Carrier Crheater Installation Instructions

  • July 2020
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Carrier Crheater Installation Instructions as PDF for free.

More details

  • Words: 43,770
  • Pages: 72
Small Rooftop Units Electric Cooling and Heat Pump Units 3 to 121/2Tons Accessory Electric Heater and Single Point Box Cancels: IIK 548-36-20

IIK 548-36-39 3/1/03

Installation Instructions Part Numbers: CRHEATER101A00 through CRHEATER119A00 CRSINGLE001A00 through CRSINGLE025A00 GENERAL

DISCONNECT MOUNTING LOCATION

Electric heater assembly consists of: 1 — Heater module 4 — Screws 1 — Wiring label 1 — Red wire (10 gage)* 1 — Splice connector* 1 — Wire tie* *Supplied with electric heater packages CRHEATER101A00, CRHEATER102A00, CRHEATER103A00, and CRHEATER104A00.

Single point kit consists of: 1 — Single point box 1 — Bushing 5 — Screws 1 — Bracket and conduit drip boot assembly 1 — Tube clamp (used only on 3 and 4 ton heat pump units) NOTE: Single point kit not required on standard efficiency, 3 to 6 ton cooling units with an MOCP of 60 or lower.

INSTALLATION

UNIT BLOCK-OFF PANEL

OUTDOOR ACCESS PANEL

INDOOR ACCESS PANEL

Fig. 1 — Typical Access Panel Location (3 to 6 Ton Units) DISCONNECT MOUNTING LOCATION

Turn off power to unit and install lockout tag. 1. Remove electric heater modules and single point box from packaging and inspect for damage. NOTE: If there is a “1” in the ninth position of the heater part number, it indicates that the heater is in a carton. For example, CRHEATER105A00 is heater CRHEATER005A00 in a carton. 2. Remove indoor and outdoor access panels. See Fig. 1 and 2. Save panels and screws. 3. Remove control box cover and center post. Save screws. See Fig. 3. 4. Remove the single point box cover. Secure single point box to the underside of the control box with the 2 screws provided (Fig. 4). 5. Secure the conduit drip boot bracket assembly to the back of the single point box with 2 of the screws provided (Fig. 4). The channel portion of the bracket assembly extends to the top panel behind the control box. Secure all wires to bracket with field-supplied wire tie as shown in Fig. 5. NOTE: The conduit drip boot and bracket are not used on standard efficiency 3 to 6 ton electric cooling units.

UNIT BLOCK-OFF PANEL

OUTDOOR ACCESS PANEL

INDOOR ACCESS PANEL

Fig. 2 — Typical Access Panel Location (71/2 to 121/2 Ton Units) 6. Remove heater cover(s) from heater mounting bracket. Save screws. Install single module electric heat option in location 1 (nearest the single point box). See Fig. 3 and 6. NOTE: Modules CRHEATER105A00, CRHEATER 109A00, CRHEATER112A00, CRHEATER114A00, CRHEATER115A00, and CRHEATER119A00 are keyed and must be installed in location 1 even when used as part of a 2-module option (Fig. 7).

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 111 Catalog No. 535-00028 Printed in U.S.A. Form 50-8SI Pg 1 3-03 Replaces: 50-4SI

Book 1 1 4 4 Tab 1b 5a 5a 6b

shown in Table 1, then there are different figures for units based on an MOCP below or above 60 Amps. Use the correct figure based on the MOCP determined from the correct electrical data table. Figures 11-15 are for electric cooling units. Figures 16-20 are for heat pump units. Figures 21-28 are for COBRA combined rooftop/energy recovery units. All fuses are 60 amp, time delay type, except for CRSINGLE025A00 which are 30 amps. All heaters are single bank heaters except CRHEATER011A00 and 012A00 which are dual bank heaters. The CRHEATER011A00 and 012A00 will be wired as two heaters (i.e., 6 leads). Fusing is shown pictorially. The single point box fuse location may not EXACTLY match the figure as shown, but the number of fuses will match the number shown. The optional factory-supplied disconnect has a maximum rating of 80 amps. Above 80 amps a fieldsupplied disconnect is required. Single point boxes CRSINGLE001A00, 006A00 and 011A00 do not include fuses and fuses are not required per the National Electric Code in these single point boxes since sub-fusing is not required below 60 amps. Field-supplied pressure connectors are required to connect wires. 12. Run control wires from heater module(s) to the control wire terminal block located next to the heater module(s). Connect the control wires as shown in Fig. 29. Heat Pump Units The electric heat is internally wired as the second stage of heat. Electric Cooling Units Electric cooling units with 2 electric heater modules can be wired for one- or 2-stage options as shown in Fig. 29. Connect single module heater option control wire (violet) to TB4 terminal 1. 13. Replace the center post and secure the single point box to the center post with one screw (Fig. 3).

7. To install module, engage flange on heater with track in unit and slide heater through mounting bracket opening. Fasten heater module to heater mounting bracket with the 4 screws saved from Step 6 (Fig. 4). NOTE: All 208/230-v heaters (except CRHEATER 105A00) are factory-wired for 3-phase applications but can be converted to single-phase by changing one wire as described in Step 8. Three-phase applications: Skip to Step 9. 8. On single-phase applications, rewire the heater as follows (see Fig. 8-10): a. Connect 10-gage red wire to splice connector. b. Remove yellow wire from heater contactor terminal 11 and connect to splice connector. c. Using the wire tie provided, fasten red wire to heater power wire harness near existing wire tie on heater module. This provides strain relief for the red wire. 9. Route power wires from heater module(s) through the foam bushing in the center partition and into the single point box (Fig. 4). If no single point box is required for the unit and heater combination, run the heater high voltage power wiring through the grommet holes to the field-supplied disconnect (or optional factory-supplied 80 amp disconnect). Heater control wiring should be run to the control box section. 10. Install bushing in hole between control box and single point box. Route unit power pigtails through bushing (Fig. 4). 11. See Table 1 to determine the correct electrical data table. Refer to Electrical Data Tables 2-25 to determine the heater and single point box. From the Electrical table determine the MOCP with heaters and accessories, the number of heaters, and the CRSINGLE---A00 part number. The correct figure can be determined using Table 1. The unit type (cooling only, heat pump, or COBRA™ combined unit), efficiency type (high, standard ASHRAE 90.1 compliant, standard), and the unit voltage are listed in Table 1. If more than one figure is

Table 1 — Electric Heater Data and Wiring Reference UNIT TYPE

EFFICIENCY TYPE

High

ELECTRIC COOLING

Standard 90.1 Compliant

Standard

High HEAT PUMP Standard

COBRA™ ENERGY RECOVERY UNITS (50HJ with 62AQ)

High

UNIT VOLTAGE-PHASE 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60

2

WIRING FIG. NO. PAGE NO. 11,13 5 12,14 5 12,15 5 15 5 11,13 5 12,14 5 12,15 5 15 5 11,13 5 12,14 5 12,15 5 15 5 16,17 36 18,19 36,37 18,20 36,37 16,17 36 18,19 36,37 18,20 36,37 18,20 36,37 21,22 54 23,24,26 55,56 23,25,27,28 55-57

ELECTRICAL DATA TABLE PAGE NO. 2,3 6-13 2,3 6-13 2,3 6-13 2,3 6-13 4-6 14-25 4-6 14-25 4-6 14-25 4-6 14-25 7-9 26-35 7-9 26-35 7-9 26-35 7-9 26-35 10-14 38-42 10-14 38-42 10-14 38-42 15-17 43-53 15-17 43-53 15-17 43-53 15-17 43-53 18-25 58-71 18-25 58-71 18-25 58-71

DISCONNECT MOUNTING LOCATION

EMT OR RIGID CONDUIT SINGLE (FIELD-SUPPLIED) POINT BOX

14. Remove knockouts for appropriate size conduit from unit block-off panel and single point box. Install conduit (rigid or electro-metallic tubing) through conduit drip boot as shown in Fig. 5. Drip boot will accept conduit sizes 3/4 in. to 11/2 inches. The drip boot eliminates the need for water-tight conduit fittings at the single point box. NOTE: Supply wiring must comply with NEC (National Electric Code) and all local requirements. 15. Place adhesive-backed wiring label on flanged side of heater cover. 16. Fasten heater cover to heater module with 2 screws provided with heater. Flanges of cover should face out. 17. Set manual reset limit switch by depressing button located between the terminals on the switch. Refer to Fig. 3 for switch location. 18. Close single point box cover and secure with one screw. 19. Replace control box cover, using remainder of screws saved from Step 3. 20. Replace indoor and outdoor panels with screws saved from Step 2. 21. Turn on unit power. 22. Mark the appropriate block on the unit nameplate for the accessory heater kW installed.

CENTER MANUAL RESET POST LIMIT SWITCH HEATER COVERS

SINGLE POINT MAIN BRACKET AND BOX HEATER HEATER HEATER CONTROL CONDUIT MOUNTING MODULE MODULE MOUNTING BOX DRIP BOOT SCREW (LOCATION 1) (LOCATION 2) BRACKET CONTROL WIRE TERMINAL BLOCK

Fig. 3 — Typical Component Location

21

11

23

13

CONTROL BOX BUSHING SINGLE POINT BOX MOUNTING SCREWS DRIP BOOT BRACKET MOUNTING SCREWS POWER WIRES

21

23

11

FOAM BUSHING

13 ALLIED PA CORP.

MODEL NO.

OD

ERIAL NO.

22.2 ISTED AIR NDITIONING UIP ACCESS 346N

23

.

P/N

2-

1 3 5610-4

REV

HEATER RELAYS HEATER MOUNTING SCREWS

Fig. 4 — Typical Single Point Kit Installation TRACK BD236B N—TRAN 3O—BV2075 E 60 HZ 30-8703 30V—OR 200V—RD OV—YL D 24V 75VA C—COMM

FLANGE

Fig. 6 — Typical Module Installation

CONDUIT

CONDUIT DRIP BOOT

WIRE TIE

Fig. 5 — Typical Conduit Installation 3

KEY

LEGEND HR — Heater Relay HTR — Heater LS — Limit Switch

Fig. 9 — Single-Phase Heater Wiring Fig. 7 — Typical Electric Heat Installation

RED WIRE

21

HEATER POWER WIRE HARNESS

23

11

13 ALLIED PA CORP.

21

MODEL NO.

OD

23

ERIAL NO.

SPLICE CONNECTOR

22.2 ISTED AIR NDITIONING UIP ACCESS 346N.

11

13

P/N

23 2-

1 3 5610-4

REV

ALLIED PA MODEL NO.

OD

ERIAL NO.

ISTED AIR NDITIONING UIP ACCESS 346N

23

.

P/N

2-

1 3 5610-4

Fig. 10 — Typical Single-Phase Wiring Installed

REV

Fig. 8 — Typical 3-Phase Wiring Installed

4

CRSINGLE002A00 OR CRSINGLE007A00 OR CRSINGLE012A00

NO SINGLE POINT BOX REQUIRED

Fig. 11 — Electric Heater Power Wiring Connections — Electric Cooling Units, 208/230-1-60 — Less Than 60 Amps MOCP

CRSINGLE009A00 OR CRSINGLE015A00

Fig. 14 — Electric Heater Power Wiring Connections — Electric Cooling Units, 208/230-3-60 — Greater Than 60 Amps MOCP

NO SINGLE POINT BOX REQUIRED (USE EXISTING SPACE IN UNIT) OR CRSINGLE006A00 OR CRSINGLE011A00

Fig. 12 — Electric Heater Power Wiring Connections — Electric Cooling Units, 208/230-3-60, 460-3-60, 575-3-60 — Less Than 60 Amps MOCP

CRSINGLE008A00 OR CRSINGLE014A00

Fig. 15 — Electric Heater Power Wiring Connections — Electric Cooling Units, 460-3-60 and 575-3-60 — Greater Than 60 Amps MOCP

CRSINGLE004A00

Fig. 13 — Electric Heater Power Wiring Connections — Electric Cooling Units, 208/230-1-60 — Greater Than 60 Amps MOCP 5

Table 2 — Electrical Data — High-Efficiency Cooling Only Units UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

CONV OUTLET

NO 208/230-1-60

STD YES

NO STD YES 208/230-3-60 NO HIGH STATIC

3 Tons

YES

NO STD YES 460-3-60 NO HIGH STATIC YES

STD 575-3-60 HIGH STATIC

NO YES NO YES

NO 208/230-1-60

STD YES

NO 4 Tons STD YES 208/230-3-60 NO HIGH STATIC YES

ELECTRIC HEAT Nominal kW† —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 9.8/13.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 9.8/13.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.0/16.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.0/16.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.0/16.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.0/16.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — — — — —/— 3.3/ 4.4 6.5/ 8.7 9.8/13.0 13.1/17.4 16.0/21.0 —/— 3.3/ 4.4 6.5/ 8.7 9.8/13.0 13.1/17.4 16.0/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 16.0/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 16.0/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 16.0/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 16.0/21.0

FLA

MCA

—/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.1 46.9/54.2 —/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.1 46.9/54.2 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — — — — —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5

25.6/ 25.6 26.0/ 29.0 35.5/ 40.0 45.4/ 51.4 53.5/ 60.0 64.8/ 73.8 31.6/ 31.6 31.6/ 34.0 40.5/ 45.0 50.4/ 56.4 58.5/ 65.0 69.8/ 78.8 18.5/ 18.5 18.5/ 19.4 23.1/ 25.7 28.8/ 32.3 33.5/ 37.7 47.8/ 54.2 24.5/ 24.5 24.5/ 24.5 28.1/ 30.7 33.8/ 37.3 38.5/ 42.7 52.8/ 59.2 19.4/ 19.4 19.4/ 20.5 24.2/ 26.8 29.9/ 33.4 34.6/ 38.8 48.9/ 55.4 25.4/ 25.4 25.4/ 25.5 29.2/ 31.8 34.9/ 38.4 39.6/ 43.8 53.9/ 60.4 9.0 11.8 16.0 20.0 23.8 11.7 15.1 18.7 22.7 26.5 9.4 12.3 16.5 20.5 24.3 12.1 15.6 19.2 23.2 27.0 7.3 9.5 7.7 9.8 35.2/ 35.2 35.2/ 35.2 45.4/ 51.4 64.8/ 73.8 84.7/ 96.8 100.9/115.5 41.2/ 41.2 41.2/ 41.2 50.4/ 56.4 69.8/ 78.8 89.7/101.8 105.9/120.5 22.5/ 22.5 23.1/ 25.7 28.8/ 32.3 47.8/ 54.2 60.8/ 69.3 28.5/ 28.5 28.5/ 30.7 33.8/ 37.3 52.8/ 59.2 65.8/ 74.3 23.4/ 23.4 24.2/ 26.8 29.9/ 33.4 48.9/ 55.4 62.0/ 70.4 29.4/ 29.4 29.4/ 31.8 34.9/ 38.4 53.9/ 60.4 67.0/ 75.4

6

DISCONNECT SIZE

POWER SUPPLY* Fuse or HACR Bkr 30/30 30/30 40/40 50/60 60/60 — 35/35 35/35 45/45 60/60 — — 25/25 25/25 25/30 30/35 35/40 50/60 30/30 30/30 30/35 35/40 40/45 60/60 25/25 25/25 30/30 35/35 35/40 50/60 30/30 30/30 35/35 40/40 40/45 — 20 20 20 25 25 20 20 20 25 30 20 20 20 25 25 20 20 20 25 30 20 20 20 20 45/45 45/45 50/60 — — — 50/50 50/50 60/60 — — — 30/30 30/30 30/35 50/60 — 35/35 35/35 35/40 60/60 — 30/30 30/30 35/35 50/60 — 35/35 35/35 40/40 — —

MOCP

FLA

LRA

— — — — — 70/ 80 — — — — 60/ 70 70/ 80 — — — — — — — — — — — — — — — — — — — — — — — 60/ 70 — — — — — — — — — — — — — — — — — — — — — — — — — — — 70/ 80 90/100 110/125 — — — 70/ 80 90/110 110/125 — — — — 70/ 70 — — — — 70/ 80 — — — — 70/ 80 — — — 60/ 70 70/ 80

25/ 25 25/ 27 33/ 37 42/ 47 49/ 55 60/ 68 30/ 30 30/ 32 38/ 42 47/ 53 55/ 61 65/ 73 18/ 18 18/ 18 21/ 24 26/ 30 31/ 35 44/ 50 24/ 24 24/ 24 27/ 29 32/ 35 36/ 40 50/ 55 19/ 19 19/ 19 22/ 25 28/ 31 32/ 36 45/ 51 25/ 25 25/ 25 28/ 30 33/ 36 37/ 41 51/ 56 9 11 15 18 22 11 13 17 21 24 9 11 15 19 22 12 14 18 21 25 7 9 8 10 34/ 34 34/ 34 42/ 47 60/ 68 78/ 89 93/106 39/ 39 39/ 39 47/ 53 65/ 73 83/ 95 98/112 22/ 22 22/ 24 26/ 30 44/ 50 56/ 64 27/ 27 27/ 29 32/ 35 50/ 55 62/ 69 23/ 23 23/ 25 28/ 31 45/ 51 57/ 65 29/ 29 29/ 30 33/ 36 51/ 56 63/ 70

101/101 101/101 101/101 101/101 101/101 101/101 106/106 106/106 106/106 106/106 106/106 106/106 90/ 90 90/ 90 90/ 90 90/ 90 90/ 90 90/ 90 95/ 95 95/ 95 95/ 95 95/ 95 95/ 95 95/ 95 120/120 120/120 120/120 120/120 120/120 120/120 124/124 124/124 124/124 124/124 124/124 124/124 46 46 46 46 46 48 48 48 48 48 60 60 60 60 60 62 63 63 63 63 36 30 48 49 139/139 139/139 139/139 139/139 139/139 139/139 144/144 144/144 144/144 144/144 144/144 144/144 106/106 106/106 106/106 106/106 106/106 111/111 111/111 111/111 111/111 111/111 136/136 136/136 136/136 136/136 136/136 140/140 140/140 140/140 140/140 140/140

Table 2 — Electrical Data — High-Efficiency Cooling Only Units (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

CONV OUTLET

NO STD YES 460-3-60 4 Tons (cont)

NO HIGH STATIC YES

STD 575-3-60 HIGH STATIC

FLA HACR IFM LRA MCA MOCP NEC UL

— — — — — — — —

NO YES NO YES

ELECTRIC HEAT Nominal kW† — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — — — —

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Underwriters’ Laboratories

DISCONNECT SIZE

POWER SUPPLY*

FLA

MCA

— 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — — — —

10.6 11.8 20.0 23.8 37.3 13.3 15.1 22.7 26.5 40.0 11.0 12.3 20.5 24.3 37.8 13.7 15.6 23.2 27.0 40.5 10.1 12.2 10.4 12.6

Fuse or HACR Bkr 20 20 25 25 40 20 20 25 30 45 20 20 25 25 40 20 20 25 30 45 20 20 20 20

MOCP

FLA

LRA

— — — — — — — — — — — — — — — — — — — — — — — —

10 11 18 22 34 13 13 21 24 37 11 11 19 22 35 13 14 21 25 37 10 12 10 12

53 54 54 54 54 55 56 56 56 56 67 68 68 68 68 70 70 70 70 70 45 47 57 58

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage =

452 + 464 + 455 3

1371 3 = 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. % Voltage Imbalance= 100 x 7 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. =

*Used to determine minimum disconnect per NEC. †Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v or 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 3. Non-fused disconnect switch cannot be used when rooftop unit electrical ratings exceed 80 amps. 4. 575-v units have UL, Canada approval only. Electric heaters are not available for 3 to 6 ton, 575-v units.

7

Table 2 — Electrical Data — High-Efficiency Cooling Only Units (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

CONV OUTLET

NO 208/230-1-60

STD YES

NO STD YES 208/230-3-60 NO HIGH STATIC 5 Tons

YES

NO STD YES 460-3-60 NO HIGH STATIC YES

STD 575-3-60 HIGH STATIC

NO YES NO YES

NO STD YES 6 Tons

208/230-3-60 NO HIGH STATIC YES

ELECTRIC HEAT Nominal kW† —/— 4.9/ 6.5 6.5/ 8.7 8.7/13.0 13.0/17.4 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 8.7/13.0 13.0/17.4 15.8/21.0 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — — — — —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5

FLA

MCA

—/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.1 — 7.2 13.8 16.8 27.7 30.1 — 7.2 13.8 16.8 27.7 30.1 — 7.2 13.8 16.8 27.7 30.1 — — — — —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8

46.3/ 46.3 46.3/ 46.3 50.3/ 56.3 69.7/ 78.7 89.5/101.6 105.8/120.4 52.3/ 52.3 52.3/ 52.3 55.3/ 61.3 74.7/ 83.7 94.5/106.6 110.8/125.4 28.9/ 28.9 28.9/ 28.9 34.6/ 38.8 48.9/ 55.4 62.0/ 70.4 76.3/ 86.9 34.9/ 34.9 34.9/ 34.9 39.6/ 43.8 53.9/ 60.4 67.0/ 75.4 81.3/ 91.9 30.6/ 30.6 30.6/ 30.6 36.7/ 40.9 51.1/ 57.5 64.1/ 72.5 78.4/ 89.1 36.6/ 36.6 36.6/ 36.6 41.7/ 45.9 56.1/ 62.5 69.1/ 77.5 83.4/ 94.1 14.7 14.7 20.5 24.3 37.8 40.8 17.4 17.4 23.2 27.0 40.5 43.5 15.5 15.5 21.5 25.3 38.8 41.8 18.2 18.2 24.2 28.0 41.5 44.5 11.6 13.8 12.2 14.4 32.8/ 32.8 32.8/ 32.8 34.6/ 38.8 48.9/ 55.4 62.0/ 70.4 76.3/ 86.9 38.8/ 38.8 38.8/ 38.8 39.6/ 43.8 53.9/ 60.4 67.0/ 75.4 81.3/ 91.9 34.5/ 34.5 34.5/ 34.5 36.7/ 40.9 51.1/ 57.5 64.1/ 72.5 78.4/ 89.1 40.5/ 40.5 40.5/ 40.5 41.7/ 45.9 56.1/ 62.5 69.1/ 77.5 83.4/ 94.1

8

DISCONNECT SIZE

POWER SUPPLY* Fuse or HACR Bkr 60/60 60/60 60/60 — — — 60/60 60/60 — — — — 35/35 35/35 35/40 50/60 — — 40/40 40/40 40/45 — — — 35/35 35/35 40/45 60/60 — — 40/40 40/40 45/50 — — — 20 20 25 25 40 45 20 20 25 30 45 45 20 20 25 30 40 45 20 20 25 30 45 45 20 20 20 20 40/40 40/40 40/40 50/60 — — 45/45 45/45 45/45 — — — 40/40 40/40 40/45 60/60 — — 45/45 45/45 45/50 — — —

MOCP

FLA

LRA

— — — 70/ 80 90/110 110/125 — — 60/ 70 80/ 90 100/110 125/150 — — — — 70/ 80 80/ 90 — — — 60/ 70 70/ 80 90/100 — — — — 70/ 80 80/ 90 — — — 60/ 70 70/ 80 90/100 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — 70/ 80 80/ 90 — — — 60/ 70 70/ 80 90/100 — — — — 70/ 80 80/ 90 — — — 60/ 70 70/ 80 90/100

45/ 45 45/ 45 46/ 52 64/ 72 82/ 93 97/111 50/ 50 50/ 50 52/ 57 70/ 78 88/ 99 103/116 28/ 28 28/ 28 32/ 36 45/ 51 57/ 65 70/ 80 34/ 34 34/ 34 37/ 41 51/ 56 63/ 70 76/ 86 30/ 30 30/ 30 34/ 38 47/ 53 59/ 67 72/ 82 36/ 36 36/ 36 39/ 43 53/ 58 65/ 72 78/ 87 14 10 19 22 35 38 17 17 21 25 37 40 15 15 20 23 36 38 18 18 22 26 38 41 11 13 12 14 32/ 32 32/ 32 32/ 36 45/ 51 57/ 65 70/ 80 37/ 37 37/ 37 37/ 41 51/ 56 63/ 70 76/ 86 34/ 34 34/ 34 34/ 38 47/ 53 59/ 67 72/ 82 39/ 39 39/ 39 39/ 43 53/ 58 65/ 72 78/ 87

216/216 216/216 216/216 216/216 216/216 216/216 221/221 221/221 221/221 221/221 221/221 221/221 168/168 168/168 168/168 168/168 168/168 168/168 173/173 173/173 173/173 173/173 173/173 173/173 187/187 187/187 187/187 187/187 187/187 187/187 192/192 192/192 192/192 192/192 192/192 192/192 84 84 84 84 84 84 86 87 87 87 87 87 93 94 94 94 94 94 96 96 96 96 96 96 67 69 75 77 200/200 200/200 200/200 200/200 200/200 200/200 205/205 205/205 205/205 205/205 205/205 205/205 219/219 219/219 219/219 219/219 219/219 219/219 224/224 224/224 224/224 224/224 224/224 224/224

Table 2 — Electrical Data — High-Efficiency Cooling Only Units (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

CONV OUTLET

NO STD YES 460-3-60 6 Tons (cont)

NO HIGH STATIC YES

STD 575-3-60 HIGH STATIC

FLA HACR IFM LRA MCA MOCP NEC UL

— — — — — — — —

NO YES NO YES

ELECTRIC HEAT Nominal kW† — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — — — —

DISCONNECT SIZE

POWER SUPPLY*

FLA

MCA

— 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — — — —

15.2 15.2 20.5 24.3 37.8 41.6 17.9 17.9 23.2 27.0 40.5 44.3 16.0 16.0 21.5 25.3 38.8 42.6 18.7 18.7 24.2 28.0 41.5 45.3 12.2 14.3 12.8 15.0

Fuse or HACR Bkr 20 20 25 25 40 45 20 20 25 30 45 45 20 20 25 30 40 45 25 25 25 30 45 50 20 20 20 20

MOCP

FLA

LRA

— — — — — — — — — — — — — — — — — — — — — — — — — — — —

15 15 19 22 35 38 17 17 21 25 37 41 16 16 20 23 36 39 18 18 22 26 38 42 13 15 13 15

97 97 97 97 97 97 99 99 99 99 99 99 106 107 107 107 107 107 108 109 109 109 109 109 78 79 87 89

Example: Supply voltage is 460-3-60.

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Underwriters’ Laboratories

AB = 452 v BC = 464 v AC = 455 v Average Voltage =

452 + 464 + 455 3

1371 3 = 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. % Voltage Imbalance= 100 x 7 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. =

*Used to determine minimum disconnect per NEC. †Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v or 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 3. Non-fused disconnect switch cannot be used when rooftop unit electrical ratings exceed 80 amps. 4. 575-v units have UL, Canada approval only. Electric heaters are not available for 3 to 6 ton, 575-v units.

9

Table 2 — Electrical Data — High-Efficiency Cooling Only Units (cont) ELECTRIC HEATER UNIT SIZE

NOMINAL V-PH-Hz

POWER SUPPLY*

DISCONNECT SIZE

Nominal kW†

FLA

MCA

Fuse or HACR Bkr

NO

— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4

—/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0

38.2/ 38.2 38.2/ 40.6 51.1/ 57.5 74.0/ 84.0 92.8/105.6 119.9/136.9

45/45 45/45 60/60 — — —

— — — 80/ 90 100/110 125/150

40/ 40 40/ 40 47/ 53 68/ 77 85/ 97 110/126

242/242 242/242 242/242 242/242 242/242 242/242

STD

YES

— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4

—/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0

44.2/ 44.2 44.2/ 45.6 56.1/ 62.5 79.0/ 89.0 97.8/110.6 124.9/141.9

50/50 50/50 — — — —

— — 60/ 70 80/ 90 100/125 125/150

46/ 46 46/ 46 53/ 58 74/ 83 91/103 116/131

247/247 247/247 247/247 247/247 247/247 247/247

HIGH STATIC

NO

— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4

—/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0

41.3/ 41.3 41.3/ 44.5 54.9/ 61.4 77.9/ 87.8 96.6/109.5 123.7/140.8

45/45 50/50 — — — —

— — 60/ 70 80/ 90 100/110 125/150

44/ 44 44/ 44 51/ 56 72/ 81 89/101 114/129

267/267 267/267 267/267 267/267 267/267 267/267

HIGH STATIC

YES

— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4

—/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0

47.3/ 47.3 47.3/ 49.5 59.9/ 66.4 82.9/ 92.8 101.6/114.5 128.7/145.8

50/50 60/60 — — — —

— — 70/ 70 90/100 110/125 150/150

49/ 49 49/ 49 56/ 62 77/ 86 94/106 119/135

271/271 271/271 271/271 271/271 271/271 271/271

STD

NO

— 13.9 16.5 27.8 33.0 41.7

— 16.7 19.8 33.4 39.7 50.2

19.2 25.1 29.1 46.0 53.9 66.9

20 20 20 50 60 —

— — — — — 70

20 23 27 42 50 62

121 121 121 121 121 121

STD

YES

— 13.9 16.5 27.8 33.0 41.7

— 16.7 19.8 33.4 39.7 50.2

21.9 28.5 31.8 48.7 56.6 69.6

20 20 35 50 60 —

— — — — — 70

23 26 29 45 52 64

123 123 123 123 123 123

HIGH STATIC

NO

— 13.9 16.5 27.8 33.0 41.7

— 16.7 19.8 33.4 39.7 50.2

20.6 26.9 30.8 47.8 55.6 68.7

20 20 35 50 60 —

— — — — — 70

22 25 28 44 51 63

133 134 134 134 134 134

HIGH STATIC

YES

— 13.9 16.5 27.8 33.0 41.7

— 16.7 19.8 33.4 39.7 50.2

23.3 30.3 33.5 50.5 58.3 71.4

20 35 35 60 60 —

— — — — — 80

24 27 31 46 54 66

135 136 136 136 136 136

STD

NO

— 17.0 34.0

— 16.4 32.7

14.6 23.8 44.3

20 20 45

— — —

15 22 41

94 95 95

STD

YES

— 17.0 34.0

— 16.4 32.7

16.8 26.5 44.3

20 20 45

— — —

17 24 43

96 96 96

HIGH STATIC

NO

— 17.0 34.0

— 16.4 32.7

15.8 25.2 45.7

20 20 50

— — —

17 23 42

104 104 104

HIGH STATIC

YES

— 17.0 34.0

— 16.4 32.7

17.9 27.9 45.7

20 20 50

— — —

19 25 44

106 106 106

STD

NO

— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4

—/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0

40.2/ 40.2 40.2/ 40.6 51.1/ 57.5 74.0/ 84.0 92.8/105.6 119.9/136.9

45/45 45/45 60/60 — — —

— — — 80/ 90 100/110 110/150

42/ 42 42/ 42 47/ 53 68/ 77 85/ 97 110/126

276/276 276/276 276/276 276/276 276/276 276/276

STD

YES

— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4

—/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0

46.2/ 46.2 46.2/ 46.2 56.1/ 62.5 79.0/ 89.0 97.8/110.6 124.9/141.9

50/50 50/50 — — — —

— — 60/ 70 80/ 90 100/125 125/150

48/ 48 48/ 48 53/ 58 74/ 83 91/103 116/131

281/281 281/281 281/281 281/281 281/281 281/281

HIGH STATIC

NO

— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4

—/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0

43.3/ 43.3 43.3/ 44.5 54.9/ 61.4 77.9/ 87.8 96.6/109.5 123.7/140.8

50/50 50/50 — — — —

— — 60/ 70 80/ 90 100/110 125/150

46/ 46 46/ 46 51/ 56 72/ 81 89/101 114/129

301/301 301/301 301/301 301/301 301/301 301/301

HIGH STATIC

YES

— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4

—/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0

49.3/ 49.3 49.3/ 49.5 59.9/ 66.4 82.9/ 92.8 101.6/114.5 128.7/145.8

60/60 60/60 — — — —

— — 70/ 70 90/100 110/125 150/150

51/ 51 51/ 51 56/ 62 77/ 86 94/106 119/135

305/305 305/305 305/305 305/305 305/305 305/305

STD

NO

— 13.9 16.5 27.8 33.0 41.7

— 16.7 19.8 33.4 39.7 50.2

21.5 25.1 29.1 46.0 53.9 66.9

20 20 20 50 60 —

— — — — — 70

23 23 27 42 50 62

143 143 143 143 143 143

STD

YES

— 13.9 16.5 27.8 33.0 41.7

— 16.7 19.8 33.4 39.7 50.2

24.2 28.5 31.8 48.7 56.6 69.6

20 20 35 50 60 —

— — — — — 70

25 26 29 45 52 64

145 145 145 145 145 145

HIGH STATIC

NO

— 13.9 16.5 27.8 33.0 41.7

— 16.7 19.8 33.4 39.7 50.2

22.9 26.9 30.8 47.8 55.6 68.7

20 20 35 50 60 —

— — — — — 70

24 25 28 44 51 63

155 156 156 156 156 156

HIGH STATIC

YES

— 13.9 16.5 27.8 33.0 41.7

— 16.7 19.8 33.4 39.7 50.2

25.6 30.3 33.5 50.5 58.3 71.4

20 35 35 60 60 —

— — — — — 80

27 27 31 46 54 66

157 158 158 158 158 158

IFM TYPE

CONV OUTLET

STD

208/230-3-60

71/2 Tons

460-3-60

575-3-60

208/230-3-60

81/2 Tons

460-3-60

10

MOCP

FLA

LRA

Table 2 — Electrical Data — High-Efficiency Cooling Only Units (cont) UNIT SIZE

NOMINAL V-PH-Hz

81/2 Tons (cont)

IFM TYPE

CONV OUTLET

STD

NO

STD

YES

HIGH STATIC

NO

HIGH STATIC

YES

STD

NO

STD

YES

HIGH STATIC

NO

HIGH STATIC

YES

STD

NO

STD

YES

HIGH STATIC

NO

HIGH STATIC

YES

STD

NO

STD

YES

HIGH STATIC

NO

HIGH STATIC

YES

575-3-60

208/230-3-60

10 Tons

460-3-60

575-3-60

ELECTRIC HEATER Nominal FLA kW† — — 17.0 16.4 34.0 32.7 — — 17.0 16.4 34.0 32.7 — — 17.0 16.4 34.0 32.7 — — 17.0 16.4 34.0 32.7 — —/— 7.8/10.4 21.7/ 25.0 12.0/16.0 33.4/ 38.5 24.0/32.0 66.7/ 77.0 31.8/42.4 88.4/102.0 37.5/50.0 104.2/120.3 — —/— 7.8/10.4 21.7/ 25.0 12.0/16.0 33.4/ 38.5 24.0/32.0 66.7/ 77.0 31.8/42.4 88.4/102.0 37.5/50.0 104.2/120.3 — —/— 7.8/10.4 21.7/ 25.0 12.0/16.0 33.4/ 38.5 24.0/32.0 66.7/ 77.0 31.8/42.4 88.4/102.0 37.5/50.0 104.2/120.3 — —/— 7.8/10.4 21.7/ 25.0 12.0/16.0 33.4/ 38.5 24.0/32.0 66.7/ 77.0 31.8/42.4 88.4/102.0 37.5/50.0 104.2/120.3 — — 13.9 16.7 16.5 19.8 33.0 39.7 41.7 50.2 50.0 60.1 — — 13.9 16.7 16.5 19.8 33.0 39.7 41.7 50.2 50.0 60.1 — — 13.9 16.7 16.5 19.8 33.0 39.7 41.7 50.2 50.0 60.1 — — 13.9 16.7 16.5 19.8 33.0 39.7 41.7 50.2 50.0 60.1 — — 17.0 16.4 34.0 32.7 51.0 49.1 — — 17.0 16.4 34.0 32.7 51.0 49.1 — — 17.0 16.4 34.0 32.7 51.0 49.1 — — 17.0 16.4 34.0 32.7 51.0 49.1

LEGEND FLA HACR IFM LRA MCA MOCP NEC UL

— — — — — — — —

18.2 23.8 44.3 20.4 26.5 46.9 18.2 23.8 44.3 21.5 27.9 48.3 53.0/ 53.0 53.0/ 53.0 54.9/ 61.4 96.6/109.5 123.7/140.8 143.5/133.5 59.0/ 59.0 59.0/ 59.0 59.9/ 66.4 101.6/114.5 128.7/145.8 148.5/137.5 57.4/ 57.4 57.4/ 57.4 60.4/ 66.9 102.1/115.0 129.2/146.3 149.0/139.0 63.4/ 63.4 63.4/ 63.4 65.4/ 71.9 107.1/120.0 134.2/151.3 154.0/143.0 24.9 26.9 30.8 55.6 68.7 66.1 27.6 30.3 33.5 58.3 71.4 70.1 27.5 30.1 34.1 58.9 71.9 69.4 30.2 33.5 36.8 61.6 74.6 73.4 19.1 25.2 45.7 53.9 21.3 27.9 48.3 56.5 21.2 27.8 48.3 56.5 23.4 30.5 50.9 59.1

POWER SUPPLY* Fuse or HACR Bkr 20 20 45 25 25 50 20 20 45 25 25 50 60/60 60/60 — — — — 70/70 — — — — — 70/70 — — — — — 70/70 — — — — — 20 20 35 60 — — 20 35 35 60 — — 20 35 40 60 — — 35 40 40 — — — 25 25 50 60 25 25 50 60 25 25 50 — 25 35 60 —

DISCONNECT SIZE MOCP

FLA

LRA

— — — — — — — — — — — — — — 60/ 70 100/110 125/150 150/150 — 70/ 70 70/ 70 110/125 150/150 150/150 — 70/ 70 70/ 80 110/125 150/150 150/175 — 70/ 70 80/ 80 110/125 150/175 175/175 — — — — 70 80 — — — — 80 80 — — — — 80 80 — — — 70 80 80 — — — — — — — — — — — 70 — — — 70

19 22 41 21 24 43 19 22 41 22 25 44 56/ 56 56/ 56 56/ 56 89/101 114/129 132/151 61/ 61 61/ 61 61/ 62 94/106 119/135 138/156 61/ 61 61/ 61 61/ 62 94/106 119/135 137/156 66/ 66 66/ 66 66/ 67 99/111 124/140 143/161 26 26 28 51 63 75 29 29 31 54 66 77 29 29 31 54 66 78 32 32 34 57 69 80 20 23 42 61 22 25 44 63 23 26 44 63 25 28 46 65

114 115 115 116 116 116 114 115 115 126 126 126 341/341 341/341 341/341 341/341 341/341 341/341 345/345 345/345 345/345 345/345 345/345 345/345 364/364 364/364 364/364 364/364 364/364 364/364 369/369 369/369 369/369 369/369 369/369 369/369 170 171 171 171 171 171 172 173 173 173 173 173 182 182 182 182 182 182 184 184 184 184 184 184 136 136 136 136 138 138 138 138 145 146 146 146 147 148 148 148

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Underwriters’ Laboratories

Average Voltage =

452 + 464 + 455 3

1371 3 = 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. % Voltage Imbalance = 100 x 7 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. =

*Used to determine minimum disconnect per NEC. †Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v or 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance = 100 x

MCA

max voltage deviation from average voltage average voltage

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 3. Non-fused disconnect switch cannot be used when rooftop unit electrical ratings exceed 80 amps. 4. 575-v units have UL, Canada approval only. Electric heaters are not available for 3 to 6 ton, 575-v units.

11

Table 2 — Electrical Data — High-Efficiency Cooling Only Units (cont) NOMINAL V-PH-Hz

UNIT

IFM TYPE

CONV OUTLET

STD

NO

STD

YES

STD

NO

STD

YES

STD

NO

STD

YES

208/230-3-60

121/2 Tons 460-3-60

575-3-60

FLA HACR IFM LRA MCA MOCP NEC UL

— — — — — — — —

ELECTRIC HEATER Nominal FLA kW† — —/— 7.8/10.4 21.7/ 25.0 12.0/16.0 33.4/ 38.5 24.0/32.0 66.7/ 77.0 31.8/42.4 88.4/102.0 37.5/50.0 104.2/120.3 — —/— 7.8/10.4 21.7/ 25.0 12.0/16.0 33.4/ 38.5 24.0/32.0 66.7/ 77.0 31.8/42.4 88.4/102.0 37.5/50.0 104.2/120.3 — — 13.9 16.7 16.5 19.8 33.0 39.7 41.7 50.2 50.0 60.1 — — 13.9 16.7 16.5 19.8 33.0 39.7 41.7 50.2 50.0 60.1 — — 17.0 16.4 34.0 32.7 51.0 49.1 — — 17.0 16.4 34.0 32.7 51.0 49.1

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Underwriters’ Laboratories

MCA 60.6/ 60.6 60.6/ 60.6 60.4/ 66.9 102.1/115.0 129.2/146.3 149.0/139.0 66.6/ 66.6 66.6/ 66.6 65.4/ 71.9 107.1/120.0 134.2/151.3 154.0/143.0 29.1 30.1 34.1 58.9 71.9 69.4 31.8 33.5 36.8 61.6 74.6 73.4 23.7 27.8 48.3 56.5 25.9 30.5 50.9 59.1

POWER SUPPLY* Fuse or HACR Bkr 70/70 — — — — — 70/70 — — — — — 35 35 40 60 — — 35 40 40 — — — 30 30 50 — 30 35 60 —

DISCONNECT SIZE MOCP

FLA

LRA

— 70/ 70 70/ 80 110/125 150/150 150/175 — 70/ 70 80/ 80 110/125 150/175 175/175 — — — — 80 80 — — — 70 80 80 — — — 70 — — — 70

64/ 64 64/ 64 64/ 64 94/106 119/135 137/156 70/ 70 70/ 70 70/ 70 99/111 124/140 143/161 31 31 31 54 66 78 33 33 34 57 69 80 25 26 44 63 27 28 46 65

426/426 426/426 426/426 426/426 426/426 426/426 431/431 431/431 431/431 431/431 431/431 431/431 197 197 197 197 197 197 199 199 199 199 199 199 153 154 154 154 155 155 155 155

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage =

452 + 464 + 455 3

1371 3 = 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. % Voltage Imbalance = 100 x 7 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. =

*Used to determine minimum disconnect per NEC. †Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v or 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 3. Non-fused disconnect switch cannot be used when rooftop unit electrical ratings exceed 80 amps. 4. 575-v units have UL, Canada approval only. Electric heaters are not available for 3 to 6 ton, 575-v units.

12

Table 3 — Electric Heating Usage — High-Efficiency Cooling Only Units UNIT SIZE

VOLTAGE (60 Hz) 208/230/240 (single phase)

3 Tons

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (single phase)

4 Tons

208/230/240 (3 phase) 460/480 (3 phase)

208/230/240 (single phase)

5 Tons

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (3 phase) 6 Tons 460/480 (3 phase)

208/230/240 (3 phase) 71/2 Tons 460/480 (3 phase) 575 (3 phase) 208/230/240 (3 phase) 81/2 Tons 460/480 (3 phase) 575 (3 phase) 208/230/240 (3 phase)

10 Tons

460/480 (3 phase) 575 (3 phase) 208/230/240 (3 phase)

121/2 Tons

460/480 (3 phase) 575 (3 phase)

ACCESSORY kW 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 9.8/11.6/13.0* 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 12.0/14.7/16.0 5.5/ 6.0 8.1/ 8.8 10.6/11.5 12.9/14.0 3.3/ 4.0/ 4.4 6.5/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 16.0/19.3/21.0* 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 12.0/14.7/16.0 15.8/19.3/21.0* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 4.9/ 5.8/ 6.5 6.6/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 15.8/19.3/21.0* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5* 7.8/ 9.6/10.4 12.0/14.7/16.0 18.6/22.8/24.8 24.0/29.4/32.0 31.8/39.0/42.4 12.8/13.9 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7 17.0 34.0 7.8/ 9.6/10.4 12.0/14.7/16.0 18.6/22.8/24.8 24.0/29.4/32.0 31.8/39.0/42.4 12.8/13.9 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7 17.0 34.0 7.8/ 9.6/10.4 12.0/14.7/16.0 24.0/29.4/32.0 31.8/38.9/42.4 37.5/46.0/50.0 12.8/13.9 15.2/16.5 30.4/33.0 38.4/41.7 46.0/50.0 17.0 34.0 51.0 7.8/ 9.6/10.4 12.0/14.7/16.0 24.0/29.4/32.0 31.8/38.9/42.4 37.5/46.0/50.0 12.8/13.9 15.2/16.5 30.4/33.0 38.4/41.7 46.0/50.0 17.0 34.0 51.0

ACCESSORY HEATER PART NUMBER CRHEATER - - - A00 001 002 003 004 002+002 001 002 003 004 005 006 007 008 009 001 003 002+002 003+003 004+004 002 003 005 004+004 006 008 009 008+008 002 003 002+002 003+003 004+004 002 004 005 004+004 004+005 006 008 009 008+008 008+009 002 004 005 004+004 004+005 006 008 009 008+008 008+009 017 010 011 012 012+017 016 013 014 015 014+016 018 019 017 010 011 012 012+017 016 013 014 015 014+016 018 019 017 010 012 012+017 010+012 016 013 015 014+016 013+015 018 019 018+019 017 010 012 012+017 010+012 016 013 015 014+016 013+015 018 019 018+019

*Two heater packages required to provide kW indicated. †004 on units with convenience outlet. **002 on high-static units with convenience outlet. NOTES: 1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly. 2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kWnew = Heater kW rated x (unit power distribution voltage/rated heater voltage)2 As an example: For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kW new = 16 kW (215/240)2 kW new = 12.8 kW (rating at 215 v)

13

SINGLE POINT BOX PACKAGE NO. CRSINGLE---A00 — — —† — 004 — — — — —** — — — — — — 004 004 004 — — —** 002 — — — — — —* 004 004 004 — — —** 002 002 — — — — — — — —** 002 002 — — — — — 006 006 007 007 009 006 006 006 006 008 006 006 011 011 012 012 015 011 011 011 011 014 011 011 011 012 012 015 015 011 011 011 014 014 011 011 014 012 012 012 015 015 011 011 011 014 014 011 014 014

Table 4 — Electrical Data — Standard-Efficiency ASHRAE 90.1 Compliant Cooling Only Units (Without Convenience Outlet) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-1-60 ALT

STD

208/230-3-60

ALT

3 Tons HIGH

STD

460-3-60

ALT

HIGH

575-3-60

STD ALT HIGH

STD 208/230-1-60 ALT

STD

208/230-3-60

ALT

4 Tons HIGH

STD

460-3-60

ALT

HIGH

575-3-60

STD ALT HIGH

ELECTRIC HEAT Nominal kW —/— 3.3/ 4.4 4.9/ 6.5 6.4/ 8.7 7.9/10.5 9.8/13.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 9.8/13.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.2/16.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.3/16.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.3/16.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — — — —/— 3.3/ 4.4 6.5/ 8.7 9.3/13.0 13.1/17.4 15.8/21.0 —/— 3.3/ 4.4 6.5/ 8.7 9.3/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — — —

FLA

MCA

—/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.8 46.9/54.2 —/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.8 46.9/54.2 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.4 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.4 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.4 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — — — —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 18.1/20.9 33.4/38.4 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.4 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.4 43.8/50.5 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — — —

25.2/25.2 25.2/27.3 33.7/38.2 43.6/49.7 51.8/59.1 63.0/72.1 26.6/26.6 26.6/29.0 35.5/40.0 45.4/51.4 53.5/60.8 64.8/73.8 17.7/17.7 17.7/17.7 21.3/23.9 27.0/30.5 31.7/35.9 46.1/52.4 19.1/19.1 19.1/19.4 23.1/25.7 28.8/32.3 33.5/37.7 47.8/54.2 19.4/19.4 19.4/19.7 23.4/26.0 29.2/32.7 33.9/38.1 48.2/54.6 7.6 10.6 14.9 18.9 22.7 8.4 11.6 15.9 19.9 23.7 8.9 12.3 16.5 20.5 24.3 5.5 6.0 6.3 34.0/ 34.0 34.0/ 34.0 43.6/ 49.7 63.0/ 72.1 82.9/ 95.0 99.2/113.8 35.4/ 35.4 35.4/ 35.4 45.4/ 51.4 64.8/ 73.8 84.7/ 96.8 100.9/115.5 24.2/ 24.2 24.2/ 24.2 27.0/ 30.5 46.1/ 52.4 59.1/ 67.5 25.6/ 25.6 25.6/ 25.7 28.8/ 32.3 47.8/ 54.2 60.8/ 69.3 25.9/ 25.9 25.9/ 26.0 29.2/ 32.7 48.2/ 54.6 61.2/ 69.6 13.0 13.0 19.5 23.3 36.8 13.3 13.3 19.9 23.7 37.2 13.8 13.8 20.5 24.3 37.8 9.2 9.3 9.7

14

DISCONNECT SIZE*

POWER SUPPLY MOCP† 30/30 30/30 35/40 45/50 60/60 70/80** 35/35 35/35 40/40 50/60 60/70** 70/80** 25/25 25/25 25/25 30/35 35/40 50/60 25/25 25/25 25/30 30/35 35/40 50/60 25/25 25/25 30/30 30/35 35/40 50/60 15 15 15 20 25 15 15 20 20 25 15 15 20 25 25 15 15 15 40/ 40 40/ 40 45/ 50 70/ 80** 90/100** 100/125** 45/ 45 45/ 45 50/ 60 70/ 80** 90/100** 110/125** 30/ 30 30/ 30 30/ 35 50/ 60 60/ 70** 30/ 30 30/ 30 30/ 35 50/ 60 70/ 70** 30/ 30 30/ 30 30/ 35 50/ 60 70/ 70** 20 20 20 25 40 20 20 20 25 40 20 20 25 25 40 15 15 15

FLA

LRA

24/24 24/25 31/35 40/46 48/54 58/66 26/26 26/27 33/37 42/47 49/56 60/68 17/17 17/17 20/22 25/28 29/33 42/48 19/19 19/19 21/24 26/30 31/35 44/50 19/19 19/19 22/24 27/30 31/35 44/50 7 10 14 17 21 8 11 15 18 22 9 11 15 19 22 6 7 7 32/ 32 32/ 32 40/ 46 58/ 66 76/ 87 91/105 34/ 34 34/ 34 42/ 47 60/ 68 78/ 89 93/106 23/ 23 23/ 23 25/ 28 42/ 48 54/ 62 25/ 25 25/ 25 26/ 30 44/ 50 56/ 64 25/ 25 25/ 25 27/ 30 44/ 50 56/ 64 13 13 18 21 34 13 13 18 22 34 13 13 19 22 35 10 10 10

106/106 106/106 106/106 106/106 106/106 106/106 111/111 111/111 111/111 111/111 111/111 111/111 85/ 85 85/ 85 85/ 85 85/ 85 85/ 85 85/ 85 90/ 90 90/ 90 90/ 90 90/ 90 90/ 90 90/ 90 109/109 109/109 109/109 109/109 109/109 109/109 44 45 45 45 45 48 48 48 48 48 57 57 57 57 57 34 37 56 129/129 129/129 129/129 129/129 129/129 129/129 133/133 133/133 133/133 133/133 133/133 133/133 101/101 101/101 101/101 101/101 101/101 105/105 105/105 105/105 105/105 105/105 124/124 124/124 124/124 124/124 124/124 51 51 51 51 51 53 53 53 53 53 62 62 62 62 62 41 42 49

Table 4 — Electrical Data — Standard-Efficiency ASHRAE 90.1 Compliant Cooling Only Units (Without Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-1-60 ALT

STD

ALT

208/230-3-60

5 Tons HIGH

STD

ALT

460-3-60

HIGH

STD ALT HIGH

575-3-60

ELECTRIC HEAT Nominal kW —/— 4.9/ 6.5 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.0 — 6.0 11.5 14.0 23.0 25.0 — 6.0 11.5 14.0 23.0 25.0 — — —

FLA

MCA

—/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.1 — 7.2 13.8 16.8 27.7 30.1 — 7.2 13.8 16.8 27.7 30.1 — — —

43.3/ 43.3 43.3/ 43.3 46.6/ 52.7 66.0/ 75.1 85.9/ 98.0 102.2/116.8 44.0/ 44.0 44.0/ 44.0 47.5/ 53.6 66.9/ 76.0 86.8/ 98.9 103.0/117.6 27.3/ 27.3 27.3/ 27.3 34.7/ 38.9 49.1/ 55.4 62.1/ 70.5 76.4/ 87.1 26.6/ 26.6 26.6/ 26.6 33.9/ 38.1 48.2/ 54.6 61.2/ 69.6 75.6/ 86.2 28.9/ 28.9 28.9 28.9 36.7/ 40.9 51.1/ 57.4 64.1/ 72.5 78.4/ 89.1 13.2 13.2 21.2 24.9 38.5 41.5 13.5 13.5 21.5 25.3 38.8 41.8 13.5 13.5 21.5 25.3 38.8 41.8 9.7 9.9 9.9

— — — — — — —

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

% Voltage Imbalance = 100 x

FLA

LRA

42/ 42 42/ 42 43/ 48 61/ 69 79/ 90 94/107 42/ 42 42/ 42 44/ 49 62/ 70 80/ 91 95/108 27/ 27 27/ 27 32/ 36 45/ 51 57/ 65 70/ 80 26/ 26 26/ 26 31/ 35 44/ 50 56/ 64 70/ 79 29/ 29 29/ 29 34/ 38 47/ 53 59/ 67 72/ 82 13 13 19 23 35 38 13 13 20 23 36 38 13 13 20 23 36 38 11 11 11

161/161 161/161 161/161 161/161 161/161 161/161 184/184 184/184 184/184 184/184 184/184 184/184 128/128 128/128 128/128 128/128 128/128 128/128 148/148 148/148 148/148 148/148 148/148 148/148 174/174 174/174 174/174 174/174 174/174 174/174 71 72 72 72 72 72 81 81 81 81 81 81 93 94 94 94 94 94 58 65 75

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 5 ton unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage average voltage

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage = =

7 457

= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. **Fuse only.

= 100 x

MOCP† 60/ 60 60/ 60 50/ 60 70/ 80** 90/100** 110/125** 60/ 60 60/ 60 50/ 60 70/ 80** 90/100** 110/125** 35/ 35 35/ 35 40/ 40 50/ 60 70/ 80** 80/ 90** 35/ 35 35/ 35 35/ 40 50/ 60 70/ 70** 80/ 90** 35/ 35 35/ 35 40/ 45 60/ 60 70/ 80** 80/ 90** 20 20 25 25 40 45 20 20 25 30 40 45 20 20 25 30 40 45 15 15 15

Determine percent of voltage imbalance.

LEGEND FLA HACR IFM LRA MCA MOCP NEC

DISCONNECT SIZE*

POWER SUPPLY

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

15

POWER EXHAUST PART NO.

MCA (230 v)

MCA (460 v)

MCA (575 v)

CRPWREXH021A00 CRPWREXH022A00 CRPWREXH023A00 CRPWREXH024A00 CRPWREXH025A00 CRPWREXH026A00 CRPWREXH027A00 CRPWREXH028A00 CRPWREXH029A00 CRPWREXH030A00

N/A 3.3 N/A 1.6 N/A 3.3 N/A 1.7 N/A 1.6

0.9 N/A 1.8 N/A 0.9 N/A 1.8 N/A 1.0 N/A

N/A 1.32 N/A 0.64 N/A 1.32 N/A 0.68 N/A 0.64

MOCP (for separate power source) 15 15 15 15 15 15 15 15 15 15

Table 4 — Electrical Data — Standard-Efficiency ASHRAE 90.1 Compliant Cooling Only Units (Without Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-3-60 HIGH

6 Tons STD 460-3-60 HIGH

575-3-60

STD HIGH

STD

208/230-3-60

ALT

HIGH

STD 71/2 Tons

460-3-60

ALT

HIGH

STD 575-3-60

ALT

HIGH

ELECTRIC HEAT Nominal kW —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — — —/— 7.8/10.4 12/16 18.4/24.8 24/32 31.8/42.4 —/— 7.8/10.4 12/16 18.6/24.8 24/32 31.8/42.4 —/— 7.8/10.4 12/16 18.6/24.8 24/32 32.3/42.4 — 13.9 16.5 27.8 33 41.7 — 13.9 16.5 27.8 33 41.7 — 13.9 16.5 27.8 33 41.7 — 17 34 — 17 34 — 17 34

POWER SUPPLY

DISCONNECT SIZE*

FLA

MCA

MOCP†

FLA

LRA

—/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — — —/— 21.7/25 33.4/38.5 51.7/59.7 66.7/77 88.4/102 —/— 21.7/25 33.4/38.5 51.7/59.7 66.7/77 88.4/102 —/— 21.7/25 33.4/38.5 51.7/59.7 66.7/77 88.4/102 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 17.1 34.1 — 17.1 34.1 — 17.1 34.1

32.4/32.4 32.4/32.4 33.9/38.1 48.2/54.6 61.2/69.6 75.6/86.2 34.7/34.7 34.7/34.7 36.7/40.9 51.1/57.4 64.1/72.5 78.4/89.1 15.4 15.4 20.5 24.3 37.8 41.6 16.2 16.2 21.5 25.3 38.8 42.6 11.4 11.9 40.1/ 40.1 40.1/ 40.1 48.9/ 55.4 71.9/ 81.8 90.6/103.5 117.7/134.8 40.1/ 40.1 40.1/ 40.1 48.9/ 55.4 71.9/ 81.8 90.6/103.5 117.7/134.8 44.9/ 44.9 44.9/ 44.9 54.9/ 61.4 77.9/ 87.8 96.6/109.5 123.7/140.8 18.4 24.1 28.1 45.0 52.9 65.9 18.4 24.1 28.1 45.0 52.9 65.9 20.6 26.9 30.8 47.8 55.6 68.7 14.9 23.9 45.3 14.9 23.9 45.3 16.7 26.1 47.5

40/40 40/40 35/40 50/60 70/70** 80/90** 40/40 40/40 40/45 60/60 70/80** 80/90** 20 20 25 25 40 45 20 20 25 30 40 45 15 15 45/ 45 45/ 45 50/ 60 80/ 90** 100/110** 125/150** 45/ 45 45/ 45 50/ 60 80/ 90** 100/110** 125/150** 50/ 50 50/ 50 60/ 70** 80/ 90** 100/110** 125/150** 20 25 30 50 60 70** 20 25 30 50 60 70** 25 30 35 50 60 70** 20 25 40 20 25 40 20 30 45

31/31 31/31 31/35 44/50 56/64 70/79 34/34 34/34 34/38 47/53 59/67 72/82 15 15 19 22 35 38 16 16 20 23 36 39 12 13 42/ 42 42/ 42 45/ 51 66/ 75 83/ 95 108/124 42/ 42 42/ 42 45/ 51 66/ 75 83/ 95 108/124 48/ 48 48/ 48 51/ 56 72/ 81 89/101 114/129 19 22 26 41 49 61 19 22 26 41 49 61 22 25 28 44 51 63 16 22 42 16 22 42 18 24 44

180/180 180/180 180/180 180/180 180/180 180/180 205/205 205/205 205/205 205/205 205/205 205/205 90 90 90 90 90 90 103 103 103 103 103 103 75 86 229/229 229/229 229/229 229/229 229/229 229/229 229/229 229/229 229/229 229/229 229/229 229/229 273/273 273/273 273/273 273/273 273/273 273/273 108 108 108 108 108 108 108 108 108 108 108 108 130 130 130 130 130 110 97 97 97 97 97 97 114 114 114

16

Table 4 — Electrical Data — Standard-Efficiency ASHRAE 90.1 Compliant Cooling Only Units (Without Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-3-60 HIGH

STD

81/2 Tons 460-3-60

HIGH

STD 575-3-60 HIGH

ELECTRIC HEAT Nominal kW —/— 7.8/10.4 12/16 18.6/24.8 24/32 31.8/42.4 —/— 7.8/10.4 12/16 18.6/24.8 24/32 31.8/42.4 — 13.9 16.5 27.8 33 41.7 — 13.9 16.5 27.8 33 41.7 — 17 34 — 17 34

FLA

MCA

MOCP†

FLA

LRA

—/— 21.7/25 33.4/38.5 51.7/59.7 66.7/77 88.4/102 —/— 21.7/25 33.4/38.5 51.7/59.7 66.7/77 88.4/102 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 17.1 34.1 — 17.1 34.1

44.3/ 44.3 44.3/ 44.3 48.9/ 55.4 71.9/ 81.8 90.6/103.5 117.7/134.8 49.1/ 49.1 49.1/ 49.1 54.9/ 61.4 77.9/ 87.8 96.6/109.5 123.7/140.8 21.0 24.1 28.1 45.0 52.9 65.9 23.2 26.9 30.8 47.8 55.6 68.7 16.7 23.9 45.3 18.5 26.1 47.5

50/ 50 50/ 50 50/ 60 80/ 90** 100/110** 125/150** 60/ 60 60/ 60 60/ 70** 80/ 90** 100/110** 125/150** 25 25 30 50 60 70** 30 30 35 50 60 70** 20 25 40 25 30 45

46/ 46 46/ 46 46/ 51 66/ 75 83/ 95 108/124 52/ 52 52/ 52 52/ 56 72/ 81 89/101 114/129 22 22 26 41 49 61 24 25 28 44 51 63 17 22 42 19 24 44

272/272 272/272 272/272 272/272 272/272 272/272 316/316 316/316 316/316 316/316 316/316 316/316 149 149 149 149 149 149 171 171 171 171 171 171 109 109 109 126 126 126

Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457

LEGEND FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code

= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. **Fuse only.

3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 5 ton unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

POWER EXHAUST PART NO.

Average Voltage = =

DISCONNECT SIZE*

POWER SUPPLY

CRPWREXH021A00 CRPWREXH022A00 CRPWREXH023A00 CRPWREXH024A00 CRPWREXH025A00 CRPWREXH026A00 CRPWREXH027A00 CRPWREXH028A00 CRPWREXH029A00 CRPWREXH030A00

452 + 464 + 455 3

1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

17

MCA MCA MCA (230 v) (460 v) (575 v) N/A 3.3 N/A 1.6 N/A 3.3 N/A 1.7 N/A 1.6

0.9 N/A 1.8 N/A 0.9 N/A 1.8 N/A 1.0 N/A

N/A 1.32 N/A 0.64 N/A 1.32 N/A 0.68 N/A 0.64

MOCP (for separate power source) 15 15 15 15 15 15 15 15 15 15

Table 4 — Electrical Data — Standard-Efficiency ASHRAE 90.1 Compliant Cooling Only Units (Without Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

208/230-3-60

ALT

HIGH

STD

10 Tons 460-3-60

ALT

HIGH

STD

575-3-60

ALT

HIGH

STD 208/230-3-60 ALT

STD 121/2 Tons 460-3-60 ALT

STD 575-3-60 ALT

ELECTRIC HEAT Nominal kW —/— 7.8/10.4 12/16 24/32 31.8/42.4 37.6/50 —/— 7.8/10.4 12/16 24/32 31.8/42.4 37.6/50 —/— 7.8/10.4 12/16 22.9/32 31.8/42.4 37.6/50 — 16.5 27.8 33 41.7 50 — 16.5 27.8 33 41.7 50 — 16.5 27.8 33 41.7 50 — 17 34 51 — 17 34 51 — 17 34 51 —/— 7.8/10.4 12/16 24/32 31.8/42.4 37.6/50 —/— 7.8/10.4 12/16 24/32 31.8/42.4 37.6/50 — 16.5 27.8 33 41.7 50 — 16.5 27.8 33 41.7 50 — 17 34 51 — 17 34 51

POWER SUPPLY

DISCONNECT SIZE*

FLA

MCA

MOCP†

FLA

LRA

—/— 21.7/25 33.4/ 38.5 66.7/77 88.4/102 104.2/120.3 —/— 21.7/25 33.4/ 38.5 66.7/77 88.4/102 104.2/120.3 —/— 21.7/25 33.4/ 38.5 66.7/77 88.4/102 104.2/120.3 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 17.1 34.1 51.2 — 17.1 34.1 51.2 — 17.1 34.1 51.2 —/— 21.7/25 33.4/ 38.5 66.7/77 88.4/102 104.2/120.3 —/— 21.7/25 33.4/ 38.5 66.7/77 88.4/102 104.2/120.3 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 17.1 34.1 51.2 — 17.1 34.1 51.2

44.6/ 44.6 44.6/ 44.6 48.9/ 55.4 90.6/103.5 117.7/134.8 137.5/157.6 46.3/ 46.3 46.3/ 46.3 51.1/ 57.5 92.8/105.6 119.9/136.9 139.7/159.7 53.8/ 53.8 53.8/ 53.8 60.4/ 66.9 102.1/115.0 129.2/146.3 149.0/169.1 22.0 28.1 45.0 52.9 65.9 78.4 22.8 29.1 46.0 53.9 66.9 79.4 26.8 34.1 51.0 58.9 71.9 84.4 17.4 23.9 45.3 66.6 18.0 24.7 46.1 67.4 21.2 28.7 50.1 71.4 56.2/ 56.2 56.2/ 56.2 56.2/ 61.4 96.6/109.5 123.7/140.8 143.5/163.6 60.6/ 60.6 60.6/ 60.6 60.6/ 66.9 102.1/115.0 129.2/146.3 149.0/169.1 26.5 30.8 47.8 55.6 68.7 81.2 29.1 34.1 51.0 58.9 71.9 84.4 21.6 26.1 47.5 68.8 23.7 28.7 50.1 71.4

50/ 50 50/ 50 50/ 60 100/110** 125/150** 150/175** 60/ 60 60/ 60 60/ 60 100/110** 125/150** 150/175** 60/ 60 60/ 60 70/ 80** 110/125** 150/150** 150/175** 25 30 40 60 70** 80** 25 30 45 60 70** 80** 30 40 60 60 80** 90** 20 25 40 70** 20 25 45 70** 25 35 50 80** 70/ 70** 70/ 70** 70/ 70** 100/110** 125/150** 150/175** 70/ 70** 70/ 70** 70/ 80** 110/125** 150/150** 150/175** 30 35 45 60 70** 90** 35 40 60 60 80** 90** 25 30 45 70** 30 35 50 80**

47/ 47 47/ 47 47/ 51 83/ 95 108/124 127/145 49/ 49 49/ 49 49/ 53 85/ 97 110/126 128/147 57/ 57 57/ 57 57/ 62 94/106 119/135 137/156 23 26 41 49 61 72 24 27 42 50 62 73 29 31 47 54 66 78 18 22 42 61 19 23 42 62 23 26 46 66 59/ 59 59/ 59 59/ 59 89/101 114/129 132/151 64/ 64 64/ 64 64/ 64 94/106 119/135 137/156 28 28 44 51 63 75 31 31 47 54 66 78 23 24 44 63 25 26 46 66

297/297 297/297 297/297 297/297 297/297 297/297 316/316 316/316 316/316 316/316 316/316 316/316 364/364 364/364 364/364 364/364 364/364 364/364 149 149 149 149 149 149 188 188 188 188 188 188 182 182 182 182 182 182 119 119 119 119 151 151 151 151 146 146 146 146 359/359 359/359 359/359 359/359 359/359 359/359 378/378 378/378 378/378 378/378 378/378 378/378 174 174 174 174 174 174 213 213 213 213 213 213 127 127 127 127 159 159 159 159

18

Table 5 — Electrical Data — Standard-Efficiency ASHRAE 90.1 Compliant Cooling Only Units (With Convenience Outlet) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-1-60 ALT

STD

ALT

208/230-3-60

3 Tons HIGH

STD

ALT

460-3-60

HIGH STD ALT HIGH

575-3-60

ELECTRIC HEAT Nominal kW —/— 3.3/ 4.4 4.9/ 6.5 6.4/ 8.7 7.9/10.5 9.8/13.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 9.8/13.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.2/16.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.3/16.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.3/16.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — — —

FLA

MCA

—/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.8 46.9/54.2 —/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.8 46.9/54.2 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.4 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.4 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.4 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — — —

31.2/31.2 31.2/32.3 38.7/43.2 48.6/54.7 56.8/64.1 68.0/77.1 32.6/32.6 32.6/34.0 40.5/45.0 50.4/56.4 58.5/65.8 69.8/78.8 22.5/22.5 22.5/23.0 27.3/29.4 33.1/36.0 37.7/42.0 52.1/57.9 23.9/23.9 23.9/24.8 29.1/31.1 34.8/37.7 39.5/43.7 53.8/59.6 24.2/24.2 24.2/25.2 29.5/31.5 35.2/38.1 39.9/44.1 54.2/60.0 9.8 13.4 17.6 21.6 25.4 10.6 14.4 18.6 22.6 26.4 11.1 15.0 19.2 23.3 27.0 7.2 7.7 8.0

— — — — — — —

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

% Voltage Imbalance = 100 x

FLA

LRA

35/35 35/35 40/45 50/60 60/70** 70/80** 40/40 40/40 45/45 60/60 60/70** 70/80** 30/30 30/30 30/30 35/40 40/45 60/60 30/30 30/30 30/35 35/40 40/45 60/60 30/30 30/30 35/35 40/40 40/45 60/60 15 15 20 25 30 15 15 20 25 30 15 20 20 25 30 15 15 15

30/30 30/31 37/41 46/51 53/60 64/72 31/31 31/32 38/42 47/53 55/61 65/73 23/23 23/23 25/28 30/34 35/39 48/54 25/25 25/25 27/29 32/35 36/40 50/55 25/25 25/25 27/29 32/36 37/41 50/56 10 12 16 20 23 11 13 17 21 24 11 14 18 21 25 8 9 9

111/111 111/111 111/111 111/111 111/111 111/111 116/116 116/116 116/116 116/116 116/116 116/116 90/ 90 90/ 90 90/ 90 90/ 90 90/ 90 90/ 90 95/ 95 95/ 95 95/ 95 95/ 95 95/ 95 95/ 95 114/114 114/114 114/114 114/114 114/114 114/114 47 47 47 47 47 50 50 50 50 50 59 59 59 59 59 36 39 58

7 457

= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. **Fuse only.

3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 5 ton unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance = 100 x

MOCP†

Determine percent of voltage imbalance.

LEGEND FLA HACR IFM LRA MCA MOCP NEC

DISCONNECT SIZE*

POWER SUPPLY

max voltage deviation from average voltage average voltage

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage = =

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

19

POWER EXHAUST PART NO.

MCA (230 v)

MCA (460 v)

MCA (575 v)

CRPWREXH021A00 CRPWREXH022A00 CRPWREXH023A00 CRPWREXH024A00 CRPWREXH025A00 CRPWREXH026A00 CRPWREXH027A00 CRPWREXH028A00 CRPWREXH029A00 CRPWREXH030A00

N/A 3.3 N/A 1.6 N/A 3.3 N/A 1.7 N/A 1.6

0.9 N/A 1.8 N/A 0.9 N/A 1.8 N/A 1.0 N/A

N/A 1.32 N/A 0.64 N/A 1.32 N/A 0.68 N/A 0.64

MOCP (for separate power source) 15 15 15 15 15 15 15 15 15 15

Table 5 — Electrical Data — Standard-Efficiency ASHRAE 90.1 Compliant Cooling Only Units (With Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-1-60 ALT

STD

208/230-3-60

ALT

4 Tons HIGH

STD

460-3-60

ALT

HIGH

575-3-60

STD ALT HIGH

STD 208/230-1-60 ALT

STD

208/230-3-60

ALT

5 Tons HIGH

STD

460-3-60

ALT

HIGH

575-3-60

STD ALT HIGH

ELECTRIC HEAT Nominal kW —/— 3.3/ 4.4 6.5/ 8.7 9.3/13.0 13.1/17.4 15.8/21.0 —/— 3.3/ 4.4 6.5/ 8.7 9.3/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — — — —/— 4.9/ 6.5 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.0 — 6.0 11.5 14.0 23.0 25.0 — 6.0 11.5 14.0 23.0 25.0 — — —

DISCONNECT SIZE*

POWER SUPPLY FLA

MCA

MOCP†

FLA

LRA

—/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 18.1/20.9 33.4/38.4 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.4 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.4 43.8/50.5 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — — — —/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.1 — 7.2 13.8 16.8 27.7 30.1 — 7.2 13.8 16.8 27.7 30.1 — — —

40.0/ 40.0 40.0/ 40.0 48.6/ 54.7 68.0/ 77.1 87.9/100.0 104.2/118.8 41.4/ 41.4 41.4/ 41.4 50.4/ 56.4 69.8/ 78.8 89.7/101.8 105.9/120.5 29.0/ 29.0 29.0/ 29.4 33.1/ 36.0 52.1/ 57.9 65.1/ 73.5 30.4/ 30.4 30.4/ 31.1 34.8/ 37.7 53.8/ 59.6 66.9/ 75.3 30.7/ 30.7 30.7/ 31.5 35.2/ 38.1 54.2/ 60.0 67.2/ 75.7 15.2 15.2 22.3 26.0 39.6 15.5 15.5 22.6 26.4 39.9 16.0 16.0 23.3 27.0 40.6 10.9 11.1 11.4 49.3/ 49.3 49.3/ 49.3 51.6/ 57.7 71.0/ 80.1 90.9/103.0 107.2/121.8 50.0/ 50.0 50.0/ 50.0 52.5/ 58.6 71.9/ 81.0 91.8/103.9 108.0/122.6 32.1/ 32.1 32.1/ 32.4 40.7/ 44.4 55.1/ 60.9 68.1/ 76.5 82.4/ 92.5 31.4/ 31.4 31.4/ 31.5 39.9/ 43.5 54.2/ 60.0 67.2/ 75.7 81.6/ 91.6 33.7/ 33.7 33.7/ 34.4 42.7/ 46.4 57.1/ 62.9 70.1/ 78.5 84.4/ 94.5 15.3 15.6 23.9 27.6 41.2 44.2 15.6 16.0 24.3 28.0 41.6 44.6 15.6 16.0 24.3 28.0 41.6 44.6 11.5 11.7 11.7

45/ 45 45/ 45 50/ 60 70/ 80** 90/100** 110/125** 50/ 50 50/ 50 60/ 60 70/ 80** 90/110** 110/125** 35/ 35 35 35 35/ 40 60/ 60 70/ 80** 35/ 35 35/ 35 35/ 40 60/ 60 70/ 80** 35/ 35 35/ 35 40/ 40 60/ 60 70/ 80** 20 20 25 30 40 20 20 25 30 40 20 20 25 30 45 15 15 15 60/ 60 60/ 60 60/ 60 80/ 90** 100/110** 110/125** 60/ 60 60/ 60 60/ 60 80/ 90** 100/110** 110/125** 40/ 40 40/ 40 45/ 45 60/ 70** 70/ 80** 90/100** 40/ 40 40/ 40 40/ 45 60/ 60 70/ 80** 90/100** 40/ 40 40/ 40 45/ 50 60/ 70** 80/ 80** 90/100** 20 20 25 30 45 45 20 20 25 30 45 45 20 20 25 30 45 45 15 15 15

38/ 38 38/ 38 46/ 51 64/ 72 82/ 93 97/110 40/ 40 40/ 40 47/ 53 65/ 73 83/ 95 98/112 29/ 29 29/ 29 30/ 34 48/ 54 60/ 68 30/ 30 30/ 30 32/ 35 50/ 55 62/ 69 31/ 31 31/ 31 32 /36 50/ 56 62/ 70 15 15 20 24 36 15 15 21 24 37 16 16 21 25 37 12 12 12 47/ 47 47/ 47 48/ 54 66/ 75 85/ 96 100/113 48/ 48 48/ 48 49/ 55 67/ 75 85/ 96 100/114 32/ 32 32/ 32 37/ 41 51/ 57 63/ 70 76/ 86 32/ 32 32/ 32 37/ 41 50/ 56 62/ 70 75/ 85 34/ 34 34/ 34 39/4 3 53/ 58 65/ 72 78/ 87 15 15 22 25 38 41 16 16 22 26 38 41 16 16 22 26 38 41 13 13 13

134/134 134/134 134/134 134/134 134/134 134/134 138/138 138/138 138/138 138/138 138/138 138/138 106/106 106/106 106/106 106/106 106/106 110/110 110/110 110/110 110/110 110/110 129/129 129/129 129/129 129/129 129/129 53 53 53 53 53 55 55 55 55 55 64 64 64 64 64 42 44 51 166/166 166/166 166/166 166/166 166/166 166/166 188/188 188/188 188/188 188/188 188/188 188/188 133/133 133/133 133/133 133/133 133/133 133/133 153/153 153/153 153/153 153/153 153/153 153/153 179/179 179/179 179/179 179/179 179/179 179/179 74 74 74 74 74 74 83 83 83 83 83 83 96 96 96 96 96 96 60 67 77

20

Table 5 — Electrical Data — Standard-Efficiency ASHRAE 90.1 Compliant Cooling Only Units (With Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-3-60 HIGH

6 Tons STD 460-3-60 HIGH

STD HIGH

575-3-60

ELECTRIC HEAT Nominal kW —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — —

FLA

MCA

MOCP†

FLA

LRA

—/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — —

37.2/37.2 37.2/37.2 37.2/38.1 54.2/60.0 67.2/75.7 81.6/91.6 39.5/39.5 39.5/39.5 39.5/40.9 57.1/62.9 70.1/78.5 84.4/94.5 17.6 17.6 20.5 27.0 40.6 44.3 18.4 18.4 21.5 28.0 41.6 45.3 13.1 13.7

45/ 45 45/ 45 40/ 45 60/ 60 70/ 80** 90/100** 45/ 45 45/ 45 45/ 50 60/ 70** 80/ 80** 90/100** 20 20 25 30 45 45 25 25 25 30 45 50 20 20

37/37 37/37 37/41 50/56 62/70 75/85 39/39 39/39 39/43 53/58 65/72 78/87 17 17 21 25 37 41 18 18 22 26 38 42 14 15

184/184 184/184 184/184 184/184 184/184 184/184 210/210 210/210 210/210 210/210 210/210 210/210 92 92 92 92 92 92 105 105 105 105 105 105 77 87

Determine percent of voltage imbalance.

LEGEND FLA HACR IFM LRA MCA MOCP NEC

— — — — — — —

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

% Voltage Imbalance = 100 x

7 457

= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. **Fuse only.

3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 5 ton unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance = 100 x

DISCONNECT SIZE*

POWER SUPPLY

max voltage deviation from average voltage average voltage

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage = =

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

21

POWER EXHAUST PART NO.

MCA (230 v)

MCA (460 v)

MCA (575 v)

CRPWREXH021A00 CRPWREXH022A00 CRPWREXH023A00 CRPWREXH024A00 CRPWREXH025A00 CRPWREXH026A00 CRPWREXH027A00 CRPWREXH028A00 CRPWREXH029A00 CRPWREXH030A00

N/A 3.3 N/A 1.6 N/A 3.3 N/A 1.7 N/A 1.6

0.9 N/A 1.8 N/A 0.9 N/A 1.8 N/A 1.0 N/A

N/A 1.32 N/A 0.64 N/A 1.32 N/A 0.68 N/A 0.64

MOCP (for separate power source) 15 15 15 15 15 15 15 15 15 15

Table 5 — Electrical Data — Standard-Efficiency ASHRAE 90.1 Compliant Cooling Only Units (With Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

208/230-3-60

ALT

HIGH

STD 71/2 Tons

460-3-60

ALT

HIGH

STD 575-3-60

ALT HIGH

STD 208/230-3-60 HIGH

81/2 Tons

STD 460-3-60 HIGH

STD 575-3-60 HIGH

ELECTRIC HEAT Nominal kW —/— 7.8/10.4 12/16 18.4/24.8 24/32 31.8/42.4 —/— 7.8/10.4 12/16 18.6/24.8 24/32 31.8/42.4 —/— 7.8/10.4 12/16 18.6/24.8 24/32 32.3/42.4 — 13.9 16.5 27.8 33 41.7 — 13.9 16.5 27.8 33 41.7 — 13.9 16.5 27.8 33 41.7 — 17 34 — 17 34 — 17 34 —/— 7.8/10.4 12/16 18.6/24.8 24/32 31.8/42.4 —/— 7.8/10.4 12/16 18.6/24.8 24/32 31.8/42.4 — 13.9 16.5 27.8 33 41.7 — 13.9 16.5 27.8 33 41.7 — 17 34 — 17 34

POWER SUPPLY

DISCONNECT SIZE*

FLA

MCA

MOCP†

FLA

LRA

—/— 21.7/25 33.4/38.5 51.7/59.7 66.7/77 88.4/102 —/— 21.7/25 33.4/38.5 51.7/59.7 66.7/77 88.4/102 —/— 21.7/25 33.4/38.5 51.7/59.7 66.7/77 88.4/102 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 17.1 34.1 — 17.1 34.1 — 17.1 34.1 —/— 21.7/25 33.4/38.5 51.7/59.7 66.7/77 88.4/102 —/— 21.7/25 33.4/38.5 51.7/59.7 66.7/77 88.4/102 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 17.1 34.1 — 17.1 34.1

44.9/ 44.9 44.9/ 44.9 55.0/ 60.8 77.9/ 87.3 96.6/108.9 123.7/140.2 44.9/ 44.9 44.9/ 44.9 55.0/ 60.8 77.9/ 87.3 96.6/108.9 123.7/140.2 49.7/ 49.7 49.7/ 50.0 61.0/ 66.8 83.9/ 93.3 102.6/114.9 129.7/146.2 20.6 26.9 28.1 47.8 55.6 68.7 20.6 26.9 28.1 47.8 55.6 68.7 22.8 29.6 30.8 50.5 58.3 71.4 16.6 26.1 47.4 16.6 26.1 47.4 18.4 28.3 49.6 49.1/ 49.1 49.1/ 49.1 55.0/ 60.8 77.9/ 87.3 96.6/108.9 123.7/140.2 53.9/ 53.9 53.9/ 53.9 61.0/ 66.8 83.9/ 93.3 102.6/114.9 129.7/146.2 23.2 26.9 28.1 47.8 55.6 68.7 25.4 29.6 30.8 50.5 58.3 71.4 18.4 26.1 47.4 20.2 28.3 49.6

50/ 50 50/ 50 60/ 60 80/ 90** 100/110** 125/150** 50/ 50 50/ 50 60/ 60 80/ 90** 100/110** 125/150** 60/ 60 60/ 60 70/ 70** 90/100** 110/125** 150/150** 25 25 30 50 60 70** 25 25 30 50 60 70** 25 30 35 60 60 80** 20 25 45 20 25 45 20 30 45 60/ 60 60/ 60 60/ 60 80/ 90** 100/110** 125/150** 60/ 60 60/ 60 70/ 70** 90/100** 110/125** 150/150** 30 30 30 50 60 70** 30 30 35 60 60 80** 25 25 45 25 30 45

48/ 48 48/ 48 51/ 56 72/ 81 89/101 114/130 48/ 48 48/ 48 51/ 56 72/ 81 89/101 114/130 53/ 53 53/ 53 56/ 61 77/ 86 94/106 119/135 22 25 28 44 51 63 22 25 28 44 51 63 24 27 31 46 54 66 18 24 44 18 24 44 20 26 46 52/ 52 52/ 52 52/ 56 72/ 81 89/101 114/130 57/ 57 57/ 57 57/ 61 77/ 86 94/106 119/135 24 25 28 44 51 63 27 27 31 46 54 66 19 24 44 21 26 46

234/234 234/234 234/234 234/234 234/234 234/234 234/234 234/234 234/234 234/234 234/234 234/234 277/277 277/277 277/277 277/277 277/277 277/277 110 110 110 110 110 110 110 110 110 110 110 110 132 132 132 132 132 132 99 99 99 99 99 99 116 116 116 277/277 277/277 277/277 277/277 277/277 277/277 320/320 320/320 320/320 320/320 320/320 320/320 151 151 151 151 151 151 173 173 173 173 173 173 111 111 111 128 128 128

22

Table 5 — Electrical Data — Standard-Efficiency ASHRAE 90.1 Compliant Cooling Only Units (With Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

ALT

208/230-3-60

HIGH

STD

10 Tons ALT

460-3-60

HIGH

STD

575-3-60

ALT

HIGH

ELECTRIC HEAT Nominal kW —/— 7.8/10.4 12/16 24/32 31.8/42.4 37.6/50 —/— 7.8/10.4 12/16 24/32 31.8/42.4 37.6/50 —/— 7.8/10.4 12/16 22.9/32 31.8/42.4 37.6/50 — 16.5 27.8 33 41.7 50 — 16.5 27.8 33 41.7 50 — 16.5 27.8 33 41.7 50 — 17 34 51 — 17 34 51 — 17 34 51

FLA

MCA

MOCP†

FLA

LRA

—/— 21.7/25 33.4/38.5 66.7/77 88.4/102 104.2/120.3 —/— 21.7/25 33.4/38.5 66.7/77 88.4/102 104.2/120.3 —/— 21.7/25 33.4/38.5 66.7/77 88.4/102 104.2/120.3 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 17.1 34.1 51.2 — 17.1 34.1 51.2 — 17.1 34.1 51.2

49.4/ 49.4 49.4/ 49.4 55.0/ 60.8 96.6/108.9 123.7/140.2 143.6/163.0 51.1/ 51.1 51.1/ 51.1 57.1/ 62.9 98.8/111.0 125.9/142.3 145.7/165.2 58.6/ 68.6 58.6/ 58.6 66.5/ 72.3 108.1/120.4 135.2/151.7 155.1/174.5 24.2 30.8 45.0 55.6 68.7 81.1 25.0 31.8 46.0 56.6 69.7 82.1 29.0 36.8 51.0 61.6 74.7 87.1 19.1 26.1 47.4 68.8 19.7 26.9 48.2 69.6 22.9 30.9 52.2 73.6

60/ 60 60/ 60 60/ 60 100/110** 125/150** 150/175** 60/ 60 60/ 60 60/ 60 100/125** 150/150** 150/175** 70/ 70** 70/ 70** 80/ 80** 110/125** 150/175** 175/175** 30 30 40 60 70** 90** 30 30 45 60 70** 90** 35 40 60 70** 80** 90** 25 25 45 70** 25 25 45 70** 25 35 50 80**

52/ 52 52/ 52 52/ 56 89/101 114/130 132/151 54/ 54 54/ 54 54/ 58 91/103 116/131 134/152 63/ 63 63/ 63 63/ 67 99/111 124/140 143/161 26 28 44 51 63 75 26 29 45 52 64 76 31 34 49 57 69 80 20 24 44 63 21 25 44 64 25 28 48 68

302/302 302/302 302/302 302/302 302/302 302/302 321/321 321/321 321/321 321/321 321/321 321/321 369/369 369/369 369/369 369/369 369/369 369/369 151 151 151 151 151 151 190 190 190 190 190 190 184 184 184 184 184 184 121 121 121 121 152 152 152 152 148 148 148 148

Determine percent of voltage imbalance.

LEGEND FLA HACR IFM LRA MCA MOCP NEC OFM RLA

— — — — — — — — —

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps

% Voltage Imbalance = 100 x

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 5 ton unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage average voltage

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage = =

7 457

= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. **Fuse only.

= 100 x

DISCONNECT SIZE*

POWER SUPPLY

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

23

POWER EXHAUST PART NO.

MCA (230 v)

MCA (460 v)

MCA (575 v)

CRPWREXH021A00 CRPWREXH022A00 CRPWREXH023A00 CRPWREXH024A00 CRPWREXH025A00 CRPWREXH026A00 CRPWREXH027A00 CRPWREXH028A00 CRPWREXH029A00 CRPWREXH030A00

N/A 3.3 N/A 1.6 N/A 3.3 N/A 1.7 N/A 1.6

0.9 N/A 1.8 N/A 0.9 N/A 1.8 N/A 1.0 N/A

N/A 1.32 N/A 0.64 N/A 1.32 N/A 0.68 N/A 0.64

MOCP (for separate power source) 15 15 15 15 15 15 15 15 15 15

Table 5 — Electrical Data — Standard-Efficiency ASHRAE 90.1 Compliant Cooling Only Units (With Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-3-60 ALT

STD 121/2 Tons 460-3-60 ALT

STD 575-3-60 ALT

ELECTRIC HEAT Nominal kW —/— 7.8/10.4 12/16 24/32 31.8/42.4 37.6/50 —/— 7.8/10.4 12/16 24/32 31.8/42.4 37.6/50 — 16.5 27.8 33 41.7 50 — 16.5 27.8 33 41.7 50 — 17 34 51 — 17 34 51

FLA

MCA

MOCP†

FLA

LRA

—/— 21.7/25 33.4/38.5 66.7/77 88.4/102 104.2/120.3 —/— 21.7/25 33.4/38.5 66.7/77 88.4/102 104.2/120.3 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 17.1 34.1 51.2 — 17.1 34.1 51.2

61.0/ 61.0 61.0/ 61.0 61.0/ 66.8 102.6/114.9 129.7/146.2 149.6/169.0 65.4/ 65.4 65.4/ 65.4 66.5/ 72.3 108.1/120.4 135.2/151.7 155.1/174.5 28.7 33.5 47.8 58.3 71.4 83.9 31.3 36.8 51.0 61.6 74.7 87.1 23.3 28.3 49.6 71.0 25.4 30.9 52.2 73.6

70/ 70** 70/ 70** 70/ 70** 110/125** 150/150** 150/175** 80/ 80** 80/ 80** 80/ 80** 110/125** 150/175** 175/175** 35 35 45 60 80** 90** 35 40 60 70** 80** 90** 30 30 45 80** 30 35 50 80**

65/ 65 65/ 65 65/ 65 94/106 119/135 138/156 70/ 70 70/ 70 70/ 70 99/111 124/140 143/161 30 31 46 54 66 77 33 34 49 57 69 80 25 26 46 65 27 28 48 68

364/364 364/364 364/364 364/364 364/364 364/364 383/383 383/383 383/383 383/383 383/383 383/383 176 176 176 176 176 176 215 215 215 215 215 215 129 129 129 129 160 160 160 160

Determine percent of voltage imbalance.

LEGEND FLA HACR IFM LRA MCA MOCP NEC OFM RLA

— — — — — — — — —

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps

% Voltage Imbalance = 100 x

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 5 ton unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage average voltage

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage =

=

7 457

= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. **Fuse only.

= 100 x

DISCONNECT SIZE*

POWER SUPPLY

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

24

POWER EXHAUST PART NO.

MCA (230 v)

MCA (460 v)

MCA (575 v)

CRPWREXH021A00 CRPWREXH022A00 CRPWREXH023A00 CRPWREXH024A00 CRPWREXH025A00 CRPWREXH026A00 CRPWREXH027A00 CRPWREXH028A00 CRPWREXH029A00 CRPWREXH030A00

N/A 3.3 N/A 1.6 N/A 3.3 N/A 1.7 N/A 1.6

0.9 N/A 1.8 N/A 0.9 N/A 1.8 N/A 1.0 N/A

N/A 1.32 N/A 0.64 N/A 1.32 N/A 0.68 N/A 0.64

MOCP (for separate power source) 15 15 15 15 15 15 15 15 15 15

Table 6 — Electric Heating Usage — Standard-Efficiency ASHRAE 90.1 Compliant Cooling Only Units UNIT SIZE

VOLTAGE (60 Hz) 208/230/240 (single phase)

3 Tons

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (single phase)

4 Tons

208/230/240 (3 phase) 460/480 (3 phase)

208/230/240 (single phase)

5 Tons

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (3 phase) 6 Tons 460/480 (3 phase)

208/230/240 (3 phase) 71/2 Tons 460/480 (3 phase) 575 (3 phase) 208/230/240 (3 phase) 81/2 Tons 460/480 (3 phase) 575 (3 phase) 208/230/240 (3 phase)

10 Tons

460/480 (3 phase) 575 (3 phase) 208/230/240 (3 phase)

121/2 Tons

460/480 (3 phase) 575 (3 phase)

ACCESSORY kW 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 9.8/11.6/13.0* 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 12.0/14.7/16.0 5.5/ 6.0 8.1/ 8.8 10.6/11.5 12.9/14.0 3.3/ 4.0/ 4.4 6.5/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 16.0/19.3/21.0* 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 12.0/14.7/16.0 15.8/19.3/21.0* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 4.9/ 5.8/ 6.5 6.6/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 15.8/19.3/21.0* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5* 7.8/ 9.6/10.4 12.0/14.7/16.0 18.6/22.8/24.8 24.0/29.4/32.0 31.8/39.0/42.4 12.8/13.9 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7 17.0 34.0 7.8/ 9.6/10.4 12.0/14.7/16.0 18.6/22.8/24.8 24.0/29.4/32.0 31.8/39.0/42.4 12.8/13.9 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7 17.0 34.0 7.8/ 9.6/10.4 12.0/14.7/16.0 24.0/29.4/32.0 31.8/38.9/42.4 37.5/46.0/50.0 12.8/13.9 15.2/16.5 30.4/33.0 38.4/41.7 46.0/50.0 17.0 34.0 51.0 7.8/ 9.6/10.4 12.0/14.7/16.0 24.0/29.4/32.0 31.8/38.9/42.4 37.5/46.0/50.0 12.8/13.9 15.2/16.5 30.4/33.0 38.4/41.7 46.0/50.0 17.0 34.0 51.0

ACCESSORY HEATER PART NUMBER CRHEATER - - - A00 001 002 003 004 002+002 001 002 003 004 005 006 007 008 009 001 003 002+002 003+003 004+004 002 003 005 004+004 006 008 009 008+008 002 003 002+002 003+003 004+004 002 004 005 004+004 004+005 006 008 009 008+008 008+009 002 004 005 004+004 004+005 006 008 009 008+008 008+009 017 010 011 012 012+017 016 013 014 015 014+016 018 019 017 010 011 012 012+017 016 013 014 015 014+016 018 019 017 010 012 012+017 010+012 013 014 015 014+016 013+015 018 019 018+019 017 010 012 012+017 010+012 013 014 015 014+016 013+015 018 019 018+019

*Two heater packages required to provide kW indicated. †004 on units with convenience outlet. **002 on high-static units. NOTES: 1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly. 2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kWnew = Heater kW rated x (unit power distribution voltage/rated heater voltage)2 As an example: For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kW new = 16 kW (215/240)2 kW new = 12.8 kW (rating at 215 v)

25

SINGLE POINT BOX PACKAGE NO. CRSINGLE---A00 — — —† — 004 — — — — — — — — — — — 004 004 004 — — — 002 — — — — — — 004 004 004 — — —** 002 002** — — — — — — — — 002** 002** — — — — — 006 006 007 007 009 006 006 006 006 008 006 006 006 006 007 007 009 006 006 006 006 008 006 006 011 012 012 015 015 011 011 011 014 014 011 011 014 012 012 012 015 015 011 011 011 014 014 011 014 014

Table 7 — Electrical Data — Standard-Efficiency Cooling Only Units (Without Convenience Outlet) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-1-60 ALT

STD

208/230-3-60

ALT

3 Tons HIGH

STD

460-3-60

ALT

HIGH

575-3-60

STD ALT HIGH

STD 208/230-1-60 ALT

STD

208/230-3-60

ALT

4 Tons HIGH

STD

460-3-60

ALT

HIGH

575-3-60

STD ALT HIGH

ELECTRIC HEAT Nominal kW —/— 3.3/ 4.4 4.9/ 6.5 6.4/ 8.7 7.9/10.5 9.8/13.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 9.8/13.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.2/16.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.3/16.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.3/16.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — — — —/— 3.3/ 4.4 6.5/ 8.7 9.3/13.0 13.1/17.4 15.8/21.0 —/— 3.3/ 4.4 6.5/ 8.7 9.3/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — — —

DISCONNECT SIZE†

POWER SUPPLY FLA

MCA

—/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.8 46.9/54.2 —/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.8 46.9/54.2 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.4 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.4 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.4 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — — — —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 18.1/20.9 33.4/38.4 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.4 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.4 43.8/50.5 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — — —

25.2/25.2 25.2/27.3 33.7/38.2 43.6/49.7 51.8/59.1 63.0/72.1 26.6/26.6 26.6/29.0 35.5/40.0 45.4/51.4 53.5/60.8 64.8/73.8 17.7/17.7 17.7/17.7 21.3/23.9 27.0/30.5 31.7/35.9 46.1/52.4 19.1/19.1 19.1/19.4 23.1/25.7 28.8/32.3 33.5/37.7 47.8/54.2 19.4/19.4 19.4/19.7 23.4/26.0 29.2/32.7 33.9/38.1 48.2/54.6 7.6 10.6 14.9 18.9 22.7 8.4 11.6 15.9 19.9 23.7 8.9 12.3 16.5 20.5 24.3 5.5 6.0 6.3 34.0/ 34.0 34.0/ 34.0 43.6/ 49.7 63.0/ 72.1 82.9/ 95.0 99.2/113.8 35.4/ 35.4 35.4/ 35.4 45.4/ 51.4 64.8/ 73.8 84.7/ 96.8 100.9/115.5 24.2/ 24.2 24.2/ 24.2 27.0/ 30.5 46.1/ 52.4 59.1/ 67.5 25.6/ 25.6 25.6/ 25.7 28.8/ 32.3 47.8/ 54.2 60.8/ 69.3 25.9/ 25.9 25.9/ 26.0 29.2/ 32.7 48.2/ 54.6 61.2/ 69.6 13.0 13.0 19.5 23.3 36.8 13.3 13.3 19.9 23.7 37.2 13.8 13.8 20.5 24.3 37.8 9.2 9.3 9.7

26

MOCP* 30/30 30/30 35/40 45/50 60/60 70/80** 35/35 35/35 40/40 50/60 60/70** 70/80** 25/25 25/25 25/25 30/35 35/40 50/60 25/25 25/25 25/30 30/35 35/40 50/60 25/25 25/25 30/30 30/35 35/40 50/60 15 15 15 20 25 15 15 20 20 25 15 15 20 25 25 15 15 15 40/ 40 40/ 40 45/ 50 70/ 80** 90/100** 100/125** 45/ 45 45/ 45 50/ 60 70/ 80** 90/100** 110/125** 30/ 30 30/ 30 30/ 35 50/ 60 60/ 70** 30/ 30 30/ 30 30/ 35 50/ 60 70/ 70** 30/ 30 30/ 30 30/ 35 50/ 60 70/ 70** 20 20 20 25 40 20 20 20 25 40 20 20 25 25 40 15 15 15

FLA

LRA

24/24 24/25 31/35 40/46 48/54 58/66 26/26 26/27 33/37 42/47 49/56 60/68 17/17 17/17 20/22 25/28 29/33 42/48 19/19 19/19 21/24 26/30 31/35 44/50 19/19 19/19 22/24 27/30 31/35 44/50 7 10 14 17 21 8 11 15 18 22 9 11 15 19 22 6 7 7 32/ 32 32/ 32 40/ 46 58/ 66 76/ 87 91/105 34/ 34 34/ 34 42/ 47 60/ 68 78/ 89 93/106 23/ 23 23/ 23 25/ 28 42/ 48 54/ 62 25/ 25 25/ 25 26/ 30 44/ 50 56/ 64 25/ 25 25/ 25 27/ 30 44/ 50 56/ 64 13 13 18 21 34 13 13 18 22 34 13 13 19 22 35 10 10 10

106/106 106/106 106/106 106/106 106/106 106/106 111/111 111/111 111/111 111/111 111/111 111/111 85/ 85 85/ 85 85/ 85 85/ 85 85/ 85 85/ 85 90/ 90 90/ 90 90/ 90 90/ 90 90/ 90 90/ 90 109/109 109/109 109/109 109/109 109/109 109/109 44 45 45 45 45 48 48 48 48 48 57 57 57 57 57 34 37 56 129/129 129/129 129/129 129/129 129/129 129/129 133/133 133/133 133/133 133/133 133/133 133/133 101/101 101/101 101/101 101/101 101/101 105/105 105/105 105/105 105/105 105/105 124/124 124/124 124/124 124/124 124/124 51 51 51 51 51 53 53 53 53 53 62 62 62 62 62 41 42 49

Table 7 — Electrical Data — Standard-Efficiency Cooling Only Units (Without Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-1-60 ALT

STD

ALT

208/230-3-60

5 Tons HIGH

STD

ALT

460-3-60

HIGH

STD ALT HIGH

575-3-60

ELECTRIC HEAT Nominal kW —/— 4.9/ 6.5 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.0 — 6.0 11.5 14.0 23.0 25.0 — 6.0 11.5 14.0 23.0 25.0 — — —

FLA

MCA

—/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.1 — 7.2 13.8 16.8 27.7 30.1 — 7.2 13.8 16.8 27.7 30.1 — — —

43.3/ 43.3 43.3/ 43.3 46.6/ 52.7 66.0/ 75.1 85.9/ 98.0 102.2/116.8 44.0/ 44.0 44.0/ 44.0 47.5/ 53.6 66.9/ 76.0 86.8/ 98.9 103.0/117.6 27.3/ 27.3 27.3/ 27.3 34.7/ 38.9 49.1/ 55.4 62.1/ 70.5 76.4/ 87.1 26.6/ 26.6 26.6/ 26.6 33.9/ 38.1 48.2/ 54.6 61.2/ 69.6 75.6/ 86.2 28.9/ 28.9 28.9 28.9 36.7/ 40.9 51.1/ 57.4 64.1/ 72.5 78.4/ 89.1 13.2 13.2 21.2 24.9 38.5 41.5 13.5 13.5 21.5 25.3 38.8 41.8 13.5 13.5 21.5 25.3 38.8 41.8 9.7 9.9 9.9

— — — — — — —

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

% Voltage Imbalance = 100 x

60/ 60 60/ 60 50/ 60 70/ 80** 90/100** 110/125** 60/ 60 60/ 60 50/ 60 70/ 80** 90/100** 110/125** 35/ 35 35/ 35 40/ 40 50/ 60 70 80** 80/ 90** 35/ 35 35/ 35 35/ 40 50/ 60 70/ 70** 80/ 90** 35/ 35 35/ 35 40/ 45 60/ 60 70/ 80** 80/ 90** 20 20 25 25 40 45 20 20 25 30 40 45 20 20 25 30 40 45 15 15 15

FLA

LRA

42/ 42 42/ 42 43/ 48 61/ 69 79/ 90 94/107 42/ 42 42/ 42 44/ 49 62/ 70 80/ 91 95/108 27/ 27 27/ 27 32/ 36 45/ 51 57/ 65 70/ 80 26/ 26 26/ 26 31/ 35 44/ 50 56/ 64 70/ 79 29/ 29 29/ 29 34/ 38 47/ 53 59/ 67 72/ 82 13 13 19 23 35 38 13 13 20 23 36 38 13 13 20 23 36 38 11 11 11

161/161 161/161 161/161 161/161 161/161 161/161 184/184 184/184 184/184 184/184 184/184 184/184 128/128 128/128 128/128 128/128 128/128 128/128 148/148 148/148 148/148 148/148 148/148 148/148 174/174 174/174 174/174 174/174 174/174 174/174 71 72 72 72 72 72 81 81 81 81 81 81 93 94 94 94 94 94 58 65 75

7 457

= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. **Fuse only.

3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 5 ton unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance = 100 x

MOCP*

Determine percent of voltage imbalance.

LEGEND FLA HACR IFM LRA MCA MOCP NEC

DISCONNECT SIZE†

POWER SUPPLY

max voltage deviation from average voltage average voltage

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage = =

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

27

POWER EXHAUST PART NO.

MCA (230 v)

MCA (460 v)

MCA (575 v)

CRPWREXH021A00 CRPWREXH022A00 CRPWREXH023A00 CRPWREXH024A00 CRPWREXH025A00 CRPWREXH026A00 CRPWREXH027A00 CRPWREXH028A00 CRPWREXH029A00 CRPWREXH030A00

N/A 3.3 N/A 1.6 N/A 3.3 N/A 1.7 N/A 1.6

0.9 N/A 1.8 N/A 0.9 N/A 1.8 N/A 1.0 N/A

N/A 1.32 N/A 0.64 N/A 1.32 N/A 0.68 N/A 0.64

MOCP (for separate power source) 15 15 15 15 15 15 15 15 15 15

Table 7 — Electrical Data — Standard-Efficiency Cooling Only Units (Without Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-3-60 HIGH

6 Tons STD 460-3-60 HIGH

575-3-60

STD HIGH STD AND ALT

208/230-3-60 HIGH

STD AND ALT

71/2 Tons 460-3-60

HIGH

575-3-60

STD AND ALT HIGH

STD 208/230-3-60 HIGH

STD

81/2 Tons 460-3-60

HIGH

STD 575-3-60 HIGH

ELECTRIC HEAT Nominal kW —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — — —/— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.9/42.4 —/— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.9/42.4 — 13.9 16.5 27.8 33.0 41.7 — 13.9 16.5 27.8 33.0 41.7 — 17.0 34.0 — 17.0 34.0 —/— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.9/42.4 —/— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.9/42.4 — 13.9 16.5 27.8 33.0 41.7 — 13.9 16.5 27.8 33.0 41.7 — 17.0 34.0 — 17.0 34.0

POWER SUPPLY

DISCONNECT SIZE†

FLA

MCA

MOCP*

FLA

LRA

—/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — — —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 17.1 34.1 — 17.1 34.1 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 17.1 34.1 — 17.1 34.1

32.4/32.4 32.4/32.4 33.9/38.1 48.2/54.6 61.2/69.6 75.6/86.2 34.7/34.7 34.7/34.7 36.7/40.9 51.1/57.4 64.1/72.5 78.4/89.1 15.4 15.4 20.5 24.3 37.8 41.6 16.2 16.2 21.5 25.3 38.8 42.6 11.4 11.9 40.1/ 40.1 40.1/ 40.1 48.9/ 55.4 71.9/ 81.8 90.6/103.5 117.7/134.8 44.9/ 44.9 44.9/ 44.9 54.9/ 61.4 77.9/ 87.8 96.6/109.5 123.7/140.8 18.4 26.9 28.1 45.0 52.9 65.9 20.6 26.9 30.8 47.8 55.6 68.7 14.9 23.9 45.3 16.7 26.1 47.5 44.6/ 44.6 44.6/ 44.6 48.9/ 55.4 71.9/ 81.8 90.6/103.5 117.7/134.8 49.4/ 49.4 49.4/ 49.4 54.9/ 61.4 77.9/ 87.8 96.6/109.5 123.7/140.8 22.7 24.1 28.1 45.0 52.9 65.9 24.9 26.9 30.8 47.8 55.6 68.7 17.6 23.9 45.3 19.4 26.1 47.5

40/40 40/40 35/40 50/60 70/70** 80/90** 40/40 40/40 40/45 60/60 70/80** 80/90** 20 20 25 25 40 45 20 20 25 30 40 45 15 15 45/ 45 45/ 45 50/ 60 80/ 90** 100/110** 125/150** 50/ 50 50/ 50 60/ 70** 80/ 90** 100/110** 125/150** 20 30 30 50 60 70** 25 30 35 50 60 70** 20 25 50 20 30 50 50/ 50 50/ 50 50/ 60 80/ 90** 100/110** 125/150** 60/ 60 60/ 60 60/ 70** 80/ 90** 100/110** 125/150** 25 25 30 50 60 70** 30 30 35 50 60 70** 20 25 50 25 30 50

31/31 31/31 31/35 44/50 56/64 70/79 34/34 34/34 34/38 47/53 59/67 72/82 15 15 19 22 35 38 16 16 20 23 36 39 12 13 42/ 42 42/ 42 45/ 51 66/ 75 83/ 95 108/124 48/ 48 48/ 48 51/ 56 72/ 81 89/101 114/129 19 25 26 41 49 61 22 25 28 44 51 63 16 22 42 18 24 44 47/ 47 47/ 47 47/ 51 66/ 75 83/ 95 108/124 52/ 52 52/ 52 52/ 56 72/ 81 89/101 114/129 24 24 26 41 49 61 26 26 28 44 51 63 18 22 42 20 24 44

180/180 180/180 180/180 180/180 180/180 180/180 205/205 205/205 205/205 205/205 205/205 205/205 90 90 90 90 90 90 103 103 103 103 103 103 75 86

28

229/229

273/273

138

130

97

114

321/321

365/365

161

184

135

152

Table 7 — Electrical Data — Standard-Efficiency Cooling Only Units (Without Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-Ph-Hz

IFM TYPE

STD

ALT

208/230-3-60

HIGH

STD

10 Tons ALT

460-3-60

HIGH

STD

ALT

575-3-60

HIGH

STD 208/230-3-60 ALT

STD 121/2 Tons 460-3-60 ALT

STD 575-3-60 ALT

ELECTRIC HEAT Nominal kW —/— 7.8/10.4 12.0/16.0 24.0/32.0 31.9/42.4 37.5/50.0 —/— 7.8/10.4 12.0/16.0 24.0/32.0 31.9/42.4 37.5/50.0 —/— 7.8/10.4 12.0/16.0 24.0/32.0 31.9/42.4 37.5/50.0 — 16.5 27.8 33.0 41.7 50.0 — 16.5 27.8 33.0 41.7 50.0 — 16.5 27.8 33.0 41.7 50.0 — 17.0 34.0 51.0 — 17.0 34.0 51.0 — 17.0 34.0 51.0 —/— 7.8/10.4 12.0/16.0 24.0/32.0 31.9/42.4 37.5/50.0 —/— 7.8/10.4 12.0/16.0 24.0/32.0 31.9/42.4 37.5/50.0 — 16.5 27.8 33.0 41.7 50.0 — 16.5 27.8 33.0 41.7 50.0 — 17.0 34.0 51.0 — 17.0 34.0 51.0

POWER SUPPLY MCA

MOCP*

FLA

—/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 17.1 34.1 51.2 — 17.1 34.1 51.2 — 18.0 36.0 51.2 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 17.1 34.1 51.2 — 17.1 34.1 51.2

44.2/ 44.2 44.2/ 44.2 48.9/ 55.4 90.6/103.5 117.7/134.8 137.5/157.6 45.9/ 45.9 45.9/ 45.9 51.1/ 57.5 92.8/105.6 119.9/136.9 139.7/159.7 53.4/ 53.4 53.4/ 53.4 60.4/ 66.9 102.1/115.0 129.2/146.3 149.0/169.0 21.8 28.1 45.0 52.9 65.9 63.4 22.6 29.1 46.0 53.9 66.9 64.4 26.6 34.1 51.0 58.9 71.9 69.4 18.9 23.9 45.3 55.8 19.7 24.7 46.1 54.6 23.7 28.7 50.1 58.6 65.2/ 65.2 65.2/ 65.2 65.2/ 65.2 96.6/109.5 123.7/140.8 143.5/163.6 69.6/ 69.6 69.6/ 69.6 69.6/ 69.6 102.1/115.0 129.2/146.3 149.0/169.0 29.6 30.8 47.8 55.6 68.7 66.1 32.2 34.1 51.0 58.9 71.9 69.4 23.6 26.1 47.5 56.0 25.7 28.7 50.1 58.6

50/ 50 50/ 50 60/ 60 100/110** 125/150** 150/175** 50/ 50 50/ 50 60/ 60 100/110** 125/150** 150/175** 50/ 50 60/ 60 60/ 80** 110/125** 150/150** 150/175** 25 30 50 60 70** 70** 25 30 50 60 70** 70** 30 35 60 60 80** 80** 25 25 50 60 25 25 50 60 30 35 60 70** 80/ 80** 80/ 80** 70/ 70** 100/110** 125/150** 150/175** 80/ 80** 80/ 80** 80/ 80** 110/125** 150/150** 150/175** 40 40 50 60 70** 80** 45 45 60 60 80** 80** 30 30 50 60 30 35 60 70**

46/ 46 45/ 45 45/ 51 83/ 95 108/124 127/147 48/ 48 47/ 47 47/ 53 85/ 97 110/126 128/147 57/ 57 56/ 56 56/ 62 94/106 119/135 137/156 23 26 41 49 61 72 24 27 42 50 62 73 28 31 47 54 66 78 20 22 42 61 21 23 42 62 25 26 46 66 68/ 68 68/ 68 68/ 68 89/101 114/129 132/151 73/ 73 73/ 73 73/ 73 94/106 119/135 137/156 31 31 44 51 63 75 34 34 47 54 66 78 25 25 44 53 27 27 46 66

— — — — — — —

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

max voltage deviation from average voltage average voltage

=

326/326

374/374

152

191

185

126

152

160

383/383

406/406

192

203

153

162

3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 71/2 ton unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage =

307/307

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. **Fuse only. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance = 100 x

LRA

Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

LEGEND FLA HACR IFM LRA MCA MOCP NEC

DISCONNECT SIZE†

FLA

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

29

POWER EXHAUST PART NO.

MCA (230 v)

MCA (460 v)

MCA (575 v)

CRPWREXH021A00 CRPWREXH022A00 CRPWREXH023A00 CRPWREXH024A00 CRPWREXH025A00 CRPWREXH026A00 CRPWREXH027A00 CRPWREXH028A00 CRPWREXH029A00 CRPWREXH030A00

N/A 3.3 N/A 1.6 N/A 3.3 N/A 1.7 N/A 1.6

0.9 N/A 1.8 N/A 0.9 N/A 1.8 N/A 1.0 N/A

N/A 1.32 N/A 0.64 N/A 1.32 N/A 0.68 N/A 0.64

MOCP (for separate power source) 15 15 15 15 15 15 15 15 15 15

Table 8 — Electrical Data — Standard-Efficiency Cooling Only Units (With Convenience Outlet) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-1-60 ALT

STD

208/230-3-60

ALT

3 Tons HIGH

STD

460-3-60

ALT

HIGH

575-3-60

STD ALT HIGH

STD 208/230-1-60 ALT

STD

208/230-3-60

ALT

4 Tons HIGH

STD

460-3-60

ALT

HIGH

575-3-60

STD ALT HIGH

ELECTRIC HEAT Nominal kW —/— 3.3/ 4.4 4.9/ 6.5 6.4/ 8.7 7.9/10.5 9.8/13.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 9.8/13.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.2/16.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.3/16.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.3/16.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — — — —/— 3.3/ 4.4 6.5/ 8.7 9.3/13.0 13.1/17.4 15.8/21.0 —/— 3.3/ 4.4 6.5/ 8.7 9.3/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — — —

FLA

MCA

—/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.8 46.9/54.2 —/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.8 46.9/54.2 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.4 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.4 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.4 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — — — —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 18.1/20.9 33.4/38.4 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.4 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.4 43.8/50.5 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — — —

31.2/31.2 31.2/32.3 38.7/43.2 48.6/54.7 56.8/64.1 68.0/77.1 32.6/32.6 32.6/34.0 40.5/45.0 50.4/56.4 58.5/65.8 69.8/78.8 22.5/22.5 22.5/23.0 27.3/29.4 33.1/36.0 37.7/42.0 52.1/57.9 23.9/23.9 23.9/24.8 29.1/31.1 34.8/37.7 39.5/43.7 53.8/59.6 24.2/24.2 24.2/25.2 29.5/31.5 35.2/38.1 39.9/44.1 54.2/60.0 9.8 13.4 17.6 21.6 25.4 10.6 14.4 18.6 22.6 26.4 11.1 15.0 19.2 23.3 27.0 7.2 7.7 8.0 40.0/ 40.0 40.0/ 40.0 48.6/ 54.7 68.0/ 77.1 87.9/100.0 104.2/118.8 41.4/ 41.4 41.4/ 41.4 50.4/ 56.4 69.8/ 78.8 89.7/101.8 105.9/120.5 29.0/ 29.0 29.0/ 29.4 33.1/ 36.0 52.1/ 57.9 65.1/ 73.5 30.4/ 30.4 30.4/ 31.1 34.8/ 37.7 53.8/ 59.6 66.9/ 75.3 30.7/ 30.7 30.7/ 31.5 35.2/ 38.1 54.2/ 60.0 67.2/ 75.7 15.2 15.2 22.3 26.0 39.6 15.5 15.5 22.6 26.4 39.9 16.0 16.0 23.3 27.0 40.6 10.9 11.1 11.4

30

DISCONNECT SIZE†

POWER SUPPLY MOCP* 35/35 35/35 40/45 50/60 60/70** 70/80** 40/40 40/40 45/45 60/60 60/70** 70/80** 30/30 30/30 30/30 35/40 40/45 60/60 30/30 30/30 30/35 35/40 40/45 60/60 30/30 30/30 35/35 40/40 40/45 60/60 15 15 20 25 30 15 15 20 25 30 15 20 20 25 30 15 15 15 45/ 45 45/ 45 50/ 60 70/ 80** 90/100** 110/125** 50/ 50 50/ 50 60/ 60 70/ 80** 90/110** 110/125** 35/ 35 35 35 35/ 40 60/ 60 70/ 80** 35/ 35 35/ 35 35/ 40 60/ 60 70/ 80** 35/ 35 35/ 35 40/ 40 60/ 60 70/ 80** 20 20 25 30 40 20 20 25 30 40 20 20 25 30 45 15 15 15

FLA

LRA

30/30 30/31 37/41 46/51 53/60 64/72 31/31 31/32 38/42 47/53 55/61 65/73 23/23 23/23 25/28 30/34 35/39 48/54 25/25 25/25 27/29 32/35 36/40 50/55 25/25 25/25 27/29 32/36 37/41 50/56 10 12 16 20 23 11 13 17 21 24 11 14 18 21 25 8 9 9 38/ 38 38/ 38 46/ 51 64/ 72 82/ 93 97/110 40/ 40 40/ 40 47/ 53 65/ 73 83/ 95 98/112 29/ 29 29/ 29 30/ 34 48/ 54 60/ 68 30/ 30 30/ 30 32/ 35 50/ 55 62/ 69 31/ 31 31/ 31 32 /36 50/ 56 62/ 70 15 15 20 24 36 15 15 21 24 37 16 16 21 25 37 12 12 12

111/111 111/111 111/111 111/111 111/111 111/111 116/116 116/116 116/116 116/116 116/116 116/116 90/ 90 90 90 90/ 90 90/ 90 90/ 90 90/ 90 95/ 95 95/ 95 95/ 95 95/ 95 95/ 95 95/ 95 114/114 114/114 114/114 114/114 114/114 114/114 47 47 47 47 47 50 50 50 50 50 59 59 59 59 59 36 39 58 134/134 134/134 134/134 134/134 134/134 134/134 138/138 138/138 138/138 138/138 138/138 138/138 106/106 106/106 106/106 106/106 106/106 110/110 110/110 110/110 110/110 110/110 129/129 129/129 129/129 129/129 129/129 53 53 53 53 53 55 55 55 55 55 64 64 64 64 64 42 44 51

Table 8 — Electrical Data — Standard-Efficiency Cooling Only Units (With Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD 208/230-1-60 ALT

STD

ALT

208/230-3-60

5 Tons HIGH

STD

ALT

460-3-60

HIGH

STD ALT HIGH

575-3-60

ELECTRIC HEAT Nominal kW —/— 4.9/ 6.5 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.0 — 6.0 11.5 14.0 23.0 25.0 — 6.0 11.5 14.0 23.0 25.0 — — —

FLA

MCA

—/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.1 — 7.2 13.8 16.8 27.7 30.1 — 7.2 13.8 16.8 27.7 30.1 — — —

49.3/ 49.3 49.3/ 49.3 51.6/ 57.7 71.0/ 80.1 90.9/103.0 107.2/121.8 50.0/ 50.0 50.0/ 50.0 52.5/ 58.6 71.9/ 81.0 91.8/103.9 108.0/122.6 32.1/ 32.1 32.1/ 32.4 40.7/ 44.4 55.1/ 60.9 68.1/ 76.5 82.4/ 92.5 31.4/ 31.4 31.4/ 31.5 39.9/ 43.5 54.2/ 60.0 67.2/ 75.7 81.6/ 91.6 33.7/ 33.7 33.7/ 34.4 42.7/ 46.4 57.1/ 62.9 70.1/ 78.5 84.4/ 94.5 15.3 15.6 23.9 27.6 41.2 44.2 15.6 16.0 24.3 28.0 41.6 44.6 15.6 16.0 24.3 28.0 41.6 44.6 11.5 11.7 11.7

— — — — — — —

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

% Voltage Imbalance = 100 x

LRA 166/166 166/166 166/166 166/166 166/166 166/166 188/188 188/188 188/188 188/188 188/188 188/188 133/133 133/133 133/133 133/133 133/133 133/133 153/153 153/153 153/153 153/153 153/153 153/153 179/179 179/179 179/179 179/179 179/179 179/179 74 74 74 74 74 74 83 83 83 83 83 83 96 96 96 96 96 96 60 67 77

7 457

3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 5 ton unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

% Voltage Imbalance max voltage deviation from average voltage average voltage

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

=

FLA 47/ 47 47/ 47 48/ 54 66/ 75 85/ 96 100/113 48/ 48 48/ 48 49/ 55 67/ 75 85/ 96 100/114 32/ 32 32/ 32 37/ 41 51/ 57 63/ 70 76/ 86 32/ 32 32/ 32 37/ 41 50/ 56 62/ 70 75/ 85 34/ 34 34/ 34 39/ 43 53/ 58 65/ 72 78/ 87 15 15 22 25 38 41 16 16 22 26 38 41 16 16 22 26 38 41 13 13 13

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

Average Voltage =

60/ 60 60/ 60 60/ 60 80/ 90** 100/110** 110/125** 60/ 60 60/ 60 60/ 60 80/ 90** 100/110** 110/125** 40/ 40 40/ 40 45/ 45 60/ 70** 70/ 80** 90/100** 40/ 40 40/ 40 40/ 45 60/ 60 70/ 80** 90/100** 40/ 40 40/ 40 45/ 50 60/ 70** 80/ 80** 90/100** 20 20 25 30 45 45 20 20 25 30 45 45 20 20 25 30 45 45 15 15 15

= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. **Fuse only.

= 100 x

MOCP*

Maximum deviation is 7 v. Determine percent of voltage imbalance.

LEGEND FLA HACR IFM LRA MCA MOCP NEC

DISCONNECT SIZE†

POWER SUPPLY

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

31

POWER EXHAUST PART NO.

MCA (230 v)

MCA (460 v)

MCA (575 v)

CRPWREXH021A00 CRPWREXH022A00 CRPWREXH023A00 CRPWREXH024A00 CRPWREXH025A00 CRPWREXH026A00 CRPWREXH027A00 CRPWREXH028A00 CRPWREXH029A00 CRPWREXH030A00

N/A 3.3 N/A 1.6 N/A 3.3 N/A 1.7 N/A 1.6

0.9 N/A 1.8 N/A 0.9 N/A 1.8 N/A 1.0 N/A

N/A 1.32 N/A 0.64 N/A 1.32 N/A 0.68 N/A 0.64

MOCP (for separate power source) 15 15 15 15 15 15 15 15 15 15

Table 8 — Electrical Data — Standard-Efficiency Cooling Only Units (With Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-Ph-Hz

IFM TYPE

FLA

MCA

MOCP†

FLA

LRA

37.2/37.2 37.2/37.2 37.2/38.1 54.2/60.0 67.2/75.7 81.6/91.6 39.5/39.5 39.5/39.5 39.5/40.9 57.1/62.9 70.1/78.5 84.4/94.5 17.6 17.6 20.5 27.0 40.6 44.3 18.4 18.4 21.5 28.0 41.6 45.3 13.1 13.7 46.1/ 46.1 46.1/ 46.1 53.9/ 60.4 76.9/ 86.8 95.6/108.5 122.7/139.8

45/ 45 45/ 45 40/ 45 60/ 60 70/ 80** 90/100** 45/ 45 45/ 45 45/ 50 60/ 70** 80/ 80** 90/100** 20 20 25 30 45 45 25 25 25 30 45 50 20 20 50/ 50 50/ 50 60/ 70** 80/ 90** 100/110** 125/150**

37/37 37/37 37/41 50/56 62/70 75/85 39/39 39/39 39/43 53/58 65/72 78/87 17 17 21 25 37 41 18 18 22 26 38 42 14 15 48/ 48 48/ 48 51/ 56 72/ 81 89/101 114/130

184/184 184/184 184/184 184/184 184/184 184/184 210/210 210/210 210/210 210/210 210/210 210/210 92 92 92 92 92 92 105 105 105 105 105 105 77 87

HIGH

— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4

— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0

50.9/ 50.9 50.9/ 50.9 59.9/ 66.4 82.9/ 92.8 101.6/114.5 128.7/145.8

60/ 60 60/ 60 70/ 70** 90/100** 110/125** 150/150**

53/ 53 53/ 53 56/ 62 77/ 86 94/106 119/135

277/277

STD AND ALT

— 13.9 16.5 27.8 33.0 41.7

— 16.7 19.8 33.4 39.7 50.2

21.1 26.8 30.8 47.8 55.6 68.6

25 25 35 50 60 70**

22 25 28 44 51 63

110

HIGH

— 13.9 16.5 27.8 33.0 41.7

— 16.7 19.8 33.4 39.7 50.2

23.3 29.5 33.5 50.4 58.3 71.3

25 30 35 60 60 80**

24 27 31 46 54 66

132

— 17.0 34.0 — 17.0 34.0 — 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4

— 17.1 34.1 — 17.1 34.1 — 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0

17.6 26.6 48.0 19.4 28.8 50.1 50.6/ 50.6 50.6/ 50.6 53.9/ 60.4 76.9/ 86.8 95.6/108.5 122.7/139.8

20 25 50 25 30 60 60/ 60 60/ 60 60/ 70** 80/ 90** 100/110** 125/150**

18 24 44 20 26 46 52/ 52 52/ 52 52/ 56 72/ 81 89/101 114/130

— 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.9/42.4

— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0

55.4/ 55.4 55.4/ 55.4 59.9/ 66.4 82.9/ 92.8 101.6/114.5 128.7/145.8

60/ 60 60/ 60 70/ 70** 90/100** 110/125** 150/150**

58/ 58 58/ 58 58/ 62 77/ 86 94/106 119/135

— 13.9 16.5 27.8 33.0 41.7 — 13.9 16.5 27.8 33.0 41.7

— 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2

25.4 26.8 30.8 47.7 55.6 68.6 27.6 29.5 33.5 50.4 58.3 71.3

30 30 35 50 60 70** 30 30 35 60 60 80**

26 26 28 44 51 63 26 29 31 46 54 66

— 17.0 34.0 — 17.0 34.0

— 17.1 34.1 — 17.1 34.1

20.3 26.6 49.9 22.1 28.8 50.1

25 25 50 25 30 60

20 24 44 22 26 46

HIGH

6 Ton STD 460-3-60 HIGH

STD HIGH STD AND ALT

208/230-3-60

460-3-60

575-3-60

STD AND ALT HIGH

STD 208/230-3-60 HIGH

81/2

STD

Ton

DISCONNECT SIZE*

—/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.4 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — — — 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0

208/230-3-60

71/2 Ton

POWER SUPPLY

Nominal kW —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — — — 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4

STD

575-3-60

ELECTRIC HEAT

460-3-60 HIGH

STD 575-3-60 HIGH

32

233/233

100

117

325/325

369/369

164

186

138

155

Table 8 — Electrical Data — Standard-Efficiency Cooling Only Units (With Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-Ph-Hz

IFM TYPE

STD

ALT

208/230-3-60

HIGH

STD 10 Ton

ALT

460-3-60

HIGH

STD

ALT

575-3-60

HIGH

FLA HACR IFM LRA MCA MOCP NEC

— — — — — — —

ELECTRIC HEAT Nominal kW — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 16.5 27.8 33.0 41.7 50.0 — 16.5 27.8 33.0 41.7 50.0 — 16.5 27.8 33.0 41.7 50.0 — 17.0 34.0 51.0 — 17.0 34.0 51.0 — 17.0 34.0 51.0

POWER SUPPLY

DISCONNECT SIZE*

FLA

MCA

MOCP†

FLA

— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 — 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 — 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 17.1 34.1 51.2 — 17.1 34.1 51.2 — 17.1 34.1 51.2

49.1/ 49.1 49.1/ 49.1 53.9/ 60.4 95.6/108.5 122.7/139.8 142.5/132.5 50.8/ 50.8 50.8/ 50.8 56.1/ 62.5 97.8/110.6 124.9/141.9 144.7/134.7 58.3/ 58.3 58.3/ 58.3 65.4/ 71.9 107.1/120.0 134.2/151.3 154.0/144.0 23.7 30.7 47.8 55.5 68.6 65.6 24.5 31.7 48.8 56.6 69.7 66.6 28.5 36.7 53.8 61.5 74.6 71.6 20.6 26.6 47.9 56.0 21.2 27.4 48.8 56.8 24.4 31.4 52.7 60.8

60/ 60 60/ 60 60/ 70** 100/110** 125/150** 150/150** 60/ 60 60/ 60 60/ 60 100/125** 125/150** 150/150** 70/ 70** 70/ 70** 60/ 80** 110/125** 150/175** 175/175** 30 30 50 60 70** 70** 30 30 50 60 70** 70** 30 35 60 70** 80** 80** 25 25 50 60 25 30 50 60 30 35 60 70**

50/ 50 50/ 50 51/ 56 89/101 114/130 132/151 52/ 52 52/ 52 53/ 58 91/103 116/131 134/152 61/ 61 61/ 61 61/ 67 99/111 124/140 143/161 24 28 44 51 63 75 25 29 45 52 64 76 30 34 49 57 69 80 21 24 44 63 21 25 44 64 25 28 48 68

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

LRA

311/311

330/330

378/378

154

194

188

110

141

136

Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. **Fuse only.

3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 71/2 ton unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v 452 + 464 + 455 Average Voltage = 3 1371 = 3 = 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

33

POWER EXHAUST PART NO.

MCA (230 v)

MCA (460 v)

MCA (575 v)

CRPWREXH021A00 CRPWREXH022A00 CRPWREXH023A00 CRPWREXH024A00 CRPWREXH025A00 CRPWREXH026A00 CRPWREXH027A00 CRPWREXH028A00 CRPWREXH029A00 CRPWREXH030A00

N/A 3.3 N/A 1.6 N/A 3.3 N/A 1.7 N/A 1.6

0.9 N/A 1.8 N/A 0.9 N/A 1.8 N/A 1.0 N/A

N/A 1.32 N/A 0.64 N/A 1.32 N/A 0.68 N/A 0.64

MOCP (for separate power source) 15 15 15 15 15 15 15 15 15 15

Table 8 — Electrical Data — Standard-Efficiency Cooling Only Units (With Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-Ph-Hz

IFM TYPE

STD 208/230-3-60 ALT

STD

121/2 Ton 460-3-60

ALT

STD 575-3-60 ALT

ELECTRIC HEAT Nominal kW — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 16.5 27.8 33.0 41.7 50.0 — 16.5 27.8 33.0 41.7 50.0 — 17.0 34.0 51.0 — 17.0 34.0 51.0

POWER SUPPLY FLA

MCA

MOCP†

FLA

— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 — 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 17.1 34.1 51.2 — 17.1 34.1 51.2

71.2/ 71.2 71.2/ 71.2 71.2/ 71.2 101.6/114.5 128.7/145.8 148.5/138.5 75.6/ 75.6 75.6/ 75.6 75.6/ 75.6 107.1/120.0 134.2/151.3 154.0/144.0 32.3 33.4 50.5 58.2 71.4 68.3 34.9 36.7 53.8 61.6 74.7 71.6 23.6 28.8 50.1 56.0 28.4 31.4 52.8 58.6

80/ 80** 80/ 80** 80/ 80** 110/125** 150/150** 150/150** 90/ 80** 90/ 80** 90/ 80** 110/125** 150/175** 175/175** 45 45 60 60 80** 80** 45 45 60 70** 80** 80** 30 30 60 70** 30 35 60 70**

74/ 74 74/ 74 74/ 74 94/106 119/135 138/156 79/ 79 79/ 79 79/ 79 99/111 124/140 143/161 34 34 46 54 66 77 37 37 49 57 69 80 27 27 46 65 29 29 48 68

LEGEND FLA HACR IFM LRA MCA MOCP NEC

— — — — — — —

LRA

387/387

410/410

195

206

156

165

Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

= 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker. **Fuse only.

3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 71/2 ton unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance = 100 x

DISCONNECT SIZE*

max voltage deviation from average voltage average voltage

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v 452 + 464 + 455 Average Voltage = 3 1371 = 3 = 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

34

POWER EXHAUST PART NO.

MCA (230 v)

MCA (460 v)

MCA (575 v)

CRPWREXH021A00 CRPWREXH022A00 CRPWREXH023A00 CRPWREXH024A00 CRPWREXH025A00 CRPWREXH026A00 CRPWREXH027A00 CRPWREXH028A00 CRPWREXH029A00 CRPWREXH030A00

N/A 3.3 N/A 1.6 N/A 3.3 N/A 1.7 N/A 1.6

0.9 N/A 1.8 N/A 0.9 N/A 1.8 N/A 1.0 N/A

N/A 1.32 N/A 0.64 N/A 1.32 N/A 0.68 N/A 0.64

MOCP (for separate power source) 15 15 15 15 15 15 15 15 15 15

Table 9 — Electric Heating Usage — Standard-Efficiency Cooling Only Units UNIT SIZE

VOLTAGE (60 Hz) 208/230/240 (single phase)

3 Tons

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (single phase)

4 Tons

208/230/240 (3 phase) 460/480 (3 phase)

208/230/240 (single phase)

5 Tons

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (3 phase) 6 Tons 460/480 (3 phase)

208/230/240 (3 phase) 71/2 Tons 460/480 (3 phase) 575 (3 phase) 208/230/240 (3 phase) 81/2 Tons 460/480 (3 phase) 575 (3 phase) 208/230/240 (3 phase)

10 Tons

460/480 (3 phase) 575 (3 phase) 208/230/240 (3 phase)

121/2 Tons

460/480 (3 phase) 575 (3 phase)

ACCESSORY kW 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 9.8/11.6/13.0* 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 12.0/14.7/16.0 5.5/ 6.0 8.1/ 8.8 10.6/11.5 12.9/14.0 3.3/ 4.0/ 4.4 6.5/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 16.0/19.3/21.0* 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 12.0/14.7/16.0 15.8/19.3/21.0* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 4.9/ 5.8/ 6.5 6.6/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 15.8/19.3/21.0* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5* 7.8/ 9.6/10.4 12.0/14.7/16.0 18.6/22.8/24.8 24.0/29.4/32.0 31.8/39.0/42.4 12.8/13.9 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7 17.0 34.0 7.8/ 9.6/10.4 12.0/14.7/16.0 18.6/22.8/24.8 24.0/29.4/32.0 31.8/39.0/42.4 12.8/13.9 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7 17.0 34.0 7.8/ 9.6/10.4 12.0/14.7/16.0 24.0/29.4/32.0 31.8/38.9/42.4 37.5/46.0/50.0 12.8/13.9 15.2/16.5 30.4/33.0 38.4/41.7 46.0/50.0 17.0 34.0 51.0 7.8/ 9.6/10.4 12.0/14.7/16.0 24.0/29.4/32.0 31.8/38.9/42.4 37.5/46.0/50.0 12.8/13.9 15.2/16.5 30.4/33.0 38.4/41.7 46.0/50.0 17.0 34.0 51.0

ACCESSORY HEATER PART NUMBER CRHEATER---A00 001 002 003 004 002+002 001 002 003 004 005 006 007 008 009 001 003 002+002 003+003 004+004 002 003 005 004+004 006 008 009 008+008 002 003 002+002 003+003 004+004 002 004 005 004+004 004+005 006 008 009 008+008 008+009 002 004 005 004+004 004+005 006 008 009 008+008 008+009 017 010 011 012 012+017 016 013 014 015 014+016 018 019 017 010 011 012 012+017 016 013 014 015 014+016 018 019 017 010 012 012+017 010+012 013 014 015 014+016 013+015 018 019 018+019 017 010 012 012+017 010+012 013 014 015 014+016 013+015 018 019 018+019

*Two heater packages required to provide kW indicated. †004 on units with convenience outlet. **002 on units with convenience outlet. NOTES: 1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly. 2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kWnew = Heater kW rated x (unit power distribution voltage/rated heater voltage)2 As an example: For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kW new = 16 kW (215/240)2 kW new = 12.8 kW (rating at 215 v)

35

SINGLE POINT BOX PACKAGE NO. CRSINGLE---A00 — — —† — 004 — — — — — — — — — — — 004 004 004 — — — 002 — — — — — — 004 004 004 — — —** 002 002 — — — — — — — — 002 002 — — — — — 006 006 007 007 009 006 006 006 006 008 006 006 006 006 007 007 009 006 006 006 006 008 006 006 011 011 012 015 015 011 011 011 014 014 011 011 014 012 012 012 015 015 011 011 011 014 014 011 014 014

NO SINGLE POINT BOX REQUIRED

Fig. 16 — Electric Heater Power Wiring Connections — Heat Pump Units, 208/230-1-60 — Less Than 60 Amps MOCP

CRSINGLE004A00

CRSINGLE005A00

Fig. 17 — Electric Heater Power Wiring Connections — Heat Pump Units, 208/230-1-60 — Greater Than 60 Amps MOCP

NO SINGLE POINT BOX REQUIRED OR CRSINGLE006A00 OR CRSINGLE0011A00

Fig. 18 — Electric Heater Power Wiring Connections — Heat Pump Units, 208/230-3-60, 460-3-60 and 575-3-60 — Less Than 60 Amps MOCP 36

CRSINGLE002A00 OR CRSINGLE007A00 OR CRSINGLE012A00

CRSINGLE003A00 OR CRSINGLE009A00 OR CRSINGLE015A00

CRSINGLE013A00

CRSINGLE017A00

Fig. 19 — Electric Heater Power Wiring Connections — Heat Pump Units, 208/230-3-60 — Greater Than 60 Amps MOCP

CRSINGLE008A00 AND CRSINGLE014A00

CRSINGLE010A00 AND CRSINGLE016A00

Fig. 20 — Electric Heater Power Wiring Connections — Heat Pump Units, 460-3-60 and 575-3-60 — Greater Than 60 Amps MOCP

37

Table 10 — Electrical Data — High-Efficiency Heat Pump Units — Standard Motor Units (Without Electrical Convenience Outlet) UNIT SIZE

NOMINAL VOLTAGE V-PH-Hz

208/230-1-60

3 Tons

208/230-3-60

460-3-60

208/230-1-60

4 Tons

208/230-3-60

460-3-60

208/230-1-60

5 Tons

208/230-3-60

460-3-60

208/230-3-60 6 Tons 460-3-60

208/230-3-60 71/2 Tons 460-3-60

208/230-3-60 10 Tons 460-3-60

ELECTRIC HEAT* kW† —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 9.8/13.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.0/16.0 — 6.0 8.8 11.5 14.0 —/— 3.3/ 4.4 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 — 6.0 11.5 14.0 23.0 —/— 4.9/ 6.5 6.5/ 8.7 9.8/16.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 — 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4 — 13.9 16.5 27.8 33.0 41.7 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 16.5 27.8 33.0 41.7 50.0

POWER SUPPLY

FLA —/— 15.9/18.3 23.6/27.1 31.3/36.3 38.0/43.8 47.1/54.2 —/— 9.2/10.6 13.6/15.6 18.0/20.9 21.9/25.3 33.3/38.5 — 7.2 10.6 13.8 16.8 —/— 15.9/18.3 31.3/36.3 47.1/54.2 63.0/72.5 76.0/87.5 —/— 13.6/15.6 18.0/20.9 33.3/38.5 43.9/50.5 — 7.2 13.8 16.8 27.7 — 23.6/27.1 31.3/36.3 47.1/54.2 63.0/72.5 76.0/87.5 —/— 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 —/— 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.0 — 16.7 19.8 33.4 39.7 50.2 — 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.3 — 19.8 33.4 39.7 50.2 60.1

MCA 25.6/ 25.6 45.5/ 48.5 55.1/ 59.5 64.7/ 71.0 73.1/ 80.4 84.5/ 93.4 18.5/ 18.5 30.0/ 31.7 35.5/ 38.0 41.0/ 44.6 45.9/ 50.1 60.1/ 66.6 9.0 18.0 22.2 26.2 30.0 35.2/ 35.2 55.1/ 58.1 74.4/ 80.6 94.1/103.0 114.0/125.9 130.2/144.6 22.5/ 22.5 39.5/ 42.0 45.0/ 48.6 64.1/ 70.6 77.4/ 85.6 11.9 20.9 29.1 32.9 46.5 46.3/ 46.3 75.8/ 80.2 85.4/ 91.7 105.2/114.1 125.1/136.9 141.3/155.7 28.9/ 28.9 45.9/ 48.4 56.3/ 60.6 70.6/ 77.1 83.8/ 92.1 97.9/108.7 14.7 23.7 31.9 35.7 49.3 53.0 32.8/ 32.8 49.8/ 52.3 60.2/ 64.5 74.5/ 81.0 87.7/ 96.0 101.8/112.6 15.2 24.2 32.5 36.2 49.8 53.6 38.2/ 38.2 65.3/ 69.5 79.8/ 86.3 102.7/112.8 121.5/134.5 148.6/165.7 19.2 40.1 44.0 61.0 68.8 82.0 56.8/ 56.8 84.0/ 88.1 98.5/105.0 140.1/153.1 167.2/184.3 187.3/177.1 28.7 53.5 70.5 78.3 91.5 88.8

38

MOCP 30/ 30** 50/ 50** 60/ 60** 70/ 80 80/ 90 90/100 20/ 20** 30/ 35** 40/ 40** 45/ 45** 50/ 60** 70/ 70 15** 20** 25** 30** 30** 40/ 40** 60/ 60** 80/ 90 100/150 125/150 150/150 25/ 25** 45/ 45** 50/ 50** 70/ 80 90/100 15** 25** 30** 35** 50** 50/ 50** 80/ 90 90/100 110/125 150/150 150/175 30/ 30** 50/ 50** 60/ 70 80/ 80 90/100 100/110 15** 25** 35** 40** 50** 60** 35/ 35** 50/ 60** 70/ 70 80/ 90 90/100 110/125 20** 25** 35** 40** 50** 60** 40/ 40** 70/ 70** 80/ 90 110/125 125/150 150/175 20** 45** 45** 70 70 90 60/ 60** 90/ 90 100/110 150/175 175/200 200/200 30** 60** 80 80 100 100

FLA 25/ 25 43/ 46 52/ 56 61/ 67 69/ 75 79/ 87 18/ 18 29/ 30 34/ 36 39/ 42 43/ 47 57/ 63 9 17 21 25 28 34/ 34 52/ 55 70/ 75 88/ 96 106/117 121/134 22/ 22 38/ 40 43/ 46 60/ 66 72/ 80 12 20 27 31 43 45/ 45 72/ 76 81/ 87 99/107 117/128 132/146 28/ 28 44/ 46 53/ 57 67/ 73 79/ 86 92/102 14 23 30 34 46 50 32/ 32 47/ 50 57/ 61 70/ 76 82/ 90 95/105 15 23 31 34 47 50 40/ 40 65/ 69 79/ 85 100/109 117/129 142/158 20 39 43 59 66 78 60/ 60 85/ 89 98/104 136/148 161/177 180/198 30 53 69 76 88 99

MINIMUM UNIT DISCONNECT SIZE LRA 101/101 117/120 125/128 133/138 139/145 148/155†† 90/ 90 99/101 104/106 108/111 112/116 124/129 46 53 57 60 63 142/142 158/161 174/179 189/196†† 205/215†† 218/230†† 112/112 126/128 130/133 146/151 156/163 57 64 70 73 84 216/216 240/243 247/252†† 263/270†† 279/289†† 292/304†† 168/168 181/183 190/193 201/208 212/218†† 223/232†† 84 92 98 101 112 115 200/200 214/216 222/225 233/239 244/251†† 255/264†† 92 99 106 109 120 123 242/242 264/267 275/281†† 294/302†† 309/319†† 330/344†† 121 138 141 155 161 171 337/337 358/362†† 370/375†† 403/414†† 425/439†† 441/457†† 170 189 203 209 220†† 230††

Table 11 — Electrical Data — High-Efficiency Heat Pump Units — High-Static Motor Units (Without Electrical Convenience Outlet) UNIT SIZE

NOMINAL VOLTAGE V-PH-Hz

208/230-3-60 3 Tons 460-3-60

208/230-3-60 4 Tons 460-3-60

208/230-3-60 5 Tons 460-3-60

208/230-3-60 6 Tons 460-3-60

208/230-3-60 71/2 Tons 460-3-60

208/230-3-60 10 Tons 460-3-60

FLA HACR LRA MCA MOCP NEC

— — — — — —

ELECTRIC HEAT* kW† —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.0/16.0 — 6.0 8.8 11.5 14.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 — 6.0 11.5 14.0 23.0 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 — 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4 — 13.9 16.5 27.8 33.0 41.7 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.5/50.0 — 16.5 27.8 33.0 41.7 50.0

POWER SUPPLY

FLA —/— 9.2/10.6 13.6/15.6 18.0/20.9 21.9/25.3 33.3/38.5 — 7.2 10.6 13.8 16.8 —/— 13.6/15.6 18.0/20.9 33.3/38.5 43.9/50.5 — 7.2 13.8 16.8 27.7 —/— 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 —/— 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.0 — 16.7 19.8 33.4 39.7 50.2 — 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.3 — 19.8 33.4 39.7 50.2 60.1

MCA 19.4/ 19.4 30.9/ 32.6 36.4/ 38.9 41.9/ 45.5 46.8/ 51.0 61.0/ 67.5 9.4 18.4 22.6 26.6 30.4 23.4/ 23.4 40.4/ 42.9 45.9/ 49.5 65.0/ 71.5 78.3/ 86.5 12.3 21.3 29.5 33.3 46.9 30.6/ 30.6 47.6/ 50.1 58.0/ 62.3 72.3/ 78.8 85.5/ 93.8 99.6/110.4 15.5 24.5 32.7 36.5 50.1 53.8 34.5/ 34.5 51.5/ 54.0 61.9/ 66.2 76.2/ 82.7 89.4/ 97.7 103.5/114.3 16.0 25.0 33.3 37.0 50.6 54.4 41.3/ 41.3 68.4/ 72.6 82.9/ 89.4 105.8/115.9 124.6/137.6 151.7/168.8 20.6 41.5 45.4 62.4 70.2 83.4 61.2/ 61.2 88.4/ 92.5 102.9/109.4 144.5/157.5 171.6/188.7 191.7/181.5 31.3 56.1 73.1 80.9 94.1 96.4

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

MOCP 20/20 35/35 40/40 45/50 50/60 70/70 15** 20** 25** 30** 35** 25/ 25 45/ 45 50/ 50 70/ 80 80/ 90 15** 25** 30** 35** 50** 35/ 35 50/ 60 60/ 70 80/ 80 90/100 100/125 20** 25** 35** 40** 60** 60** 35/ 35 60/ 60 70/ 70 80/ 90 90/100 110/125 20** 25** 35** 40** 60** 60** 45/ 45** 70/ 80 90/ 90 110/125 125/150 175/175 25** 45** 50** 70 80 90 70/ 70 90/100 110/110 150/175 175/200 200/200 35** 60** 80 90 100 100

MINIMUM UNIT DISCONNECT SIZE FLA LRA 19/ 19 120/120 30/ 32 129/130 35/ 37 133/135 40/ 43 138/141 45/ 48 142/145 58/ 64 153/158 9 60 18 68 22 71 25 74 29 77 23/ 23 142/142 39/ 41 155/157 44/ 47 160/163 61/ 67 175/180 73/ 81 186/192†† 12 71 20 78 28 85 31 88 44 99 30/ 30 187/187 46/ 48 200/202 55/ 59 209/212 69/ 75 220/225 81/ 88 231/237** 94/104 242/251** 15 94 23 101 31 108 35 111 47 122 50 125 34/ 34 219/219 49/ 52 233/235 59/ 63 241/244 72/ 78 252/258 84/ 92 263/270** 97/107 274/283** 16 107 24 114 32 120 35 123 47 134 51 137 44/ 44 267/267 69/ 73 288/292 82/ 88 300/305†† 103/113 318/336†† 121/132 333/344†† 145/169 355/369†† 22 134 41 150 45 153 60 167 68 173 80 184 65/ 65 360/360 90/ 94 382/385†† 103/109 393/399†† 141/153 427/437†† 166/182 448/462†† 185/203 464/480†† 33 181 56 201 72 215 79 221 91 231†† 102 241††

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage =

452 + 464 + 455 3

1371 3 = 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. % Voltage Imbalance = 100 x 7 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. =

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. †Heaters are field installed only. **Fuse or HACR circuit breaker. ††Electrical disconnect cannot be used if electric heater is installed. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

39

Table 12 — Electrical Data — High-Efficiency Heat Pump Units — Standard Motor Units (With Electrical Convenience Outlet) UNIT SIZE

NOMINAL VOLTAGE V-PH-Hz

208/230-1-60

3 Tons

208/230-3-60

460-3-60

208/230-1-60

4 Tons

208/230-3-60

460-3-60

208/230-1-60

5 Tons

208/230-3-60

460-3-60

208/230-3-60 6 Tons 460-3-60

208/230-3-60 71/2 Tons 460-3-60

208/230-3-60 10 Tons 460-3-60

ELECTRIC HEAT* kW† —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 9.8/13.0 —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.0/16.0 — 6.0 8.8 11.5 14.0 —/— 3.3/ 4.4 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 — 6.0 11.5 14.0 23.0 —/— 4.9/ 6.5 6.5/ 8.7 9.8/16.0 13.1/17.4 15.8/21.0 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 — 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4 — 13.9 16.5 27.8 33.0 41.7 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 16.5 27.8 33.0 41.7 50.0

POWER SUPPLY

FLA — 15.9/18.3 23.6/27.1 31.3/36.3 38.0/43.8 47.1/54.2 —/— 9.2/10.6 13.6/15.6 18.0/20.9 21.9/25.3 33.3/38.5 — 7.2 10.6 13.8 16.8 —/— 15.9/18.3 31.3/36.3 47.1/54.2 63.0/72.5 76.0/87.5 —/— 13.6/15.6 18.0/20.9 33.3/38.5 43.9/50.5 — 7.2 13.8 16.8 27.7 — 23.6/27.1 31.3/36.3 47.1/54.2 63.0/72.5 76.0/87.5 —/— 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 —/— 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.0 — 16.7 19.8 33.4 39.7 50.2 — 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.3 — 19.8 33.4 39.7 50.2 60.1

MCA 30.4/ 30.4 50.3/ 53.3 59.9/ 64.3 69.5/ 75.8 77.9/ 85.2 89.3/ 98.2 23.3/ 23.3 34.8/ 36.5 40.3/ 42.8 45.8/ 49.4 50.7/ 54.9 64.9/ 71.4 11.2 20.2 24.4 28.4 32.2 40.0/ 40.0 59.9/ 62.9 79.2/ 85.4 98.9/107.8 118.8/130.7 135.0/149.4 27.3/ 27.3 44.3/ 46.8 49.8/ 53.4 68.9/ 75.4 82.2/ 90.4 14.0 23.0 31.3 35.0 48.7 51.1/ 51.1 80.6/ 85.0 90.2/ 96.5 110.0/118.9 129.9/141.7 146.1/160.5 33.7/ 33.7 50.7/ 53.2 61.1/ 65.4 75.4/ 81.9 88.6/ 96.9 102.7/113.5 16.8 25.8 34.1 37.8 51.5 55.2 37.6/ 37.6 54.6/ 57.1 65.0/ 69.3 79.3/ 85.8 92.5/100.8 106.6/117.4 17.4 26.4 34.6 38.4 52.0 55.8 43.0/ 43.0 70.1/ 74.3 84.6/ 91.1 107.5/117.6 126.3/139.3 153.4/170.5 21.4 42.3 46.1 63.1 71.0 84.1 61.6/ 61.6 88.8/ 92.9 103.3/109.8 144.9/157.9 172.0/189.1 192.1/181.9 30.9 55.6 72.6 80.5 93.6 91.0

40

MOCP 35/ 35** 60/ 60** 60/ 70 70/ 80 80/ 90 90/100 25/ 25** 35/ 40** 45/ 45** 50/ 50** 60/ 60** 70/ 80 15** 25** 25** 30** 35** 45/ 45** 60/ 70 80/ 90 100/110 125/150 150/150 30/ 30** 45/ 50** 50/ 60** 70/ 80 90/100 15** 25** 35** 40** 50** 60/ 60** 90/ 90 100/100 110/125 150/150 150/175 35/ 35** 60/ 60** 70/ 70 80/ 90 90/100 110/125 20** 30** 35** 40** 60** 60** 40/ 40** 60/ 60** 70/ 70 80/ 90 100/110 110/125 20** 30** 35** 40** 60** 60** 45/ 45** 80/ 80 90/100 110/125 150/150 175/175 25** 45** 50** 70 80 90 70/ 70 90/100 110/110 150/175 175/200 200/200 35** 60** 80 90 100 100

MINIMUM UNIT DISCONNECT SIZE FLA LRA 30/ 30 106/106 49/ 51 122/124 58/ 62 130/133 66/ 72 137/142 74/ 81 144/150†† 85/ 93 153/160†† 24/ 24 95/ 95 34/ 36 104/106 39/ 42 109/111 45/ 48 113/116 49/ 53 117/120 62/ 68 128/134 11 48 20 55 24 59 27 62 31 65 39/ 39 147/147 58/ 60 163/165 75/ 81 178/183†† 93/102 194/201†† 112/123 210/220†† 127/140 223/235†† 27/ 27 117/117 43/ 45 131/133 48/ 52 135/138 66/ 72 150/156 78/ 86 161/168†† 14 59 22 66 30 73 33 76 46 86 50/ 50 221/221 78/ 82 245/248†† 86/ 92 252/257†† 105/113 268/275†† 123/134 284/293†† 138/151 297/308†† 34/ 34 173/173 49/ 52 186/188 59/ 63 194/198 72/ 78 206/211 84/ 92 216/223†† 97/107 228/236†† 17 87 25 94 33 100 36 103 49 114 52 117 37/ 37 205/205 53/ 55 219/221 63/ 66 227/230 76/ 82 238/243†† 88/ 95 249/255†† 101/111 260/269†† 17 99 26 106 33 113 37 116 49 127 53 130 46/ 46 247/247 71/ 75 269/272 84/ 90 280/285†† 105/115 298/307†† 122/134 313/324†† 147/163 335/349†† 23 123 42 140 46 143 61 157 68 163 80 174 65/ 65 341/341 90/ 94 363/366†† 104/110 375/380†† 142/154 408/418†† 167/183 430/443†† 185/204 446/462†† 33 172 55 191 71 205 78 211 90 222†† 102 232††

Table 13 — Electrical Data — High-Efficiency Heat Pump Units — High-Static Motor Units (With Electrical Convenience Outlet) UNIT SIZE

NOMINAL VOLTAGE V-PH-Hz

208/230-3-60 3 Tons 460-3-60

208/230-3-60 4 Tons 460-3-60

208/230-3-60 5 Tons 460-3-60

208/230-3-60 6 Tons 460-3-60

208/230-3-60 71/2 Tons 460-3-60

208/230-3-60 10 Tons 460-3-60

FLA HACR LRA MCA MOCP NEC

— — — — — —

ELECTRIC HEAT* kW† —/— 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.0/16.0 — 6.0 8.8 11.5 14.0 —/— 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 — 6.0 11.5 14.0 23.0 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 —/— 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 — 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4 — 13.9 16.5 27.8 33.0 41.7 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.5/50.0 — 16.5 27.8 33.0 41.7 50.0

POWER SUPPLY

FLA —/— 9.2/10.6 13.6/15.6 18.0/20.9 21.9/25.3 33.3/38.5 — 7.2 10.6 13.8 16.8 —/— 13.6/15.6 18.0/20.9 33.3/38.5 43.9/50.5 — 7.2 13.8 16.8 27.7 —/— 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 —/— 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.0 — 16.7 19.8 33.4 39.7 50.2 — 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.3 — 19.8 33.4 39.7 50.2 60.1

MCA 24.2/ 24.2 35.7/ 37.4 41.2/ 43.7 46.7/ 50.3 51.6/ 55.8 65.8/ 72.3 11.6 20.6 24.8 28.8 33.6 28.2/ 28.2 45.2/ 47.7 50.7/ 54.3 69.8/ 76.3 83.1/ 91.3 14.4 23.4 31.7 35.4 49.1 35.4/ 35.4 52.4/ 54.9 62.8/ 67.1 77.1/ 83.6 90.3/ 98.6 104.4/115.2 17.6 26.6 34.9 38.6 52.3 56.0 39.3/ 39.3 56.3/ 58.8 66.7/ 71.0 81.0/ 87.5 94.2/102.5 108.3/119.1 18.2 27.2 35.4 39.2 52.8 56.6 46.1/ 46.1 73.2/ 77.4 87.7/ 94.2 110.6/120.7 129.4/142.4 156.5/173.6 22.8 43.7 47.5 64.5 72.4 85.5 66.0/ 66.0 93.2/ 97.3 107.7/114.2 149.3/162.3 176.4/193.5 196.5/186.3 33.5 58.2 75.2 83.1 96.2 93.6

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

MOCP 25/ 25 40/ 40 45/ 45 50/ 60 60/ 60 70/ 80 15** 25** 25** 30** 35** 30/ 30 50/ 50 60/ 60 70/ 80 90/100 15** 25** 35** 40** 50** 40/ 40 60/ 60 70/ 70 80/ 90 100/100 110/125 20** 30** 35** 40** 60** 60** 40/ 40 60/ 60 70/ 80 90/ 90 100/110 110/125 20** 30** 40** 40** 60** 60** 50/ 50** 80/ 80 90/100 125/125 150/150 175/175 25** 45** 50** 70 80 90 70/ 70 100/100 110/125 150/175 200/200 200/200 35** 60** 80 90 100 100

MINIMUM UNIT DISCONNECT SIZE FLA LRA 25/ 25 124/124 35/ 37 134/135 40/ 43 138/140 46/ 49 142/145 50/ 54 146/150 63/ 69 158/163 12 63 20 70 24 73 28 76 31 79 29/ 29 146/146 44/ 46 160/162 49/ 53 164/167 67/ 73 180/185 79/ 87 190/197†† 14 73 23 80 30 87 34 90 46 101 36/ 36 192/192 51/ 54 205/207 61/ 65 213/217 74/ 80 225/230†† 86/ 94 235/242†† 99/109 247/255†† 18 96 26 103 34 110 37 113 50 124 53 127 39/ 39 224/224 55/ 57 238/240 65/ 68 246/249 78/ 84 257/262†† 90/ 97 268/274†† 103/113 279/288†† 18 109 26 116 34 123 37 126 50 136 53 139 49/ 49 271/271 74/ 78 293/296 88/ 94 305/310†† 109/118 323/331†† 126/138 338/348†† 159/167 360/373†† 24 136 44 152 47 155 63 169 70 175 82 186†† 70/ 70 365/365 95/ 99 387/390†† 109/115 398/403†† 147/159 431/442†† 172/188 453/467†† 190/209 469/485†† 36 183 58 203 74 217 81 223†† 93 234†† 105 243††

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v Average Voltage =

452 + 464 + 455 3

1371 3 = 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. % Voltage Imbalance = 100 x 7 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. =

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. †Heaters are field installed only. **Fuse or HACR circuit breaker. ††Electrical disconnect cannot be used if electric heater is installed. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

41

Table 14 — Electric Heater Usage — High-Efficiency Heat Pump Units UNIT SIZE

VOLTAGE (60 Hz) 208/230/240 (single phase)

3 Tons

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (single phase)

4 Tons

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (single phase)

5 Tons

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (3 phase) 6 Tons 460/480 (3 phase)

208/230/240 (3 phase) 71/2 Tons 460/480 (3 phase)

208/230/240 (3 phase) 10 Tons 460/480 (3 phase)

ACCESSORY HEATER PART NUMBER CRHEATER---A00 001 002 003 004 002+002 001 002 003 004 005 006 007 008 009 001 003 002+002 003+003 004+004 002 003 005 004+004 006 008 009 008+008 002 003 002+002 003+003 004+004 002 004 005 004+004 004+005 006 008 009 008+008 008+009 002 004 005 004+004 004+005 006 008 009 008+008 008+009 117 110 111 112 112+117 116 113 114 115 114+116 117 110 112 112+117 112+110 113 114 115 114+116 115+113

ACCESSORY kW 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 9.8/11.6/13.0* 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 12.0/14.7/16.0 5.5/ 6.0 8.1/ 8.8 10.6/11.5 12.9/14.0 3.3/ 4.0/ 4.4 6.5/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 16.0/19.3/21.0* 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 12.0/14.7/16.0 15.8/19.3/21.0* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 4.9/ 5.8/ 6.5 6.6/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 15.8/19.3/21.0* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5* 7.8/ 9.6/10.4 12.0/14.7/16.0 18.6/22.8/24.8 24.0/29.4/32.0 31.8/39.0/42.4* 12.8/13.9 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7* 7.8/ 9.6/10.4 12.0/14.7/16.0 24.0/29.4/32.0 31.8/39.0/42.4* 37.5/46.2/50.0* 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7* 46.0/50.0*

SINGLE POINT BOX PACKAGE NO. CRSINGLE---A00 — — 004 004 005 — — — — 002 — — — — — 004 005 005 005 — — 002 003 — — — — 004 004 005 005 005 — 002 002 003 002 — — — — — — 002 002 003 003 — — — — — 007 007 009 009 013 006 006 008 008 — 012 012 015 017 017 011 014 014 016 016

*Two heater packages required to provide kW indicated. NOTES: 1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly. 2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kWnew = Heater kW rated x (unit power distribution voltage/rated heater voltage)2 As an example: For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kWnew = 16 kW (215/240)2 kWnew = 12.8 kW (rating at 215 v)

42

Table 15 — Electrical Data — Standard-Efficiency Heat Pump Units (Without Convenience Outlet) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

208/230-1-60

ALT

STD

208/230-3-60

ALT

3 Tons

HIGH-STATIC

STD

460-3-60

ALT

HIGH-STATIC

575-3-60

STD ALT HIGH-STATIC

ELECTRIC HEAT* Nominal kW** — 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 9.8/13.0 — 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 9.8/13.0 — 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.0/16.0 — 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.0/16.0 — 3.3/ 4.4 4.9/ 6.5 6.5/ 8.7 7.9/10.5 12.0/16.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — 6.0 8.8 11.5 14.0 — — —

FLA — 15.9/18.3 23.6/27.1 31.3/36.3 38.0/43.8 47.1/54.2 — 15.9/18.3 23.6/27.1 31.3/36.3 38.0/43.8 47.1/54.2 — 9.2/10.6 13.6/15.6 18.0/20.9 21.9/25.3 33.3/38.5 — 9.2/10.6 13.6/15.6 18.0/20.9 21.9/25.3 33.3/38.5 — 9.2/10.6 13.6/15.6 18.0/20.9 21.9/25.3 33.3/38.5 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — — —

LEGEND FLA HACR IFM LRA MCA MOCP NEC

— — — — — — —

DISCONNECT SIZE†

POWER SUPPLY

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

MCA

MOCP

FLA

25.5/ 25.5 30/ 30†† 45.4/ 48.4 50/ 50†† 55.0/ 59.4 60/ 60†† 64.6/ 70.9 70/ 80 73.0/ 80.3 80/ 90 84.4/ 93.3 90/100 26.9/ 26.9 30/ 30†† 46.8/ 49.8 50/ 50†† 56.4/ 60.8 60/ 70 66.0/ 72.3 70/ 80 74.4/ 81.7 80/ 90 85.8/ 94.7 90/100 17.8/ 17.8 20/ 20†† 29.3/ 31.0 30/ 35†† 34.8/ 37.3 35/ 40†† 40.3/ 43.9 45/ 45†† 45.1/ 49.4 50/ 50†† 59.4/ 65.9 60/ 70 19.2/ 19.2 20/ 20†† 30.7/ 32.4 35/ 35†† 36.2/ 38.7 40/ 40†† 41.7/ 45.3 45/ 50†† 46.5/ 50.8 50/ 60†† 60.8/ 67.3 70/ 70 20.1/ 20.1 25/ 25†† 31.6/ 33.3 35/ 35†† 37.1/ 39.6 40/ 40†† 42.6/ 46.2 45/ 50†† 47.4/ 51.7 50/ 60†† 61.7/ 68.2 70/ 70 8.1 15†† 17.1 20†† 21.4 25†† 25.4 30†† 29.1 30†† 8.9 15†† 17.9 20†† 22.2 25†† 26.2 30†† 29.9 30†† 9.4 15†† 18.4 20†† 22.7 25†† 26.7 30†† 30.4 35†† 6.4 15†† 7.1 15†† 7.5 15†† Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

25/ 43/ 52/ 61/ 68/ 79/ 26/ 45/ 53/ 62/ 70/ 80/ 17/ 28/ 33/ 38/ 43/ 56/ 19/ 30/ 35/ 40/ 44/ 57/ 20/ 31/ 36/ 41/ 45/ 58/

25 46 56 66 75 87 26 47 57 68 77 89 17 30 35 42 47 62 19 31 37 43 48 63 20 32 38 44 49 64 8 16 20 24 27 9 17 21 25 28 9 18 22 25 29 6 7 7

Average Voltage =

*Heaters are field installed only. †Used to determine minimum disconnect size per NEC. **Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. ††Fuse or HACR circuit breaker. ***Optional disconnect switch is unavailable. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage

LRA 107/107 123/125 131/184 138/143 145/151 154/161*** 111/111 127/130 135/138 143/148 149/155 158/166*** 86/ 86 95/ 97 100/102 104/107 108/111 119/124 90/ 90 100/101 104/106 108/111 112/116 124/129 120/120 129/130 133/135 138/141 142/145 153/158 45 52 55 59 62 48 55 59 62 65 62 70 73 76 79 35 37 49

452 + 464 + 455 3

=

1371 3

=

457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. % Voltage Imbalance

= 100 x

7

457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

43

Table 15 — Electrical Data — Standard-Efficiency Heat Pump Units (Without Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

208/230-1-60

ALT

STD

208/230-3-60

ALT

4 Tons HIGH-STATIC

STD

460-3-60

ALT

HIGH-STATIC

575-3-60

STD ALT HIGH-STATIC

STD

208/230-1-60

ALT

STD

208/230-3-60

ALT

5 Tons HIGH-STATIC

STD

460-3-60

ALT

HIGH-STATIC

575-3-60

STD ALT HIGH-STATIC

ELECTRIC HEAT* Nominal kW** — 3.3/ 4.4 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 — 3.3/ 4.4 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 — 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 — 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 — 4.9/ 6.5 6.5/ 8.7 12.0/16.0 15.8/21.0 — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — 6.0 11.5 14.0 23.0 — — — — 4.9/ 6.5 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 — 4.9/ 6.5 6.5/ 8.7 9.8/13.0 13.1/17.4 15.8/21.0 — 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — — —

DISCONNECT SIZE†

POWER SUPPLY FLA

MCA

MOCP

FLA

LRA

— 15.9/18.3 31.3/36.3 47.1/54.2 63.0/72.5 76.0/87.5 — 15.9/18.3 31.3/36.3 47.1/54.2 63.0/72.5 76.0/87.5 — 13.6/15.6 18.0/20.9 33.3/38.5 43.9/50.5 — 13.6/15.6 18.0/20.9 33.3/38.5 43.9/50.5 — 13.6/15.6 18.0/20.9 33.3/38.5 43.9/50.5 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — — — — 23.6/27.1 31.3/36.3 47.1/54.2 63.0/72.5 76.0/87.5 — 23.6/27.1 31.3/36.3 47.1/54.2 63.0/72.5 76.0/87.5 — 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — — —

41.4/ 41.4 61.3/ 64.3 80.5/ 86.8 100.3/109.1 120.1/132.0 136.4/150.8 42.8/ 42.8 62.7/ 65.7 81.9/ 88.2 107.7/110.5 121.5/133.4 137.8/152.2 26.0/ 26.0 43.0/ 45.5 48.5/ 52.1 67.6/ 74.1 80.9/ 89.1 27.4/ 27.4 44.4/ 46.9 49.9/ 53.5 69.0/ 75.5 82.3/ 90.5 28.3/ 28.3 45.3/ 47.8 50.8/ 54.4 69.9/ 76.4 83.2/ 91.4 13.1 22.1 30.4 34.1 47.7 13.4 22.4 30.7 34.4 48.0 13.9 22.9 31.2 34.9 48.5 10.5 10.7 11.1 40.8/ 40.8 70.3/ 74.7 79.9/ 86.2 99.7/108.5 119.5/131.4 135.8/150.2 48.5/ 48.5 78.0/ 82.4 87.6/ 93.9 107.4/116.2 127.2/139.1 143.5/157.9 26.7/ 26.7 43.7/ 46.2 54.0/ 58.3 68.3/ 74.8 81.5/ 89.8 95.7/106.4 26.6/ 26.6 43.6/ 46.1 53.9/ 58.2 68.2/ 74.7 81.4/ 89.7 95.6/106.3 28.3/ 28.3 45.3/ 47.8 55.6/ 59.9 69.9/ 76.4 83.1/ 91.4 97.3/108.0 13.6 22.6 30.9 34.6 48.3 52.0 13.0 22.0 30.3 34.0 47.7 51.4 13.8 22.8 31.1 34.8 48.5 52.2 11.0 10.5 11.1

45/ 45†† 70/ 70 90/ 90 110/110 125/150 150/175 45/ 45†† 70/ 70 90/ 90 110/125 125/150 150/175 30/ 30†† 45/ 50†† 50/ 60†† 70/ 80 90/ 90 30/ 30†† 45/ 50†† 50/ 60†† 70/ 80 90/100 30/ 30†† 50/ 50†† 60/ 60†† 70/ 80 90/100 15†† 25†† 35†† 35†† 50†† 15†† 25†† 35†† 35†† 50†† 15†† 25†† 35†† 35†† 50†† 15†† 15†† 15†† 45/ 45†† 80/ 80 80/ 90 100/110 125/150 150/175 50/ 50†† 80/ 90 90/100 110/125 150/150 150/175 30/ 30†† 45/ 50†† 60/ 60†† 70/ 80 90/ 90 100/110 30/ 30†† 45/ 50†† 60/ 60 70/ 80 90/ 90 100/110 30/ 30†† 50/ 50†† 60/ 60†† 70/ 80 90/100 100/110 15†† 25†† 35†† 35†† 50†† 60†† 15†† 25†† 35†† 35†† 50†† 60†† 15†† 25†† 35†† 35†† 50†† 60†† 15†† 15†† 15††

39/ 39 58/ 60 75/ 81 93/102 112/123 127/140 41/ 41 59/ 62 77/ 83 95/103 113/124 128/141 25/ 25 41/ 43 46/ 49 63/ 69 76/ 83 27/ 27 42/ 45 47/ 51 65/ 71 77/ 85 28/ 28 43/ 46 48/ 52 66/ 72 78/ 86 13 21 29 32 45 13 21 29 32 45 14 22 29 33 45 10 10 11 39/ 39 66/ 70 75/ 81 93/102 112/123 127/140 48/ 48 75/ 79 84/ 90 102/110 121/131 135/149 26/ 26 42/ 44 51/ 55 65/ 70 77/ 84 90/100 26/ 26 42/ 44 51/ 55 64/ 70 77/ 84 90/ 99 28/ 28 44/ 46 53/ 57 66/ 72 79/ 86 92/101 13 22 29 33 45 49 13 21 29 32 45 48 14 22 30 33 46 49 11 10 11

143/143 159/161 174/179 190/197 206/215 219/230 147/147 163/166 179/184 194/202 210/220 223/235 102/102 115/117 120/123 135/140 146/152 106/106 120/122 124/127 140/145 150/157 136/136 149/151 154/157 169/174 180/186*** 56 63 70 73 84 58 65 72 75 86 72 80 86 89 100 42 43 55 184/184 208/211 215/220*** 231/238*** 247/257*** 260/272*** 222/222 246/249 253/258*** 269/276*** 285/294*** 298/309*** 138/138 152/154 160/163 171/177 182/189*** 193/202*** 169/169 182/184 191/194 202/207 213/219*** 224/233*** 188/188 201/203 210/213 221/226 232/238*** 243/252*** 67 75 81 84 95 98 82 89 96 99 110 113 92 99 105 108 119 122 56 67 75

44

Table 15 — Electrical Data — Standard-Efficiency Heat Pump Units (Without Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

208/230-3-60

HIGH-STATIC

6 Tons STD

460-3-60

HIGH-STATIC

575-3-60

FLA HACR IFM LRA MCA MOCP NEC

— — — — — — —

STD HIGH-STATIC

ELECTRIC HEAT* Nominal kW** — 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 4.9/ 6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 — 6.0 11.5 14.0 23.0 25.5 — 6.0 11.5 14.0 23.0 25.5 — —

DISCONNECT SIZE†

POWER SUPPLY

FLA

MCA

MOCP

FLA

LRA

— 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 13.6/15.6 21.9/25.3 33.3/38.5 43.9/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — —

35.6/ 35.6 52.6/ 55.1 63.0/ 67.2 77.2/ 83.7 90.5/ 98.7 104.6/115.3 37.3/ 37.3 54.3/ 56.8 64.7/ 68.9 78.9/ 85.4 92.2/100.4 106.3/117.0 17.6 26.6 34.8 38.6 52.2 55.9 18.4 27.4 35.6 39.4 53.0 56.7 14.0 14.7

40/ 40†† 60/ 60†† 70/ 70 80/ 90 100/100 110/125 40/ 40†† 60/ 60†† 70/ 70 80/ 90 100/110 110/125 20†† 30†† 35†† 40†† 60†† 60†† 20†† 30†† 40†† 40†† 60†† 60†† 15†† 15††

34/ 34 50/ 52 60/ 63 73/ 79 85/ 92 98/108 36/ 36 52/ 54 62/ 65 75/ 81 87/ 94 100/110 17 25 33 36 49 52 18 26 34 37 50 53 14 14

190/190 204/206 212/215 223/229 234/241*** 245/254*** 209/209 223/225 231/234 242/248*** 253/260*** 264/273*** 95 102 109 112 123 126 105 112 118 121 132 135 76 84

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

Average Voltage =

=

*Heaters are field installed only. †Used to determine minimum disconnect size per NEC. **Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. ††Fuse or HACR circuit breaker. ***Optional disconnect switch is unavailable.

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage

Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

45

Table 15 — Electrical Data — Standard-Efficiency Heat Pump Units (Without Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

208/230-3-60

HIGH-STATIC

71/2 Tons

STD

460-3-60

HIGH-STATIC

STD 575-3-60

HIGH-STATIC

STD

208/230-3-60

HIGH-STATIC

81/2 Tons

STD

460-3-60

HIGH-STATIC

STD 575-3-60

HIGH-STATIC

ELECTRIC HEAT* Nominal kW** — 7.8/10.5 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4 — 7.8/10.5 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4 — 14.0 16.5 27.8 33.0 41.7 — 14.0 16.5 27.8 33.0 41.7 — 17.0 34.0 — 17.0 34.0 — 7.8/10.5 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4 — 7.8/10.5 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4 — 14.0 16.5 27.8 33.0 41.7 — 14.0 16.5 27.8 33.0 41.7 — 17.0 34.0 — 17.0 34.0

DISCONNECT SIZE†

POWER SUPPLY

FLA

MCA

MOCP

FLA

LRA

— 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.0 — 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.0 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 17.1 34.1 — 17.1 34.1 — 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.0 — 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.0 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 17.1 34.1 — 17.1 34.1

38.8/ 38.8 65.9/ 70.0 80.4/ 86.9 103.3/113.4 122.0/135.0 149.1/166.3 43.6/ 43.6 70.7/ 74.8 85.2/ 91.7 108.1/118.2 126.8/139.8 153.9/171.1 19.1 40.0 43.8 60.8 68.7 81.8 21.3 42.2 46.0 63.0 70.9 84.0 15.4 36.7 58.0 17.1 38.5 59.7 44.6/ 44.6 71.7/ 75.9 86.2/ 92.7 109.1/119.2 127.9/140.9 155.0/172.1 49.4/ 49.4 76.5/ 80.7 91.0/ 97.5 113.9/124.0 132.7/145.7 159.8/176.9 22.7 43.6 47.4 64.4 72.3 85.4 24.9 45.8 49.6 66.6 74.5 87.6 17.6 39.0 60.2 19.4 40.7 62.0

40/ 40†† 70/ 70 90/ 90 110/125 125/150 150/175 45/ 45†† 80/ 80 90/100 110/125 150/150 175/175 20†† 40†† 45†† 70 70 90 25†† 45†† 50†† 70 80 90 20†† 40†† 60†† 20†† 40†† 60†† 45/ 45†† 80/ 80 90/100 110/125 150/150 175/175 50/ 50†† 80/ 90 100/100 125/125 150/150 175/200 25†† 45†† 50†† 70 80 90 25†† 50†† 50†† 70 80 90 20†† 40†† 70†† 20†† 45†† 70

41/ 41 66/ 69 79/ 85 100/109 117/129 142/158 46/ 46 71/ 75 85/ 91 106/115 123/135 148/164 20 39 43 58 66 78 23 42 45 61 68 80 16 36 55 18 38 57 47/ 47 72/ 75 85/ 91 106/115 123/135 148/164 52/ 52 77/ 81 91/ 96 112/121 129/141 154/170 24 43 46 62 69 81 26 45 49 65 72 84 18 38 58 20 40 60

229/229 251/254 262/268*** 281/289*** 296/306*** 317/331*** 273/273 294/298 306/311*** 324/332*** 339/350*** 361/375*** 108 124 128 141 147 158 130 146 149 163 169 180*** 97 114 131 114 132 149 321/321 343/346 354/360*** 373/381*** 388/398*** 409/428*** 365/365 386/390*** 398/403*** 416/424*** 431/442*** 453/467*** 162 178 182 195 201 212*** 184 200 203 217 223 234*** 135 152 169 152 170 187

46

Table 15 — Electrical Data — Standard-Efficiency Heat Pump Units (Without Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

208/230-3-60

ALT

HIGH-STATIC

STD

10 Tons

460-3-60

ALT

HIGH-STATIC

STD

575-3-60

ALT

HIGH-STATIC

FLA HACR IFM LRA MCA MOCP NEC

— — — — — — —

ELECTRIC HEAT* Nominal kW** — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 16.5 27.8 33.0 41.7 50.0 — 16.5 27.8 33.0 41.7 50.0 — 16.5 27.8 33.0 41.7 50.0 — 17.0 34.0 51.0 — 17.0 34.0 51.0 — 17.0 34.0 51.0

DISCONNECT SIZE†

POWER SUPPLY

FLA

MCA

— 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.3 — 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.3 — 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.3 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 17.1 34.1 51.2 — 17.1 34.1 51.2 — 17.1 34.1 51.2

47.3/ 47.3 74.4/ 78.6 88.9/ 95.4 130.6/143.6 157.7/174.8 177.8/167.6 49.0/ 49.0 76.1/ 80.8 90.6/ 97.1 132.3/145.3 159.4/176.5 179.5/169.3 56.5/ 56.5 83.6/ 87.8 98.1/104.6 139.8/152.8 166.9/184.0 187.0/176.8 23.4 48.1 65.1 73.0 86.1 83.5 24.2 48.9 65.9 73.8 86.9 84.3 28.2 52.9 69.9 77.8 90.9 88.3 18.7 40.1 61.4 69.9 19.4 40.7 62.0 70.6 22.6 43.9 65.2 73.8

MOCP

FLA

50/ 50†† 80/ 80 90/100 150/150 175/175 200/175 50/ 50†† 80/ 90 100/100 150/150 175/200 200/200 60/ 60†† 90/ 90 100/110 150/175 175/200 200/200 25†† 50†† 70 80 90 90 25†† 50†† 70 80 90 90 30†† 60†† 70 80 100 100 20†† 45†† 70 70 20†† 45†† 70 80 25†† 45†† 70 80

49/ 49 74/ 78 88/ 94 126/138 151/167 170/188 51/ 51 76/ 80 90/ 96 128/140 153/169 171/190 60/ 60 85/ 89 98/104 137/149 162/177 180/198 24 47 63 70 82 93 25 48 64 71 83 94 30 53 68 76 88 99 20 39 59 78 20 40 60 79 24 44 63 83

LRA 295/295 317/320 328/334*** 362/372*** 383/397*** 399/415*** 314/314 336/389*** 347/353*** 381/391*** 402/416*** 418/434*** 362/362 384/387*** 395/401*** 429/439*** 450/464*** 466/482*** 143 163 176 183 193*** 203*** 182 202 216 222 233*** 243*** 176 196 210 216 227*** 237*** 118 135 152 169 149 166 183 201*** 145 162 179 196***

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

Average Voltage =

=

*Heaters are field installed only. †Used to determine minimum disconnect size per NEC. **Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. ††Fuse or HACR circuit breaker. ***Optional disconnect switch is unavailable.

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage

Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

47

Table 16 — Electrical Data — Standard-Efficiency Heat Pump Units (With Convenience Outlet) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

208/230-1-60

ALT

STD

208/230-3-60

ALT

3 Tons

HIGH-STATIC

STD

460-3-60

ALT

HIGH-STATIC

575-3-60

STD ALT HIGH-STATIC

STD

208/230-1-60

ALT

4 Tons STD

208/230-3-60

ALT

HIGH-STATIC

ELECTRIC HEAT* Nominal FLA kW** — — 3.3/ 4.4 15.9/18.3 4.9/ 6.5 23.6/27.1 6.5/ 8.7 31.3/36.3 7.9/10.5 38.0/43.8 9.8/13.0 47.1/54.2 — — 3.3/ 4.4 15.9/18.3 4.9/ 6.5 23.6/27.1 6.5/ 8.7 31.3/36.3 7.9/10.5 38.0/43.8 9.8/13.0 47.1/54.2 — — 3.3/ 4.4 9.2/10.6 4.9/ 6.5 13.6/15.6 8.5/ 8.7 18.0/20.9 7.9/10.5 21.9/25.3 12.0/16.0 33.3/38.5 — — 3.3/ 4.4 9.2/10.6 4.9/ 6.5 13.6/15.6 6.5/ 8.7 18.0/20.9 7.9/10.5 21.9/25.3 12.0/16.0 33.3/38.5 — — 3.3/ 4.4 9.2/10.6 4.9/ 6.5 13.6/15.6 6.5/ 8.7 18.0/20.9 7.9/10.5 21.9/25.3 12.0/16.0 33.3/38.5 — — 6.0 7.2 8.8 10.6 11.5 13.8 14.0 16.8 — — 6.0 7.2 8.8 10.6 11.5 13.8 14.0 16.8 — — 6.0 7.2 8.8 10.6 11.5 13.8 14.0 16.8 — — — — — — — — 3.3/ 4.4 15.9/18.3 6.5/ 8.7 31.3/36.3 9.8/13.0 47.1/54.2 13.1/17.4 63.0/72.5 15.8/21.0 76.0/87.5 — — 3.3/ 4.4 15.9/18.3 6.5/ 8.7 31.3/36.3 9.8/13.0 47.1/54.2 13.1/17.4 63.0/72.5 15.8/21.0 76.0/87.5 — — 4.9/ 6.5 13.6/15.6 6.5/ 8.7 18.0/20.9 12.0/16.0 33.3/38.5 15.8/21.0 43.9/50.5 — — 4.9/ 6.5 13.6/15.6 6.5/ 8.7 18.0/20.9 12.0/16.0 33.3/38.5 15.8/21.0 43.9/50.5 — — 4.9/ 6.5 13.6/15.6 6.5/ 8.7 18.0/20.9 12.0/16.0 33.3/38.5 15.8/21.0 43.9/50.5

48

DISCONNECT SIZE†

POWER SUPPLY MCA 30.3/ 30.3 50.2/ 53.2 59.8/ 64.2 69.4/ 75.7 77.8/ 85.1 89.2/ 98.1 31.7/ 31.7 51.6/ 54.6 61.2/ 65.6 70.8/ 77.1 79.2/ 86.5 90.6/ 99.5 22.6/ 22.6 34.1/ 35.8 39.6/ 42.1 45.1/ 48.7 49.9/ 54.2 64.2/ 70.7 24.0/ 24.0 35.5/ 37.2 41.0/ 43.5 46.5/ 50.1 51.3/ 55.6 65.6/ 72.1 24.9/ 24.9 36.4/ 38.1 41.9/ 44.4 47.4/ 51.0 52.2/ 56.5 66.5/ 73.0 10.3 19.3 23.5 27.5 31.3 11.1 20.1 24.3 28.3 32.1 11.6 20.6 24.8 28.8 32.6 8.2 8.8 9.2 46.2/ 46.2 66.1/ 69.1 85.3/ 91.6 105.1/113.9 124.1/136.8 141.2/155.6 47.6/ 47.6 67.5/ 70.5 86.7/ 93.0 106.5/115.3 126.3/138.2 142.6/157.0 30.8/ 30.8 47.8/ 50.3 53.3/ 56.9 72.4/ 78.9 85.7/ 93.9 32.2/ 32.2 49.2/ 51.7 54.7/ 58.3 73.8/ 80.3 87.1/ 95.3 33.1/ 33.1 50.1/ 52.6 55.6/ 59.2 74.7/ 81.2 88.0/ 96.2

MOCP 35/ 35†† 60/ 60†† 60/ 70 70/ 80 80/ 90 90/100 35/ 35†† 60/ 60†† 70/ 70 80/ 80 80/ 90 100/110 25/ 25†† 35/ 40†† 40/ 45†† 50/ 50†† 50/ 60†† 70/ 80†† 30/ 30†† 40/ 40†† 45/ 45†† 50/ 60†† 60/ 60†† 70/ 80 25/ 25†† 40/ 40†† 45/ 45†† 50/ 60†† 60/ 60†† 70/ 80 15†† 20†† 25†† 30†† 35†† 15†† 25†† 25†† 30†† 35†† 15†† 25†† 25†† 30†† 35†† 15†† 15†† 15†† 50/ 50†† 70/ 70 90/100 110/125 125/150 150/175 50/ 50†† 70/ 80 90/100 110/125 150/150 150/175 35/ 35†† 50/ 60†† 60/ 60†† 80/ 80 90/100 35/ 35†† 50/ 60†† 60/ 60†† 80/ 90 90/100 35/ 35†† 60/ 60†† 60/ 60†† 80/ 90 90/100

FLA 30/ 30 48/ 51 57/ 61 66/ 72 74/ 81 84/ 92 32/ 32 50/ 53 59/ 63 68/ 73 75/ 82 86/ 94 23/ 23 34/ 35 39/ 41 44/ 47 48/ 52 61/ 67 25/ 25 35/ 37 40/ 43 45/ 49 50/ 54 63/ 69 26/ 26 36/ 38 41/ 44 46/ 50 51/ 55 64/ 70 10 19 23 26 30 11 20 24 27 31 12 20 24 28 31 8 9 9 45/ 45 63/ 66 81/ 86 99/107 117/128 132/145 46/ 46 65/ 67 82/ 88 101/109 119/130 134/147 31/ 31 46/ 49 51/ 55 69/ 75 81/ 89 32/ 32 48/ 50 53/ 56 71/ 76 83/ 90 33/ 33 49/ 51 54/ 57 72/ 78 84/ 91

LRA 112/112 128/130 135/139 143/148 150/156*** 159/166*** 116/116 132/134 140/143 147/152 154/160*** 163/170*** 91/ 91 100/101 104/106 109/112 113/116 124/129 95/ 95 104/106 109/111 113/116 117/120 128/134 125/125 134/135 138/140 143/145 146/150 158/163 47 54 58 61 64 50 57 61 64 67 65 72 75 78 81 37 39 51 148/148 163/166 179/184 195/202 211/220 224/235 152/152 168/170 183/188 199/206 215/225 228/240 107/107 120/122 125/127 140/145 150/157 111/111 125/127 129/132 144/150 155/162 141/141 154/156 159/161 174/179 184/191***

Table 16 — Electrical Data — Standard-Efficiency Heat Pump Units (With Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

460-3-60

ALT

4 Tons (cont)

HIGH-STATIC

575-3-60

STD ALT HIGH-STATIC

STD

208/230-1-60

ALT

5 Tons

STD

208/230-3-60

ALT

HIGH-STATIC

FLA HACR IFM LRA MCA MOCP NEC

— — — — — — —

ELECTRIC HEAT* Nominal FLA kW** — — 6.0 7.2 11.5 13.8 14.0 16.8 23.0 27.7 — — 6.0 7.2 11.5 13.8 14.0 16.8 23.0 27.7 — — 6.0 7.2 11.5 13.8 14.0 16.8 23.0 27.7 — — — — — — — — 4.9/ 6.5 23.6/27.1 6.5/ 8.7 31.3/36.3 9.8/13.0 47.1/54.2 13.1/17.4 63.0/72.5 15.8/21.0 76.0/87.5 — — 4.9/ 6.5 23.6/27.1 6.5/ 8.7 31.3/36.3 9.8/13.0 47.1/54.2 13.1/17.4 63.0/72.5 15.8/21.0 76.0/87.5 — — 4.9/ 6.5 13.6/15.6 7.9/10.5 21.9/25.3 12.0/16.0 33.3/38.5 15.8/21.0 43.9/50.5 19.9/26.5 55.2/63.8 — — 4.9/ 6.5 13.6/15.6 7.9/10.5 21.9/25.3 12.0/16.0 33.3/38.5 15.8/21.0 43.9/50.5 19.9/26.5 55.2/63.8 — — 4.9/ 6.5 13.6/15.6 7.9/10.5 21.9/25.3 12.0/16.0 33.3/38.5 15.8/21.0 43.9/50.5 19.9/26.5 55.2/63.8

DISCONNECT SIZE†

POWER SUPPLY MCA

MOCP

FLA

15.3 24.3 32.5 36.3 49.9 15.6 24.6 32.8 36.6 50.2 16.1 25.1 33.3 37.1 50.7 12.2 12.4 12.8 45.6/ 45.6 75.1/ 79.5 84.7/ 91.0 104.3/113.3 124.3/136.2 140.6/155.0 48.5/ 48.5 78.0/ 82.4 87.6/ 93.9 107.4/116.2 127.2/139.1 143.5/157.9 31.5/ 31.5 48.5/ 51.0 58.8/ 63.1 73.1/ 79.6 86.3/ 94.6 100.5/111.2 31.4/ 31.4 48.4/ 50.9 58.7/ 63.0 73.0/ 79.5 86.2/ 94.5 100.4/111.1 33.1/ 33.1 50.1/ 52.6 60.4/ 64.7 74.7/ 81.2 87.9/ 96.2 102.1/112.8

20†† 25†† 35†† 40†† 50†† 20†† 25†† 35†† 40†† 60†† 20†† 30†† 35†† 40†† 60†† 15†† 15†† 15†† 50/ 50†† 80/ 80 90/100 110/125 125/150 150/175 50/ 50†† 80/ 90 90/100 110/125 150/150 150/175 35/ 40†† 50/ 60†† 60/ 70 80/ 90 90/100 110/125 35/ 35†† 50/ 60†† 60/ 70 80/ 80 90/100 110/125 35/ 35†† 60/ 60†† 70/ 70 80/ 80 90/100 110/125

15 23 31 34 47 15 24 31 35 47 16 24 32 35 48 12 12 13 45/ 45 72/ 76 81/ 86 99/107 117/128 132/145 48/ 48 75/ 79 84/ 90 102/110 121/131 135/149 32/ 32 47/ 50 57/ 61 70/ 76 82/ 90 95/105 32/ 32 47/ 50 57/ 61 70/ 76 82/ 90 95/105 34/ 34 49/ 52 59/ 63 72/ 78 84/ 92 97/107

LRA 58 66 72 75 86 60 67 74 77 88 75 82 88 91 102 44 45 57 189/189 213/216 220/225*** 236/243*** 252/261*** 265/276*** 222/222 246/249 253/258*** 269/276*** 285/294*** 298/309*** 143/143 157/159 165/168 176/181 187/193*** 198/207*** 174/174 187/189 195/199 207/212 217/224*** 229/237*** 193/193 206/208 214/218 226/231 236/243*** 248/256***

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

Average Voltage =

=

*Heaters are field installed only. †Used to determine minimum disconnect size per NEC. **Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. ††Fuse or HACR circuit breaker. ***Optional disconnect switch is unavailable.

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage

Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

49

Table 16 — Electrical Data — Standard-Efficiency Heat Pump Units (With Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

460-3-60

ALT

5 Tons (cont)

HIGH-STATIC

575-3-60

STD ALT HIGH-STATIC

STD

208/230-3-60

HIGH-STATIC

6 Tons STD

460-3-60

HIGH-STATIC

575-3-60

STD HIGH-STATIC

ELECTRIC HEAT* Nominal FLA kW** — — 6.0 7.2 11.5 13.8 14.0 16.8 23.0 27.7 25.5 30.7 — — 6.0 7.2 11.5 13.8 14.0 16.8 23.0 27.7 25.5 30.7 — — 6.0 7.2 11.5 13.8 14.0 16.8 23.0 27.7 25.5 30.7 — — — — — — — — 4.9/ 6.5 13.6/15.6 7.9/10.5 21.9/25.3 12.0/16.0 33.3/38.5 15.8/21.0 43.9/50.5 19.9/26.5 55.2/63.8 — — 4.9/ 6.5 13.6/15.6 7.9/10.5 21.9/25.3 12.0/16.0 33.3/38.5 15.8/21.0 43.9/50.5 19.9/26.5 55.2/63.8 — — 6.0 7.2 11.5 13.8 14.0 16.8 23.0 27.7 25.5 30.7 — — 6.0 7.2 11.5 13.8 14.0 16.8 23.0 27.7 25.5 30.7 — — — —

50

POWER SUPPLY MCA 15.8 24.8 33.1 36.8 50.4 54.2 15.2 24.2 32.5 36.2 49.8 53.6 16.0 25.0 33.3 37.0 50.6 54.4 12.7 12.2 12.9 40.4/ 40.4 57.4/ 59.9 67.8/ 72.0 82.0/ 88.5 95.3/103.5 109.4/120.1 42.1/ 42.1 59.1/ 61.6 69.5/ 73.7 83.7/ 90.2 97.0/105.2 111.1/121.8 19.7 28.7 37.0 40.7 54.4 58.1 20.5 29.5 37.8 41.5 55.2 58.9 15.8 16.4

MOCP 20†† 25†† 35†† 40†† 60†† 60†† 20†† 25†† 35†† 40†† 60†† 60†† 20†† 25†† 35†† 40†† 60†† 60†† 15†† 15†† 15†† 45/ 45†† 60/ 60†† 70/ 80 90/ 90 100/110 110/125 45/ 45†† 60/ 70 70/ 80 90/100 100/110 125/125 20†† 30†† 40†† 45†† 60†† 60†† 25†† 30†† 40†† 45†† 60†† 60†† 20†† 20††

DISCONNECT SIZE† FLA

LRA

16 24 32 35 48 51 15 24 31 35 47 51 16 24 32 36 48 51 13 12 13 40/ 40 56/ 58 65/ 69 78/ 84 90/ 98 103/113 42/ 42 58/ 60 67/ 71 80/ 86 92/100 105/115 19 28 35 39 51 55 20 29 36 40 52 56 16 16

70 77 83 86 97 100 84 91 98 101 112 115 94 101 107 110 121 124 57 69 77 195/195 208/211 217/220 228/233*** 239/245*** 250/259*** 214/214 227/229 236/239 247/252*** 258/264*** 269/278*** 97 104 111 114 125 128 107 114 121 124 134 137 78 85

Table 16 — Electrical Data — Standard-Efficiency Heat Pump Units (With Convenience Outlet) (cont) UNIT SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

208/230-3-60

HIGH-STATIC

71/2 Tons

STD

460-3-60

HIGH-STATIC

STD 575-3-60 HIGH-STATIC

FLA HACR IFM LRA MCA MOCP NEC

— — — — — — —

ELECTRIC HEAT* Nominal FLA kW** — — 7.8/10.5 21.7/ 25.0 12.0/16.0 33.3/ 38.5 18.6/24.8 51.6/ 59.7 24.0/32.0 66.6/ 77.0 31.8/42.4 88.3/102.0 — — 7.8/10.5 21.7/ 25.0 12.0/16.0 33.3/ 38.5 18.6/24.8 51.6/ 59.7 24.0/32.0 66.6/ 77.0 31.8/42.4 88.3/102.0 — — 14.0 16.7 16.5 19.8 27.8 33.4 33.0 39.7 41.7 50.2 — — 14.0 16.7 16.5 19.8 27.8 33.4 33.0 39.7 41.7 50.2 — — 17.0 17.1 34.0 34.1 — — 17.0 17.1 34.0 34.1

DISCONNECT SIZE†

POWER SUPPLY MCA

MOCP

FLA

LRA

43.6/ 43.6 70.7/ 74.8 85.2/ 91.7 108.1/118.2 126.8/139.8 153.9/171.1 48.4/ 48.4 75.5/ 79.6 90.0/ 96.5 112.9/123.0 131.6/144.6 158.7/175.9 21.3 42.1 46.0 63.0 70.9 84.0 23.5 44.3 48.2 65.2 73.1 86.2 17.1 38.5 59.7 18.9 40.2 61.5

45/ 45†† 80/ 80 90/100 110/125 150/150 175/175 50/ 50†† 80/ 80 90/100 125/125 150/150 175/200 25†† 45†† 50†† 70 80 90 25†† 45†† 50†† 70 80 90 20†† 40†† 60†† 20†† 45†† 70

46/ 46 71/ 75 85/ 91 106/115 123/135 148/164 52/ 52 77/ 81 90/ 96 111/120 128/140 153/169 23 42 45 61 68 80 25 44 48 63 71 83 18 38 57 20 40 59

234/234 256/259 267/272*** 285/294*** 300/311*** 322/336*** 277/277 299/302*** 311/316*** 329/337*** 344/354*** 366/379*** 110 127 130 143 150 160*** 132 148 151 165 171 182*** 99 116 133 116 133 150

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code

Average Voltage =

=

*Heaters are field installed only. †Used to determine minimum disconnect size per NEC. **Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. ††Fuse or HACR circuit breaker. ***Optional disconnect switch is unavailable.

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage

Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

51

Table 16 — Electrical Data — Standard-Efficiency Heat Pump Units (With Convenience Outlet) (cont) UNIT

SIZE

NOMINAL V-PH-Hz

IFM TYPE

STD

208/230-3-60

HIGH-STATIC

81/2 Tons

STD

460-3-60

HIGH-STATIC

STD 575-3-60 HIGH-STATIC

STD

208/230-3-60

ALT

HIGH-STATIC

STD

10 Tons

460-3-60

ALT

HIGH-STATIC

STD

575-3-60

ALT

HIGH-STATIC

ELECTRIC HEAT* Nominal kW** — 7.8/10.5 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4 — 7.8/10.5 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4 — 14.0 16.5 27.8 33.0 41.7 — 14.0 16.5 27.8 33.0 41.7 — 17.0 34.0 — 17.0 34.0 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 16.5 27.8 33.0 41.7 50.0 — 16.5 27.8 33.0 41.7 50.0 — 16.5 27.8 33.0 41.7 50.0 — 17.0 34.0 51.0 — 17.0 34.0 51.0 — 17.0 34.0 51.0

DISCONNECT SIZE†

POWER SUPPLY FLA

MCA

MOCP

FLA

LRA

— 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.0 — 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.0 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 17.1 34.1 — 17.1 34.1 — 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.3 — 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.3 — 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.3 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 19.8 33.4 39.7 50.2 60.1 — 17.1 34.1 51.2 — 17.1 34.1 51.2 — 17.1 34.1 51.2

49.4/ 49.4 76.5/ 80.7 91.0/ 97.5 113.9/124.0 132.7/145.7 154.8/176.9 54.2/ 54.2 81.3/ 85.5 95.8/102.3 118.7/128.8 137.5/150.5 164.6/181.7 24.9 45.7 49.6 66.6 74.5 87.6 27.1 47.9 51.8 68.8 76.7 89.8 19.3 40.7 62.0 21.1 42.5 63.7 52.1/ 52.1 79.2/ 83.4 93.7/100.2 135.4/148.4 162.5/179.6 182.6/172.4 53.8/ 53.8 80.9/ 85.1 95.4/101.9 137.1/150.1 164.2/181.3 184.3/174.1 61.3/ 61.3 88.4/ 92.6 102.9/109.4 144.6/157.6 171.7/188.8 191.8/181.6 25.5 50.3 67.3 75.2 88.3 85.6 26.3 51.1 68.1 76.0 89.1 86.4 30.3 55.1 72.1 80.0 93.1 90.4 20.5 41.8 63.1 71.7 21.1 42.5 63.7 72.3 24.3 45.7 66.9 75.5

50/ 50†† 80/ 90 100/100 125/125 150/150 175/200 60/ 60†† 90/ 90 100/110 125/150 150/175 175/200 25†† 50†† 50†† 70 80 90 30†† 50†† 60†† 70 80 90 20†† 45†† 70 25†† 45†† 70 60/ 60†† 80/ 90 100/110 150/150 175/200 200/200 60/ 60†† 90/ 90 100/110 150/175 175/200 200/200 70/ 70 90/100 110/110 150/175 175/200 200/200 30†† 60†† 70 80 90 90 30†† 60†† 70 80 90 90 35†† 60†† 80 80 100 100 25†† 45†† 70 80 25†† 45†† 70 80 25†† 50†† 70 80

52/ 52 77/ 81 91/ 96 112/121 129/141 154/170 58/ 58 83/ 86 96/102 117/126 134/146 159/175 26 45 49 65 72 84 29 48 51 67 74 86 20 40 60 22 42 62 55/ 55 80/ 84 93/ 99 132/144 157/172 175/193 57/ 57 82/ 86 95/101 134/145 158/174 177/195 66/ 66 91/ 94 104/110 142/154 167/183 186/204 27 50 65 73 85 96 28 51 66 73 86 97 32 55 71 78 90 102 22 41 61 80 22 42 62 81 26 46 65 85

326/326 348/351 359/364 377/386 392/403 414/428 369/369 391/394*** 403/408*** 421/429*** 436/446*** 458/471*** 164 181 184 197 204 214*** 186 202 205 219 225 236*** 137 154 171 154 171 188 300/300 322/325*** 333/338*** 366/377*** 388/402*** 404/420*** 319/319 341/344*** 352/357*** 385/396*** 407/421*** 423/439*** 367/367 389/392*** 400/405*** 433/444*** 455/459*** 471/487*** 145 165 178 185 195*** 205*** 185 204 218 224 235*** 245*** 179 198 212 218 229*** 239*** 120 137 154 171*** 151 168 185 202*** 146 163 180 198***

52

Table 17 — Electric Heater Usage — Standard-Efficiency Heat Pump Units UNIT SIZE

VOLTAGE (60 Hz) 208/230/240 (single phase)

3 Tons

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (single phase)

4 Tons

208/230/240 (3 phase) 460/480 (3 phase)

208/230/240 (single phase)

5 Tons

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (3 phase) 6 Tons 460/480 (3 phase)

208/230/240 (3 phase) 71/2 and 81/2 Tons

460/480 (3 phase) 575 (3 phase) 208/230/240 (3 phase)

10 Tons

460/480 (3 phase) 575 (3 phase)

ACCESSORY HEATER PART NUMBER CRHEATER---A00 001 002 003 004 002+002 001 002 003 004 005 006 007 008 009 001 003 002+002 003+003 004+004 002 003 005 004+004 006 008 009 008+008 002 003 002+002 003+003 004+004 002 004 005 004+004 004+005 006 008 009 008+008 008+009 002 004 005 004+004 004+006 006 008 009 008+008 008+009 017 010 011 012 012+017 016 013 014 015 014+016 018 019 017 010 012 012+017 010+012 013 014 015 014+016 013+015 018 019 018+019

ACCESSORY kW 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 9.8/11.6/13.0* 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 12.0/14.7/16.0 5.5/ 6.0 8.1/ 8.8 10.6/11.5 12.9/14.0 3.3/ 4.0/ 4.4 6.5/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 16.0/19.3/21.0* 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 12.0/14.7/16.0 15.8/19.3/21.0* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 4.9/ 5.8/ 6.5 6.6/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 15.8/19.3/21.0* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5* 7.8/ 9.6/10.4 12.0/14.7/16.0 18.6/22.8/24.8 24.0/29.4/32.0 31.8/39.0/42.4* 12.8/13.9 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7* 17.0 34.0 7.8/ 9.6/10.4 12.0/14.7/16.0 24.0/29.4/32.0 31.8/39.0/42.4* 37.6/46.2/50.0* 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7* 45.9/50.0* 17.0 34.0 51.0*

SINGLE POINT BOX PACKAGE NO. CRSINGLE---A00 — —† 004 004 004** — — — — 002 — — — — —† 004 004 005 005 — — 002 003 — — — — 004 004 005 005 005 — —†† 002 003 003 — — — — — —*** 002 002 003 003 — — — — — 007 007 009 009 013 006 006 008 008 010 006 006††† 012 012 015 017 017 011 014 014 016 016 011 014 016

*Two heater packages required to provide kW indicated. †Use CRSINGLE004A00 for units with convenience outlet. **Use CRSINGLE005A00 for units with convenience outlet. ††Use CRSINGLE002A00 for units with convenience outlet. ***Use CRSINGLE002A00 for units with high-static motor and convenience outlet. †††Use CRSINGLE008A00 for units with an electrical convenience outlet. NOTES: 1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly. 2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kW new = Heater kW rated x (unit power distribution voltage/rated heater voltage)2 As an example: For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kW new = 16 kW (215/240)2 kW new = 12.8 kW (rating at 215 v)

53

NO SINGLE POINT BOX REQUIRED

Fig. 21 — Electric Heater Power Wiring Connections — Combination 50HJ004-007/62AQ Units — 208/230-1-60 — Less Than 60 Amps MOCP

CRSINGLE004A00

CRSINGLE005A00 WITH SINGLE HEATER

CRSINGLE005A00 WITH TWO HEATERS

Fig. 22 — Electric Heater Power Wiring Connections — Combination 50HJ004-007/62AQ Units — 208/230-1-60 — Greater Than 60 Amps MOCP

54

NO SINGLE POINT BOX REQUIRED

Fig. 23 — Electric Heater Power Wiring Connections — Combination 50HJ004-007/62AQ Units — 208/230-3-60 — Less Than 60 Amps MOCP, 460-3-60 — Less Than 30 Amps MOCP

CRSINGLE002A00

CRSINGLE003A00 WITH SINGLE HEATER

CRSINGLE003A00 WITH TWO HEATERS

Fig. 24 — Electric Heater Power Wiring Connections — Combination 50HJ004-007/62AQ Units — 208/230-3-60 — Greater Than 60 Amps MOCP

55

TO ER2

TO UNIT

TRAN DISCONNECT PER NEC (FIELD SUPPLIED)

1 2 3 EQUIP GND

HTR

FIELD POWER SUPPLY FU FU

TRAN — Transformer

CRSINGLE025A00

Fig. 25 — Electric Heater Power Wiring Connections — Combination 50HJ004-007/62AQ Units — 460-3-60 — Greater Than 30 Amps MOCP

CRSINGLE007A00 OR CRSINGLE012A00

CRSINGLE009A00 WITH SINGLE HEATER OR CRSINGLE015A00 WITH SINGLE HEATER

CRSINGLE009A00 WITH TWO HEATERS OR CRSINGLE015 WITH TWO HEATERS

CRSINGLE017A00

Fig. 26 — Electric Heater Power Wiring Connections — Combination 50HJ008-014/62AQ Units — 208/230-3-60 — Greater Than 60 Amps MOCP

56

CRSINGLE006A00 OR CRSINGLE011A00

Fig. 27 — Electric Heater Power Wiring Connections — Combination 50HJ008-014/62AQ Units — 460-3-60 — Less Than 60 Amps MOCP

CRSINGLE008A00 OR CRSINGLE014A00

CRSINGLE010A00 OR CRSINGLE016A00

Fig. 28 — Electric Heater Power Wiring Connections — Combination 50HJ008-014/62AQ Units — 460-3-60 — Greater Than 60 Amps MOCP

57

Table 18 — Electrical Data (COBRA™ Energy Recovery Unit 50HJ004-007 Units with 62AQ060) UNIT

NOMINAL V-PH-Hz

IFM TYPE

CONV OUTLET

62AQ FLA

STD

NO

9.2

STD

YES

9.2

STD

NO

9.2

STD

YES

9.2

HIGH STATIC

NO

9.2

HIGH STATIC

YES

9.2

STD

NO

9.2

STD

YES

9.2

HIGH STATIC

NO

9.2

HIGH STATIC

YES

9.2

STD

NO

9.2

STD

YES

9.2

STD

NO

9.2

STD

YES

9.2

HIGH STATIC

NO

9.2

HIGH STATIC

YES

9.2

STD

NO

9.2

208/230-1-60

208/230-3-60

50HJ004

460-3-60

208/230-1-60

50HJ005

208/230-3-60

460-3-60

HEAT FLA

MCA

—/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.8 46.9/54.2 —/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.8 46.9/54.2 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 — 7.2 13.8 16.8 27.7

34.8/ 34.8 35.7/ 38.8 45.2/ 49.7 55.1/ 61.2 63.2/ 70.5 74.5/ 83.6 40.8/ 40.8 40.8/ 43.0 50.0/ 53.9 59.9/ 65.4 68.0/ 74.7 79.3/ 87.8 27.7/ 27.7 27.7/ 29.1 32.8/ 35.4 38.5/ 42.0 43.2/ 47.4 57.5/ 64.0 33.7/ 33.7 33.7/ 33.7 37.6/ 39.6 43.3/ 46.2 48.0/ 51.6 62.3/ 68.2 28.6/ 28.6 28.6/ 30.0 33.7/ 36.3 39.4/ 42.9 44.1/ 48.3 58.4/ 64.9 34.6/ 34.6 34.6/ 34.6 38.5/ 40.5 44.2/ 47.1 48.9/ 52.5 63.2/ 69.1 13.6 16.7 20.9 25.0 28.7 16.3 18.8 23.0 27.1 30.8 14.0 17.1 21.3 25.4 29.1 16.7 19.2 23.4 27.5 31.2 44.4/ 44.4 44.4/ 44.4 55.1/ 61.2 74.5/ 83.6 94.4/106.5 110.6/125.2 50.4/ 50.4 50.4/ 50.4 59.9/ 65.4 79.3/ 87.8 99.2/110.7 115.4/129.4 31.7/ 31.7 32.8/ 35.4 38.5/ 42.0 57.5/ 64.0 70.6/ 79.0 37.7/ 37.7 37.7/ 39.6 43.3/ 46.2 62.3/ 68.2 75.4/ 83.2 32.6/ 32.6 33.7/ 36.3 39.4/ 42.9 58.4/ 64.9 71.5/ 79.9 38.6/ 38.6 38.6/ 40.5 44.2/ 47.1 63.2/ 69.1 76.3/ 84.1 15.2 16.7 25.0 28.7 42.3

58

POWER SUPPLY FUSE OR HACR BKR 40/40 40/45 50/50 — — — 45/45 45/50 60/60 — — — 35/35 35/35 40/40 45/45 45/50 — 40/35 40/40 45/45 50/50 50/60 — 35/35 35/35 40/40 45/45 50/50 — 40/40 40/40 45/45 50/50 60/60 — 20 20 25 25 30 20 25 25 30 35 20 20 25 30 30 20 25 25 30 35 60/60 60/60 — — — — 60/60 60/60 — — — — 40/40 40/40 45/45 — — 40/40 45/45 50/50 — — 40/40 40/40 45/45 — — 45/45 45/45 50/50 — — 20 20 25 30 45

DISCONNECT SIZE* MOCP

FLA

LRA

— — — 60/ 70 70/ 80 80/ 90 — — — 60/ 70 70/ 80 80/ 90 — — — — — 60/ 70 — — — — — 70/ 70 — — — — — 60/ 70 — — — — — 70/ 70 — — — — — — — — — — — — — — — — — — — — — — 60/ 70 80/ 90 100/110 125/150 — — 60/ 70 80/ 90 100/125 125/150 — — — 60/ 70 80/ 80 — — — 70/ 70 80/ 90 — — — 60/ 70 80/ 80 — — — 70/ 70 80/ 90 — — — — —

35/ 35 35/ 37 43/ 47 52/ 58 60/ 67 70/ 79 41/ 41 41/ 42 49/ 52 58/ 63 65/ 71 76/ 83 29/ 29 29/ 29 32/ 34 37/ 40 41/ 45 55/ 60 34/ 34 34/ 34 37/ 39 43/ 45 47/ 50 60/ 65 30/ 30 30/ 30 33/ 35 38/ 41 42/ 46 56/ 62 35/ 35 35/ 35 38/ 40 44/ 46 48/ 51 61/ 66 14 14 15 24 27 20 20 20 29 32 15 15 15 24 28 20 20 20 29 32 44/ 44 44/ 44 52/ 58 70/ 79 88/100 103/117 50/ 50 50/ 50 58/ 63 76/ 83 94/104 109/122 33/ 33 33/ 34 37/ 40 55/ 60 67/ 74 38/ 38 38/ 39 43/ 45 60/ 65 72/ 79 34/ 34 34/ 35 38/ 41 56/ 62 68/ 75 39/ 39 39/ 40 44/ 46 61/ 66 73/ 80 16 16 18 27 40

135/135 135/135 135/135 135/135 135/135 135/135 140/140 140/140 140/140 140/140 140/140 140/140 124/124 124/124 124/124 124/124 124/124 124/124 129/129 129/129 129/129 129/129 129/129 129/129 154/154 154/154 154/154 154/154 154/154 154/154 158/158 158/158 158/158 158/158 158/158 158/158 63 63 63 63 63 67 68 68 68 68 77 77 77 77 77 82 82 82 82 82 173/173 173/173 173/173 173/173 173/173 173/173 178/178 178/178 178/178 178/178 178/178 178/178 140/140 140/140 140/140 140/140 140/140 145/145 145/145 145/145 145/145 145/145 170/170 170/170 170/170 170/170 170/170 174/174 174/174 174/174 174/174 174/174 70 71 71 71 71

Table 18 — Electrical Data (COBRA™ Energy Recovery Unit 50HJ004-007 Units with 62AQ060) (cont) NOMINAL V-PH-Hz

UNIT

50HJ005 (cont)

460-3-60

IFM TYPE

CONV OUTLET

62AQ FLA

STD

YES

9.2

HIGH STATIC

NO

9.2

HIGH STATIC

YES

9.2

STD

NO

9.2

STD

YES

9.2

STD

NO

9.2

STD

YES

9.2

HIGH STATIC

NO

9.2

HIGH STATIC

YES

9.2

STD

NO

9.2

STD

YES

9.2

208/230-1-60

50HJ006

208/230-3-60

460-3-60

FLA HACR IFM LRA MCA MOCP NEC UL

— — — — — — — —

HEAT FLA

MCA

— 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 —/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7

17.9 18.8 27.1 30.8 44.4 15.6 17.1 25.4 29.1 42.7 18.3 19.2 27.5 31.2 44.8 55.5/ 55.5 55.5/ 55.5 59.5/ 65.5 78.9/ 87.9 98.7/110.8 115.0/129.6 61.5/ 61.5 61.5/ 61.5 64.3/ 69.7 83.7/ 92.1 103.5/115.0 119.8/133.8 38.1/ 38.1 38.1/ 38.1 44.1/ 48.3 58.4/ 64.9 71.5/ 79.9 85.8/ 96.4 44.1/ 44.1 44.1/ 44.1 48.9/ 52.5 63.2/ 69.1 76.3/ 84.1 90.6/100.6 39.8/ 39.8 39.8/ 39.8 45.9/ 50.1 60.3/ 66.7 73.3/ 81.7 87.6/ 98.3 45.8/ 45.8 45.8/ 45.8 50.7/ 54.3 65.1/ 70.9 78.1/ 85.9 92.4/102.5 19.3 19.3 25.4 29.1 42.7 46.4 22.0 22.0 27.5 31.2 44.8 48.5

POWER SUPPLY FUSE OR HACR BKR 20 25 30 35 45 20 20 30 30 45 20 25 30 35 45 70/70 — — — — — 70/70 — — — — — 45/45 45/45 50/50 — — — 50/50 50/50 60/60 — — — 45/45 45/45 50/60 — — — 50/50 50/50 60/60 — — — 25 25 30 30 45 50 25 25 30 35 45 50

DISCONNECT SIZE* MOCP

FLA

LRA

— — — — — — — — — — — — — — — — 70/ 70 70/ 70 80/ 90 100/125 125/150 — 70/ 70 70/ 70 90/100 110/125 125/150 — — — 60/ 70 80/ 80 90/100 — — — 70/ 70 80/ 90 100/110 — — — 70/ 70 80/ 90 90/100 — — — 70/ 80 80/ 90 100/110 — — — — — — — — — — — —

21 21 21 32 44 16 16 19 28 40 22 22 22 32 45 56/ 56 56/ 56 57/ 62 75/ 83 93/104 108/121 61/ 61 61/ 61 62/ 67 80/ 88 98/109 113/126 39/ 39 39/ 39 42/ 46 56/ 62 68/ 75 81/ 91 44/ 44 44/ 44 48/ 51 61/ 66 73/ 80 86/ 95 41/ 41 41/ 41 44/ 48 58/ 63 70/ 77 83/ 93 46/ 46 46/ 46 50/ 53 63/ 68 75/ 82 88/ 97 20 20 20 28 40 44 25 25 25 32 45 48

75 75 75 75 75 84 85 85 85 85 89 90 90 90 90 250/250 250/250 250/250 250/250 250/250 250/250 255/255 255/255 255/255 255/255 255/255 255/255 202/202 202/202 202/202 202/202 202/202 202/202 207/207 207/207 207/207 207/207 207/207 207/207 221/221 221/221 221/221 221/221 221/221 221/221 226/226 226/226 226/226 226/226 226/226 226/226 101 101 101 101 101 101 106 106 106 106 106 106

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Underwriters’ Laboratories

Average Voltage = =

*Used to determine minimum disconnect per NEC.

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. % Voltage Imbalance = 100 x 7 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. max voltage deviation from average voltage = 100 x average voltage

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

59

Table 18 — Electrical Data (COBRA™ Energy Recovery Unit 50HJ004-007 Units with 62AQ060) (cont) NOMINAL V-PH-Hz

UNIT

50HJ006 (cont)

IFM TYPE

CONV OUTLET

62AQ FLA

HIGH STATIC

NO

9.2

HIGH STATIC

YES

9.2

STD

NO

9.2

STD

YES

9.2

HIGH STATIC

NO

9.2

HIGH STATIC

YES

9.2

STD

NO

9.2

STD

YES

9.2

HIGH STATIC

NO

9.2

HIGH STATIC

YES

9.2

460-3-60

208/230-3-60

50HJ007

460-3-60

FLA HACR IFM LRA MCA MOCP NEC UL

— — — — — — — —

HEAT FLA

MCA

— 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7

20.1 20.1 26.2 29.9 43.5 47.2 22.8 22.8 28.3 32.0 45.6 49.3 42.0/ 42.0 42.0/ 42.0 44.1/ 48.3 58.4/ 64.9 71.5/ 79.9 85.8/ 96.4 48.0/ 48.0 48.0/ 48.0 48.9/ 52.5 63.2/ 69.1 76.3/ 84.1 90.6/100.6 43.7/ 43.7 43.7/ 43.7 45.9/ 50.1 60.3/ 66.7 73.3/ 81.7 87.6/ 98.3 49.7/ 49.7 49.7/ 49.7 50.7/ 54.3 65.1/ 70.9 78.1/ 85.9 92.4/102.5 19.8 19.8 25.4 29.1 42.7 46.4 22.5 22.5 27.5 31.2 44.8 48.5 20.6 20.6 26.2 29.9 43.5 47.2 23.3 23.3 28.3 32.0 45.6 49.3

POWER SUPPLY FUSE OR HACR BKR 25 25 30 30 45 50 25 25 30 35 50 50 50/50 50/50 50/50 — — — 60/60 60/60 60/60 — — — 50/50 50/50 50/60 — — — 60/60 60/60 60/60 — — — 25 25 30 30 45 50 25 25 30 35 45 50 25 25 30 30 45 50 30 30 30 35 50 50

DISCONNECT SIZE* MOCP

FLA

LRA

— — — — — — — — — — — — — — — 60/ 70 80/ 80 90/100 — — — 70/ 70 80/ 90 100/110 — — — 70/ 70 80/ 90 90/100 — — — 70/ 80 80/ 90 100/110 — — — — — — — — — — — — — — — — — — — — — — — —

20 20 20 29 41 44 26 26 26 33 46 49 42/42 42/42 42/46 56/62 68/75 81/91 48/48 48/48 48/51 61/66 73/80 86/95 44/44 44/44 44/48 58/63 70/77 83/93 50/50 50/50 50/53 63/68 75/82 88/97 20 20 20 28 40 44 26 26 26 32 45 48 21 21 21 29 41 44 26 26 26 33 46 49

110 111 111 111 111 111 115 116 116 116 116 116 234/234 234/234 234/234 234/234 234/234 234/234 239/239 239/239 239/239 239/239 239/239 239/239 253/253 253/253 253/253 253/253 253/253 253/253 258/258 258/258 258/258 258/258 258/258 258/258 114 114 114 114 114 114 118 119 119 119 119 119 123 124 124 124 124 124 128 128 128 128 128 128

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Underwriters’ Laboratories

Average Voltage = =

*Used to determine minimum disconnect per NEC.

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. % Voltage Imbalance = 100 x 7 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. max voltage deviation from average voltage = 100 x average voltage

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

60

Table 19 — Electric Heater Usage — COBRA™ Energy Recovery Unit 50HJ004-007 Units with 62AQ060 UNIT 50HJ/62AQ

VOLTAGE (60 Hz) 208/230/240 (single phase)

004

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (single phase)

005

208/230/240 (3 phase) 460/480 (3 phase)

208/230/240 (single phase)

006

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (3 phase) 007 460/480 (3 phase)

ACCESSORY HEATER PART NUMBER CRHEATER---A00 001 002 003 004 002 & 002 001 002 003 004 005 006 007 008 009 001 003 002 & 002 003 & 003 004 & 004 002 003 005 004 & 004 006 008 009 008 & 008 002 003 002 & 002 003 & 003 004 & 004 002 004 005 004 & 004 004 & 005 006 008 009 008 & 008 008 & 009 002 004 005 004 & 004 004 & 005 006 008 009 008 & 008 008 & 009

ACCESSORY kW 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 9.8/11.6/13.0* 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 12.0/14.7/16.0 5.5/ 6.0 8.1/ 8.8 10.6/11.5 12.9/14.0 3.3/ 4.0/ 4.4 6.5/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 16.0/19.3/21.0* 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 12.0/14.7/16.0 15.8/19.3/21.0* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 4.9/ 5.8/ 6.5 6.6/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 15.8/19.3/21.0* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5*

SINGLE POINT BOX PACKAGE NO. CRSINGLE---A00 — — 004 004† 005 — — — — 002** — — — — — 004 005 005 005 — — 002** 003 — — —†† 025 004 004† 005 005 005 — — 002 003 003 — — —†† 025 025 — — 002** 003 003 — — —†† 025 025

*Two heater packages required to provide kW indicated. †005 on units with convenience outlet. **003 on high-static units with convenience outlet. ††025 on units with convenience outlet. NOTES: 1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly. 2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kWnew = Heater kW rated x (unit power distribution voltage/rated heater voltage)2 As an example: For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kWnew = 16 kW (215/240)2 kWnew = 12.8 kW (rating at 215 v)

61

Table 20 — Electrical Data (COBRA™ Energy Recovery Unit 50HJ004-007 Units with 62AQ100) UNIT

NOMINAL V-PH-Hz

IFM TYPE

CONV OUTLET

62AQ FLA

STD

NO

15.1

STD

YES

15.1

STD

NO

15.1

STD

YES

15.1

HIGH STATIC

NO

15.1

HIGH STATIC

YES

15.1

STD

NO

15.1

STD

YES

15.1

HIGH STATIC

NO

15.1

HIGH STATIC

YES

15.1

STD

NO

15.1

STD

YES

15.1

STD

NO

15.1

STD

YES

15.1

HIGH STATIC

NO

15.1

HIGH STATIC

YES

15.1

STD

NO

15.1

208/230-1-60

208/230-3-60

50HJ004

460-3-60

208/230-1-60

50HJ005

208/230-3-60

460-3-60

HEAT FLA

MCA

—/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.8 46.9/54.2 —/— 15.9/18.3 23.5/27.1 31.4/36.3 37.9/43.8 46.9/54.2 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 —/— 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 — 7.2 10.6 13.8 16.8 —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 15.9/18.3 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 —/— 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 — 7.2 13.8 16.8 27.7

40.7/ 40.7 42.5/ 45.5 52.0/ 56.5 61.9/ 67.9 70.0/ 77.3 81.3/ 90.3 46.7/ 46.7 47.3/ 49.7 56.8/ 60.7 66.7/ 72.1 74.8/ 81.5 86.1/ 94.5 33.6/ 33.6 34.1/ 35.9 39.6/ 42.2 45.3/ 48.8 50.0/ 54.2 64.3/ 70.7 39.6/ 39.6 39.6/ 40.1 44.4/ 46.4 50.1/ 53.0 54.8/ 58.4 69.1/ 74.9 34.5/ 34.5 35.0/ 36.8 40.5/ 43.1 46.2/ 49.7 50.9/ 55.1 65.2/ 71.6 40.5/ 40.5 40.5/ 41.0 45.3/ 47.3 51.0/ 53.9 55.7/ 59.3 70.0/ 75.8 16.5 20.1 24.3 28.4 32.1 19.2 22.2 26.4 30.5 34.2 16.9 20.5 24.7 28.8 32.5 19.6 22.6 26.8 30.9 34.6 50.3/ 50.3 50.3/ 50.3 61.9/ 67.9 81.3/ 90.3 101.2/113.3 117.4/132.0 56.3/ 56.3 56.3/ 56.3 66.7/ 72.1 86.1/ 94.5 106.0/117.5 122.2/136.2 37.6/ 37.6 39.6/ 42.2 45.3/ 48.8 64.3/ 70.7 77.3/ 85.8 43.6/ 43.6 44.4/ 46.4 50.1/ 53.0 69.1/ 74.9 82.1/ 90.0 38.5/ 38.5 40.5/ 43.1 46.2/ 49.7 65.2/ 71.6 78.2/ 86.7 44.5/ 44.5 45.3/ 47.3 51.0/ 53.9 70.0/ 75.8 83.0/ 90.9 18.2 20.1 28.4 32.1 45.6

62

POWER SUPPLY FUSE OR HACR BKR 45/45 50/60 — — — — 50/50 60/60 — — — — 40/40 45/45 50/50 60/60 60/60 — 45/45 50/50 60/60 60/60 — — 40/40 45/45 50/50 60/60 60/60 — 45/45 50/50 60/60 60/60 — — 20.0 25.0 30.0 35.0 35.0 20.0 30.0 30.0 35.0 40.0 20.0 25.0 30.0 35.0 35.0 25.0 30.0 30.0 35.0 40.0 60/60 60/60 — — — — 70/70 — — — — — 45/45 50/50 60/60 — — 50/50 60/60 60/60 — — 45/45 50/50 60/60 — — 50/50 60/60 60/60 — — 20 25 35 30 50

DISCONNECT SIZE* MOCP

FLA

LRA

— — 60/ 70 70/ 70 80/ 80 90/100 — — 70/ 70 70/ 80 80/ 90 90/100 — — — — — 70/ 80 — — — — 60/ 70 80/ 80 — — — — — 70/ 80 — — — — 70/ 70 80/ 80 — — — — — — — — — — — — — — — — — — — — — — 70 70 90/100 110/125 125/150 — 70/ 70 70/ 80 90/100 110/125 125/150 — — — 70/ 80 80/ 90 — — — 80/ 80 90/ 90 — — — 70/ 80 80/ 90 — — — 80/ 80 90/100 — — — — —

42/ 42 42/ 44 50/ 54 59/ 65 67/ 73 77/ 85 48/ 48 48/ 49 56/ 59 65/ 70 72/ 78 82/ 90 36/ 36 36/ 36 39/ 41 44/ 47 48/ 52 61/ 67 41/ 41 41/ 41 44/ 46 49/ 52 54/ 57 67/ 72 37/ 37 37/ 37 40/ 42 45/ 48 49/ 53 62/ 68 42/ 42 42/ 42 45/ 47 50/ 53 55/ 58 68/ 73 18 18 18 27 31 23 23 23 32 35 18 18 18 28 31 24 24 24 32 36 51/ 51 51/ 51 59/ 65 77/ 85 95/106 110/124 57/ 57 57/ 57 65/ 70 82/ 90 101/111 116/128 39/ 39 39/ 41 44/ 47 61/ 67 73/ 81 45/ 45 45/ 46 49/ 52 67/ 72 79/ 86 40/ 40 40/ 42 45/ 48 62/ 68 74/ 82 46/ 46 46/ 47 50/ 53 68/ 73 80/ 87 19 19 19 31 43

161/161 161/161 161/161 161/161 161/161 161/161 166/166 166/166 166/166 166/166 166/166 166/166 150/150 150/150 150/150 150/150 150/150 150/150 155/155 155/155 155/155 155/155 155/155 155/155 180/180 180/180 180/180 180/180 180/180 180/180 184/184 184/184 184/184 184/184 184/184 184/184 76 76 77 80 83 80 81 81 82 85 90 90 91 94 97 95 95 95 96 99 199/199 199/199 199/199 199/199 199/199 199/199 204/204 204/204 204/204 204/204 204/204 204/204 166/166 166/166 166/166 166/166 166/166 171/171 171/171 171/171 171/171 171/171 196/196 196/196 196/196 196/196 196/196 200/200 200/200 200/200 200/200 200/200 83 84 84 84 94

Table 20 — Electrical Data (COBRA™ Energy Recovery Unit 50HJ004-007 Units with 62AQ100) (cont) NOMINAL V-PH-Hz

UNIT

50HJ005 (cont)

460-3-60

IFM TYPE

CONV OUTLET

62AQ FLA

STD

YES

15.1

HIGH STATIC

NO

15.1

HIGH STATIC

YES

15.1

STD

NO

15.1

STD

YES

15.1

STD

NO

15.1

STD

YES

15.1

HIGH STATIC

NO

15.1

HIGH STATIC

YES

15.1

STD

NO

15.1

208/230-1-60

50HJ006 208/230-3-60

460-3-60

FLA HACR IFM LRA MCA MOCP NEC UL

— — — — — — — —

HEAT FLA

MCA

— 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 — 7.2 13.8 16.8 27.7 —/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 23.5/27.1 31.4/36.3 46.9/54.2 62.8/72.5 75.8/87.5 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7

20.9 22.2 30.5 34.2 47.7 18.6 20.5 28.8 32.5 46.0 21.3 22.6 30.9 34.6 48.1 61.4/ 61.4 61.4/ 61.4 65.8/ 71.8 85.2/ 94.2 105.1/117.2 121.3/135.9 67.4/ 67.4 67.4/ 67.4 70.6/ 76.0 90.0/ 98.4 109.9/121.4 126.1/140.1 44.0/ 44.0 44.0/ 44.0 50.9/ 55.1 65.2/ 71.6 78.2/ 86.7 92.6/103.2 50.0/ 50.0 50.0/ 50.0 55.7/ 59.3 70.0/ 75.8 83.0/ 90.9 97.4/107.4 45.7/ 45.7 45.7/ 45.7 52.6/ 56.8 66.9/ 73.3 79.9/ 88.4 94.3/104.9 51.7/ 51.7 51.7/ 51.7 57.4/ 61.0 71.7/ 77.5 84.7/ 92.6 99.1/109.1 22.2 22.2 28.8 32.5 46.0 49.8

POWER SUPPLY FUSE OR HACR BKR 25 30 35 40 50 25 25 35 35 50 25 30 35 40 50 70/70 — — — — — 80/80 — — — — — 50/50 50/50 60/60 — — — 60/60 60/60 — — — — 60/60 60/60 — — — — 60/60 60/60 — — — — 25 25 35 35 50 50

DISCONNECT SIZE* MOCP

FLA

LRA

— — — — — — — — — — — — — — — — 70/ 70 70/ 80 90/100 110/125 125/150 — 80/ 80 80/ 80 90/100 110/125 150/150 — — — 70/ 80 80/ 90 100/110 — — 70/ 70 80/ 80 90/100 100/110 — — 60/ 70 70/ 80 80/ 90 100/110 — — 70/ 70 80/ 80 90/100 100/110 — — — — — —

25 25 25 35 48 19 19 19 31 43 25 25 25 36 48 62/ 62 62/ 62 64/ 69 81/ 90 100/111 115/128 68/ 68 68/ 68 69/ 74 87/ 95 105/116 120/133 46/ 46 46/ 46 49/ 53 62/ 68 74/ 82 88/ 97 51/ 51 51/ 51 55/ 58 68/ 73 80/ 87 93/102 48/ 48 48/ 48 51/ 55 64/ 70 76/ 84 90/ 99 53/ 53 53/ 53 57/ 60 70/ 75 82/ 89 95/104 23 23 23 31 43 47

88 88 88 88 96 97 98 98 98 108 102 103 103 103 110 276/276 276/276 276/276 276/276 276/276 276/276 281/281 281/281 281/281 281/281 281/281 281/281 228/228 228/228 228/228 228/228 228/228 228/228 233/233 233/233 233/233 233/233 233/233 233/233 247/247 247/247 247/247 247/247 247/247 247/247 252/252 252/252 252/252 252/252 252/252 252/252 114 114 114 114 114 114

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Underwriters’ Laboratories

Average Voltage = =

*Used to determine minimum disconnect per NEC.

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. max voltage deviation from average voltage = 100 x average voltage

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

63

Table 20 — Electrical Data (COBRA™ Energy Recovery Unit 50HJ004-007 Units with 62AQ100) (cont) NOMINAL V-PH-Hz

UNIT

50HJ006 (cont)

460-3-60

IFM TYPE

CONV OUTLET

62AQ FLA

STD

YES

15.1

HIGH STATIC

NO

15.1

HIGH STATIC

YES

15.1

STD

NO

15.1

STD

YES

15.1

HIGH STATIC

NO

15.1

HIGH STATIC

YES

15.1

STD

NO

15.1

STD

YES

15.1

HIGH STATIC

NO

15.1

HIGH STATIC

YES

15.1

208/230-3-60

50HJ007

460-3-60

FLA HACR IFM LRA MCA MOCP NEC UL

— — — — — — — —

HEAT FLA

MCA

— 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 —/— 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7 — 7.2 13.8 16.8 27.7 30.7

24.9 24.9 30.9 34.6 48.1 51.9 23.0 23.0 29.6 33.3 46.8 50.6 25.7 25.7 31.7 35.4 48.9 52.7 47.9/ 47.9 47.9/ 47.9 50.9/ 55.1 65.2/ 71.6 78.2/ 86.7 92.6/103.2 53.9/ 53.9 53.9/ 53.9 55.7/ 59.3 70.0/ 75.8 83.0/ 90.9 97.4/107.4 49.6/ 49.6 49.6/ 49.6 52.6/ 56.8 66.9/ 73.3 79.9/ 88.4 94.3/104.9 55.6/ 55.6 55.6/ 55.6 57.4/ 61.0 71.7/ 77.5 84.7/ 92.6 99.1/109.1 22.8 22.8 28.8 32.5 46.0 49.8 25.5 25.5 30.9 34.6 48.1 51.9 23.6 23.6 29.6 33.3 46.8 50.6 26.3 26.3 31.7 35.4 48.9 52.7

POWER SUPPLY FUSE OR HACR BKR 30 30 35 40 50 60 30 30 35 35 50 60 30 30 35 40 50 60 60/60 60/60 60/60 — — — 60/60 60/60 — — — — 60/60 60/60 — — — — 60/60 60/60 — — — — 30 30 35 35 50 50 30 30 35 40 50 60 30 30 35 35 50 60 30 30 35 40 50 60

DISCONNECT SIZE* MOCP

FLA

LRA

— — — — — — — — — — — — — — — — — — — — — 70/ 80 80/ 90 100/110 — — 70/ 70 80/ 80 90/100 100/110 — — 60/ 70 70/ 80 80/ 90 100/110 — — 70/ 70 80/ 80 90/100 100/110 — — — — — — — — — — — — — — — — — — — — — — — —

28 28 28 36 48 52 24 24 24 32 44 48 29 29 29 37 49 53 49/ 49 49/ 49 49/ 53 62/ 68 74/ 82 88/ 97 55/ 55 55/ 55 55/ 58 68/ 73 80/ 87 93/102 51/ 51 51/ 51 51/ 55 64/ 70 76/ 84 90/ 99 57/ 57 57/ 57 57/ 60 70/ 75 82/ 89 95/104 23 23 23 31 43 47 29 29 29 36 48 52 24 24 24 32 44 48 30 30 30 37 49 53

119 119 119 119 119 119 123 124 124 124 124 124 128 129 129 129 129 129 260/260 260/260 260/260 260/260 260/260 260/260 265/265 265/265 265/265 265/265 265/265 265/265 279/279 279/279 279/279 279/279 279/279 279/279 284/284 284/284 284/284 284/284 284/284 284/284 127 127 127 127 127 127 131 132 132 132 132 132 136 137 137 137 137 137 141 141 141 141 141 141

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Underwriters’ Laboratories

Average Voltage = =

*Used to determine minimum disconnect per NEC.

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. % Voltage Imbalance = 100 x 7 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. max voltage deviation from average voltage = 100 x average voltage

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

64

Table 21 — Electric Heater Usage — COBRA™ Energy Recovery Units 50HJ004-007 with 62AQ100 UNIT 50HJ/62AQ

VOLTAGE (60 Hz) 208/230/240 (single phase)

004

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (single phase)

005

208/230/240 (3 phase) 460/480 (3 phase)

208/230/240 (single phase)

006

208/230/240 (3 phase)

460/480 (3 phase)

208/230/240 (3 phase) 007 460/480 (3 phase)

ACCESSORY HEATER PART NUMBER CRHEATER---A00 001 002 003 004 002 & 002 001 002 003 004 005 006 007 008 009 001 003 002 & 002 003 & 003 004 & 004 002 003 005 004 & 004 006 008 009 008 & 008 002 003 002 & 002 003 & 003 004 & 004 002 004 005 004 & 004 004 & 005 006 008 009 008 & 008 008 & 009 002 004 005 004 & 004 004 & 005 006 008 009 008 & 008 008 & 009

ACCESSORY kW 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 9.8/11.6/13.0* 3.3/ 4.0/ 4.4 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 7.9/ 9.6/10.5 12.0/14.7/16.0 5.5/ 6.0 8.1/ 8.8 10.6/11.5 12.9/14.0 3.3/ 4.0/ 4.4 6.5/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 16.0/19.3/21.0* 4.9/ 5.8/ 6.5 6.5/ 8.0/ 8.7 12.0/14.7/16.0 15.8/19.3/21.0* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 4.9/ 5.8/ 6.5 6.6/ 8.0/ 8.7 9.8/11.6/13.0* 13.1/16.0/17.4* 15.8/19.3/21.0* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5* 4.9/ 5.8/ 6.5 7.9/ 9.6/10.5 12.0/14.7/16.0 15.8/19.3/21.0* 19.9/24.3/26.5* 5.5/ 6.0 10.6/11.5 12.9/14.0 21.1/23.0* 23.4/25.5*

SINGLE POINT BOX PACKAGE NO. CRSINGLE---A00 — 004 004 004 005 — — — —† 002** — — 025 025 —†† 004 005 005 005 — — 002** 003 — 025 025 025 004 004 005 005 005 — —† 002** 003 003 — 025 025 025 025 — —† 002** 003 003 — 025 025 025 025

*Two heater packages required to provide kW indicated. †002 on units with convenience outlet. **003 on high-static units with convenience outlet. ††004 on units with convenience outlet. NOTES: 1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly. 2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kWnew = Heater kW rated x (unit power distribution voltage/rated heater voltage)2 As an example: For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kWnew = 16 kW (215/240)2 kWnew = 12.8 kW (rating at 215 v)

65

Table 22 — Electrical Data (COBRA™ Energy Recovery Units 50HJ008-014 with 62AQ200) UNIT

NOMINAL V-PH-Hz

IFM TYPE

CONV OUTLET

62AQ FLA

STD

NO

21.9

STD

YES

21.9

HIGH STATIC

NO

21.9

HIGH STATIC

YES

21.9

STD

NO

10.2

STD

YES

10.2

HIGH STATIC

NO

10.2

HIGH STATIC

YES

10.2

STD

NO

21.9

STD

YES

21.9

HIGH STATIC

NO

21.9

HIGH STATIC

YES

21.9

STD

NO

10.2

STD

YES

10.2

HIGH STATIC

NO

10.2

HIGH STATIC

YES

10.2

208/230-3-60

50HJ008

460-3-60

208/230-3-60

50HJ009

460-3-60

HEAT FLA

MCA

—/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2

60.1/ 60.1 60.1/ 64.0 74.5/ 80.9 97.4/107.4 116.2/129.0 143.3/160.3 66.1/ 66.1 66.1/ 68.2 79.3/ 85.1 102.2/111.6 121.0/133.2 148.1/164.5 63.2/ 63.2 63.2/ 67.1 77.6/ 84.0 100.5/110.5 119.3/132.1 146.4/163.4 69.2/ 69.2 69.2/ 71.3 82.4/ 88.2 105.3/114.7 124.1/136.3 151.2/167.6 29.4 36.1 40.0 57.0 64.8 77.9 32.1 38.2 42.1 59.1 66.9 80.0 30.8 37.5 41.4 58.4 66.2 79.3 33.5 39.6 43.5 60.5 68.3 81.4 62.1/ 62.1 62.1/ 64.0 74.5/ 80.9 97.4/107.4 116.2/129.0 143.3/160.3 68.1/ 68.1 68.1/ 68.2 79.3/ 85.1 102.2/111.6 121.0/133.2 148.1/164.5 65.2/ 65.2 65.2/ 67.1 77.6/ 84.0 100.5/110.5 119.3/132.1 146.4/163.4 71.2/ 71.2 71.2/ 71.3 82.4 /88.2 105.3/114.7 124.1/136.3 151.2/167.6 31.7 36.1 40.0 57.0 64.8 77.9 34.4 38.2 42.1 59.1 66.9 80.0 33.1 37.5 41.4 58.4 66.2 79.3 35.8 39.6 43.5 60.5 68.3 81.4

66

POWER SUPPLY FUSE OR HACR BKR 70/70 — — — — — 70/70 — — — — — 70/70 — — — — — 80/80 — — — — — 35.0 40.0 45.0 60.0 — — 35.0 45.0 45.0 60.0 — — 35.0 40.0 45.0 60.0 — — 35.0 45.0 45.0 — — — 70/70 — — — — — 70/70 — — — — — 70/70 — — — — — 80/80 — — — — — 35.0 40.0 45.0 60.0 — — 40.0 45.0 45.0 60.0 — — 35.0 40.0 45.0 60.0 — — 40.0 45.0 45.0 — — —

DISCONNECT SIZE* MOCP

FLA

LRA

—/— 70/ 80 80/ 90 100/110 125/150 150/175 —/— 80/ 80 90/ 90 110/125 125/150 150/175 —/— 80/ 80 90/ 90 110/125 125/150 150/175 —/— 80/ 80 90/100 110/125 125/150 175/175 — — — — 70.0 80.0 — — — — 70.0 80.0 — — — — 70.0 80.0 — — — 70.0 70.0 90.0 — 70/ 80 80/ 90 100/110 125/150 150/175 — 80/ 80 90/ 90 110/125 125/150 150/175 —/— 80/ 80 90/ 90 110/125 125/150 150/175 —/— 80/ 80 90/100 110/125 125/150 175/175 — — — — 70.0 80.0 — — — — 70.0 80.0 — — — — 70.0 80.0 — — — 70.0 70.0 90.0

66/ 66 66/ 66 72/ 78 93/102 111/122 135/151 71/ 71 71/ 71 78/ 83 99/107 116/127 141/156 69/ 69 69/ 69 76/ 82 97/106 114/126 139/155 75/ 75 75/ 75 81/ 86 102/111 120/131 145/160 32.0 35.0 38.0 54.0 61.0 73.0 34.0 37.0 41.0 57.0 64.0 76.0 34.0 36.0 40.0 56.0 63.0 75.0 36.0 39.0 42.0 58.0 65.0 77.0 68/ 68 68/ 68 72/ 78 93/102 111/122 135/151 73/ 73 73/ 73 78/ 83 99/107 116/127 141/156 71/ 71 71/ 71 76/ 82 97/106 114/126 139/155 77/ 77 77/ 77 81/ 86 102/111 120/131 145/160 34.0 35.0 38.0 54.0 61.0 73.0 37.0 37.0 41.0 57.0 64.0 76.0 36.0 36.0 40.0 56.0 63.0 75.0 38.0 39.0 42.0 58.0 65.0 77.0

366/366 366/366 366/366 366/366 366/366 366/366 371/371 371/371 371/371 371/371 371/371 371/371 391/391 391/391 391/391 391/391 391/391 391/391 395/395 395/395 395/395 395/395 395/395 395/395 184.0 184.0 184.0 184.0 184.0 184.0 186.0 186.0 186.0 186.0 186.0 186.0 196.0 197.0 197.0 197.0 197.0 197.0 198.0 199.0 199.0 199.0 199.0 199.0 400/400 400/400 400/400 400/400 400/400 400/400 405/405 405/405 405/405 405/405 405/405 405/405 425/425 425/425 425/425 425/425 425/425 425/425 429/429 429/429 429/429 429/429 429/429 429/429 206.0 206.0 206.0 206.0 206.0 206.0 208.0 208.0 208.0 208.0 208.0 208.0 218.0 219.0 219.0 219.0 219.0 219.0 220.0 221.0 221.0 221.0 221.0 221.0

Table 22 — Electrical Data (COBRA™ Energy Recovery Units 50HJ008-014 with 62AQ200) (cont) UNIT

NOMINAL V-PH-Hz

IFM TYPE

CONV OUTLET

62AQ FLA

STD

NO

21.9

STD

YES

21.9

HIGH STATIC

NO

21.9

HIGH STATIC

YES

21.9

STD

NO

10.2

STD

YES

10.2

HIGH STATIC

NO

10.2

HIGH STATIC

YES

10.2

STD

NO

21.9

STD

YES

21.9

STD

NO

10.2

STD

YES

10.2

208/230-3-60

50HJ012

460-3-60

208/230-3-60

50HJ014

460-3-60

HEAT FLA

MCA

—/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 — 16.7 19.8 39.7 50.2 60.1 — 16.7 19.8 39.7 50.2 60.1 — 16.7 19.8 39.7 50.2 60.1 — 16.7 19.8 39.7 50.2 60.1 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 — 16.7 19.8 39.7 50.2 60.1 — 16.7 19.8 39.7 50.2 60.1

74.9/ 74.9 74.9/ 74.9 77.6/ 84.0 119.3/132.1 146.4/163.4 166.2/156.2 80.9/ 80.9 80.9/ 80.9 82.4/ 88.2 124.1/136.3 151.2/167.6 171.0/160.4 79.3/ 79.3 79.3/ 79.3 82.3/ 88.8 124.0/136.9 151.1/168.2 170.9/160.9 85.3/ 85.3 85.3/ 85.3 87.1/ 93.0 128.8/141.1 155.9/172.4 175.7/165.1 35.1 37.5 41.4 66.2 79.3 76.7 37.8 39.6 43.5 68.3 81.4 78.8 37.7 40.3 44.3 69.1 82.1 79.6 40.4 42.4 46.4 71.2 84.2 81.7 82.5/ 82.5 82.5/ 82.5 82.3/ 88.8 124.0/136.9 151.1/168.2 170.9/160.9 88.5/ 88.5 88.5/ 88.5 87.1/ 93.0 128.8/141.1 155.9/172.4 175.7/165.1 39.3 40.3 44.3 69.1 82.1 79.6 42.0 42.4 46.4 71.2 84.2 81.7

LEGEND FLA HACR IFM LRA MCA MOCP NEC UL

— — — — — — — —

DISCONNECT SIZE* MOCP

FLA

LRA

80/ 80 80/ 80 90/ 90 125/150 150/175 175/175 90/ 90 90/ 90 90/100 125/150 175/175 175/175 90/ 90 90/ 90 90/100 125/150 175/175 175/200 90/ 90 90/ 90 100/100 150/150 175/175 200/200 — — — 70.0 80.0 90.0 — — — 70.0 90.0 90.0 — — — 70.0 90.0 90.0 — — — 80.0 90.0 90.0 90/ 90 90/ 90 90/100 125/150 175/175 175/200 100/100 100/100 100/100 150/150 175/175 200/200 — — — 70.0 90.0 90.0 — — — 80.0 90.0 90.0

81/ 81 81/ 81 81/ 82 114/126 139/155 157/176 87/ 87 87/ 87 87/ 87 120/131 145/160 163/181 86/ 86 86/ 86 86/ 87 119/131 144/160 162/181 92/ 92 92/ 92 92/ 92 125/136 150/165 168/186 38.0 38.0 40.0 63.0 75.0 86.0 40.0 40.0 42.0 65.0 77.0 89.0 41.0 41.0 43.0 66.0 78.0 89.0 43.0 43.0 45.0 68.0 80.0 92.0 89/ 89 89/ 89 89/ 89 119/131 144/160 162/181 95/ 95 95/ 95 95/ 95 125/136 150/165 168/186 43.0 43.0 43.0 66.0 78.0 89.0 45.0 45.0 45.0 68.0 80.0 92.0

465/465 465/465 465/465 465/465 465/465 465/465 469/469 469/469 469/469 469/469 469/469 469/469 488/488 488/488 488/488 488/488 488/488 488/488 493/493 493/493 493/493 493/493 493/493 493/493 233.0 234.0 234.0 234.0 234.0 234.0 235.0 236.0 236.0 236.0 236.0 236.0 245.0 245.0 245.0 245.0 245.0 245.0 247.0 247.0 247.0 247.0 247.0 247.0 550/550 550/550 550/550 550/550 550/550 550/550 555/555 555/555 555/555 555/555 555/555 555/555 260.0 260.0 260.0 260.0 260.0 260.0 262.0 262.0 262.0 262.0 262.0 262.0

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Underwriters’ Laboratories

Average Voltage = =

*Used to determine minimum disconnect per NEC. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. = 100 x

POWER SUPPLY FUSE OR HACR BKR — — — — — — — — — — — — — — — — — — — — — — — — 40.0 40.0 45.0 — — — 40.0 45.0 45.0 — — — 40.0 45.0 50.0 — — — 45.0 50.0 50.0 — — — — — — — — — — — — — — — 45.0 45.0 50.0 — — — 45.0 50.0 50.0 — — —

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

max voltage deviation from average voltage average voltage

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

67

Table 23 — Electric Heater Usage — COBRA™ Energy Recovery Units 50HJ008-014 with 62AQ200 UNIT 50HJ

VOLTAGE (60 Hz) 208/230/240 (3 phase)

008 460/480 (3 phase)

208/230/240 (3 phase) 009 460/480 (3 phase)

208/230/240 (3 phase) 012 460/480 (3 phase)

208/230/240 (3 phase) 014 460/480 (3 phase)

ACCESORY kW 7.8/ 9.6/10.4 12.0/14.7/16.0 18.6/22.8/24.8 24.0/29.4/32.0 31.8/39.0/42.4 12.8/13.9 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7 7.8/ 9.6/10.4 12.0/14.7/16.0 18.6/22.8/24.8 24.0/29.4/32.0 31.8/39.0/42.4 12.8/13.9 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7 7.8/ 9.6/10.4 12.0/14.7/16.0 24.0/29.4/32.0 31.8/38.9/42.4 37.5/46.0/50.0 12.8/13.9 15.2/16.5 30.4/33.0 38.4/41.7 46.0/50.0 7.8/ 9.6/10.4 12.0/14.7/16.0 24.0/29.4/32.0 31.8/38.9/42.4 37.5/46.0/50.0 12.8/13.9 15.2/16.5 30.4/33.0 38.4/41.7 46.0/50.0

ACCESSORY HEATER PART NUMBER CRHEATER---A00 017 010 011 012 012+017 016 013 014 015 014+016 017 010 011 012 012+017 016 013 014 015 014+016 017 010 012 012+017 010+012 016 013 015 014+016 013+015 017 010 012 012+017 010+012 016 013 015 014+016 013+015

ACCESSORY SINGLE POINT BOX PART NUMBER CRSINGLE---A00 007 007* 009 009 009 006 006 006† 008 010 012 012** 015 015 015 011 011 011†† 014 016 *** *** *** *** *** 011 011 014 014 016 *** *** *** *** *** 011 011 016 016 016

*009 on units with convenience outlet or high-static motor. †008 on high-static units with convenience outlet. **015 on units with convenience outlet or high-static motor. ††014 on high-static units with convenience outlet. ***Part of base unit. NOTES: 1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW vary accordingly. 2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kW new = Heater kW rated x (unit power distribution voltage / rated heater voltage) 2 As an example: For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kW new = 16 kW (215/240) 2 kW new = 12.8 kW (rating at 215 v)

68

Table 24 — Electrical Data (COBRA™ Energy Recovery Units 50HJ008-014 with 62AQ300) UNIT

NOMINAL V-PH-Hz

IFM TYPE

CONV OUTLET

62AQ FLA

STD

NO

29.8

STD

YES

29.8

HIGH STATIC

NO

29.8

HIGH STATIC

YES

29.8

STD

NO

15.8

STD

YES

15.8

HIGH STATIC

NO

15.8

HIGH STATIC

YES

15.8

STD

NO

29.8

STD

YES

29.8

HIGH STATIC

NO

29.8

HIGH STATIC

YES

29.8

STD

NO

15.8

STD

YES

15.8

HIGH STATIC

NO

15.8

HIGH STATIC

YES

15.8

208/230-3-60

50HJ008

460-3-60

208/230-3-60

50HJ009

460-3-60

HEAT FLA

MCA

—/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 —/— 21.7/ 25.0 33.4/ 38.5 51.7/ 59.7 66.7/ 77.0 88.4/102.0 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2 — 16.7 19.8 33.4 39.7 50.2

68.0/ 68.0 68.7/ 72.9 83.3/ 89.7 106.2/116.2 125.0/137.8 152.1/169.1 74.0/ 74.0 74.0/ 77.1 88.1/ 93.9 111.0/120.4 129.8/142.0 156.9/173.3 71.1/ 71.1 71.8/ 76.0 86.4/ 92.8 109.3/119.3 128.1/140.9 155.2/172.2 77.1/ 77.1 77.1/ 80.2 91.2/ 97.0 114.1/123.5 132.9/145.1 160.0/176.4 35.0 44.4 48.3 65.3 73.1 86.2 37.7 46.5 50.4 67.4 75.2 88.3 36.4 45.8 49.7 66.7 74.5 87.6 39.1 47.9 51.8 68.8 76.6 89.7 70.0/ 70.0 70.0/ 72.9 83.3/ 89.7 106.2/116.2 125.0/137.8 152.1/169.1 76.0/ 76.0 76.0/ 77.1 88.1/ 93.9 111.0/120.4 129.8/142.0 156.9/173.3 73.1/ 73.1 73.1/ 76.0 86.4/ 92.8 109.3/119.3 128.1/140.9 155.2/172.2 79.1/ 79.1 79.1/ 80.2 91.2/ 97.0 114.1/123.5 132.9/145.1 160.0/176.4 37.3 44.4 48.3 65.3 73.1 86.2 40.0 46.5 50.4 67.4 75.2 88.3 38.7 45.8 49.7 66.7 74.5 87.6 41.4 47.9 51.8 68.8 76.6 89.7

69

POWER SUPPLY FUSE OR HACR BKR 80/80 — — — — — 80/80 — — — — — 80/80 — — — — — 80/80 — — — — — 40.0 60.0 60.0 — — — 40.0 60.0 60.0 — — — 40.0 60.0 60.0 — — — 45.0 60.0 60.0 — — — 80/80 — — — — — 80/80 — — — — — 80/80 — — — — — 80/80 — — — — — 40.0 60.0 60.0 — — — 45.0 60.0 60.0 — — — 45.0 60.0 60.0 — — — 45.0 60.0 60.0 — — —

DISCONNECT SIZE* MOCP

FLA

LRA

— 90/ 90 100/100 125/125 150/150 175/175 — 90/ 90 100/110 125/125 150/150 175/175 — 90/ 90 100/110 125/125 150/150 175/175 — 90/100 110/110 125/150 150/150 175/200 — — — 80.0 90.0 100.0 — — — 80.0 90.0 100.0 — — — 80.0 90.0 100.0 — — — 80.0 90.0 100.0 — 90/ 90 100/100 125/125 150/150 175/175 — 90/ 90 100/110 125/125 150/150 175/175 — 90/ 90 100/110 125/125 150/150 175/175 — 90/100 110/110 125/150 150/150 175/200 — — — 80.0 90.0 100.0 — — — 80.0 90.0 100.0 — — — 80.0 90.0 100.0 — — — 80.0 90.0 100.0

75/ 75 75/ 75 81/ 87 102/112 120/131 145/160 80/ 80 80/ 80 87/ 92 108/116 125/136 150/165 78/ 78 78/ 78 85/ 91 106/115 123/135 148/164 84/ 84 84/ 84 90/ 96 111/120 129/140 154/169 38.0 41.0 45.0 61.0 68.0 80.0 41.0 44.0 47.0 63.0 70.0 82.0 40.0 43.0 47.0 62.0 69.0 81.0 43.0 45.0 49.0 65.0 72.0 84.0 77/ 77 77/ 77 81/ 87 102/112 120/131 145/160 82/ 82 82/ 82 87/ 92 108/116 125/136 150/165 80/ 80 80/ 80 85/ 91 106/115 123/135 148/164 86/ 86 86/ 86 90/ 96 111/120 129/140 154/169 41.0 41.0 45.0 61.0 68.0 80.0 43.0 44.0 47.0 63.0 70.0 82.0 42.0 43.0 47.0 62.0 69.0 81.0 45.0 45.0 49.0 65.0 72.0 84.0

420/420 420/420 420/420 420/420 420/420 420/420 425/425 425/425 425/425 425/425 425/425 425/425 445/445 445/445 445/445 445/445 445/445 445/445 449/449 449/449 449/449 449/449 449/449 449/449 211.0 211.0 211.0 211.0 211.0 211.0 213.0 213.0 213.0 213.0 213.0 213.0 223.0 224.0 224.0 224.0 224.0 224.0 225.0 226.0 226.0 226.0 226.0 226.0 454/454 454/454 454/454 454/454 454/454 454/454 459/459 459/459 459/459 459/459 459/459 459/459 479/479 479/479 479/479 479/479 479/479 479/479 483/483 483/483 483/483 483/483 483/483 483/483 233.0 233.0 233.0 233.0 233.0 233.0 235.0 235.0 235.0 235.0 235.0 235.0 245.0 246.0 246.0 246.0 246.0 246.0 247.0 248.0 248.0 248.0 248.0 248.0

Table 24 — Electrical Data (COBRA™ Energy Recovery Units 50HJ008-014 with 62AQ300) (cont) UNIT

NOMINAL V-PH-Hz

IFM TYPE

CONV OUTLET

62AQ FLA

STD

NO

29.8

STD

YES

29.8

HIGH STATIC

NO

29.8

HIGH STATIC

YES

29.8

STD

NO

15.8

STD

YES

15.8

HIGH STATIC

NO

15.8

HIGH STATIC

YES

15.8

STD

NO

29.8

STD

YES

29.8

STD

NO

15.8

STD

YES

15.8

208/230-3-60

50HJ012

460-3-60

208/230-3-60

50HJ014

460-3-60

HEAT FLA

MCA

—/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 —/— 21.7/ 25.0 33.4/3 8.5 66.7/ 77.0 88.4/102.0 104.2/120.3 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 — 16.7 19.8 33.4 50.2 60.1 — 16.7 19.8 33.4 50.2 60.1 — 16.7 19.8 33.4 50.2 60.1 — 16.7 19.8 33.4 50.2 60.1 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 —/— 21.7/ 25.0 33.4/ 38.5 66.7/ 77.0 88.4/102.0 104.2/120.3 — 16.7 19.8 16.7 50.2 60.1 — 16.7 19.8 16.7 50.2 60.1

82.8/ 82.8 82.8/ 82.8 86.4/ 92.8 128.1/140.9 155.2/172.2 175.0/165.0 88.8/ 88.8 88.8/ 88.8 91.2/ 97.0 132.9/145.1 160.0/176.4 179.8/169.2 87.2/ 87.2 87.2/ 87.2 90.8/ 97.2 132.5/145.3 159.6/176.6 179.4/169.4 93.2/ 93.2 93.2/ 93.2 95.6/101.4 137.3/149.5 164.4/180.8 184.2/173.6 40.7 45.8 49.7 66.7 87.6 85.0 43.4 47.9 51.8 68.8 89.7 87.1 43.3 48.4 52.3 69.3 90.2 87.6 46.0 50.5 54.4 71.4 92.3 89.7 90.4/ 90.4 90.4/ 90.4 90.8/ 97.2 132.5/145.3 159.6/176.6 179.4/169.4 96.4/ 96.4 96.4/ 96.4 95.6/101.4 137.3/149.5 164.4/180.8 184.2/173.6 44.9 48.4 52.3 48.4 90.2 87.6 47.6 50.5 54.4 50.5 92.3 89.7

LEGEND FLA HACR IFM LRA MCA MOCP NEC UL

— — — — — — — —

DISCONNECT SIZE* MOCP

FLA

LRA

90/ 90 90/ 90 100/110 150/150 175/175 175/200 100/100 100/100 110/110 150/150 175/200 200/200 100/100 100/100 100/110 150/150 175/200 200/200 100/100 100/100 110/110 150/150 175/200 200/200 — — — 80.0 100.0 110.0 — — — 80.0 100.0 110.0 — — — 80.0 100.0 110.0 — — — 90.0 100.0 110.0 100/100 100/100 100/110 150/150 175/200 200/200 100/100 100/100 110/110 150/150 175/200 200/200 — — — 70.0 100.0 110.0 — — — 70.0 100.0 110.0

90/ 90 90/ 90 90/ 91 123/135 148/164 166/185 96/ 96 96/ 96 96/ 96 129/140 154/169 172/190 95/ 95 95/ 95 95/ 96 128/140 153/169 171/190 101/101 101/101 101/101 134/145 159/174 177/195 44.0 44.0 47.0 62.0 81.0 93.0 47.0 47.0 49.0 65.0 84.0 95.0 47.0 47.0 50.0 65.0 84.0 96.0 50.0 50.0 52.0 68.0 87.0 98.0 98/ 98 98/ 98 98/ 98 128/140 153/169 171/190 104/104 104/104 104/104 134/145 159/174 177/195 49.0 49.0 50.0 49.0 84.0 96.0 51.0 51.0 52.0 51.0 87.0 98.0

519/519 519/519 519/519 519/519 519/519 519/519 523/523 523/523 523/523 523/523 523/523 523/523 542/542 542/542 542/542 542/542 542/542 542/542 547/547 547/547 547/547 547/547 547/547 547/547 260.0 261.0 261.0 261.0 261.0 261.0 262.0 263.0 263.0 263.0 263.0 263.0 272.0 272.0 272.0 272.0 272.0 272.0 274.0 274.0 274.0 274.0 274.0 274.0 604/604 604/604 604/604 604/604 604/604 604/604 609/609 609/609 609/609 609/609 609/609 609/609 287.0 287.0 287.0 287.0 287.0 287.0 289.0 289.0 289.0 289.0 289.0 289.0

Example: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v

Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Underwriters’ Laboratories

Average Voltage = =

*Used to determine minimum disconnect per NEC. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. = 100 x

POWER SUPPLY FUSE OR HACR BKR — — — — — — — — — — — — — — — — — — — — — — — — 45.0 60.0 60.0 — — — 45.0 60.0 60.0 — — — 50.0 60.0 60.0 — — — 50.0 60.0 60.0 — — — — — — — — — — — — — — — 50.0 60.0 60.0 — — — 50.0 60.0 60.0 — — —

452 + 464 + 455 3 1371 3

= 457 Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

max voltage deviation from average voltage average voltage

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

70

Table 25 — Electric Heater Usage — COBRA™ Energy Recovery Units 50HJ008-014 with 62AQ300 UNIT 50HJ

VOLTAGE (60 Hz) 208/230/240 (3 phase)

008 460/480 (3 phase)

208/230/240 (3 phase) 009 460/480 (3 phase)

208/230/240 (3 phase) 012 460/480 (3 phase)

208/230/240 (3 phase) 014 460/480 (3 phase)

ACCESORY kW 7.8/ 9.6/10.4 12.0/14.7/16.0 18.6/22.8/24.8 24.0/29.4/32.0 31.8/39.0/42.4 12.8/13.9 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7 7.8/ 9.6/10.4 12.0/14.7/16.0 18.6/22.8/24.8 24.0/29.4/32.0 31.8/39.0/42.4 12.8/13.9 15.2/16.5 25.6/27.8 30.4/33.0 38.4/41.7 7.8/ 9.6/10.4 12.0/14.7/16.0 24.0/29.4/32.0 31.8/38.9/42.4 37.5/46.0/50.0 12.8/13.9 15.2/16.5 30.4/33.0 38.4/41.7 46.0/50.0 7.8/ 9.6/10.4 12.0/14.7/16.0 24.0/29.4/32.0 31.8/38.9/42.4 37.5/46.0/50.0 12.8/13.9 15.2/16.5 30.4/33.0 38.4/41.7 46.0/50.0

ACCESSORY HEATER PART NUMBER CRHEATER---A00 017 010 011 012 012+017 016 013 014 015 014+016 017 010 011 012 012+017 016 013 014 015 014+016 017 010 012 012+017 010+012 016 013 015 014+016 013+015 017 010 012 012+017 010+012 016 013 015 014+016 013+015

ACCESSORY SINGLE POINT BOX PART NUMBER CRSINGLE---A00 007 007* 009 009 009 006 006 008 008 010 012 012† 015 015 015 011 011 014 014 016 ** ** ** ** ** 011 011 014 014 016 ** ** ** ** ** 014 011 014 016 016

*009 on units with convenience outlet or high-static motor. †015 on units with convenience outlet or high-static motor. **Single point box is part of base unit. NOTES: 1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW vary accordingly. 2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kW new = Heater kW rated x (unit power distribution voltage / rated heater voltage) 2 As an example: For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kW new = 16 kW (215/240) 2 kW new = 12.8 kW (rating at 215 v)

71

ALL SINGLE MODULE HEAT OPTIONS

HEAT PUMP UNITS — 2-MODULE HEAT OPTIONS

ELECTRIC COOLING UNITS — 2-MODULE HEAT OPTIONS

Fig. 29 — Control Wiring

Copyright 2003 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 111 Catalog No. 535-00028 Printed in U.S.A. Form 50-8SI Pg 72 3-03 Replaces: 50-4SI Book 1 1 4 4 Tab 1b 5a 5a 6b

Related Documents