FXMQ36MVJU WG

FXMQ48MVJU WG

WG

Note: 1. The remote controller can be used to switch between HIGH and LOW. 2. The airflow is set to STANDARD before leaving the factory. It is possible to switch between STANDARD ESP and HIGH ESP by changing the terminals in the indoor unit electrical box.

FXMQ-M

11

Sound Levels

EDUS39-600-F4

9. Sound Levels Overall „ Ceiling Mounted Duct Type

Notes: Operation noise differs with operation and ambient conditions.

dBA Model

208~230V, 60Hz H

L

FXMQ30MVJU

45

41

FXMQ36MVJU

45

41

FXMQ48MVJU

48

45

Octave Band Level 208V~230V FXMQ30MVJU

FXMQ36MVJU

4D052489

12

FXMQ48MVJU

4D052490

4D052491

FXMQ-M

EDUS39-600-F4

Installation

10. Installation Center of Gravity

FXMQ30MVJU FXMQ36, 48MVJU

A 28-3/8 43-3/4

B 11-3/8 20-1/8 4D042517

1.

SAFETY CONSIDERATIONS

Read these SAFETY CONSIDERATIONS carefully before installing air conditioning equipment, and be sure to install it correctly. After completing the installation, make sure that the unit operates properly during the start-up operation. Instruct the customer how to operate and maintain the unit. Inform customers that they should store this Installation Manual with the Operation Manual for future reference. Always use a licensed installer or contractor to install this product. Improper installation can result in water or refrigerant leakage, electrical shock, fire, or explosion. Meanings of DANGER, WARNING, CAUTION, and NOTE symbols: DANGER .............. Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING ............ Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION ............. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. NOTE .................... Indicates situation that may result in equipment or property-damage accidents only.

DANGER • Refrigerant gas is heavier than air and displaces oxygen. A massive leak could led to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious injury or death. • Do not install unit in an area where flammable materials are present due to risk of explosion resulting in serious injury or death. • Any abnormalities in the operation of the air conditioner, such as smoke or fire, could result in severe injury or death. Turn off the power and contact your dealer immediately for instructions. FXMQ-M

• If the refrigerant gas leaks during installation, ventilate the area immediately. Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan, heater, stove or cooking device. Exposure to this gas could cause severe injury or death. • If equipment utilizing a burner is used in the same room as the air conditioner, there is the danger of oxygen deficiency which can lead to an asphyxiation hazard resulting in serious injury or death. Be sure to sufficiently ventilate the room to avoid this hazard. • After completing the installation work, check that the refrigerant gas does not leak. Refrigerant gas may produce toxic gas if it comes in contact with fire from a fan, heater, stove, cooking device, or other heat source. Exposure to this gas can cause severe injury or death. • Do not ground units to water pipes, telephone wires, or lightning rods because incomplete grounding can cause a severe shock hazard resulting in severe injury or death. Do not ground units to gas pipes because a gas leak can result in an explosion which could lead to severe injury or death. • Safely dispose of the packing materials. • Children playing with plastic bags face the danger of death by suffocation. Tear apart and throw away plastic packaging bags so that children cannot play with them. WARNING • Ask your dealer or qualified personnel to carry out installation work. Do not try to install the machine by yourself. Improper installation may result in water leakage, electric shocks or fire. • Perform installation work in accordance with this installation manual. Improper installation may result in water leakage, electric shocks or fire. • Be sure to use only the specified accessories and parts for installation work. Failure to use the specified parts may result in water leakage, electric shocks, fire or the unit falling.

13

Installation

• Install the air conditioner on a foundation strong enough to withstand the weight of the unit. A foundation of insufficient strength may result in the equipment falling and causing injuries. • Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes. Improper installation work may result in the equipment falling and causing accidents. • Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local laws and regulations and this installation manual. An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire. • Make sure that all wiring is secured, the specified wires and used, and no external forces act on the terminal connections or wires. Improper connections or installation may result in fire. • When wiring the power supply and connecting the remote controller wiring and transmission wiring, position the wires so that the electric parts box lid can be securely fastened. Improper positioning of the electric parts box lid may result in electric shocks, fire or the terminals overheating. • Before touching electrical parts, turn off the unit. • Check the unit stand for damage on a continuous basis, especially if it has been used for a long time. If left in a damaged condition, the unit may fall and cause injury. • Do not touch the air outlet or the horizontal flaps while the swing flap is in operation as fingers may get caught and injured. • Be sure to establish a ground. Do not ground the unit to a utility pipe, arrester, or telephone ground. Incomplete ground may cause electrical shock, or fire. A high surge current from lightning or other sources may cause damage to the air conditioner. • Do not touch the switch with wet fingers. Touching a switch with wet fingers can cause electric shock. • Be sure to install a ground leakage breaker. Failure to install a ground leakage breaker may result in electric shocks, or fire. • Do not install the air conditioner in the following Do not install the air conditioner in the following locations: (a) Where a mineral oil mist or oil spray or vapor is produced, for example, in a kitchen. Plastic parts may deteriorate and fall off or result in water leakage. (b) Where corrosive gas, such as sulfurous acid gas, is produced. Corroding copper pipes or soldered parts may result in refrigerant leakage. (c) Near machinery emitting electromagnetic waves Electromagnetic waves may disturb the operation of the control system and result in a malfunction of the equipment. • Heat exchanger fins are sharp enough to cut.

14

EDUS39-600-F4

• •

• •





• •

To avoid injury wear gloves or cover the fins when working around them. Use of unspecified parts can result in the unit falling, leaks, and even electric shock or fire. Entrust installation to the place of purchase or a qualified serviceman. Improper installation can lead to result in leaks and even electric shock or fire. Do not allow children to play on or around the unit as they could be injured. Placing a flower vase or other containers with water or other liquids can result in a shock hazard or fire if a spill occurs. Do not remove the front panel because some parts are dangerous to touch. In addition, some parts may be damaged. For checking and adjusting internal parts, contact your dealer. Do not put a finger or other objects into the air inlet or air outlet. The fan is rotating at high speed and injury can result. Do not let the indoor unit get wet as it may cause an electric shock or fire. Refrigerant pipes may be very hot or very cold during or immediately after operation. Touching them can result in burns or frostbite. To avoid injury give the pipes time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.

CAUTION • While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation. Improper drain piping may result in water leakage and property damage. • Be very careful about product transportation. Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous. • Safely dispose of the packing materials. Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries. • Tear apart and throw away plastic packaging bags so that children will not play with them and risk suffocation. Do not turn off the power immediately after stopping operation. Always wait at least five minutes before turning off the power or water leakage and other problems may occur. • Take adequate measures to prevent the outdoor unit from being used as a shelter by small animals. Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.

NOTE • Install the indoor and outdoor units, power supply wiring, and connecting wires at least 3.5 ft. away from televisions or radios in order to prevent image interference or noise. Depending on the radio waves, a distance of 3.5 ft. may not be sufficient to eliminate the noise.

FXMQ-M

EDUS39-600-F4

• Remote controller (wireless kit) transmitting distance is shorter than expected in rooms with electronic fluorescent lamps Install the indoor unit as far away from fluorescent lamps as possible. • Radio interference may result if installed too close to other electrical devices. • Arrange the drain hose to ensure smooth drainage. Incomplete drainage may cause leaks in the building and on furniture. • Dismantling of the unit, and treatment of the refrigerant, oil, and other parts, should be done in accordance with the relevant local and national regulations.

Installation

2.

BEFORE INSTALLATION

• When moving the unit while removing it from the packing case, be sure to lift it by the four hanger brackets. Avoid putting any pressure on other parts especially the refrigerant piping. • Be sure to check the type of R-410A refrigerant to be used before installing the unit as using an incorrect refrigerant will prevent normal operation of the unit. • The accessories needed for installation must be retained in your custody until the installation work is completed. Do not discard them! • Decide upon a line of transport. • Leave the unit inside its packaging until reaching the installation site. Where unpacking is unavoidable, use a sling of soft material or protective plates together with a rope when lifting, to avoid damage or scratches to the unit. • When moving the unit after opening, hold the unit by the hanger brackets (× 4). Do not apply force to the refrigerant piping, drain piping or plastic parts. • For the installation of an outdoor unit, refer to the installation manual attached to the outdoor unit. • Do not install or operate the unit in the following areas: • Kitchens or rooms that might be laden with mineral oil, or filled with oil vapor or spray. Plastic parts may deteriorate and eventually cause the unit to fall out of place or leaks. • Where sulfurous or other corrosive gas exists. Copper tubing and brazed spots may corrode and lead to refrigerant leaks. • Where machines generate electromagnetic waves and cause the control system to malfunction. • Where the air contains high levels of salt as near the ocean, and where voltage fluctuates greatly as in factories. Also in vehicles or vessels. • This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment. If installed as a household appliance, it could cause electromagnetic interference. WARNING • Entrust installation to the place of purchase or a qualified serviceman. Improper installation can result in leaks or even electric shock or fire. • Use of unspecified parts could result in the unit falling, leaks, or even electric shock or fire.

NOTE • Be sure to read this manual before installing the indoor unit. • Be sure to procure an air filter in the field and mount it in the suction air passage to prevent water leaks or other problems.

FXMQ-M

15

Installation

2-1

EDUS39-600-F4

ACCESSORIES

Check the following accessories are included with your unit.

b. Items to be checked at time of delivery Also review the SAFETY CONSIDERATIONS. Items to be checked

Check

Name

Metal clamp

Drain hose

Insulation for fitting

Sealing pad

Did you explain about operations while showing the operation manual to your customer?

Quantity

1 pc.

1 pc.

1 each

1 each

Did you hand the operation manual over to your customer?

2-3 for gas pipe

Shape

Large

Mid

for liquid pipe Name

Clamp

Screws for duct flanges

Quantity

6 pcs.

As described in table below

Shape FXMQ30MVJU

·

FXMQ36 48MVJU

2-2

16 28

(Other) • Operation manual • Installation manual • Washers for hanger bracket (8 pcs.)

OPTIONAL ACCESSORIES

Table 1 Remote controller Wired type

BRD1C71

TAKE SPECIAL CARE DURING CONSTRUCTION AND AFTER INSTALLATION IS COMPLETED, CAREFULLY CHECK THE FOLLOWING ITEMS: a. Items to be checked after completion of work Items to be checked

The following problems may Check occur If not properly done:

Are the indoor and outdoor unit fixed firmly?

Units may drop, vibrate, or make noise.

Is the gas leak test finished?

May result in insufficient cooling.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltUnit may malfunction or the age correspond to that components burn out. shown on the name plate? Are wiring and piping correct?

Unit may malfunction or the components burn out.

Is the unit safely grounded?

Danger of electrical leakage.

Is wiring size according to specifications?

Unit may malfunction or the components burn out.

Is something blocking the air outlet or inlet of either the indoor or outdoor units?

NOTE TO INSTALLER

• Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating different functions, and adjusting the temperature) by having them carry out operations themselves while looking at the manual.

3.

SELECTING INSTALLATION SITE

Please attach additional thermal insulation material to the unit body when it is believed that the relative humidity in the ceiling exceeds 80%. Use glass wool, polyethylene foam, or similar with a thickness of 3/8”. or more as thermal insulation material. (1) Select and installation site that meets your customer’s approval and where the following conditions are fulfilled: • The upper space (including the back of the ceiling) of the indoor unit has no possibility of dripping of water from the refrigerant pipe, drain pipe, water pipe, etc. • Optimum air distribution can be ensured. • Nothing blocks air passage. • Condensate can be properly drained. • In the upper space (including the back of the ceiling) of the indoor unit where there is no possible dripping of water from the refrigerant pipe, drain pipe, water pipe, etc. • False ceiling is not noticeably on an incline. • Sufficient clearance for maintenance and service can be ensured. • Piping between indoor and outdoor units is possible within the allowable limit. (Refer to the installation manual for the outdoor unit.)

DANGER • Do not install unit in an area where flammable materials are present due to the risk of explosion resulting in serious injury or death. • If the supporting structural members are not strong enough to withstand the unit’s weight, the unit can fall out of place and cause serious injury.

NOTE • Install the indoor and outdoor units, power supply wiring and connecting wires at least 3.5 feet away from televisions or radios in order to prevent image interference or noise. Depending on the radio waves, a distance of 3.5 feet may not be enough to eliminate the noise.

Insufficient cooling.

Are refrigerant piping length The refrigerant charge in and additional refrigerant the system is not clear. charge noted down?

16

FXMQ-M

EDUS39-600-F4

Installation

(2) Use suspension bolts for installation. Check to make sure the ceiling is strong enough to support the weight of the unit . If there is a risk, reinforce the ceiling before installing the unit.

Min. 17 11/16

FXMQ30 · 36 · 48MVJU

(3) Install suspension bolts. Use bolts of 3/8” diameter. • Install the equipment where supporting structures are strong enough to bear the equipment’s weight. Use embedded inserts or anchor bolts with new buildings and hole-in-anchors with old buildings. Installation example Ceiling slab Anchor Long nut or turn-buckle Suspension bolt

A

Indoor unit Model

A

FXMQ30MVJU

29 1/2

FXMQ36MVJU 48MVJU

43 5/16

5.

Min. 27 9/16 (service space) (length: in.)

Fig. 1

4.

Note) All the above parts are field supplied.

PREPARATIONS BEFORE INSTALLATION

(1) Relative positions of indoor unit and suspension bolt. (Refer to Fig. 2)

INDOOR UNIT INSTALLATION

Installing optional accessories before installing the indoor unit is easier. Use only the provided specific accessories and parts designated by Daikin AC. (1) Fix the hanger bracket to the suspension bolt. Use washers to firmly tighten both upper and lower nuts. . Part to be procured in the field

FXMQ30 · 36 · 48MVJU

Washer (accessory)

Suspension bolt (× 4) Hanger bracket Tighten from above and below (Double nut)

B

A

Indoor unit Air inlet

Air outlet

(2) Adjust the height of the unit.

Inspection hatch 17 11/16 27 1/8 29 1/8 Model

A

B

FXMQ30MVJU

26 5/16

28 5/16

FXMQ36MVJU 41 11/16 43 11/16 48MVJU Fig. 2

(length: in.)

(2) Install a canvas duct to the air discharge outlet and air inlet so that vibration from the machine body is not transmitted to the duct or ceiling. You should also apply acoustic (insulation material) to the inside of the duct, and vibration insulation rubber to the suspension bolts.

FXMQ-M

(3) Make sure the unit is level. • Level the unit with a level when installing. If the unit is not level, it could become the source of water leaks. • When leveling the unit, check all four corners with a level or a vinyl tube containing water. (See the figure on the right.)

Level

Vinyl tube Hanger bracket setting bolt

(4) Tighten the nuts on the top.

NOTE • Setting the unit at an angle opposite to the drain piping can cause leaks.

17

Installation

6.

EDUS39-600-F4

REFRIGERANT PIPING WORK

6-1

NOTE

GENERAL INSTRUCTIONS

• For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit. • Before refrigerant piping work, check which type of refrigerant is used. Proper operation is not possible if the types of refrigerant are not the same. • Ensure outdoor unit is charged with refrigerant.

NOTE • Use a pipe cutter and flare suitable for the type of refrigerant. • To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end or cover it with tape. • Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit, such as air, etc. If any refrigerant gas leaks while working on the unit, immediately ventilate the room thoroughly.

6-2

• Apply ester oil or ether oil around the flare portions before connecting. • The flare nuts used must be those included with the main body. • Over-tightening may damage the flare and cause a refrigerant leakage. Not recommended but in case of emergency You should use a torque wrench but if one is unavailable, you may follow the following installation method: After the work is finished, make sure to check that there is no gas leak. When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque suddenly increases. From that position, further tighten the flare nut using the angle shown below: Table 3

Connecting the refrigerant piping

• When connecting the flare nut, coat the flare both inside and outside with ester oil or ether oil and initially tighten by hand 3 or 4 turns before tightening firmly. Ester oil or ether oil.

• To prevent flare nut cracking and gas leaks, be sure to use both a spanner and torque wrench together, as shown in the drawing below, when connecting or disconnecting pipes to/from the unit. Torque wrench

Spanner

Piping union Flare nut

• Refer to Table 2 for the dimensions of flare nut spaces. • Refer toTable 2 to determine the proper tightening torque. Table 2

φ 1/4”

10.4 – 12.7

0.342-0.358

φ 3/8”

24.1 – 29.4

0.504-0.520

φ 1/2”

36.5 – 44.5

0.638-0.654

φ 5/8”

45.6 – 55.6

0.760-0.776

Flare shape (in.)

45˚±2˚

Flare dimensions A (in.)

A

Tightening torque (ft.lbf)

90˚±2˚

Pipe size

6-3

Pipe size

Further tightening angle

Recommended arm length of tool (in.)

φ 1/4”

60 to 90 degrees

Approx. 5 7/8

φ 3/8”

60 to 90 degrees

Approx. 7 7/8

φ 1/2”

30 to 60 degrees

Approx. 9 13/16

φ 5/8”

30 to 60 degrees

Approx. 11 13/16

Piping insulation

• Execute heat insulation work completely on both sides of the gas piping and the liquid piping or a water leakage may result . • When using a heat pump, the temperature of the gas piping can reach up to approximately 250°F, so use sufficiently resistant insulation. • Also, in cases where the temperature and humidity of the refrigerant piping sections might exceed 86°F or RH80%, reinforce the refrigerant insulation. (13/16” or thicker) Condensation may form on the surface of the insulating material. • Check the pipe connector for gas leaks, then insulate it as shown in the drawing below. • Make absolutely sure to execute heat insulation works on the pipe-connecting section after checking gas leakage by thoroughly studying the following figure and using the attached heat insulating materials for fitting. Fasten both ends with the accessory clamps. • Wrap the accessory sealing pad only around the insulation for the joints on the gas piping side.

R0.0160.031 Mid sealing pad (accessory)

Clamp (× 4) (accessory) Insulation for fitting (accessory) (for gas line)

Gas pipe Liquid pipe

18

FXMQ-M

EDUS39-600-F4

Installation

7.

CAUTION • Be sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping may cause condensation or burns if touched.

6-4

Brazing refrigerant piping

DRAIN PIPING WORK

Install the drain pipe as shown below and take measures against condensation. Improperly rigged piping could lead to leaks on furniture and belongings. Insulate the drain piping inside the building. (1) Install drain piping as shown in the following figure:

• Before brazing local refrigerant piping, nitrogen gas must be blown through the piping to expel air from the piping. If your brazing is done without nitrogen gas blowing, a large amount of oxide film develops inside the piping, and could cause system malfunction. • When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution or while inserting nitrogen into the refrigerant piping. Once this is done, connect the indoor unit with a flared or a flanged connection. • Nitrogen should be set to 2.9psi. with a pressure-reducing valve if brazing while inserting nitrogen into the piping. Refrigerant piping

Pressurereducing valve Part to be Taping brazed

hands valve

Nitrogen Nitrogen

DANGER

Attached drain hose

1 15/16 or more

1 15/16 or more

Bottom of unit

(length: in.)

• Keep piping as short as possible and slope it downward so that air cannot remain trapped inside the pipe. • Keep pipe size equal to or greater than that of the connecting pipe (Vinyl pipe of 1 “ nominal diameter and 1 1/4” outer diameter). • Use the attached drain hose and clamp. Tighten the clamp firmly. • Insulate the metal clamp with the sealing pad. Metal clamp (accessory)

• Use of oxygen could result in an explosion resulting in serious injury or death. Only use nitrogen gas. • Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater, stove or cooking device. Exposure to this gas could cause severe injury or death.

Drain hose 13/16” or less

NOTE • Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copper brazing filter metal (BCuP) which does not require flux. Flux has an extremely negative effect on refrigerant piping systems. For instance, if chlorine based flux is used, it will cause pipe corrosion. Flux containing fluorine will damage refrigerant oil.

Large sealing pad (accessory)

Metal clamp

Tape

Drain hose

• When the unit is running, the negative pressure inside the unit is relative to the atmospheric pressure so be sure to provide a condensate trap on the condensate outlet. (See the figure) • In order to prevent foreign matter from building up inside the piping, avoid curves as much as possible and arrange so the trap can be cleaned.

NOTE

3 15/16” or more

• If converging multiple drain pipes, install according to the procedure shown below. Install a condensate trap for each indoor unit.

FXMQ-M

19

Installation

EDUS39-600-F4

(2) After piping work is finished, check that drainage flows smoothly. • Add approximately 61in3 of water slowly from the air inlet and check drainage flow.

8-3

SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Remote controller wiring Transmission wiring

Power supply wiring

NOTE

Model

• Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.

Field fuses FXMQ30MVJU FXMQ36MVJU

15A

FXMQ48MVJU

8. 8-1

ELECTRIC WIRING WORK GENERAL INSTRUCTIONS

DANGER • Do not ground units to water pipes, telephone wires, or lightning rods because incomplete grounding can cause a severe shock hazard resulting in severe injury or death. Do not ground units to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death.

ELECTRICAL CHARACTERISTICS Power supply

Units Model

Hz Volts

FXMQ30MVJU FXMQ36MVJU FXMQ48MVJU

60

208230

Voltage range Max. 253 Min. 187

Wire

Size

Wire size must comply with local codes.

Sheathed wire (2 wire)

AWG 18-16

NOTE

• All field supplied parts, materials, and electrical works must conform to local codes. • Use copper wire only. • For electric wiring work, refer to also “Wiring diagram label” attached to the electric parts box lid. • For remote controller wiring details, refer to the installation manual attached to the remote controller. • All wiring must be performed by an authorized electrician. • This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B, and so forth, and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched. If controls wiring and piping between the outdoor and indoor units are mismatched, a communications malfunction is likely. • A circuit breaker capable of shutting down power supply to the entire system must be installed. • Refer to the installation manual attached to the outdoor unit for the size of its power supply, the capacity of the circuit breaker and switch, and wiring instructions. • Be sure to ground the air conditioner.

8-2

Size

MCA MFA

• Allowable length of transmission wiring between indoor/ outdoor units and between the indoor unit and the remote controller is as follows. (1) Outdoor unit – Indoor unit: Max. 3280 ft. (1000 m); Total wiring length: 6560 ft. (2000 m) (2) Indoor unit – Remote controller: Max. 1640 ft. (500 m)

9.

WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER

9-1

HOW TO CONNECT WIRINGS

Remove the electric parts box lid and wire as shown in the following figure: FXMQ30 - 36 - 48MVJU FXMQ30 · 36 · 48MVJU Conduit Lock nut Electric parts box lid

Ground wiring Power supply wiring (Field wiring) Transmission wiring (Field wiring)

Clamp (accessory) Fan motor W

FLA

1.6

15

160

1.3

2.9

15

270

2.4

4.4

15

430

3.5

Wire locking bracket

Remote controller wiring (Field wiring)

Wiring (Remote controller and transmission)

MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A) kW: Fan Motor Rated Output (W); FLA: Full Load Amps (A)

20

FXMQ-M

EDUS39-600-F4

Installation

NOTE

Power supply terminal block

Power supply wiring, ground wiring L1 L2

X1M

P1 P2 F1 F2 T1 T2

Terminal block for remote controller

REMOTE TRANSMISSION FORCED CNTRL WIRING OFF

Conduit

X2M

Field supply wire Transmission wiring Remote controller wiring

1. Use round crimp-style terminals for connecting wires to the power supply terminal block. If unavailable, observe the following points when wiring. • Do not connect wires of a different gauge to the same power supply terminal because looseness in the connection may cause overheating. • Use the specified electrical wire. and connect it securely to the terminal. Lock the wire down without applying excessive force to the terminal. (Tightening torque: 0.97ft.lbf ±10 %) Attach insulation sleeve

Round crimp-style terminal Electric wire

DANGER • Use only specified wire and connect wires to terminals tightly. Be careful that wires do not place external stress on terminals. Keep wires in neat order so as to not to obstruct other equipment. Make sure that the electric parts box lid closes tightly. Incomplete connections could result in overheating, and in worse cases, electric shock or fire.

CAUTION • Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire system. • To avoid short circuits in the electric parts box, be sure to apply the sealing material or putty (not included) to the wiring hole to prevent the infiltration of water, insects or other small creatures. • When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping material to make appropriate clamps. Also, when wiring, make sure the lid on the electric parts box fits snugly by arranging the wires neatly and attaching the electric parts box lid firmly. When attaching the electric parts box lid, make sure no wires get caught in the edges. Pass wiring through the wiring through holes to prevent damage to them. • Make sure the remote controller wiring, the wiring between the units, and other electrical wiring do not pass through the same locations outside of the unit, separating them by at least 1 15/16”, otherwise electrical noise (external static) could cause mistaken operation or breakage.

FXMQ-M

2. Tightening torque for the terminal screws. • Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small, the head of the screw might be damaged, and the screw will not be properly tightened. • If the terminal screws are tightened too hard, screws might be damaged. • Refer to the table below for the tightening torque of the terminal screws. Terminal Terminal block for remote controller (6P) Power supply terminal block

Size

Tightening torque (ft.lbf)

M3.5

0.58 – 0.72

M4

0.87 – 1.06

3. Do not connect wires of a different gauge to the same grounding terminal because looseness in the connection may reduce protection. 4. Outside of the unit, keep transmission wiring at least 1 15/16” away from power supply wiring. The equipment may malfunction if subjected to electrical (external) noise. For remote controller wiring, refer to the INSTALLATION MANUAL OF REMOTE CONTROLLER attached to the remote controller.

21

Installation

9-2

EDUS39-600-F4

WIRING EXAMPLE

• Fit the power supply wiring of each unit with a switch and fuse as shown in the following drawing. COMPLETE SYSTEM EXAMPLE Power supply wiring Transmission wiring

Power supply Main switch

Switch

2. Example of group control or use with 2 remote controllers: Note: It is not necessary to designate indoor unit address when using group control. The address is automatically set when power is activated. Power supply Power supply Power supply Power supply 208-230V Outdoor unit 208-230V 208-230V 208-230V Control box 60Hz~ 60Hz~ 60Hz~ 60Hz~ IN/D OUT/D F1 F2 F1 F2

L1 L2

L1 L2

L1 L2

L1 L2

No. 2 System

Fuse

L1 L2

P1 P2 F1 F2 T1 T2

Indoor unit A

Most downstream indoor unit L1 L2

Indoor unit B

P1 P2 F1 F2 T1 T2

L1 L2

P1 P2 F1 F2 T1 T2

L1 L2

P1 P2 F1 F2 T1 T2

Indoor unit C P1 P2

P1 P2

P1 P2

Remote controller

Indoor unit

For use with 2 remote controllers

NOTE

Remote controller

Remote Remote controller controller

1. Example of 1 remote controller for 1 indoor unit during normal operation: Power supply Power supply Power supply 208-230V Outdoor unit 208-230V 208-230V 60Hz~ 60Hz~ 60Hz~ Control box L1 L2

Fig. 3

IN/D OUT/D F1 F2 F1 F2

L1 L2

L1 L2

Power supply 208-230V 60Hz~

1. A single switch can be used to supply power to units on the same system. However, branch switches and branch circuit breakers must be selected carefully.

CAUTION 2. Do not ground the equipment on gas pipes, water pipes or lightning rods, or crossground with telephones. Improper grounding could result in electric shock.

9-3

L1 L2

No. 1 System

CONTROLLING ONE INDOOR UNIT BY 2 REMOTE CONTROLLERS

• Set one controller to MAIN and the other to SUB. MAIN/SUB CHANGEOVER

L1 L2

L1 L2

P 1 P 2 F 1 F2 T 1 T 2

P1 P2

Remote contoroller

P 1 P 2 F 1 F2 T 1 T 2

L1 L2

P 1 P2 F 1 F 2 T 1 T 2

Indoor unit C

Indoor unit B

Indoor unit A

L1 L2

P 1 P 2 F 1 F2 T 1 T 2

P1 P 2

Remote contoroller

P1 P 2

P1 P2

Remote Remote contoroller contoroller Most downstream Indoor unit

(1) Insert a screw driver into the recess between the upper and lower part of remote controller and, working from the 2 positions, pry off the upper part. The remote controller PC board is attached to the upper part of remote controller. Upper part of remote controller

Lower part of remote controller Insert the screwdriver here and gently work off the upper part of remote controller.

22

FXMQ-M

EDUS39-600-F4

Installation

(2) Turn the MAIN/SUB changeover switch on one of the two remote controller PC boards to [S]. Leave the switch of the other remote controller set to “[M].

Input A OFF (Open Circuit)

Input A OFF (Open Circuit)

An open circuit between terminals T1 and T2 allows the unit to run normally.

(Factory setting)

S M

An open circuit between terminals T1 and T2 prevents unit operation.

Remote controller PC board Only one remote controller needs to be changed if factory settings have remained untouched.

S M

Input A ON (Closed Circuit)

Wiring Method (See ‘‘ELECTRIC WIRING WORK’’) (3) Remove the electric parts box lid (4) Add remote controller 2 (slave) to the terminal block for remote controller (P1, P2) in the electric parts box. There is no polarity. (Refer to Fig. 3 and 8-3.)

9-4

COMPUTERIZED CONTROL (FORCED OFF AND ON/OFF OPERATION)

(1) Wire specifications and how to perform wiring • Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller.

F2

T1

T2

Closing the normally open circuit between terminals T1 and T2 stops operation of the A closed circuit unit. When T1-T2 is opened, the unit must between terminals T1 and T2 allows norbe restarted with the remote controller. mal operation of the unit. .

(3) How to select FORCED OFF and ON/OFF OPERATION • Turn the power on and then use the remote controller to select operation. These codes are programmed at the remote controller. Individual unit groups can be programmed independently.

9-5

CENTRALIZED CONTROL

• For centralized control, it is necessary to designate the group number. For details, refer to the manual of each optional centralized controller.

10. FIELD SETTING

FORCED OFF Input A

Wire specification

Input A ON (Closed Circuit)

2-conductor, stranded, non-shielded copper cable / PVC or vinyl jacket

Gauge

AWG 18

Length

Max. 328ft.

External terminal

Contact that can ensure the minimum applicable load of 15 V DC, 10 mA.

Make sure the terminal box lids are closed on the indoor and outdoor units. Field setting must be made from the remote controller in accordance with the installation condition. • Setting can be made by changing the MODE NO., FIRST CODE NO., and SECOND CODE NO. • For setting and operation, refer to the FIELD SETTING in the installation manual of the remote controller.

    

  

     

(2) Actuation • The following table explains FORCED OFF and ON/ OFF OPERATIONS in response to Input A. The T1-T2 terminals are standard on all Daikin indoor units and allow for remote starting and stopping of equipment. Individual indoor units can be field prgrammed at the remote controller to change the T1-T2 sequence of operation of the equipment based upon the application

    

• Set the remote controller to the field set mode. For details, refer to the section HOW TO SET IN THE FIELD in the REMOTE CONTROLLER MANUAL. • When in the field set mode, select the MODE NO. to [12] and set the FIRST CODE SWITCH (switch) No. to [1]. Then set the SECOND CODE NO. (position) to [01] for FORCED OFF and [02] for ON/OFF OPERATION. FORCED OFF is factory setting.

11. TEST OPERATION FORCED OFF (Manual Restart) Mode No. 12 First Code No. 1 Second Code No. 01

DEFAULT SETTING

FXMQ-M

ON/OFF OPERATION Mode No. 12 First Code No. 1 Second Code No. 02

Refer to the installation manual of the outdoor unit. • The operation lamp of the remote controller will flash when a malfunction occurs. Check the malfunction code on the liquid crystal display to identify the point of trouble. An explanation of all malfunction codes and the corresponding trouble is provided in can be found in the service manual. If any of the items in the following table are displayed, there 23

Installation

EDUS39-600-F4

may be a problem with the wiring or power and you must check the wiring again. Table Remote control display

Content

• There is a short circuit at the Concentrated Management FORCED OFF terminals (T1, is lit T2)

24

U3 is lit

• The check operation has not been performed on the outdoor unit’s PCB.

U4 is lit UH is lit

• The power on the outdoor unit is off. • The outdoor unit has not been wired for power supply. • Incorrect wiring for the transmission wiring and / or FORCED OFF wiring.

No display

• The power on the indoor unit is off. • The indoor unit has not been wired for power supply. • Incorrect wiring for the remote controller wiring, the transmission wiring and / or the FORCED OFF wiring.

FXMQ-M

EDUS39-600-F4

Accessories

11. Accessories Standard Accessories Name

Metal clamp

Drain hose

Insulation for fitting

Sealing pad

Clamp

Screws for duct flanges

Quantity

1 pc.

1 pc.

1 each.

1 each.

6 pcs.

As described in table below

Shape

for liquid pipe

Large FXMQ30MVJU

·

FXMQ36 48MVJU

for gas pipe

16 28

(Other) • Operation manual • Installation manual • Washers (8 pcs.)

Small 3P086156-9T

Optional Accessories (For Unit) Type Item

FXMQ30MVJU

FXMQ36MVJU

FXMQ48MVJU

65%

KAFP372A80

90%

KAFP373A80

KAFP373A160

Filter chamber

KDDFP37A80

KDDFP37A160

Long life replacement filter

KAFP371A80

KAFP371A160

High efficiency filter

KAFP372A160

C:3D042519

For Controller optional accessories, refer to Controller Manual.

FXMQ-M

25

EDUS 39 - 600 - F2

FXDQ-M Slim Ceiling Mounted Duct Type

AMERICAS

1645 Wallace Drive, Suite 110 Carrollton, TX75006

[email protected] www.daikinac.com

May 2007

EDUS39-600-F4 Printed in U.S.A. 05/2007

AMERICAS

Related Documents

Duct
June 2020 13
Daikin-1
June 2020 5
Ceiling Systems
May 2020 14
Ceiling Tile
November 2019 27
Ceiling Panel
November 2019 23