Cable Support Systems

Cable Trays and Integrated Ceilings

06

Index

Cable trays & accessories Bends, Junctions, Risers Adjustable bend W10/40 Adjustable bend W10/60 90° Bend W10/40 90° Bend W10/60 90° Bend W10F/40 90° Bend W4 T-joint W9/40 T-joint W9/60 T-joint W29/40 T-joint W29/60 T-junction W12/40 T-junction W12/60 T-junction W12F/40 X-junction W13/40 X-junction W13/60 X-junction W13F/40 Vertical riser W11/40 Vertical riser W11/60 Vertical riser W4, interior Vertical riser W4, exterior

page

Reducers Reducer W28/40 Reducer W28/60 Reducing piece W14/40 left Reducing piece W14/40 left Hdg Reducing piece W14/40 right Reducing piece W14/40 right Hdg Reducing piece W14/60 left Reducing piece W14/60 right Reducing piece W15/40 straight Reducing piece W15/40 straight Hdg Reducing piece W15/60 straight Brackets Angle bracket W8 Angle bracket W8S Bracket 60/40 Combi bracket 53 Cover clamp W62 End bracket WN17 Luminaire bracket W25/40 Luminaire bracket W25/60 Luminaire bracket W35 Luminaire bracket W50 Luminaire bracket W55 Luminaire bracket W56 Pendant attachment W21 Pendant bar 1 Pendant bracket W80, W81 Tube pendant attachment W73 Wall bracket 80 Cable trays Cable tray W1/40 Pre-galv Cable tray W1/60 Pre-galv Cable tray W3/40 Hdg Cable tray W3/40 Pre-galv Cable tray W3/60 Pre-galv Ceiling mesh tray WN2 Fixing tray N for casting-in Installation tray W4 Lighting trunking W70 Lighting trunking W71

30 54 32 56 33 77 27 52 28 53 34 57 35 36 58 37 31 55 78 79

26 51 38 39 40 41 59 60 42 43 61

105 106 94 116 115 104 45 65 71 118 72 72 86 95 71 87 83

18 46 21 20 47 108 107 75 68 69

page Cantilever arms Adjustable cantilever arm W1840 23 Adjustable cantilever arm W1860 48 Cantilever arm 50L, 50 80-81 Cantilever arm 80 82 Internal cantilever arm W17/40 22 Cantilever arms – accessories Back plate W30 83 Mounting rail 40 84 Wall bracket 80 83 Ceiling brackets Ceiling attachment W31 98 Ceiling bracket 5 93 Ceiling bracket 7 88 Ceiling bracket WN16 109 Clamps Cover clamp W62 115 Earth clamp W79 109 Locking clamp W77 98 Covers Cover plate W16 110 Cover strip W47/60 66 Cover W5 114 End cover W45/40 29 End cover W45/60 62 Dividers Dividing strip 39 111 Dividing strip 39/55 64 Insert piece W39 112 Insert piece W39/55 65 Strip fixing W44 117 Support band W6 64 and 112 End plugs End plug 28C,D,E and F 92 End plug 7 90 Protection strip W48 117 Fixings Adapter TLF-A12 137 Angled bracket TLF-F12 137 Bitro adapter 131 Bits holder 132 Concrete screws 125-129 Expansion bolts 122 Expansion nail 130 Express hanger SVH 138 Eye screw 130 Fixing strips 140 Hammer drill SDS plus 133 Hammer tool TLF-S 136 Light concrete screw 130 Low density anchor TLF 135 Magnetic socket for Concrete screw 131 Mounting tool for Eye screw 130 Mounting tool SVH-T 139 Securing spring SVH-L 139 Sleeve TLF-H12 136 Socket for Concrete screw 131 Square peg 132

Fixings Torxbits Installation summeries Cable trays Installation tray W4 Suspension components Joints Joint W2 Side joint W49/40 Side joint W49/60 Junction box plates Junction box plate W24/40 Junction box plate W24/60

page 132

14-15 74 16-17

76 26 51

44 63

Lashing wires Lashing wire 108 Mesh trays Wibe Defem system. See sep. brochure Mounting rails Mounting rail 40 Mounting rail WMS25 Ogebe fixings Fixings Ogebe Ogebe fixing type E Ogebe fixing type D Ogebe fixing type ED Ogebe fixing type Eg Paint Anti-corrosive paint “Galvafroid” Repair paint

84 84

141 142 143 144 145

Support brackets Support bracket W1940 Support bracket W1960 Support bracket W20 Support bracket W20A Support bracket/joint W7/40 Support bracket/joint W7/60 Surface treatment Corrosion classes Current load of cables Environment/Quality Potential balancing Product certificates Surface treatments

Wibe reserve the right to make changes to manufacture and design without prior notice.

25 49 70 70 24 50

7 9 9 12 10-11 8

Tele-conduits Tele-conduit 36 with knock-out holes 113 Integrated ceilings & accessories Integrated ceilings 146 Acoustic lamina 147 Installation summaries Ceilings in corridor Ceilings with sound baffles Ceilings with wire baskets Open ceilings Sound baffles Wire baskets W-swing in corridor

151 149 150 148 152 153 159

Sound baffles Sound baffles - accessories

155-158

W-swing ceilings Angle strip W46 Integrated channel W27/40 Pendant/Fixing rails, Vertical pieces Integrated channel W27/60 Fixing rail 24/26x53 for casting-in 99 Profile W-swing 1/40 Pendant/Fixing rail 24/34 91 Profile W-swing 1/60 Pendant/Fixing rail 7L,7 88 Profile W-swing 2 Pendant rail W32 97 Profile W-swing 3 Pendant strip W33 96 Profile W-swing 4A Threaded rod M10 W76 85 Profile W-swing 5 Vertical piece 2 101 Shade ledge W26/40 Vertical piece 2F 102 Shade ledge W26/60 Vertical piece 2FPK 100 Wall bracket W-swing 2 Vertical piece 20 103 Wall tray W60/40 Vertical piece 7L, 7 89 Wall tray W60/60 Installation examples Screw sets Expansion bolts 122-123 Installation examples Locking plug W41 120 Mounting set W78 119 Screw set 22S 119 Screw set W34 120 Screw set W36 119 Screw set W36C 119 Screw set W37 120 Screw set W38P 120 Screw W40 120 Spring nut M8 119 T-bolt 26F 121 118 118

page

167 166 167 160 160 161 163 164 165 165 166 162 168 168

169

Cable trays Cable trays - view

4

Corrosion classes, Surface treatments, Current load of cables

7

Environmental policy and certification, Product certificates, Potential balancing

9

Cable trays – installation summary

14

Suspension components – installation summary

16

Cable tray system W1/40, W3/40

18

Cable tray system W1/60, W3/60

46

Lighting trunking system W70, W71

67

Installation tray system W4

73

Suspension components, common parts Cantilever arms, Wall bracket, Back plate, Mounting rail

80

Threaded rod, Pendant attachments, Pendant/Fixing rails, Brackets

85

Pendant rails, Ceiling attachment, Vertical pieces

96

End bracket, Angle brackets, Fixing tray N

104

Ceiling mesh tray, Earth clamp, Cover plate, Dividing strip

108

Tele-conduit, Cover W5, Components

113

Screw sets,T-bolt, Expander bolts

119

Fixing system

124

Ogebe fixings

141

Integrated ceilings

146

Installation examples

169

1

Wibe in Mora, Sweden

There is always a next time. Usually it’s a matter of a few extras, sometimes more radical changes. New and old have to fit together regardless. Hand in glove – even in 15 years’ time. We delivered our first – and the world’s first – cable ladder just over 75 years ago. And we can still supply additions to it if necessary. We carry over 10,000 items in our range. Just over a hundred are ladders and trays. The remainder consists of components to meet every possible requirement. And some pretty impossible ones too. So don’t just think about this time, think about the next time. We are the biggest supplier on the market. More concretely, we provide cable ladders and cable trays, lighting trunking and installation rails, steel wire systems, integrated ceilings – and Defem® mesh trays. We hot dip galvanize in one of the most modern plants in Scandinavia and do powder coating in one that is just as technologically advanced. Wibe is the market leader in telescopic masts and masts for lighting and communication. We have experience from thousands of projects, from planning, to fitting and erection, to commissioning and service.

Wibe is part of the worldwide Schneider Electric group, which also includes leading brands such as Eljo, Lexel, Merlin Gerin, Telemecanique and Thorsman.

2

3

Cable trays - view Cable tray W1

Height Length Width

Pre-galvanized Hot dip galvanized Powder coated white Electro-galvanized Stainless steel AISI 316

4

Cable tray W3/40

40 and 60 mm 2000 and 3000 mm 70-600 mm

Height Length Width

Pre-galvanized Hot dip galvanized Powder coated white Electro-galvanized Stainless steel AISI 316

40 mm 3000 mm 50-600 mm

Cable trays - view Cable tray W3/60

Height Length Width

Pre-galvanized Hot dip galvanized Powder coated white Electro-galvanized Stainless steel AISI 316

Installation tray W4

60 mm 3000 mm 50-600 mm

Height Length Width

15 mm 3000 mm 50-400 mm

Pre-galvanized Hot dip galvanized Powder coated white Electro-galvanized Stainless steel AISI 316

5

Cable trays - view Lighting trunking W70, W71

Mesh trays

Wibe Defem system - see separate brochure

Height Length Width

Pre-galvanized Hot dip galvanized Powder coated white Electro-galvanized Stainless steel AISI 316

6

22 and 40 mm 3000 and 6000 mm 40-200 mm

Corrosion classes The life expectancy of a cable support system is dependent on the environment in which it is placed. Therefore, it is important to establish the corrosive properties of an environment to ensure that the right treatment and the right material are chosen. To achieve this, several corrosion classes have been drawn up in accordance with BSK99.

The table below shows various corrosion classes. As a guide, we have included the surface treatment recommended by Wibe for the different classes. On the next page, we briefly outline the various surface treatments and materials.

As regards environmental corrosion, a steel design component can usually be assigned to one of the corrosion classes (C1-C5-M) as shown in table 1:23a. Reference values for the average level of corrosion in steel and zinc are given in table 1:23c. The corrosion classes comply with those stipulated in SS-EN ISO 12944-2. Table 1:23a Corrosion classes as stipulated by SS-EN ISO 12944-2 with atmospheric corrosion levels and examples of the environment in which they are most suitable for use.

7

Surface treatments Electro-galvanized Some of Wibe’s products are electro-galvanized in accordance with ISO 2081. Such products are intended for use only in warm, dry areas with negligible pollutant levels. Pre-galvanized Products are manufactured from Z 275 pre-galvanized sheet steel in accordance with SS-EN 10142. Surface sections created during cutting and drilling will, under normal conditions, repair themselves, providing the plant with superb anti-corrosion protection. Hot dip galvanized Wibe has one of the most modern hot dip galvanization plants in the Nordic countries. The hot dip process is continuous, guaranteeing a high and even quality. Once manufactured products are hot dip galvanized in accordance with SS-EN ISO 1461 whilst nuts and bolts are hot dip galvanized in accordance with SS-EN ISO 10684:2004. This form of galvanization affords very good value-for-money anti-corrosion protection in atmospheres with a pH value of between 6 and 13. However, in acidic environments where pH levels fall below 6 and in alkaline environments where the pH value exceeds 13, the protective zinc layer breaks down relatively quickly.

Rate of dissolution

The rate of dissolution is determined by the pH value of pure zinc in distilled oxygenated water that has been pH adjusted to various levels using HCl or NaOH. NB The curve only applies to conditions shown, and gives only an indication of the propensity for corrosion without consideration to time. Zinkpox® The Zinkpox® method involves the coating of the zinc layer with a homogenous covering of epoxy/polyester. Epoxy/polyester is a plastic paint that displays the greatest resistance to most chemicals. The layer of zinc on the steel prevents the formation of underfilm corrosion, which is a contributing factor in paint degradation. The paint layer is only affected by atmospheric erosion. The zinc layer only deteriorates once the paint has been eroded, and this gives you considerable breathing room before the steel is subject to attack. By using this treatment process, the life expectancy of the product is more than double that had it only been treated using hot dip galvanization. In addition to providing excellent anti-corrosion protection, Zinkpox® also allows freedom of choice as regards product colour. Powder coating is an extremely environmentally friendly finishing method. The pigment contains no solvents and has, to a great extent, replaced wet finishes. In the case of visible cable tray installations, both trays and accessories can be painted in colours matching the décor of their surroundings.

8

Modern painting plant produces perfect results Carefully and thoroughly pre-treating of galvanized products is the cornerstone of achieving perfect adhesion. We employ a nine-stage process, consisting of alkaline degreasing, rinsing, rinsing, activation, zinc-manganese phosphatising, rinsing, rinsing, passivation and rinsing with de-ionised water. Immediately after the pre-treatment process, products are dried in a tunnel oven and are then powder coated by an electronically controlled robot, guaranteeing that all components are treated perfectly. Finally, the coating is cured in a 24-section tunnel oven, the temperature in each section being regulated in a stepless manner, producing a perfect hardening curve. At no stage in the process does a human hand touch any of the products. Instead, they are moved between the various stages using a 355-metre long electronically controlled conveyor belt. A perfect result! The surface is now resistant to both scratches and impact. Colour schemes As standard, cable trays, lighting trunking, mounting fittings and accessories are painted white RAL9003 Gloss 30. Other colours of your choice can also be offered. If the powder-coated surface is broken, e.g. when cutting during mounting, repair paint for minor damages can be supplied. Quality - Epoxy/polyester (very high chemical tolerance) Zinc Epoxy/polyester................(min 70 µm) Lustre (ISO 2813)..............30 Finish (ISO 1519)...............6 mm Cross hatch (ISO 2409) Erichsen test (ISO 1520)....8 mm Stainless steel Wibe stainless steel products, manufactured in accordance with SS 2333 AISI 304, or in accordance with SS 2348 AISI 316L are designed for use in highly aggressive environments, either indoors or outdoors, on industrial sites where there are high levels of potent airborne pollution such as in certain chemical industries, celluloserelated industries, refineries or artificial fertiliser factories, high humidity tunnels, etc. Stainless steel products are also ideal for use in environments where special hygiene requirements are in force, such as dairies, abattoirs, other food industries and pharmaceuticals factories. Stainless steel AISI 304 or AISI 316L? The deciding factor in choosing between stainless steel AISI 304 or AISI 316L is the aggressiveness of the environment in which it is to be used, and for this atmospheric chlorine content plays a significant role. Environments with a high chlorine content - coastal areas being a prime example - are aggressive and usually require the use of AISI 316L materials. When assessing the needs of factories, consideration should be given to the materials previously used to suspend equipment such as pipe tubing, and from this determine whether stainless steel AISI 304 or AISI 316L material is required.

Current load of cables Installation instructions Installation The ladders and trays shall be installed in such a way that, as often as possible the cables can be laid directly in place rather than being pulled through. Ladders and trays for current carrying cables along the ceiling shall be installed in such a way that the distance from the top of the ladder or tray to the ceiling shall not be less than 300 mm. The free vertical distance between parallel ladders and trays shall be at least 200 mm. Ladders and trays near walls shall be installed with a minimum free distance of 50 mm to the wall, so that cables can pass between the ladders and the wall. Ladders and trays along partition walls shall be installed with minimum free distance of 100 mm to the wall. Sharp edges and screw ends on ladders or trays should be removed before the cables can be installed. Expansion bolts for the installation of brackets/fixings shall be installed with such a distance between them, that the designated load for ladders and trays will not be exceeded. When selecting the distance between cantilever arms or brackets/fixings, the bearing strength and designated load of the ladders and trays must be taken into consideration.

Reinforced heavy duty cable ladders Ladders shall be designed for a uniform load of at least 600 N per 1000 mm ladder length with a distance of 6000 mm between brackets/fixings. They shall also be able to carry an occasional point load as to the heavy duty ladders. Heavy duty cable ladders, cable trays Ladders and trays shall be designed for a uniform load of at least 200 N per 1000 mm ladder length and 100 mm width with a distance of 2000 mm between brackets/fixings. They shall also be able to carry an occasional point load of 1000 N with a double safety factor measured between supporting points 3 and 4 when using an installation with six supporting points. Light duty cable ladders, cable trays Ladders and trays shall be designed for a uniform load of at least 100 N per 1000 mm ladder length and 100 mm width with a distance of 2000 mm between brackets/fixings.

Environmental policy and certification Environmental product declarations are available for all Wibe products. These can be ordered direct from Wibe. Declarations may also be downloaded from the Wibe website at www.wibe.com Our product sheets and brochures are marked successively with the name of the environmental document (WEF-0001-). Environmental policy AB Wibe shall actively strive to minimise any negative impact its operations may have on the environment. Besides working in a way that prevents pollution, we shall also ensure that, given Wibe’s production and quality requirements, the most environment-friendly solutions are always chosen. All of this shall be within a framework of continual improvement. Our environmental initiatives shall go beyond what is required by legislation. In its work for the environment, Wibe shall maintain suitable dialogues and collaborations with all interested parties. The environmental policy shall always be available to the public. The company’s environmental reviews shall be the base on which our environmental goals and programmes are founded. We shall achieve the above by:

Management system - Quality and Environment Wibe has a third-party certified management system for quality and environment in accordance with ISO 9001:2000 and ISO 14001:2004 CE-marking of products is placed on the product or on the packing according to "Declaration of Conformity" (D o C), applicable to Wibe Cable ladders, Cable trays and Lighting trunkings. EMC directive 89/336 EEC Above mentioned products are neutral according to the EMC directive 89/336 EEC. Low voltage directive 73/23 EEC According to the low voltage directive we refer to: SFS 1993:1068 Regulations concerning electrical material. SFS 1993:1068 General obligations regarding electrical material. Wibe fulfils the demands according to the harmonized standard SS-EN 6153 Edition 1:2002.

• Ensuring that, throughout manufacture and design, full attention is paid to ecological considerations, quality requirements, health factors and environmental sustainability • Setting up environment-focused collaborations with suppliers and customers • Giving training on our environmental initiatives and promoting staff involvement • Maximising efficiency in the use of energy and raw materials • Minimising the production of waste that cannot be recycled within our operations • Ensuring that chemicals and dangerous waste are handled in the best possible manner • Continuously evaluating the success of our initiatives

9

Product certificates

10

Product certificates

11

Potential balancing Resistance testing of Wibe cable trays has been performed by the Swedish National Testing & Research Institute in Borås and Wibe test laboratory.

12

The tests have been carried out according to SS-EN 61537, IEC 61537 and EL-AMA SBD 2.

Potential balancing

13

Installation summary Potential balancing

4 64

35 33

61

53

35 21 51 49 32 55 31

44

17

2

1 50

51 52 21

63 62 18,19

2

16

62

36

39

5

60

37 22

3

25

20

22

30 29

26

28

14

42 41 7

25

59

40 28

47

23,24

9

45

32

14

Potential balancing Components

54 46

34 5 56 45

7 11

12 8

43

13

48

46 6 45 1 15

38 7 10 58

57

14

27

27

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

3 61 62 63 64

Cable tray W1/40 Cable tray W3/40 Cable tray system W1/60, W3/60 Mesh trays – Wibe Defem system Installation tray W4 (system) Internal cantilever arm W17/40 Adjustable cantilever arm W1840 Support bracket/joint W7/40 Support bracket W1940 Side joint W49/40 T-joint W9/40 T-joint W29/40 End cover W45/40 Adjustable bend W10/40 Vertical riser W11/40 90° bend W10/40 T-junction W12/40 X-junction W13/40 Reducing piece W14/40 left Reducing piece W14/40 right Reducing piece W15/40 straight Junction box plate W24/40 Luminaire bracket W25/40 Lighting trunking W70 Lighting trunking W71 Support bracket W20 Support bracket W20A Pendant brackets W80 and W81 Luminaire bracket W35 Luminaire bracket W55 Luminaire bracket W56 Cantilever arm 50 Cantilever arm 80 Wall bracket 80 Back plate W30 Mounting rail WMS25 Threaded rod M8 W76 Threaded rod M10 W76 Pendant attachment W21 Tube pendant attachment W73 Pendant/Fixing rail 7L, 7 Ceiling bracket 7 Vertical piece 7L, 7 Pendant bar 1 Pendant strip W33 Pendant rail W32 Ceiling attachment W31 Locking clamp W77 Vertical piece 2F Angle bracket W8 Fixing tray N for casting-in Earth clamp W79 Cover plate W16 Dividing strip 39 Insert piece W39 Support band W6 Tele-conduit 36 Cover W5 Cover clamp W62 Strip fixing W44 Luminaire bracket W50 Screw sets Fixing system Fixings - Ogebe Integrated ceilings Sound baffles and accessories Profile W-swing Wall tray W60/40 and W60/60

1Page 18 20-21 46-66 73-79 22 23 24 25 26 27 28 29 30 31 32-33 34-35 36-37 38-39 40-41 42-43 44 45 68 69 70 70 71 71 72 72 80 82 83 83 84 85 85 86 87 88 88 89-90 95 96 97 98 98 102 105 107 109 110 111 112 112 113 114 115 117 118 119-123 124-140 141-145 146-168 155-158 160-167 168

15

Common balancing parts, suspension components Potential

31 20 20

38

20 20 20

30 18

18

18

18

18

13

12

33 26

11 9 10

8

28

32 25 31 20 31 20

20

29

18

18

18

30

25

30 20

19

36

35

19 20

14

3, (7)

4, (6)

16

Potential balancing

34 22 23 27 38

25

21

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

Components

1Page

Internal cantilever arm W17/40 Adjustable cantilever arm W1840 Support bracket/joint W7/40 Support bracket W1940 Adjustable cantilever arm W1860 Support bracket W1960 Support bracket/joint W7/60 Support bracket W20-70 Support bracket W20-100 Support bracket W20A-70 Support bracket W20A-100 Pendant bracket W80 Pendant bracket W81 Cantilever arm 50 Cantilever arm 80 Wall bracket 80 Back plate W30 Threaded rod W76 Pendant attachment W21 Tube pendant attachment W73 Pendant/Fixing rail 7L,7 Ceiling bracket 7 Vertical piece 7L, 7 End plug 7 Pendant/Fixing rail 24/34 Ceiling bracket 5 Bracket 60/40 Pendant bar 1 Pendant strip W33 Pendant rail W32 Ceiling attachment W31 Vertical piece 2 Vertical piece 2F Vertical piece 20 Angle bracket W8 Angle bracket W8S Screw sets Fixing system

22 23 24 25 48 49 50 70 70 70 70 71 71 80 82 83 83 85 86 87 88 88 89-90 90 91 93 94 95 96 97 98 101 102 103 105 106 119-123 124-140

16 17 24

15 2, (5) 1

17

Potential Cable traybalancing W1/40, unperforated WEF-0001 Side height 40 mm, length 2000 and 3000 mm. Secondary trays 1300-1800 mm. Holes Ø5,8 mm at the tray ends can be used for locking of joints.

A mm

L mm

Cable tray W1/40-70 70 2000 Cable tray W1/40-100 100 2000 Cable tray W1/40-200 200 2000 Cable tray W1/40-300 300 2000 Cable tray W1/40-400 400 2000 Cable tray W1/40-500 500 2000 Cable tray W1/40-600 600 2000 Cable tray W1/40-500 FS 500 2000 Cable tray W1/40-600 FS 600 2000 Secondary W1/40-200 200 1300 Secondary W1/40-200 200 1600 Secondary W1/40-200 200 1800 Cable tray W1/40-70 70 3000 Cable tray W1/40-100 100 3000 Cable tray W1/40-200 200 3000 Cable tray W1/40-300 300 3000 Cable tray W1/40-400 400 3000 Cable tray W1/40-500 500 3000 Cable tray W1/40-600 600 3000 *EAN-code=732167+Part.no+C (control figure)

Plate thickness mm

Pre-galv. Part.No. C*

Pre-galv. White30 Part.No. C*

Weight kg 100 m

0.7 0.7 0.7 1.25 1.25 1.5 1.5 1.5 1.5 0.7 0.7 0.7 0.7 0.7 0.7 1.25 1.25 1.5 1.5

713251 5 713252 2 713254 6 713256 0 713257 7 713258 4 723219 2 786831 5 786832 2

728986 8 728987 5 728988 2 728989 9 728990 5 728991 2 728992 9 786833 9 786834 6 737504 2 737505 9 737506 6 781334 6 781335 3 781336 0 781337 7 781338 4 781339 1 781340 7

95 115 170 400 500 710 825 715 830 170 170 170 95 115 170 400 500 710 825

Use and installation

Cable tray W1/40 is joined with 2 Side joints W49/40 or Support bracket/joint W7/40.

18

For trays 300 mm and wider we recommend to use Support bracket/joint W7/40.

720822 7 720984 2 720985 9 726664 7 726665 4 726666 1 726667 8

Cable tray W1/40, unperforated WEF-0001

Loadings In order to calculate the total deflection in the middle of the tray: add up transversal deflection + longitudinal deflection + deflection of unloaded tray. Transversal deflection

Deflection of unloaded tray Tray, length 2 m Transversal deflection at 0 kg Longitudinal deflection at 0 kg

Longitudinal deflection

W1/40-100-200 0 mm 5 mm

W1/40-300-400 3 mm 5 mm

W1/40-500-600 5 mm 6 mm

19

Cable tray W3/40, perforated WEF-0001 Pre-galvanized Side height 40 mm, length 3000 mm. Holes Ø5.8 at the tray ends can be used for locking of joints. Oval holes along the tray sides can be used for mounting of accessories.

A mm

Cable tray W3/40-50 50 Cable tray W3/40-70 70 Cable tray W3/40-100 100 Cable tray W3/40-150 150 Cable tray W3/40-200 200 Cable tray W3/40-300 300 Cable tray W3/40-400 400 Cable tray W3/40-500 500 Cable tray W3/40-600 600 *EAN-code=732167+Part.no+C (control figure)

L mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 m

3000 3000 3000 3000 3000 3000 3000 3000 3000

1.0 1.0 1.0 1.0 1.0 1.25 1.25 1.5 1.5

735388 0 735389 7 735390 3 735391 0 735392 7 735393 4 735394 1 735395 8 735396 5

737537 0 737538 7 737539 4 737540 0 737541 7 737542 4 737543 1 737544 8 737545 5

103 120 136 170 196 316 390 590 683

Use and installation

Cable tray W3/40 is joined with 2 Side joints W49/40 or Support bracket/joint W7/40.

20

For trays 300 mm and wider we recommend to use Support bracket/joint W7/40.

Cable tray W3/40, perforated WEF-0001 Hot dip galvanized Side height 40 mm, length 3000 mm. Holes Ø5.8 at the tray ends can be used for locking of joints. Oval holes along the tray sides can be used for mounting of accessories.

A mm

Cable tray W3/40-50 50 Cable tray W3/40-70 70 Cable tray W3/40-100 100 Cable tray W3/40-150 150 Cable tray W3/40-200 200 Cable tray W3/40-300 300 Cable tray W3/40-400 400 Cable tray W3/40-500 500 Cable tray W3/40-600 600 *EAN-code=732167+Part.no+C (control figure)

L mm

Plate thickness mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part.No. C*

Weight kg 100 m

3000 3000 3000 3000 3000 3000 3000 3000 3000

1.0 1.0 1.0 1.0 1.0 1.25 1.25 1.5 1.5

735400 9 735401 6 735402 3 735403 0 735404 7 735405 4 735406 1 735407 8 735408 5

735412 2 735413 9 735414 6 735415 3 735416 0 735417 7 735418 4 735419 1 735420 7

110 120 156 170 220 350 453 620 723

Use and installation

Cable tray W3/40 is joined with 2 Side joints W49/40 or Support bracket/joint W7/40.

For trays 300 mm and wider we recommend to use Support bracket/joint W7/40

21

Internal cantilever arm W17/40 WEF-0001 For mounting inside Cable trays W1/40 and W3/40.

Internal cantilever arm

A mm

B mm

C mm

D mm

W17/40-100 89 140 70 55 W17/40-200 189 140 70 55 W17/40-300 289 165 95 75 W17/40-400 389 165 95 75 *EAN-code=732167+Part.no+C (control figure)

E mm

Pre-galv. Part. No. C*

Hot dip Galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

42 42 55 55

716911 5 716912 2 716913 9 716914 6

734572 4 734573 1 734574 8 734575 5

729029 1 729030 7 729031 4 729032 1

783066 4 783067 1 783068 8 783069 5

16 35 80 100

Loading table for Internal cantilever arm W17/40 on wall

F

Mounted onto wall with Expansion bolt. Breaking load for cantilever arm mounted onto wall, see below. Type of cantilever arm

W17/40-100 W17/40-200 W17/40-300 W17/40-400

Max load F at 3˚ deflection of cantilever arm kN kg

1.0 0.8 1.1 1.0

100 80 110 100

Deflection in mm at 3˚ deflection of cantilever arm

5.2 10.5 15.7 20.9

Breaking load kN

kg

3.0 2.0 3.0 2.0

300 200 300 200

Use and installation

Internal cantilever arm W17/40 is mounted on Vertical piece 2F using a T-bolt.

22

When mounting an Internal cantilever arm W17/40 on a porous wall or when surface pressure must be reduced use Mounting rail 40.

The Internal cantilever arm is mounted onto the wall with an Expansion bolt alt. a Concrete screw.

Internal cantilever arm W17/40 can be mounted right over support bracket/joint.

Adjustable cantilever arm W1840 For installation inside Cable trays W1/40 and W3/40.

Adjustable cantilever arm

A mm

B mm

C mm

D mm

W1840-100 88 160 70 0-25 W1840-200 188 160 70 0-50 W1840-300 289 185 95 0-50 W1840-400 389 185 95 0-50 W1840-500 489 185 95 0-50 W1840-600 589 185 95 0-50 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

718360 9 718361 6 783587 4 783588 1 783589 8 783590 4

734578 6 734579 3 734580 9 734581 6 734582 3 734583 0

729033 8 729034 5 783591 1 783592 8 783593 5 783594 2

783018 3 783019 0 783020 6 783021 3 783022 0 783023 7

36 47 120 139 156 175

Loading table for cantilever arm W1840 on wall

Mounted onto wall with Expansion bolt. Breaking load for cantilever arm mounted onto wall - see below. Type of cantilever arm

Max load F at 3˚ deflection of cantilever arm kN kg

W1840-100 W1840-200 W1840-300 W1840-400 W1840-500 W1840-600

1.0 0.8 1.1 1.0 0.65 0.5

100 80 110 100 65 50

Deflection in mm at 3˚ deflection of cantilever arm

5.2 10.5 15.7 20.9 26 31.5

Breaking load kN

kg

3.0 2.0 3.0 2.0 1.3 1.0

300 200 300 200 130 100

Use and installation

Mounting directly onto wall. At this type of installation the adjusting allowance of the tray is limited. Breaking load - see table above.

Mounting on Vertical piece 2F using T-bolt. The Cantilever arm W1840 can be adjusted to a max. of 50 mm.

Mounting of two adjustable cantilever arms on the same Vertical piece 2F. (Tray widths more than 400 mm). Use Screw set 20S if the two trays have the same width. At different tray widths T -bolt and Screw set W37 must be used.

When mounting cable trays width 500-600 mm - it might be necessary with a reinforcement of the cantilever arm. Installation band and stretching screw can be used for mounting in ceiling or on a vertical piece.

23

Support bracket/joint W7/40 Used as a support bracket or joint for Cable tray W1/40 and W3/40 and for Lighting trunking W70/W71. When joining Cable tray W1/40 FS (reinforced), Side joint W49/40 must be used.

W7/40-70,100,200,300,400

WEF-0001

W7/40-50,150,500,600

W7/40-40 Support bracket/ joint

A mm

B mm

Plate thickness mm

W7/40-40 36 180 W7/40-50 48 200 W7/40-70 68 200 W7/40-100 98 200 W7/40-150 148 200 W7/40-200 198 200 W7/40-300 297 300 W7/40-400 397 300 W7/40-500 498 300 W7/40-600 598 300 *EAN-code=732167+Part.no+C (control figure)

1.5 1.0 1.0 1.0 1.0 1.0 1.25 1.25 1.25 1.25

Pre-galv Part. No. C*

Hot dip galv. Part. No. C*

718480 4 734554 0 720825 8 717021 0 734555 7 717022 7 717023 4 717024 1 720990 3 723180 5

734556 4 734557 1 734558 8 734559 5 734560 1 734561 8 734562 5 734563 2 734564 9

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

783080 0 783081 7 783082 4 783083 1 783084 8 783085 5 783086 2 783087 9 783088 6

12 14 16 25 35 43 110 140 170 200

729053 6 729046 8 729047 5 729048 2 729049 9 729050 5 729051 2 729052 9

Use and installation

Support bracket/joint W7/40 is used for straight joining. Push-in mounting.

If necessary trays and lighting trunkings are locked using Screw set W38P or Locking plug W41. The Joint W7/40-40 is locked with Screw set W36/W36C at the bottom of the trunking.

With Pendant attachment W21 installed on Support bracket/joint W7/40-100, 200, 300 or 400 a complete support bracket is obtained.

W7/40-50, 150, 500 and 600 are only used for joining, not as support brackets. Reinforced tray is to be joined with Side joint W49/40.

End bracket WN17 can be used as vertical piece on Support bracket/joint W7/40 mounted with Screw set W36/W36C.

Support bracket/joint W7/40 is used to achieve an invisible suspension in or in connection with bends or junctions, here with End bracket WN17 mounted as vertical piece.

24

Tube pendant attachment W73 or the one half of Pendant attachment W21 are mounted on Support bracket/joint W7/40-70, 100, 200, 300 or 400 with Screw set W36/W36C.

Support bracket W1940 WEF-0001 For installation inside Cable trays W1/40 and W3/40.

A

Support bracket A mm

W1940-100 90 W1940-200 190 W1940-300 289 W1940-400 389 W1940-500 489 W1940-600 589 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

718711 9 734401 7 734402 4 734403 1 782342 0 782343 7

734452 9 734453 6 734454 3 734455 0 734456 7 734457 4

729041 3 729042 0 729043 7 729044 4 783753 3 783754 0

783060 2 783061 9 783062 6 783063 3 783064 0 783065 7

11 22 50 68 91 110

Use and installation

Tray W1/40 and W3/40 with widths of 200 to 400 are mounted with suitable Support bracket W1940, Pendant rail W32, Pendant attachment W21, Screw sets W37 and W36/ W36C. Trays with width 100 can be mounted with Support bracket W1940-100, one half of Pendant attachment W21 or Tube pendant W73 and Screw set W36/W36C.

Support bracket W1940 mounted with Ceiling bracket 5, Pendant/ Fixing rail 24/34 and Angle bracket W8S. Screw set 22S must be used. For cable trays with width 500 and 600.

Support bracket W1940 mounted on Vertical piece 2 and Ceiling bracket 5. Screw set 22S must be used. For cable trays with width 500 och 600.

Support bracket W1940 can be mounted with Vertical piece 2, Pendant joint 2J, Pendant/Fixing rail 24/34 and Ceiling bracket 5. Screw set 22S must be used. For cable trays with width 500 and 600.

Alternatively, Tray W1/40 and W3/40 with widths 500 and 600 can be installed with suitable Support bracket W1940, Threaded rod M10 W76 and 2 M10 nuts.

Alternatively, Tray W1/40 and W3/40 with widths 500 and 600 can be installed with suitable Support bracket W1940, Threaded rod M10 W76 and Tube pendant attachment W73.

Alternatively, Tray W1/40 and W3/40 with widths 500 and 600 can be installed with suitable Support bracket W1940, Pendant rail W32, Pendant attachment W21 and Screw set W37.

Tray W1/40 and W3/40 can be mounted on suitable Support bracket W1940 and 2 End bracket WN17 as pendant. The end brackets are joined with 2 Screw sets 22S and can be adjusted in height. The pendant can be mounted in the support bracket with Screw set W36/ W36C.

25

Side joint W49/40 WEF-0001 For straight joining of Cable tray W1/40 and W3/40.

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Side joint W49/40 786837 7 730191 1 *EAN-code=732167+Part.no+C (control figure) **Produced to order

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

786838 4

790231 6**

17

Use and installation 2 Side joints W49/40 are used for straight joining of Cable tray W1/40, W1/40 FS and W3/40. 4 Screw sets W38P are required (not included). For trays 300 mm and wider we recommend to use Support bracket/joint W7/40.

Reducer W28/40 WEF-0001 Used for transition joining from a wider to a narrower cable tray.

Reducer W28/40-100 Reducer W28/40-200 *EAN-code=732167+Part.no+ (control figure)

A mm

B mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

100 200

37.5 37.5

787436 1 787437 8

787438 5 787439 2

17 23

Use and installation

Used together with 1 Side joint W49/40 at one-side transition joining of Cable tray W1/40 and W3/40, to be mounted with 2 Screw sets W38P. Always use support close to the reducer.

26

2 Reducers W28/40 are used at centered transition joining, to be mounted with Screw set W38P. Always use support close to the reducer.

T-joint W9/40 WEF-0001 Mounted in T- or X-branches. Also used for oblique branches.

Part. No. includes 2 T-joints W9/40 Plate thickness mm

T-joint W9/40 1.0 (Screw set W38P incl) *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

718205 3

734622 6

729094 9

783128 9

6

Use and installation

1

2 Potential balancing In order to fulfil the potential balancing according to SS-EN 61537 the T-joint must be secured with 1 Self-drilling screw RXB 4.2 x 13 2 Screw set W38P, drilling is required. Tightening torque 2 Nm.

T-joint W9/40 is mounted on the side edges of the tray with Screw set W38P.

Straight angling. If necessary, the lugs are locked to the edge of the tray using pliers. Can also be locked with blind rivets or selftapping screws.

Oblique angling. If necessary, the lugs are locked to the edge of the tray using pliers. Can also be locked with blind rivets or selftapping screws.

27

T-joint W29/40 WEF-0001 Simple push-in assembly. Is hung over the edge of the tray and locked in a suitable way.

T-joint W29/40-70 T-joint W29/40-100 T-joint W29/40-200 T-joint W29/40-300 T-joint W29/40-400 T-joint W29/40-500 T-joint W29/40-600 *EAN-code=732167+Part.no+C (control figure)

A mm

B mm

Pre-galv. Part. No. C*

Pre-galv. White 30 Part. No. C*

Weight kg 100 pcs

68 98 198 301 401 501 601

120 220 320 420 520

790984 1 790985 8 790986 5 790987 2 790988 9 790989 6 790990 2

724942 8 724943 5 724944 2 724945 9 724946 6 724947 3 724948 0

8 12 21 30 40 50 59

Use and installation

Potential balancing In order to fulfil the potential balancing according to SS-EN 61537 the T-joint must be secured with 1 Self-drilling screw RXB 4.2 x 13 2 Screw set W38P, Tightening torque 2 Nm.

Simply installed with push-in mounting. Lock into tray with Screw set W38P.

Used with T- and X-junction. Mounted directly onto tray edge. Can be attached to tray by pinching the lip at the top of the tray.

Used with open junction together with Joint W7/40 with opening and Tray W1/40 with opening. Attached with Screw set W38P.

Examples of suspensions with open junction where T-joint W29/40, Tray W1/40 with opening and Joint W7/40 with opening are included.

Suspension with Pendant strip W33.

28

Suspension with Pendant rail W32 and half a Pendant attachment W21.

Suspension with End bracket WN17.

Suspension with wire and Ogebe fixing type E.

End cover W45/40 WEF-0001 For push-in assembly. Mounted as end cover in Cable trays W1/40 and W3/40 and lighting trunking.

A mm

End cover W45/40-70 68 End cover W45/40-100 98 End cover W45/40-150 148 End cover W45/40-200 198 End cover W45/40-300 298 End cover W45/40-400 398 End cover W45/40-500 498 End cover W45/40-600 598 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

731730 1 731731 8

783030 5 783031 2 783032 9 783033 6 783034 3 783035 0 783036 7 783037 4

731732 5 731733 2 731734 9 731735 5 731736 1

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

729177 9 729178 6

783000 8 783001 5 783002 2 783003 9 783004 6 783005 3 783006 0 783007 7

8 9 10 12 15 18 21 24

729179 3 729180 9 729181 6 729182 3 729183 0

Use and installation

Mounted as end in trays and lighting trunking. Locked with Locking plug W41 or Screw set W38P.

29

Adjustable bend W10/40 WEF-0001 Adjustable bend W10/40 permits horizontal angling from 105º to 165º in steps of 7.5º. Push-in installation.

A mm

Plate thickness mm

Adjustable bend W10/40-50 47 1.0 Adjustable bend W10/40-70 67 1.0 Adjustable bend W10/40-100 97 1.0 Adjustable bend W10/40-150 147 1.0 Adjustable bend W10/40-200 197 1.0 Adjustable bend W10/40-300 297 1.0 Adjustable bend W10/40-400 397 1.0 Adjustable bend W10/40-500 497 1.25 Adjustable bendW10/40-600 597 1.25 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

734584 7 716833 0 716834 7 734585 4 716835 4 716836 1 716837 8 724965 7 724966 4

734591 5 734592 2 734593 9 734594 6 734595 3 734596 0 734597 7 734598 4 734599 1

Pre-galv. White30 Part. No. C*

729103 8 729104 5 729105 2 729106 9 729107 6 729108 3 729109 0

Use and installation

V Push-in installation. Turn up inner and outer sides and mount the Adjustable bend W10/40 inside the tray.

30

Adjustable bend W10/40 permits desired horizontal angling between 105º and 165º in stages of 7.5º.

If necessary, Adjustable bend W10/40 may be locked using Screw set W38P or Locking plug W41.

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

782850 0 782851 7 782852 4 782853 1 782854 8 782855 5 782856 2 782857 9 782858 6

9 10 13 24 40 75 125 270 380

Vertical riser W11/40 WEF-0001 For upward or downward angling to a desired angle up to 90˚, push-in assembly. Should be locked with Screw set W38P or Locking plug W41.

Vertical riser A mm

L mm

Plate thickness mm

W11/40-50 48 150 0.7 W11/40-70 68 150 0.7 W11/40-100 98 150 0.7 W11/40-150 148 150 0.7 W11/40-200 198 200 0.7 W11/40-300 298 200 0.7 W11/40-400 398 200 0.7 W11/40-500 498 200 0.7 W11/40-600 598 200 0.7 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

733498 8 723226 0 723227 7 733499 5 723228 4 723229 1 723230 7 723231 4 723232 1

734101 1 734102 3 734103 0 734104 7 734105 4 734106 1 734107 8 734108 5 734109 2

Pre-galv. White30 Part. No. C*

729126 7 729127 4 729128 1 729129 8 729130 4 729131 1 729132 8

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

783040 4 783041 1 783042 8 783043 5 783044 2 783045 9 783046 6 783047 3 783048 0

8 10 12 17 28 39 50 61 73

Use and installation

For upward or downward angling at a desired angle up to 90˚. Push-in installation.

Should be attached with Screw set W38P or Locking plug W41.

Vertical riser W11/40 is delivered flat and must be bent by the installer on the job site.

31

90˚ bend W10/40 WEF-0001 Pre-galvanized For 90˚ horizontal junction of Cable trays W1/40 and W3/40. Push-in assembly.

A mm

90˚ bend W10/40-70 67 90˚ bend W10/40-100 97 90˚ bend W10/40-200 197 90˚ bend W10/40-300 297 90˚ bend W10/40-400 397 90˚ bend W10/40-500 497 90˚ bend W10/40-600 597 *EAN-code=732167+Part.no+C (control figure)

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

1.25 1.25 1.25 1.25 1.25 1.25 1.25

717903 9 717904 6 717905 3 717906 0 717907 7 721184 5 723196 6

729201 1 729133 5 729134 2 729135 9 729136 6 729137 3 729138 0

38 51 108 185 281 400 540

Use and installation

Used for 90˚ horizontal angling. Suspension components should be mounted in or in connection with the junction. Push-in installation.

32

If necessary, the 90˚ bend W10/ 40 can be locked using Screw set W38P or Locking plug W41. Can be provided with holes in bottom for suspension in Pendant attachment W21 alt. W73. Valid for max. width 200 mm.

Support bracket/joint W7/40, with a suitable pendant, is used to achieve an invisible suspension, here with End bracket WN17 mounted as vertical piece.

90˚ bend W10F/40 WEF-0001 Hot dip galvanized For 90˚ horizontal junction of Cable trays W1/40 and W3/40. Push-in assembly.

A mm

L mm

Plate thickness mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

90˚ bend W10F/40-50 47 90˚ bend W10F/40-70 67 90˚ bend W10F/40-100 97 90˚ bend W10F/40-150 147 90˚ bend W10F/40-200 197 90˚ bend W10F/40-300 297 90˚ bend W10F/40-400 397 90˚ bend W10F/40-500 497 90˚ bend W10F/40-600 597 *EAN-code=732167+Part.no+C (control figure)

119 153 204 290 375 480 580 714 814

1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

783660 4 783661 1 783662 8 783663 5 783664 2 783665 9 783666 6 783667 3 783668 0

783600 0 783601 7 783602 4 783603 1 783604 8 783605 5 783606 2 783607 9 783608 6

18 28 48 92 148 242 353 528 685

Use and installation

Used for 90˚ horizontal angling. Suspension components should be mounted in or in connection with the junction. Push-in installation.

33

T-junction W12/40 WEF-0001 Pre-galvanized For 90˚ horizontal junction of Cable trays W1/40 and W3/40. Push-in assembly.

A mm

T-junction W12/40-70 67 T-junction W12/40-100 97 T-junction W12/40-200 197 T-junction W12/40-300 297 T-junction W12/40-400 397 T-junction W12/40-500 497 T-junction W12/40-600 597 *EAN-code=732167+Part.no+C (control figure)

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

1.25 1.25 1.25 1.25 1.25 1.25 1.25

717908 4 717909 1 717910 7 717911 4 717912 1 721186 9 723198 0

729139 7 729140 3 729141 0 729142 7 729143 4 729144 1 729145 8

49 64 128 212 314 438 580

Use and installation

Used for horizontal 90˚ junction. Suspension components should be mounted in or in connection with the junction. Push-in installation.

Support bracket/joint W7/40, with a suitable pendant, is used to achieve an invisible suspension, here with End bracket WN17 mounted as vertical piece.

34

If necessary, the T-junction W12/40 can be locked using Screw set W38P or Locking plug W41. Can be provided with holes in bottom for suspension in Pendant attachment W21 or Tube pendant attachment W73. Valid for max. width 200 mm.

T-junction W12F/40 WEF-0001 Hot dip galvanized For 90˚ horizontal junction of Cable trays W1/40 and W3/40. Push-in assembly.

A mm

T-junction W12F/40-50 47 T-junction W12F/40-70 67 T-junction W12F/40-100 97 T-junction W12F/40-150 147 T-junction W12F/40-200 197 T-junction W12F/40-300 297 T-junction W12F/40-400 397 T-junction W12F/40-500 497 T-junction W12F/40-600 597 *EAN-code=732167+Part.no+C (control figure)

L mm

Plate thickness mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

171 219 312 432 553 662 762 932 1032

1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

783670 3 783671 0 783672 7 783673 4 783674 1 783675 8 783676 5 783677 2 783678 9

783620 8 783621 5 783622 2 783623 9 783624 6 783625 3 783626 0 783627 7 783628 4

26 35 60 110 192 300 428 640 817

Use and installation

Used for horizontal 90˚ junction. Suspension components should be mounted in or in connection with the junction. Push-in installation.

35

X-junction W13/40 WEF-0001 Pre-galvanized For 90˚ horizontal junction of Cable trays W1/40 and W3/40. Push-in assembly.

A mm

X-junction W13/40-70 67 X-junction W13/40-100 97 X-junction W13/40-200 197 X-junction W13/40-300 297 X-junction W13/40-400 397 X-junction W13/40-500 497 X-junction W13/40-600 597 *EAN-code=732167+Part.no+C (control figure)

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

1.25 1.25 1.25 1.25 1.25 1.25 1.25

717913 8 717914 5 717915 2 717916 9 717917 6 721188 3 723200 0

729146 5 729147 2 729148 9 729149 6 729150 2 729151 9 729152 6

64 80 150 240 350 480 630

Use and installation

Used for horizontal 90˚ junction of four trays with the same width. Suspension components should be mounted in or in connection with the junction. Push-in installation.

Support bracket/joint W7/40, with a suitable pendant, is used to achieve an invisible suspension, here with End bracket WN17 mounted as vertical piece.

36

If necessary, the X-junction W13/40 can be locked using Screw set W38P or Locking plug W41. Can be provided with holes in bottom for suspension in Pendant attachment W21 or Tube pendant attachment W73. Valid for max. width 200 mm.

X-junction W13F/40 WEF-0001 Hot dip galvanized For 90˚ horizontal junction of Cable trays W1/40 and W3/40. Push-in assembly.

A mm

X-junction W13F/40-50 47 X-junction W13F/40-70 67 X-junction W13F/40-100 97 X-junction W13F/40-150 147 X-junction W13F/40-200 197 X-junction W13F/40-300 297 X-junction W13F/40-400 397 X-junction W13F/40-500 497 X-junction W13F/40-600 597 *EAN-code=732167+Part.no+C (control figure)

L mm

Plate thickness mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

148 217 313 434 555 662 762 932 1032

1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

783680 2 783681 9 783682 6 783683 3 783684 0 783685 7 783686 4 783687 1 783688 8

783640 6 783641 3 783642 0 783643 7 783644 4 783645 1 783646 8 783647 5 783648 2

27 43 74 147 243 370 510 766 966

Use and installation

Used for horizontal 90˚ junction of four trays with the same width. Suspension components should be mounted in or in connection with the junction. Push-in installation.

37

Reducing piece W14/40 left WEF-0001 Pre-galvanized For push-in assembly. Fitted for transition between different widths of Cable trays W1/40 and W3/40 at wall mountings.

Reducing piece W14/40 200-100 left Reducing piece W14/40 300-100 left Reducing piece W14/40 400-100 left Reducing piece W14/40 300-200 left Reducing piece W14/40 400-200 left Reducing piece W14/40 400-300 left *EAN-code=732167+Part.no+C (control figure)

A mm

B mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

198 298 398 298 398 398

98 98 98 198 198 298

1.0 1.25 1.25 1.25 1.25 1.25

713620 9 713622 3 713623 0 713631 5 713632 2 713637 7

729159 5 729160 1 729161 8 729162 5 729163 2 729164 9

53 81 96 96 111 126

Use and installation

For transition between different widths of trays and rails during wall mounting. Push-in installation.

38

If necessary, the Reducing piece W14/40 can be locked using Screw set W38P or Locking plug W41.

Suspension components should be mounted in or in connection with the reducing piece. Support bracket/joint W7/40 and a suitable pendant can be used to achieve an invisible suspension, here with End bracket WN17 mounted as vertical piece.

Reducing piece W14/40 left WEF-0001 Hot dip galvanized For push-in assembly. Fitted for transition between different widths of Cable trays W1/40 and W3/40 at wall mountings.

E WIBE C

Reducing piece W14/40 150-100 left Reducing piece W14/40 200-100 left Reducing piece W14/40 200-150 left Reducing piece W14/40 300-100 left Reducing piece W14/40 300-150 left Reducing piece W14/40 300-200 left Reducing piece W14/40 400-100 left Reducing piece W14/40 400-150 left Reducing piece W14/40 400-200 left Reducing piece W14/40 400-300 left Reducing piece W14/40 500-100 left Reducing piece W14/40 500-150 left Reducing piece W14/40 500-200 left Reducing piece W14/40 500-300 left Reducing piece W14/40 500-400 left Reducing piece W14/40 600-100 left Reducing piece W14/40 600-150 left Reducing piece W14/40 600-200 left Reducing piece W14/40 600-300 left Reducing piece W14/40 600-400 left Reducing piece W14/40 600-500 left *EAN-code=732167+Part.no+C (control figure)

A mm

B mm

L mm

Plate thickness mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

147 197 197 297 297 297 397 397 397 397 497 497 497 497 497 597 597 597 597 597 597

97 97 147 97 147 197 97 147 197 297 97 147 197 297 397 97 147 197 297 397 497

132 182 132 282 222 182 382 332 282 182 482 432 382 282 182 582 532 482 382 282 182

1.25 1.0 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

787796 6 783696 3 787797 3 783697 0 787798 0 783699 4 783698 7 787799 7 783700 7 783701 4 787785 0 787786 7 787787 4 787788 1 787789 8 787790 4 787791 1 787792 8 787793 5 787794 2 787795 9

787811 6 783708 3 787812 3 783709 0 787813 0 783711 3 783710 6 787814 7 783712 0 783713 7 787800 0 787801 7 787802 4 787803 1 787804 8 787805 5 787806 2 787807 9 787808 6 787809 3 787810 9

23 38 30 75 67 56 121 113 102 74 178 170 159 130 92 245 236 226 197 158 101

Use and installation

E WIBE C

For transition between different widths of trays and rails during wall mounting. Push-in installation.

39

Reducing piece W14/40 right WEF-0001 Pre-galvanized For push-in assembly. Fitted for transition between different widths of Cable trays W1/40 and W3/40 at wall mountings.

Reducing piece W14/40 200-100 right Reducing piece W14/40 300-100 right Reducing piece W14/40 400-100 right Reducing piece W14/40 300-200 right Reducing piece W14/40 400-200 right Reducing piece W14/40 400-300 right *EAN-code=732167+Part.no+C (control figure)

A mm

B mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

198 298 398 298 398 398

98 98 98 198 198 298

1.0 1.25 1.25 1.25 1.25 1.25

713536 3 713538 7 713539 4 713547 9 713548 6 713553 0

729165 6 729166 3 729167 0 729168 7 729169 4 729170 0

53 81 96 96 111 126

Use and installation

For transition between different widths of trays and rails during wall mounting. Push-in installation.

40

If necessary, the Reducing piece W14/40 can be locked using Screw set W38P or locking plug W41.

Suspension components should be mounted in or in connection with the reducing piece. Support bracket/joint W7/40 and a suitable pendant can be used to achieve an invisible suspension, here with End bracket WN17 mounted as vertical piece.

Reducing piece W14/40 right WEF-0001 Hot dip galvanized For push-in assembly. Fitted for transition between different widths of Cable trays W1/40 and W3/40 at wall mountings.

Reducing piece W14/40 150-100 right Reducing piece W14/40 200-100 right Reducing piece W14/40 200-150 right Reducing piece W14/40 300-100 right Reducing piece W14/40 300-150 right Reducing piece W14/40 300-200 right Reducing piece W14/40 400-100 right Reducing piece W14/40 400-150 right Reducing piece W14/40 400-200 right Reducing piece W14/40 400-300 right Reducing piece W14/40 500-100 right Reducing piece W14/40 500-150 right Reducing piece W14/40 500-200 right Reducing piece W14/40 500-300 right Reducing piece W14/40 500-400 right Reducing piece W14/40 600-100 right Reducing piece W14/40 600-150 right Reducing piece W14/40 600-200 right Reducing piece W14/40 600-300 right Reducing piece W14/40 600-400 right Reducing piece W14/40 600-500 right *EAN-code=732167+Part.no+C (control figure)

A mm

B mm

L mm

Plate thickness mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

147 197 197 297 297 297 397 397 397 397 497 497 497 497 497 597 597 597 597 597 597

97 97 147 97 147 197 97 147 197 297 97 147 197 297 397 97 147 197 297 397 497

132 182 132 282 222 182 382 332 282 182 482 432 382 282 182 582 532 482 382 282 182

1.25 1.0 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

787841 3 783690 1 787842 0 783691 8 787843 7 783693 2 783692 5 787844 4 783694 9 783695 6 787830 7 787831 4 787832 1 787833 8 787834 5 787835 2 787836 9 787837 6 787838 3 787839 0 787840 6

787856 7 783714 4 787857 4 783715 1 787858 1 783717 5 783716 8 787859 8 783718 2 783719 9 787845 1 787846 8 787847 5 787848 2 787849 9 787850 5 787851 2 787852 9 787853 6 787854 3 787855 0

23 38 30 75 67 56 121 113 102 74 178 170 159 130 92 245 236 226 197 158 101

Use and installation

For transition between different widths of trays and rails during wall mounting. Push-in installation.

41

Reducing piece W15/40 straight WEF-0001 Pre-galvanized For push-in assembly. Fitted for transition between different widths of Cable trays W1/40 and W3/40 at symmetric ceiling installation.

Reducing piece W15/40 200-100 straight Reducing piece W15/40 300-100 straight Reducing piece W15/40 400-100 straight Reducing piece W15/40 300-200 straight Reducing piece W15/40 400-200 straight Reducing piece W15/40 400-300 straight *EAN-code=732167+Part.no+C (control figure)

A mm

B mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

198 298 398 298 398 398

98 98 98 198 198 298

1.0 1.25 1.25 1.25 1.25 1.25

713704 6 713706 0 713707 7 713715 2 713716 9 713721 3

729171 7 729172 4 729173 1 729174 8 729175 5 729176 2

53 81 96 96 111 126

Use and installation

For transition between different tray widths during symmetric ceiling installation. Push-in assembly.

42

If necessary, the Reducing piece W15/40 can be locked using Screw set W38P or Locking plug W41.

Suspension components should be mounted in or in connection with the reducing piece Support bracket/joint W7/40 and a suitable pendant can be used to achieve an invisible suspension, here with End bracket WN17 mounted as vertical piece.

Reducing piece W15/40 straight WEF-0001 Hot dip galvanized For push-in assembly. Fitted for transition between different widths of Cable trays W1/40 and W3/40 at symmetric ceiling installation.

Reducing piece W15/40 150-100 straight Reducing piece W15/40 200-100 straight Reducing piece W15/40 200-150 straight Reducing piece W15/40 300-100 straight Reducing piece W15/40 300-150 straight Reducing piece W15/40 300-200 straight Reducing piece W15/40 400-100 straight Reducing piece W15/40 400-150 straight Reducing piece W15/40 400-200 straight Reducing piece W15/40 400-300 straight Reducing piece W15/40 500-100 straight Reducing piece W15/40 500-150 straight Reducing piece W15/40 500-200 straight Reducing piece W15/40 500-300 straight Reducing piece W15/40 500-400 straight Reducing piece W15/40 600-100 straight Reducing piece W15/40 600-150 straight Reducing piece W15/40 600-200 straight Reducing piece W15/40 600-300 straight Reducing piece W15/40 600-400 straight Reducing piece W15/40 600-500 straight *EAN-code=732167+Part.no+C (control figure)

A mm

B mm

L mm

Plate thickness mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

147 197 197 297 297 297 397 397 397 397 497 497 497 497 497 597 597 597 597 597 597

97 97 147 97 147 197 97 147 197 297 97 147 197 297 397 97 147 197 297 397 497

118 154 118 225 190 154 297 261 225 154 368 333 297 225 154 440 404 368 297 225 154

1.25 1.0 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

787751 5 783702 1 787752 2 783703 8 787753 9 783705 2 783704 5 787754 6 783706 9 783707 6 787740 9 787741 6 787742 3 787743 0 787744 7 787745 4 787746 1 787747 8 787748 5 787749 2 787750 8

787766 9 783720 5 787767 6 783721 2 787768 3 783723 6 783722 9 787769 0 783724 3 783725 0 787755 3 787756 0 787757 7 787758 4 787759 1 787760 7 787761 4 787762 1 787763 8 787764 5 787765 2

20 25 26 59 53 46 94 88 81 61 135 129 122 103 76 183 178 171 151 125 91

Use and installation

For transition between different tray widths during symmetric ceiling installation. Push-in assembly.

43

Junction box plate W24/40 WEF-0001 Junction box plate W24 for installing junction boxes, light fittings etc. in Cable trays W1/40, W3/40 and lighting trunkings.

Unholed Junction box plate

Plate thickness mm

W24/40 1.0 W24/40 unholed 1.0 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

717995 4 730247 5

734617 2

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

729184 7 734211 2

783130 2

Weight kg 100 pcs

31 31

Use and installation

The Junction box plate W24/40 is mounted between the bottom of the trunking or tray and its folded seam.

44

If necessary, the Junction box plate W24/40 can be screwed tight directly in Tray W3/40 with Screw set W38P. If one requires a hidden socket box, the junction box should be folded inwards.

Can be mounted in the middle of Lighting trunking W70/W71-100 and W70-200 with Screw set W36 or Tray W3/40 with Screw set W38P.

To firmly attach Junction box plate W24/40 in Tray W1/40 or W3/40, use blind rivets, selftapping screws or Screw set W38P.

Luminaire bracket W25/40 WEF-0001 Used for assembly of light fittings under Cable trays W1/40 and W3/40 or Lighting trunking W70/W71.

Luminaire bracket W25/40-70 Luminaire bracket W25/40-100 Luminaire bracket W25/40-200 Luminaire bracket W25/40-300 Luminaire bracket W25/40-400 Luminaire bracket W25/40-500 Luminaire bracket W25/40-600 *EAN-code=732167+Part.no+C (control figure)

A mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

72 101 201 301 401 501 601

1.25 1.25 1.25 1.25 1.25 1.25 1.25

713911 8 713912 5 713914 9 713916 3 713917 0 713918 7 713913 2

729185 4 729186 1 729187 8 729188 5 729189 2 729190 8 729191 5

7 8 11 19 23 27 31

Use and installation

Used for installation of light fittings under tray or trunking. Can easily be moved along the tray or trunking.

For mounting of light fittings between and under two trays or lighting trunking. The light fitting is easily moved along the tray or lighting trunking.

45

Cable tray W1/60, unperforated WEF-0001 Side height 60 mm, length 2000 mm. Holes Ø 5.8 mm at the tray ends can be used for locking of joints.

A mm

Cable tray W1/60-70 70 Cable tray W1/60-100 100 Cable tray W1/60-200 200 Cable tray W1/60-300 300 Cable tray W1/60-400 400 Cable tray W1/60-500 500 Cable tray W1/60-600 600 Cable tray W1/60-500 FS 500 Cable tray W1/60-600 FS 600 *EAN-code=732167+Part.no+C (control figure)

L mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 m

2000 2000 2000 2000 2000 2000 2000 2000 2000

1.0 1.0 1.25 1.25 1.25 1.5 1.5 1.5 1.5

781999 7 782000 9 782001 6 723974 0 723975 7 723976 4 723977 1 782046 7 782047 4

782011 5 782012 2 782013 9 782014 6 782015 3 782016 0 782017 7 782048 1 782049 8

165 185 335 440 540 755 870 760 875

Use and installation

Cable tray W1/60 is joined with 2 Side joints W49/60 or Support bracket/joint W7/60.

46

For trays 300 mm and wider we recommend to use Support bracket/joint W7/60.

Cable tray W3/60, perforated WEF-0001 Side height 60 mm, length 3000 mm. Holes Ø 5.8 mm at the tray ends can be used for locking of joints. Oval holes along the sides can be used for mounting of accessories.

60

A mm

Cable tray W3/60-70 70 Cable tray W3/60-100 100 Cable tray W3/60-150 150 Cable tray W3/60-200 200 Cable tray W3/60-300 300 Cable tray W3/60-400 400 *EAN-code=732167+Part.no+C (control figure)

L mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 m

3000 3000 3000 3000 3000 3000

1.0 1.0 1.0 1.0 1.25 1.25

782202 7 782203 4 782204 1 782205 8 782206 5 782207 2

782306 2 782307 9 782308 6 782309 3 782310 9 782311 6

150 180 200 240 337 440

Use and installation

Cable tray W3/60 is joined with 2 Side joints W49/60 or Support bracket/joint W7/60.

For trays 300 mm and wider we recommend to use Support bracket/joint W7/60.

47

Adjustable cantilever arm W1860 WEF-0001 For installation inside Cable tray W1/60 and W3/60.

W1860 100-200

W1860 300-600

Adjustable cantilever arm

B mm

C mm

D mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

W1860-100 89 160 W1860-200 189 160 W1860-300 289 185 W1860-400 389 185 W1860-500 489 185 W1860-600 589 185 *EAN-code=732167+Part.no+C (control figure)

70 70 95 95 95 95

0-25 0-50 0-50 0-50 0-50 0-50

782392 5 782393 2 782394 9 782395 6 782396 3 782397 3

783504 1 783505 8 783506 5 783507 2 783508 9 783509 6

47 65 123 142 161 180

A mm

Loading table for cantilever arm on wall

Mounted onto wall with Expansion bolt. Breaking load for cantilever arm mounted onto wall - see below.

Type of cantilever arm

Max load F at 3˚ deflection of cantilever arm kN kg

W1860-100 W1860-200 W1860-300 W1860-400 W1860-500 W1860-600

1.0 0.8 1.1 1.0 0.65 0.5

100 80 110 100 65 50

Deflection in mm vid 3˚ deflection of cantilever arm

5.2 10.5 15.7 20.9 26 31.5

Breaking load kN

kg

3.0 2.0 3.0 2.0 1.3 1.0

300 200 300 200 130 100

Use and installation

Mounting directly onto wall. At this type of installation the adjusting allowance of the tray is limited. Breaking load - see table above.

48

Mounting on Vertical piece 2F using T-bolt. The Cantilever arm W1860 can be adjusted to a max. of 50 mm.

Mounting of two adjustable cantilever arms on the same Vertical piece 2F. (Tray widths more than 400 mm). Use Screw set 20S if the two trays have the same width. At different tray widths T -bolt 26 and Screw set W37 must be used.

When mounting cable trays widths 500-600 mm - it might be necessary with a reinforcement of the cantilever arm. Installation band and stretching screw can be used for mounting in ceiling or on a vertical piece.

Support bracket W1960 WEF-0001 For installation inside Cable trays W1/60 and W3/60.

A

Support bracket W1960-100 Support bracket W1960-200 Support bracket W1960-300 Support bracket W1960-400 Support bracket W1960-500 Support bracket W1960-600 *EAN-code=732167+Part.no+C (control figure)

A mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

89 189 289 389 489 589

782332 1 782333 8 782334 5 782335 2 782336 9 782337 6

783166 1 783167 8 783168 5 783169 2 783170 8 783171 5

19 37 58 77 96 115

Use and installation

Tray W1/60 and W3/60 with widths of 200 to 400 are mounted with suitable Support bracket W1960 and Pendant rail W32, Pendant attachment W21 and Screw set W37. Trays with width 100 can be mounted with Support bracket W1960-100, one half of Pendant attachment W21 or Tube pendant W73 and Screw set W36/ W36C.

Support bracket W1960 mounted with Ceiling bracket 5, Pendant/ Fixing rail 24/34 and Angle bracket W8S. Screw set 22S must be used. For cable trays with width 500 and 600.

Support bracket W1960 mounted on Vertical piece 2 and Ceiling bracket 5. Screw set 22S must be used. For cable trays with width 500 och 600.

Support bracket W1960 can be mounted with Vertical piece 2, Pendant joint 2J, Pendant/Fixing rail 24/34 and Ceiling bracket 5. Screw set 22S must be used. For cable trays with width 500 and 600.

Alternatively, Tray W1/60 and W3/60 with widths 500 and 600 can be installed with suitable Support bracket W1960, Threaded rod M10 W76 and 2 M10 nuts.

Alternatively, Tray W1/60 and W3/60 with widths 500 and 600 can be installed with suitable Support bracket W1960, Threaded rod M10 W76 and Tube pendant attachment W73.

Alternatively, Tray W1/60 and W3/60 with widths 500 and 600 can be installed with suitable Support bracket W1960, Pendant rail W32, Pendant attachment W21 and Screw set W37.

Tray W1/60 and W3/60 can be mounted on suitable Support bracket W1960 and 2 End brackets WN17 as pendant. The end brackets are joined with 2 Screw sets 22S and can be adjusted in height. The pendant can be mounted in the support bracket with 1 Screw set W36/W36C.

49

Support bracket/joint W7/60 Used as a support bracket or joint for Cable tray W1/60 and W3/60. When joining Cable tray W1/60 FS (reinforced), Side joint W49/60 must be used.

W7/60-70,150

W7/60-500,600

W7/60-100,200,300,400

Support bracket/joint W7/60-70 Support bracket/joint W7/60-100 Support bracket/joint W7/60-150 Support bracket/joint W7/60-200 Support bracket/joint W7/60-300 Support bracket/joint W7/60-400 Joint W7/60-500 Joint W7/60-600 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

A mm

B mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

68 98 148 198 297 397 498 598

152 200 200 200 300 300 300 300

1.0 1.0 1.0 1.0 1.25 1.25 1.25 1.25

782209 6 718445 3 782210 2 718446 0 718447 7 718448 4 782211 9 782212 6

782318 5 782319 2 782320 8 782321 5 782322 2 782323 9 782324 6 782325 3

22 33 41 49 122 152 180 210

Use and installation

Support bracket/joint W7/60 is used for straight joining. Push-in mounting.

If necessary trays are locked using Screw set W38P or Locking plug W41.

With Pendant attachment W21 installed, a complete support bracket is obtained. Does not apply to W7/60-70,150,500 and 600.

W7/60-500 och 600 are only used for joining, not as support brackets. Reinforced tray is to be joined with Side joint W49/60.

End bracket WN17 can be used as vertical piece on Support bracket/joint W7/60 mounted with Screw set W36/W36C.

Support bracket/joint W7/60 is used to achieve an invisible suspension in or in connection with bends or junctions, here with End bracket WN17 mounted as vertical piece.

50

Tube pendant attachment W73 or the one half of Pendant attachment W21 are mounted with Screw set W36/W36C.Does not apply to W7/60-500 and 600.

Side joint W49/60 WEF-0001 For straight joining of Cable tray W1/60 and W3/60.

Side joint W49/60 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

782267 6

782330 7

27

Use and installation 2 Side joints W49/60 are used for straight joining of Cable tray W1/60, W1/60 FS and W3/60. 4 Screw sets W38P are required (not included). For trays 300 mm and wider we recommend to use Support bracket/joint W7/60.

Reducer W28/60 WEF-0001 Used for transition joining of Cable trays W1/60 or W3/60.

Reducer W28/60-100 Reducer W28/60-200 *EAN-code=732167+Part.no+C (control figure)

A mm

B mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

100 200

57.5 57.5

787442 2 787443 9

787444 6 787445 3

27 36

Use and installation

Used together with 1 Side joint W49/60 at one-side transition joining of Cable trays W1/60 and W3/60, to be mounted with 2 Screw sets W38P. Always use support close to the reducer.

2 Reducers W28/60 are used at centered transition joining, to be mounted with Screw set W38P. Always use support close to the reducer.

51

T-joint W9/60 WEF-0001 Used for straight or oblique branches of Cable trays W1/60 or W3/60.

T-joint W9/60 (Screw set W38P incl.) *EAN-code=732167+Part.no+C (control figure)

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. NoC*

Weight kg 100 pcs

1.25

782217 1

782218 8

5

Use and installation

1

2 Potential balancing In order to fulfil the potential balancing according to SS-EN 61537 the T-joint must be secured with 1 Self-drilling screw RXB 4.2x13 2 Screw set W38P, drilling is required Tightening torque 2 Nm

52

T-joint W9/60 is mounted on the sides of the tray with Screw set W38P.

Straight branches. If necessary, the lugs are locked to the edge of the tray using pliers. Can also be locked with blind rivets or self-tapping screws.

Oblique branches. If necessary, the lugs are locked to the edge of the tray using pliers. Can also be locked with blind rivets or self-tapping screws.

T-joint W29/60 WEF-0001 Simple push-in assembly. Locks into tray via locking flap. Is hung over the edge of the tray and locked in a suitable way.

T-joint W29/60-70 T-joint W29/60-100 T-joint W29/60-200 T-joint W29/60-300 T-joint W29/60-400 T-joint W29/60-500 T-joint W29/60-600 *EAN-code=732167+Part.no+C (control figure)

A mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

68 98 198 298 398 498 598

783178 4 783179 1 783180 7 783181 4 783182 1 783183 8 783184 5

783185 2 783186 9 783187 6 783188 3 783189 0 783190 6 783191 3

22 27 37 47 57 67 77

Use and installation

Potential balancing In order to fulfil the potential balancing according to SS-EN 61537 the T-joint must be secured with 1 Self-drilling screw RXB 4.2x13 2 Screw set W38P, drilling is required Tightening torque 2 Nm

Used with T- and X-junction. Mounted directly onto tray edge. Can be attached to tray by pinching the lip at the top of the tray.

53

Adjustable bend W10/60 WEF-0001 For horizontal angling of Cable ladders W1/60 or W3/60. Push-in installation.

Adjustable bend W10/60-70 Adjustable bend W10/60-100 Adjustable bend W10/60-150 Adjustable bend W10/60-200 Adjustable bend W10/60-300 Adjustable bend W10/60-400 Adjustable bend W10/60-500 Adjustable bend W10/60-600 *EAN-code=732167+Part.no+C (control figure)

A mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No C*

Weight kg 100 pcs

67 97 147 197 297 397 497 597

1.0 1.0 1.0 1.0 1.0 1.0 1.25 1.25

782268 3 782269 0 782270 6 782271 3 782272 0 782273 7 782274 4 782275 1

782471 7 782472 4 782473 1 782474 8 782475 5 782476 2 782477 9 782478 6

17 23 37 53 97 156 292 406

Use and installation

V Push-in installation. Turn up inner and outer sides and mount the Adjustable bend W10/60 inside the tray.

54

Adjustable bend W10/60 permits desired horizontal angling between 105˚ and 165˚ in stages of 7.5˚.

If necessary, Adjustable bend W10/60 may be locked using Screw set W38P or Locking plug W41.

Vertical riser W11/60 WEF-0001 For upward or downward branching of Cable trays W1/60 or W3/60 to desired angle. Push-in assembly.

A mm

L mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

Vertical riser W11/60-70 67 Vertical riser W11/60-100 97 Vertical riser W11/60-150 147 Vertical riser W11/60-200 197 Vertical riser W11/60-300 297 Vertical riser W11/60-400 397 Vertical riser W11/60-500 497 Vertical riser W11/60-600 597 *EAN-code=732167+Part.no+C (control figure)

150 150 150 200 200 200 200 200

0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7

782276 8 782277 5 782278 2 782279 9 782280 5 782281 2 782282 9 782283 6

782593 6 782594 3 782595 0 782596 7 782597 4 782598 1 782599 8 782600 1

12 15 19 31 42 53 64 75

Use and installation

Vertical riser W11/60 is delivered flat and must be bent by the installer on the job site.

For upward or downward branching at a desired angle up to 90˚. Push-in installation.

Should be attached with Screw set W38P or Locking plug W41.

55

90˚ bend W10/60 WEF-0001 For 90˚ horizontal angling of Cable trays W1/60 or W3/60. Push-in assembly.

A mm

B mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

90˚ bend W10/60-70 67 90˚ bend W10/60-100 97 90˚ bend W10/60-150 147 90˚ bend W10/60-200 197 90˚ bend W10/60-300 297 90˚ bend W10/60-400 397 90˚ bend W10/60-500 497 90˚ bend W10/60-600 597 90˚ bend W10/60-500 FS 497 90˚ bend W10/60-600 FS 597 *EAN-code=732167+Part.no+C (control figure)

167 197 247 297 397 497 597 697 597 697

1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

782038 2 782039 9 782040 5 782041 2 782042 9 782043 6 782044 3 782045 0 782458 8 782459 5

782408 3 782409 0 782410 6 782411 3 782412 0 782413 7 782414 4 782415 1 787188 9 787189 6

43 55 85 117 196 295 413 551 343 465

Use and installation

Used for 90˚ horizontal angling. Suspension components should be mounted in or in connection with the bend. Push-in installation.

56

If necessary, the 90˚ bend W1060 can be locked using Screw set W38P or Locking plug W41. Can be provided with holes in bottom for suspension in Pendant attachment W21 alternatively W73. Valid for max. width 200 mm.

Support bracket/joint W7/60, with a suitable pendant, is used to achieve an invisible suspension, here with End bracket WN17 mounted as vertical piece.

T-junction W12/60 WEF-0001 For 90˚ horizontal junction of Cable trays W1/60 or W3/60. Push-in assembly.

T-junction W12/60-70 T-junction W12/60-100 T-junction W12/60-150 T-junction W12/60-200 T-junction W12/60-300 T-junction W12/60-400 T-junction W12/60-500 T-junction W12/60-600 T-junction W12/60-500 FS T-junction W12/60-600 FS *EAN-code=732167+Part.no+C (control figure)

A mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

67 97 147 197 297 397 497 597 497 597

1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

782052 8 782053 5 782054 2 782055 9 782056 6 782057 3 782058 0 782059 7 782460 1 782461 8

782424 3 782425 0 782426 7 782427 4 782428 1 782429 8 782430 4 782431 1 787192 6 787193 3

54 70 99 133 217 320 443 585 337 454

Use and installation

Used for 90˚ horizontal junction. Suspension components should be mounted in or in connection with the junction. Push-in installation.

If necessary, the junction can be locked using Screw set W38P or Locking plug W41. Can be provided with holes in bottom for suspension in Pendant attachment W21 alternatively W73. Valid for max. width 200 mm.

Support bracket/joint W7/60, with a suitable pendant, is used to achieve an invisible suspension, here with End bracket WN17 mounted as vertical piece.

57

X-junction W13/60 WEF-0001 For 90˚ horizontal junction of Cable trays W1/60 or W3/60. Push-in assembly.

A mm

B mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

X-junction W13/60-70 67 X-junction W13/60-100 97 X-junction W13/60-150 147 X-junction W13/60-200 197 X-junction W13/60-300 297 X-junction W13/60-400 397 X-junction W13/60-500 497 X-junction W13/60-600 597 X-junction W13/60-500 FS 497 X-junction W13/60-600 FS 597 *EAN-code=732167+Part.no+C (control figure)

268 298 348 398 498 598 698 798 698 798

1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

782095 5 782096 2 782097 9 782098 6 782099 3 782100 6 782101 3 782102 0 782462 5 782463 2

782440 3 782441 0 782442 7 782443 4 782444 1 782445 8 782446 5 782447 2 787196 4 787197 1

62 78 110 146 234 342 469 616 328 441

Use and installation

Used for 90˚ horizontal junction of four trays with the same width. Suspension components should be mounted in or in connection with the junction. Push-in installation.

58

If necessary, the junction can be locked using Screw set W38P or Locking plug W41. Can be provided with holes in bottom for suspension in Pendant attachment W21 alternatively W73. Valid for max. width 200 mm.

Support bracket/joint W7/60, with a suitable pendant, is used to achieve an invisible suspension, here with End bracket WN17 mounted as vertical piece.

Reducing piece W14/60 left WEF-0001 Push-in assembly fitted for transition between different widths of Cable trays W1/60 or W3/60.

Reducing piece W14/60 200-100 left Reducing piece W14/60 300-100 left Reducing piece W14/60 400-100 left Reducing piece W14/60 300-200 left Reducing piece W14/60 400-200 left Reducing piece W14/60 400-300 left *EAN-code=732167+Part.no+C (control figure)

A mm

B mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

197 297 397 297 397 397

97 97 97 197 197 297

1.25 1.25 1.25 1.25 1.25 1.25

782163 1 782164 8 782165 5 782166 2 782167 9 782168 6

782517 2 782518 9 782519 6 782520 2 782521 9 782522 6

89 139 198 123 183 158

Use and installation

Used for transition between different widths of trays during wall mounting. Push-in installation.

If necessary, the Reducing piece W14/60 can be locked using Screw set W38P or Locking plug W41.

Suspension components should be mounted in or in connection with the reducing piece. Support bracket/joint W7/60, mounted with a suitable pendant, is used to achieve an invisible suspension, here with End bracket WN17 mounted as vertical piece.

59

Reducing piece W14/60 right WEF-0001 Push-in assembly fitted for transition between different widths of Cable trays W1/60 or W3/60.

Reducing piece W14/60 200-100 right Reducing piece W14/60 300-100 right Reducing piece W14/60 400-100 right Reducing piece W14/60 300-200 right Reducing piece W14/60 400-200 right Reducing piece W14/60 400-300 right *EAN-code=732167+Part.no+C (control figure)

A mm

B mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

197 297 397 297 397 397

97 97 97 197 197 297

1.25 1.25 1.25 1.25 1.25 1.25

782153 2 782154 9 782155 6 782156 3 782157 0 782158 7

782505 9 782506 6 782507 3 782508 0 782509 7 782510 3

89 139 198 123 183 158

Use and installation

Used for transition between different widths of trays during wall mounting. Push-in installation.

60

If necessary, the Reducing piece W14/60 can be locked using Screw set W38P or Locking plug W41.

Suspension components should be mounted in or in connection with the reducing piece. Support bracket/joint W7/60, mounted with a suitable pendant, is used to achieve an invisible suspension, here with End bracket WN17 mounted as vertical piece.

Reducing piece W15/60 straight WEF-0001 Push-in assembly fitted for transition between different widths of Cable trays W1/60 or W3/60.

Reducing piece W15/60 200-100 straight Reducing piece W15/60 300-100 straight Reducing piece W15/60 400-100 straight Reducing piece W15/60 300-200 straight Reducing piece W15/60 400-200 straight Reducing piece W15/60 400-300 straight *EAN-code=732167+Part.no+C (control figure)

A mm

B mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

197 297 397 297 397 397

97 97 97 197 197 297

1.25 1.25 1.25 1.25 1.25 1.25

782104 4 782105 1 782106 8 782107 5 782108 2 782109 9

782491 5 782492 2 782493 9 782494 6 782495 3 782496 0

76 122 179 105 162 134

Use and installation

Used for transition between different tray widths during symmetric ceiling installation. Push-in assembly.

If necessary, the Reducing piece W15/60 can be locked using Screw set W38P or Locking plug W41.

Suspension components should be mounted in or in connection with the reducing piece. Support bracket/joint W7/60, mounted with a suitable pendant, is used to achieve an invisible suspension, here with End bracket WN17 mounted as vertical piece.

61

End cover W45/60 WEF-0001 Push-in assembly mounted as end cover in Cable trays W1/60 or W3/60.

A mm

End cover W45/60-70 68 End cover W45/60-100 98 End cover W45/60-200 198 End cover W45/60-300 298 End cover W45/60-400 398 End cover W45/60-500 498 End cover W45/60-600 598 *EAN-code=732167+Part.no+C (control figure) Use and installation

Mounted as end cover in cable trays. Locked with Screw set W38P or Locking plug W41.

62

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

1.0 1.0 1.0 1.0 1.0 1.0 1.0

782292 8 782293 5 782294 2 782295 9 782296 6 782297 3 782298 0

786771 4 786772 1 786773 8 786774 5 786775 2 786776 9 786777 6

12 13 18 23 28 34 39

Junction box plate W24/60 WEF-0001 Used for installing junction boxes, light fittings etc. in Cable trays W1/60 or W3/60.

Junction box plate W24/60 *EAN-code=732167+Part.no+C (control figure)

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

1.0

718193 3

782659 9

34

Use and installation

The Junction box plate W24/60 is mounted between the bottom of the tray and its folded seam.

If necessary, the Junction box plate W24/60 can be tightened directly in Tray W3/60 with Screw set W38P. If one requires a hidden socket box, the junction box should be folded inwards.

Can be mounted in the middle of Tray W3/60 with Screw set W38P.

To firmly attach Junction box plate W24/60 in Tray W1/60 or W3/60, use blind rivets, selftapping screws or Screw set W38P.

63

Dividing strip 39/55 WEF-0001 Mounted to divide Cable trays W1/60 or W3/60.

Dividing strip 39/55 *EAN-code=732167+Part.nr+C (control figure)

Plate thickness mm

H mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

0.6

55

725785 0

782787 9

73

Use and installation Used to separate tray in two or more ducts, thereby separating control cables from other cables and pipes. The hole structure at distances of 250 mm permits two fixing opportunities with Support band W6 even after cutting.

Support band W6 WEF-0001 The Support band W6 is mounted to fix the lateral position of one or several Dividing strips 39/55.

Support band W6-70 Support band W6-100 Support band W6-200 Support band W6-300 Support band W6-400 Support band W6-500 Support band W6-600 *EAN-code=732167+Part.no+C (control figure)

L mm

Pre-galv. Part. No. C*

Weight kg 100 pcs

67 97 197 297 397 497 597

718828 4 718829 1 718830 7 718831 4 718832 1 718833 8 718834 5

1.0 1.4 2.8 4.3 5.7 7.2 8.6

Use and installation

Support band W6 is mounted to fix one or more Dividing strips 39 laterally. The holes in the support band and the locking pins in Dividing strip 39 allow for a fixed division with intervals of 25 mm.

64

Insert piece W39/55 WEF-0001 Insert piece W39/55 is used to join Dividing strips 39/55.

Insert piece W39/55 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

782299 7

786873 5

19

Use and installation

Insert piece W39/55 is used to join Dividing strips 39/55 and is mounted on Support bracket/joint W7/60.

Luminaire bracket W25/60 Used for assembly of light fittings under Cable trays W1/60 and W3/60.

Luminaire bracket W25/60-70 Luminaire bracket W25/60-100 Luminaire bracket W25/60-200 Luminaire bracket W25/60-300 Luminaire bracket W25/60-400 Luminaire bracket W25/60-500 Luminaire bracket W25/60-600 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

A mm

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

72 101 201 301 401 501 601

1.25 1.25 1.25 1.25 1.25 1.25 1.25

782284 3 782285 0 782286 7 782287 4 782288 1 782289 8 782290 4

782614 8 782615 5 782616 2 782617 9 782618 6 782619 3 782620 9

7.7 8.6 14 18 23 27 32

Use and installation

The luminaire bracket can easily be moved along the tray.

For mounting of lighting fittings under Cable tray W1/60 and W3/60.

65

Cover strip W47/60 WEF-0001 Used for covering space between joined Cable trays W1/60 or W3/60.

B mm

Cover strip W47/60-70 71.5 Cover strip W47/60-100 101.5 Cover strip W47/60-200 202 Cover strip W47/60-300 302 Cover strip W47/60-400 402 Cover strip W47/60-500 502.5 Cover strip W47/60-600 602.5 *EAN-code=732167+Part.no+C (control figure) Use and installation

Cover strip W47/60 is mounted to cover the space that might occur when joining cable trays.

66

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

1.0 1.0 1.0 1.0 1.0 1.0 1.0

786799 8 786800 1 786801 8 786802 5 786803 2 786804 9 786805 6

786806 3 786807 0 786808 7 786809 4 786810 0 786811 7 786812 4

8 9 12 15 18 21 24

Lighting trunking W70

67

Lighting trunking W70 WEF-0001 Use Support bracket W7/40 for joining.

A mm

B mm

C mm

D mm

t mm

L mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 m

40 70 100 200

22 40 40 40

10.5 8.5 8.5 8.5

6 5 5 5

1.5 1 1 1

2995 3000 3000 3000

720980 4 720792 3 720793 0 720794 7

729023 9 729024 6 729025 3 729026 0

107 125 147 220

A mm

B mm

C mm

D mm

t mm

L mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 m

Lighting trunking W70-40 40 22 Lighting trunking W70-70 70 40 Lighting trunking W70-100 100 40 Lighting trunking W70-200 200 40 *EAN-code=732167+Part.no+C (control figure)

10.5 8.5 8.5 8.5

6 5 5 5

1.5 1 1 1

2995 3000 3000 3000

790067 1 790068 8 790069 5 790079 1

790071 8 790072 5 790073 2 790074 9

113 133 157 237

Lighting trunking W70-40 Lighting trunking W70-70 Lighting trunking W70-100 Lighting trunking W70-200

Load capacity

Downward deflection refers to outer compartment

Downward deflection refers to middle compartment

K = Bracket distance

Load kg W70/70-200

A

25 50 30 60 20 40

B C D

68

Installation method K = 1.5 m Deflection mm W70-40 W70/70-200 W70-40

20 40 20 40 20 40

Installation method K = 3 m suspended in joints Load kg Deflection mm W70/70-200 W70-40 W70/70-200 W70-40

1.5 2 25 10 3.5 4.5 50 20 1 2.5 30 10 2.5 5 60 20 2 3 20 10 4 6.5 40 20 Breaking load for Support bracket/joint W7/40-70 = 120 kg

15 30 7 14 13 26

15 31 4 8 19 38

Lighting trunking W71 WEF-0001 Use Support bracket W7/40 for joining.

A mm

Lighting trunking W71-70 70 Lighting trunking W71-100 100 *EAN-code=732167+Part.no+C (control figure)

B mm

C mm

D mm

t mm

L mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 m

40 40

8.5 8.5

6 6

1 1

6000 6000

734511 3 734512 0

734513 7 734514 4

130 153

Load capacity

Downward deflection refers to outer compartment

Downward deflection refers to middle compartment

K = Bracket distance Installation method K = 1.5 m Load kg Deflection mm W71/70-100 W71/70-100

A B C D

25 50 30 60 20 40

Installation method K = 3 m suspended in joints Load kg Deflection mm W71/70-100 W71/70-100

1.5 25 3.5 50 1 30 2.5 60 2 20 4 40 Breaking load for Support bracket/Joint W7/40-70 = 120 kg

15 30 7 14 13 26

69

Support bracket W20 WEF-0001 For invisible installation of Lighting trunking W70/71, width 70 and 100 mm. The support bracket is snapped firmly into the trunking. Threaded rod M10 W76 is used.

W20-100

W20-70

Pre-galv. Part. No. C*

Weight kg 100 pcs

720973 6 721943 8

9 13

Support bracket W20-70 (2 nuts M10 are included) Support bracket W20-100 (2 nuts M10 are included) *EAN-code=732167+Part.no+C (control figure) Use and installation

Support bracket W20-70 is mounted with Threaded rod M10 W76 and 2 M10 nuts.

Lightly press down Support bracket W20-70 into Lighting trunking W70/W71-70.

Support bracket W20-100 is mounted with Threaded rod M10 W76 with 2 M10 nuts.

Support bracket W20A WEF-0001 For invisible installing of Lighting trunking W70/W71, width 70 and 100 mm. Threaded rod M10 W76 is used. The support bracket’s spring locking device facilitates easy vertical adjustment.

W20A-100

W20A-70

Support bracket W20A-70 Support bracket W20A-100 *EAN-code=732167+Part. No.+C (control figure)

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

720970 5 721180 7

729027 7 729028 4

15 20

Use and installation

Support brackets W20A-70 and W20A-100 are mounted on Threaded rod M10 W76. This enables simple vertical adjustment of ±30 mm.

70

Lightly press down Support bracket W20A-70 into Lighting trunking W70/W71-70.

Support bracket W20A-100 is easily snapped firmly into Lighting trunking W70/W71-100.

Pendant brackets W80 and W81 WEF-0001 Used together with Lighting trunking W70-40.

Pendant bracket W80 Pendant bracket W81 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

718474 3 718477 4

729056 7 729057 4

9 8

Use and installation (Only for Lighting trunking W70-40) Pendant bracket W80 mounted under Lighting trunking W70-40 and attached with Screw set W36/W36C. Threaded rod M10 W76 is easily mounted in the spring clasp without bolts. Adjustable to ±30 mm.

Pendant bracket W81 is mounted under Lighting trunking W70-40 and is attached with Screw set W36/W36C. Pendant rail W32 is mounted using Screw set W37. Adjustable to ±18 mm.

Luminaire bracket W35 WEF-0001 For mounting of strip lighting centred under Lighting trunking W70/W71. Use Screw set W36/W36C or W34.

Luminaire bracket W35 *EAN-code=732167+Part.no+C (control figure)

Plate thickness mm

Pre-galv. Part. No. C*

Weight kg 100 pcs

1.5

715650 4

3

Use and installation

Mounted in the rail’s module holes with Screw set W36/W36C or W34. Note! The fork openings must be mounted in the same direction.

71

Luminaire bracket W55 WEF-0001 Used for mounting of light fittings under Lighting trunking W70.

Luminaire bracket W55 *EAN-code=732167+Part.no+C (control figure)

Electro-galv. Part. No. C*

Weight kg 100 pcs

720979 8

0.8

Use and installation

Mounted in the mounting holes in Lighting trunking W70.

Always mount the Luminaire bracket W55 from above so that it rests in the tray.

Luminaire bracket W56 WEF-0001 Used for installation of light fittings in Lighting trunking W71.

Luminaire bracket W56 (screw MSCS6x12) *EAN-code=732167+Part.no+C (control figure) Use and installation

Always mount the Luminaire bracket W56 from above so that it rests in the tray.

72

Aluminium Part. No. C*

Weight kg 100 pcs

734565 6

1

Installation tray W4

73

Installation tray W4, outline of assembly

Components 1. Cantilever arm 50 2. Installation tray W4 3. Joint W2 4. 90˚ bend W4 5. Vertical riser W4, interior 6. Vertical riser W4, exterior 7. Angle bracket W8 8. Screw set W38P 9. Screw set W34

74

Installation tray W4 WEF-0001 Wibe installation trays W4 are perforated with a hole structure suitable for the majority of clamping methods. Suitable even for vertical wall mounting in industries, in lifts and fan rooms. Holes Ø 3.5 mm in the tray bottom allow clamping of cables with plate screws. The tray can also be used for horizontal mounting on cantilever arms. Maximum bracket distance 1.5 m. Joints are to be mounted on the cantilever. A varity of colours can be offered.

t mm

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 m

Installation tray W4-50 3000 50 1.0 Installation tray W4-75 3000 75 1.0 Installation tray W4-100 3000 100 1.0 Installation tray W4-150 3000 150 1.0 Installation tray W4-200 3000 200 1.25 Installation tray W4-250 3000 250 1.25 Installation tray W4-300 1960 300 1.25 Installation tray W4-400 1960 400 1.25 *EAN-code=732167+Part.no+C (control figure)

735988 2 735989 9 735990 5 735991 2 735992 9 735993 6 736609 5 736610 1

735977 6 735978 3 735979 0 735980 6 735981 3 735982 0 736619 4 736620 0

787227 5 787228 2 787229 9 787230 5 787231 2 787232 9 736639 2 736640 8

735999 8 736000 0 736001 7 736002 4 736003 1 736004 8 736005 5 736006 2

57 76 93 125 195 228 238 313

L mm

A mm

Use and installation

Suitable for leading cables down from a cable ladder to machine cabinet etc.

75

Joint W2 WEF-0001 For joining of Installation tray W4.

Plate thickness mm

Pre-galv. Part. No. C*

Joint W2 1.25 788572 5 *EAN-code=732167+Part.no+C (control figure) Use and installation

Used for joining Tray W4. To be mounted on the outside of the tray and attached in bottom with 2 Screw sets W34/W38P.

76

Hot dip galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

788573 2

788574 9

788575 8

8

90˚ bend W4 WEF-0001 For horizontal 90˚ angling of Installation tray W4.

A mm

90˚ bend W4-50 52 90˚ bend W4-75 77 90˚ bend W4-100 102 90˚ bend W4-150 152 90˚ bend W4-200 202 90˚ bend W4-250 252 90˚ bend W4-300 302 90˚ bend W4-400 402 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

724848 3 724849 0 724850 6 724851 3 724852 0 724853 7 724854 4 724855 1

724981 7 724982 4 724983 1 724984 8 724985 5 724986 2 724987 9 724988 6

729095 6 729096 3 729097 0 729098 7 729099 4 729100 7 729101 4 729102 1

782930 9 782931 6 782932 3 782933 0 782934 7 782935 4 782936 1 782937 8

12 19 26 44 66 92 121 192

Use and installation

Used for horizontal 90˚ angling. Mounted outside of W4 trays. Attached in bottom with Screw set W34 (pre-galvanized and powder coated trays). In hot dip galvanized trays Screw set W38P must be used.

77

Vertical riser W4, interior WEF-0001 For vertical 90˚ angling of Installation tray W4.

A mm

Vertical riser W4-50, interior 52 Vertical riser W4-75, interior 77 Vertical riser W4-100, interior 102 Vertical riser W4-150, interior 152 Vertical riser W4-200, interior 202 Vertical riser W4-250, interior 252 Vertical riser W4-300, interior 302 Vertical riser W4-400, interior 402 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

724840 7 724841 4 724842 1 724843 8 724844 5 724845 2 724846 9 724847 6

724934 3 734935 0 734936 7 724937 4 727938 1 724939 8 724940 4 724941 1

729110 6 729111 3 729112 0 729113 7 729114 4 729115 1 729116 8 729117 5

782950 7 782951 4 782952 1 782953 8 782954 5 782955 2 782956 9 782957 6

18 24 30 41 53 65 76 99

Use and installation

Used for vertical 90˚ angling. Mounted outside of trays W4. Attached in bottom with Screw set W34 (pre-galvanized and powder coated trays). In hot dip galvanized trays Screw set W38P must be used.

78

Used for vertical 90˚ angling from cable ladder. Attached to cable ladders with strips.

Vertical riser W4, exterior WEF-0001 For vertical 90˚ angling of Installation tray W4.

A mm

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

Vertical riser W4-50, exterior 52 Vertical riser W4-75, exterior 77 Vertical riser W4-100, exterior 102 Vertical riser W4-150, exterior 152 Vertical riser W4-200, exterior 202 Vertical riser W4-250, exterior 252 Vertical riser W4-300, exterior 302 Vertical riser W4-400, exterior 402 *EAN-code=732167+Part.no+C (control figure)

724832 2 724833 9 724834 6 724835 3 724836 0 724837 7 724838 4 724839 1

724926 8 724927 5 724928 2 724929 9 724930 5 724931 2 724932 9 724933 6

729118 2 729119 9 729120 5 729121 2 729122 9 729123 6 729124 3 729125 0

782970 5 782971 2 782972 9 782973 6 782974 3 782975 0 782976 7 782977 4

18 24 30 41 53 65 76 99

Use and installation

Used for vertical 90˚ angling. Mounted outside of Trays W4. Attached in bottom with Screw set W34 (pre-galvanized and powder coated trays). In hot dip galvanized trays Screw set W38P must be used.

Used for vertical 90˚ angling from cable ladder. Attached to cable ladders with strips.

79

Cantilever arm 50 WEF-0001 For mounting on walls, pendant/fixing rails or vertical pieces.

50L,50/100-300 50L,50/400-600 50L,50/700-1000

A mm

Cantilever arm 50L-100 150 Cantilever arm 50L-150 200 Cantilever arm 50L-200 250 Cantilever arm 50L-250 298 Cantilever arm 50L-300 348 Cantilever arm 50L-400 447 Cantilever arm 50L-500 548 Cantilever arm 50L-600 646 Cantilever arm 50-100 150 Cantilever arm 50-150 200 Cantilever arm 50-200 250 Cantilever arm 50-250 300 Cantilever arm 50-300 350 Cantilever arm 50-400 450 Cantilever arm 50-500 550 Cantilever arm 50-600 650 Cantilever arm 50-700 750 Cantilever arm 50-800 850 Cantilever arm 50-900 950 Cantilever arm 50-1000 1050 *EAN-code=732167+Part.no+C (control figure)

80

F mm

H mm

T mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

34 36 39 56 60 70 77 84 34 36 39 56 60 70 77 84 90 95 100 105

85 85 85 105 105 120 140 150 85 85 85 105 105 120 140 150 150 160 160 170

4 4 4 4 4 5 6 6 4 4 4 6 6 8 8 10 10 10 10 10

725105 6 725106 3 725107 0 725108 7 725109 4 725110 0 725111 7 725112 4 723432 5 723433 2 723434 9 723435 6 723436 3 723437 0 723438 7 723439 4 727125 2 727126 9 727127 6 727128 3

725113 1 725114 8 725115 5 725116 2 725117 9 725118 6 725119 3 725120 9 723440 0 723441 7 723442 4 723443 1 723444 8 723445 5 723446 2 723447 9 727782 7 727783 4 727784 1 727785 8

24 28 34 46 54 103 160 191 24 28 34 52 60 118 172 215 270 310 350 390

Cantilever arm 50 Use and installation

F

F

Installation of a Cantilever arm 50 to a wall using an Expansion bolt. Breaking load F, see table below.

Installation of a Cantilever arm 50 using a T-bolt on pendant/ fixing rails mounted on the wall. Breaking load F, see table below.

F

Installation of Cantilever arm 50 using T-bolt with vertical pieces. Breaking load F, see table below. Also check the breaking load of vertical pieces.

Breaking load F F

Type of cantilever arm 50L-100 50L-150 50L-200 50L-250 50L-300 50L-400 50L-500 50L-600 50-100 50-150 50-200 50-250 50-300 50-400 50-500 50-600 50-700 50-800 50-900 50-1000

Mounted on wall kN kg 1.5 150 1.5 150 1.5 150 2.0 200 2.0 200 3.0 300 3.0 300 3.0 300 3.0 300 3.0 300 2.5 250 4.0 400 4.0 400 6.5 650 7.0 700 7.0 700 6.0 600 5.5 550 5.3 530 5.0 500

Mounted on P/F rail 24/48 with T-bolt 26F kN kg 1.5 150 1.5 150 1.5 150 2.0 200 2.0 200 3.0 300 3.0 300 3.0 300 3.0 300 3.0 300 2.5 250 4.0 400 4.0 400 6.5 650 7.0 700 7.0 700 5.5 550 5.2 520 4.8 480 4.2 420

81

Cantilever arm 80 WEF-0001 For installation of Cable trays W1 and W3. The cantilever arm can be mounted on Vertical piece 7/7L or Wall bracket 80. (Screw set 22S not included)

L mm

H mm

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Weight kg 100 pcs

Cantilever arm 80-100 155 70 730448 6 Cantilever arm 80-150 205 71 730449 3 Cantilever arm 80-200 255 70 730450 9 Cantilever arm 80-250 305 70 730451 6 Cantilever arm 80-300 355 70 730452 3 Cantilever arm 80-400 455 80 730453 0 Cantilever arm 80-500 555 90 730454 7 Cantilever arm 80-600 655 100 730455 4 * EAN-code=732167+Part.no+( (control figure) **Produced to order

732124 7** 732125 4** 732126 1** 732127 8** 732128 5** 732129 2** 732130 8** 732131 5**

12 16 20 28 35 50 65 110

Use and installation

Cantilever arm 80 mounted on Vertical piece 7/7L with Screw set 22S. Infinitely adjustable along the vertical piece. Breaking load see loading table below.

Cantilever arm 80 can also be mounted on both sides of Vertical piece 7 at the same level.

When mounting Cantilever arm 80 on wall, Wall bracket 80 shall be used together with Screw set 22S. Breaking load see loading table below.

Breaking load F

Type of Cantilever arm 80-100 80-150 80-200 80-250 80-300 80-400 80-500 80-600

82

Mounted on Wall bracket 80 kN kg 2.5 250 2.3 230 2.2 220 2.0 200 1.9 190 1.7 170 1.7 170 1.7 170

Mounted at the end of Vertical piece 7/7L kN kg 2.5 250 2.5 250 2.5 250 2.0 200 2.2 220 1.9 190 1.9 190 1.9 190

Mounted along the Vertical piece 7/7L kN kg 2.3 230 2.3 230 2.3 230 2.0 200 2.0 200 1.8 180 1.8 180 1.6 160

Wall bracket 80 For installation of Cantilever arm 80 on wall. Fits all widths. (Screw set 22S not included.)

WEF-0001

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Weight kg 100 pcs

Wall bracket 80 729216 5 * EAN-code=732167+Part.no+C (control figure) **Produced to order

733209 0**

23

Use and installation

Wall bracket 80 shall be mounted with Screw set 22S. Breaking load see loading table for Cantilever arm 80.

Back plate W30 For installation behind internal cantilever arms to reduce the surface pressure on porous walls.

WEF-0001

t mm

Pre-galv. Part. No. C *

Pre-galv. White30 Part. No. C *

Weight kg 100 pcs

Back plate W30 3.0 *EAN-code=732167+Part.no+C (control figure)

786792 9

786793 6

42

Use and installation

Mount Back plate W30 as shown in the illustration to reduce the surface stress on porous walls.

83

Mounting rail 40 Mounting rail 40 is installed between a cantilever arm and wall to reduce surface pressure on porous walls or to enable height adjustment of cantilever arms.

Mounting rail 40 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv. Part. No. C*

ZINKPOX® White30 Part. No. C*

ZINKPOX® White80 Part. No C*

Weight kg 100 pcs

717001 2

729045 1

717006 7

56

Use and installation

The mounting rail is installed between a cantilever arm and wall to reduce surface pressure on porous walls or to enable vertical adjustment of cantilever arms.

Cantilever arm 50 is installed using a T-bolt. The arm is adjustable vertically.

Internal cantilever arm W17 and Adjustable cantilever arm W1840 are mounted with T-bolt. The cantilever arm is vertically adjustable.

Mounting rail WMS25 WEF-0001

Mounting rail WMS 25 *EAN-code=732167+Part.no+C (control figure) Use and installation

Mounting of cables with lashing wire, strips etc.

84

The mounting rail is installed directly onto wall.

Hot dip galv. Part. No. C*

Weight kg 100 pcs

725000 4

147

Threaded rod M8 and M10 W76 WEF-0001 Used for installations of cable trays and lighting trunkings. Joint nut M8 and M10 are used for joining of Threaded rods M8 and M10 W76.

L mm

Threaded rod M8 500 Threaded rod M8 1000 Threaded rod M10 W76-2000 2000 Threaded rod M10 W76-3000 3000 Joint nut M8 Joint nut M10 *EAN-code=732167+Part.no+C (control figure)

Electro-galv. Part. No. C*

Stainl. steel (AISI316) Part. No. C*

725077 6 725079 0 716792 0 716793 7 725083 7 724806 3

725078 3 725080 6 723925 2 723926 9 725084 4 724807 0

Electro-galv. White30 Part. No. C*

729061 1 729062 8

Electro-galv. White80 Part. No. C*

Weight kg 100 pcs

718795 9 718797 3

16 32 100 150 5 7.2

Nut M8 and M10 are used with Threaded rod M8 and M10 W76.

Nut M8 Nut M10 *EAN-code=732167+Part.no+C (control figure)

Hot dip galv. Part. No. C*

Stainl. steel (AISI316) Part. No. C*

Weight kg 100 pcs

725085 1 723938 2

725086 8 723939 9

0.54 1.1

Use and installation

Use Joint nut M8 or M10 when joining 2 pieces of Threaded rods M8 or M10 W76.

The Threaded rod M10 W76 is cut to required length and mounted with 2 Tube pendant attachments W73.

Installation of Threaded rod M8 or M10 W76 with Concrete screw MMS-I.

85

Pendant attachment W21 WEF-0001 Mounted in Support bracket/joint W7 etc.

Plate thickness mm

Pendant attachment W21 2 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

716630 5

734618 9

729054 3

783107 4

12

Use and installation

The Pendant attachment W21 is inserted into the slits in the Support bracket/joint W7 (100400). Does not apply to W7-50, 150, 500 and 600.

The required length of Pendant rail W32 is mounted in the Pendant attachment W21 with Screw set W37. Adjustable to ±30 mm.

For lighter installations with small loads, only one half of the Pendant attachment W21 is mounted in Support bracket W7 with Screw set W36/W36C. The second part of the Pendant attachment W21 is used as a ceiling bracket. The Pendant rail W32 is mounted using Screw set W37.

When mounting with wire, only one half of the Pendant attachment W21 is mounted in Support bracket/joint W7 using Screw set W36/W36C. The wire is mounted through the oval hole and locked with a wire lock.

When mounting cable tray or Lighting trunking W70/W71, one half of Pendant attachment W21 is mounted directly in Support bracket/joint W7 with Screw set W36/W36C. Pendant rail W32 is mounted with Screw set W37.

In concrete ceilings Pendant attachment W21 is mounted with Expansion bolt.

In metal plate ceilings, Pendant attachment W21 is mounted with Ogebe fixing type ED. Use Screw set W36/W36C.

1. Pendant attachment W21 2. Screw set W36/W36C 3. Support bracket/joint W7 4. Cable tray/Lighting trunking

Ceiling installation with cable tray/lighting trunking W7 = Support bracket/joint W21 = Pendant attachment W31 = Ceiling attachment W32 = Pendant rail W36 = Screw set W37 = Screw set W73 = Tube pendant attachment W76 = Pendant bolt M10

86

Tube pendant attachment W73 WEF-0001 Used for mounting of Pendant bolt M10 W76 in ceilings and trays.

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

734621 9

729055 0

783117 3

7

Tube pendant attachment W73 716634 3 *EAN-code=732167+Part.no+C (control figure) Use and installation

The Tube pendant attachment W73 is mounted in Support bracket/joint W7 with Screw set W36/W36C. Does not apply to W7-500 and 600.

The Tube pendant attachment can also be mounted directly in the lighting trunking using Screw set W36/W36C. Does not apply to Lighting trunking W70-40, where Pendant bracket W80 must be used.

Pendant bolt M10 W76 is easily Mounted in wood with self-drilling mounted in the spring clasp with- screws. out screws. Simple adjustment up to ±30 mm. Mounted in concrete ceilings with Expansion bolt.

87

Pendant/Fixing rail 7L, 7 Used with Ceiling bracket 7 to form vertical pieces on site. End plug 7 must be used in Pendant/Fixing rail 7. Pendant/Fixing rail 7L

Pendant/Fixing rail 7

WEF-0001

7L

7

L mm

Pendant/Fixing rail 7L 3020 Pendant/Fixing rail 7 3020 * EAN-code=732167+part.no+C (control figure)

Pre-galvanized Part. No. C*

Hot dip galv. Part. No. C*

Weight kg 100 pcs

734206 8

735432 0 734205 1

360 370

Use and installation

Using Ceiling bracket 7 together with Pendant/Fixing rail 7L/7 makes it possible to produce vertical pieces in different lengths on site. Use 2 Screw sets 22S.

Cantilever arm 80 is infinitely adjustable along Pendant/Fixing rail 7L/7. Screw set 22S shall be used when mounting. End plug 7 must be used on Pendant/Fixing rail 7.

Cantilever arm 80 can also be mounted on both sides of the Pendant/Fixing rail 7 at the same level (not 7L). Breaking load for symmetrical loading 2500 kg (25 kN).

Ceiling bracket 7 To be used with Pendant/Fixing rail 7/7L to form vertical pieces on site.

WEF-0001

11 x 18

Ceiling bracket 7 * EAN-code=732167+Part.no+C (control figure)

Plate thickness mm

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Weight kg 100 pcs

2.5

734331 7

734458 1

40

Use and installation

Using Ceiling bracket 7 together with Pendant/Fixing rail 7/7L makes it possible to produce vertical pieces in different lengths on site. Use 2 Screw sets 22S.

88

Vertical piece 7L, 7 WEF-0001 To be used together with Cantilever arm 80. The Cantilever arm is infinitely adjustable along the Vertical piece. End plug 7 is mounted on Vertical piece 7 on delivery. Vertical piece 7L

Vertical piece 7

L mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

218 290 398 506 614 722 794 902 1010 1118 1190

735207 4 735208 1 735209 8 735210 4 735211 1 735212 8 735213 5 735214 2 735215 9 735216 6 735217 3

780417 7** 780418 4** 780419 1** 780420 7** 780421 4** 780422 1** 780423 8** 780424 5** 780425 2** 780426 9** 780427 6**

46 56 69 83 98 111 120 135 148 162 171

Vertical piece 7-200 216 731871 1 Vertical piece 7-300 288 731872 8 Vertical piece 7-400 396 731873 5 Vertical piece 7-500 504 731874 2 Vertical piece 7-600 612 731875 9 Vertical piece 7-700 720 731876 6 Vertical piece 7-800 792 731877 3 Vertical piece 7-900 900 731878 0 Vertical piece 7-1000 1008 731879 7 Vertical piece 7-1100 1116 731880 3 Vertical piece 7-1200 1188 731881 0 Vertical piece 7-1300 1296 731882 7 Vertical piece 7-1400 1404 731883 4 Vertical piece 7-1500 1512 731884 1 Vertical piece 7-1600 1620 731885 8 * EAN-code=732167+Part.no+C (control figure) **Produced to order

738487 7** 738488 4** 738489 1** 738490 7** 738491 4** 738492 1** 738493 8** 738494 5** 738495 2** 738496 9** 738497 6** 738498 3** 738499 0** 738500 3** 738501 0**

60 70 80 100 110 120 130 150 170 180 190 200 220 230 250

Vertical piece 7L-200 Vertical piece 7L-300 Vertical piece 7L-400 Vertical piece 7L-500 Vertical piece 7L-600 Vertical piece 7L-700 Vertical piece 7L-800 Vertical piece 7L-900 Vertical piece 7L-1000 Vertical piece 7L-1100 Vertical piece 7L-1200

89

Vertical piece 7L, 7 WEF-0001

Loading tables for Vertical piece 7L and 7 Vertical piece 7L

Vertical piece 7

The bending moment M is the total sum of F x A in kgcm. F = Force on cantilever arms in kg F = Loading (kg/m) x Support distance (m) A = Distance between force and centerline vertical piece in cm A = Width of ladder + 1.75 cm 2

The bending moment M is the total sum of F x A in kgcm. F = Force on cantilever arms in kg F = Loading (kg/m) x Support distance (m) A = Distance between force and centerline vertical piece in cm A = Width of ladder + 3.5 cm 2

Use and installation

Cantilever arm 80 is infinitely adjustable along Vertical piece 7L. Screw set 22S must be used when mounting. The cantilever arm must always be mounted in the same direction as the ceiling bracket.

Cantilever arm 80 is infinitely adjustable along Vertical piece 7. Screw set 22S must be used when mounting. End plug 7 must be used on Vertical piece 7.

Cantilever arm 80 can also be mounted on both sides of the Vertical piece 7 at the same level (not 7L). Breaking load for symmetrical loading 2500 kg (25 kN).

End plug 7 For Vertical piece 7 or Pendant/Fixing rail 7.

End plug 7 *EAN-code=732167+Part.no+C (control figure) Use and installations

End plug 7 must always be used at the cut end of Vertical piece 7 or Pendant/-Fixing rail 7.

90

WEF-0014

Polyamide (PA) Red Part. No. C*

Weight kg 100 pcs

730178 2

1.5

U

Pendant/Fixing rail 24/34 WEF-0001 For mounting together with Ceiling bracket 5 to provide vertical pieces.

L mm

Pendant/Fixing rail 24/34 292.5 Pendant/Fixing rail 24/34 382.5 Pendant/Fixing rail 24/34 495 Pendant/Fixing rail 24/34 697.5 Pendant/Fixing rail 24/34 990 Pendant/Fixing rail 24/34 2970 *Ean-code=732167+Part.no+C (control figure)

Pre-galv Part. No. C*

725357 9 725358 6 725359 3 725360 9 725361 6 721102 5

Hot dip galv Part. No. C*

715879 9

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

716309 0

23 31 40 56 80 240

Use and installation

MAX 20 o

1 Pendant/Fixing rail 24/34, 1 Ceiling bracket 5 and 1 Screw set 22S together provide a vertical piece that can be mounted with up to 20º slope.

Side mounting of pendant/fixing rails may be done using 2 Expansion bolts.

91

End plug 28C,D,E and F WEF-0003 Used for mounting in pendant ends to provide protection against personal injury.

End plug 28C End plug 28D End plug 28E End plug 28F * EAN-code=732167+Part.no+C (control figure) Use and installation

End plug 28C fits Vertical piece 2 and Pendant/ Fixing rail 24/34. End plug 28E fits Vertical piece 2F and Pendant/ Fixing rail 24/48.

92

End plug 28F fits Vertical piece 20FS and Pendant/ Fixing rail 24/20FS. End plug 28D fits Vertical piece 20 and Pendant/ Fixing rail 24/20.

Orange plastic Part. No. C*

Weight kg 100 pcs

789875 6 709020 4 709021 1 789876 3

0.5 1 0.5 4

Ceiling bracket 5 WEF-0001 Can be used together with Pendant/Fixing rail 24/34.

Ceiling bracket 5 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

721101 2

718640 2

716293 2

35

Use and installation

Max 20°

1 Pendant/Fixing rail 24/34, 1 Ceiling bracket 5 and 1 Screw set 22S together provide a vertical piece that can be mounted with up to 20º slope. Breaking load for rail 24/34 =1000 kg (10 kN). Breaking load for rail 24/48 = 1200 kg (12 kN).

Ceiling bracket 5 is installed against the back of the pendant rail by turning the bracket 90º and by pushing the lip into the hole of the rail. Next the bracket is turned back again and fastened in the desired position with 1 Screw set 22S. When installing against a horizontal ceiling the bolt must be locked in the recess of the slot for better stability sideways.

93

Bracket 60/40 WEF-0001 Bracket 60/40 is installed together with Pendant/Fixing rail 24/34 to reduce the deflection of long pendants.

Bracket 60/40 *EAN-code=732167+Part.no+C (control figure) Use and installation

Use Bracket 60/40 with Pendant/Fixing rail 24/34 to reduce the deflection of long pendants. Cut the pendant/fixing rail to a suitable length on site.

94

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

718904 5

720531 8

10

Pendant bar 1 WEF-0001 Installed in order to reduce the deflection of long Vertical pieces 2F and 20. A

A

B

Pendant bar 1/300-800

B

Pendant bar 1-1500 A mm

B mm

Pendant bar 1-300 80 300 Pendant bar 1-500 130 500 Pendant bar 1-800 215 800 Pendant bar 1-1500 May vary *EAN-code=732167+Part.no+C (control figure) **Produced to order

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

717640 3 717641 0 717642 7 718903 8

717643 4** 717644 1** 717645 8** 720530 1**

50 80 125 560

Use and installation

In order to reduce deflection of Vertical piece 2F for heavy loads on Internal cantilever arm W17/40 and Cantilever arm 50/50L, Pendant bar 1 is installed with T-bolt. Loadings in accordance with table below. Loading table for Cantilever arm W17/40 Max. loading F at 3˚ deflection of cantilever arm Cantilever arm type Without bar W17/40-100 200 300 400 With bar 1-300 W17/40-100 200 300 400 With bar 1-500 W17/40-100 200 300 400 With bar 1-800 W17/40-100 200 300 400

2F-280 kN kg 0.65 65 0.60 60 0.70 70 0.55 55

2F-370 kN kg 0.65 65 0.60 60 0.70 70 0.55 55

2F-505 kN kg 0.60 60 0.50 50 0.70 70 0.55 55 0.75 75 0.60 60 0.80 80 0.70 70

2F-730 kN kg 0.55 55 0.50 50 0.65 65 0.50 50 0.70 70 0.55 55 0.75 75 0.65 65 0.90 90 0.70 70 0.95 95 0.70 70

2F-1000 kN kg 0.55 55 0.45 45 0.55 55 0.45 45 0.65 65 0.50 50 0.70 70 0.50 50 0.70 70 0.60 60 0.80 80 0.55 55 0.80 80 0.60 60 0.85 85 0.65 65

95

Pendant strip W33 WEF-0001 The Pendant strip W33 is delivered in straight 1 m lengths and bent on site.

Pendant strip W33 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

721786 1

729059 8

19

Use and installation

The Pendant strip W33 is delivered straight. Can be bent on site. Pendants longer than 1 m are joined by overlapping using Screw set W36/W36C.

96

If an adjustment of pendant length is required this can be achieved by cutting the strip in the middle and overlapping the two parts so that a joint can be achieved using Screw set W36/ W36C.

Mounted in open intersections for ceiling installation. Mounted with Screw set W36/W36C in Support bracket/joint W7.

Pendant rail W32 WEF-0001 Pendant rail W32 can be installed in ceilings together with Ceiling attachment W31 or Ogebe fixing type E.

Pre-galv Part. No. C*

Hot dip galv Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

Pendant rail W32 716798 2 *EAN-code=732167+Part.no+C (control figure)

734620 2

729058 1

783122 7

180

Use and installation

The Pendant rail W32 is cut to the required length and mounted in the ceiling with Ceiling attachment W31 and Pendant attachment W21 mounted onto Support bracket/joint W7.

For lighter installations with small loads, only one half of the Pendant attachment W21 is mounted in Support bracket W7 with Screw set W36/W36C. The second part of the Pendant attachment W21 is used as a ceiling bracket. The Pendant rail W32 is mounted using Screw set W37.

The Pendant rail W32 can be joined by placing overlapping and assembly using Screw set W37

Using Locking clamp W77, the Pendant rail W32 can be mounted between two lighting trunkings or cable trays either as a stabiliser or to form a simple dukt.

97

Ceiling attachment W31 Ceiling attachment W31 for Pendant rail W32.

Plate thickness mm

Ceiling attachment W31 2 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

716816 3

734619 6

729063 5

783120 3

6.5

Use and installation

The Ceiling attachment W31 is mounted in concrete ceilings with one or two Expansion bolts. Pendant rail W32 is mounted with Screw set W37. The Ceiling attachment W31 can be rotated 90˚.

The Ceiling attachment W31 can be mounted directly in a slanted ceiling with 2 Expansion bolts.

The Ceiling attachment W31 can be mounted directly in TP ceilings using an Ogebe fixing type E.

The Ceiling attachment W31 can be mounted onto a concrete beam with Expansion bolts.

Locking clamp W77 Mounted to lock Pendant rail W32 when installed between lighting trunking or cable trays as a stabilizer.

Locking clamp W77 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

1.25

716797 5

729060 4

1.5

Use and installation

Pendant rail W32 mounted with Screw set W36/W36C or W34.

98

Locking clamp W77 used when Pendant rail W32 is mounted between two Lighting trunking W70/W71 or cable trays as a stabilizer.

Locking clamp W77 fixed to the fold of trunking/tray with a pair of pliers.

Fixing rail 24/26x53, casting-in For casting-in in walls and ceilings.

WEF-0001

lx

Fixing rail 24/26x53 for casting-in

10.39 cm4

Transverse force Wx ly 3 3.92 cm 2.78 cm4

Wy

Hot dip galv. Part. No. C*

Weight kg 100 pcs

1.90 cm3

768063 4

970

* EAN-code=732167+Part.no+C (control figure) Use and installation

Fixing rail 24/26 x 53 for castingin in walls and ceilings. Mount cantilever arms with T-bolt 26F.

Max. pull-out load: 1000 kg/0.5 m of casting-in fixing rail (Concrete class K200).

99

Vertical piece 2FPK For installations in ceilings close to wall.

L mm

WEF-0001

Hot dip galv. Part. No. C*

Vertical piece 2FPK-300 280 788655 5 Vertical piece 2FPK-500 500 788656 2 Vertical piece 2FPK-750 730 788657 9 Vertical piece 2FPK-1000 1000 788658 6 * EAN-code=732167+Part.no+C (control figure) **Produced to order

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

788660 9** 788661 6** 788662 3** 788663 0**

120 155 205 250

Loadings

Vertical piece 2FPK mounted in Vertical piece 2FPK mounted in Deflection of Vertical piece 2FPK the inner hole. the outer hole. is reduced by installing Pendant Breaking load=1400 kg Breaking load=200 kg bar 1. Loadings in accordance (14 kN) at symmetrical loading. (2kN) at symmetrical loading. with table below. Max permitted load F at max permitted deflection 1/20 of the length L of the cantilever arm in accordance to standard IEC 61537. Cantilever arm Without Pendant bar 1 With Pendant bar 1/500

50-200 L=250 50-400 L=450 50-600 L=650 50-200 L=250 50-400 L=450 50-600 L=650

2FPK-300 kg 140 145 105

Use and installation

Vertical piece 2FPK can be mounted in ceiling close to wall.

100

Vertical piece 2FPK is suitable for floor mounting.

2FPK-500 kg 130 135 100

2FPK-750 kg 100 95 80 155 165 115

2FPK-1000 kg 80 75 60 125 120 90

Vertical piece 2 WEF-0001 To be used for installation of centre pendant of Cable trays W1 and W3, mesh trays and lighting trunking.

Vertical piece 2-300 Vertical piece 2-400 Vertical piece 2-500 Vertical piece 2-700 Vertical piece 2-1000 *EAN-code=732167+Part.no+C (control figure)

L mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

279 392 504 729 1022

717191 0 717192 7 717193 4 717194 1 717195 8

716283 3 716284 0 716285 7 716286 4 716287 1

52 62 72 93 120

Use and installation

Mount Vertical piece 2 using an Expansion bolt alt. Concrete screw.

Mount Vertical piece 2 on Fixing rail 24/26x53 for casting-in using T-bolt.

Vertical piece 2 may be joined to achieve the required length using Pendant/Fixing rail 24/34 and Pendant joint 2J.

Support bracket W1940/W1960 can be mounted on Vertical piece 2 with Angle bracket W8S. Use Screw set W36/W36C.

Support bracket W1940/1960 mounted in the fixing plate of the vertical piece with Screw set W36/W36C.

Use Pendant joint 2J to join two Vertical pieces 2.

101

Vertical piece 2F WEF-0001 Used for installation of Internal cantilever arm W17/40, Adjustable cantilever arm W1840/W1860 or Cantilever arm 50.

Vertical piece 2F-280 Vertical piece 2F-370 Vertical piece 2F-505 Vertical piece 2F-730 Vertical piece 2F-1000 Vertical piece 2F-1500 *EAN-code=732167+Part.no+C (control figure)

L mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

280 370 505 730 1000 1495

717196 5 717197 2 717198 9 717199 6 717200 9 787276 3

717201 6 717202 3 717203 0 717204 7 717205 4 787277 0

80 100 130 170 220 290

Use and installation

Mounted in ceiling with Expansion bolt alt. Concrete screw.

102

Cantilever arm 50 is mounted with a T-bolt.

Internal cantilever arm W17/40 is mounted with a T-bolt.

In order to reduce the deflection of Vertical piece 2F for heavy loads on Internal cantilever arm W17/40 and Adjustable cantilever arm W1840/W1860, Pendant bar 1 is installed.

Vertical piece 20 WEF-0001 Used for vertical installation with cantilever arms from a ceiling or on a floor.

Vertical piece 20-505 Vertical piece 20-730 Vertical piece 20-1000 Vertical piece 20-1500 Vertical piece 20-2000 Vertical piece 20-3000 *EAN-code=732167+Part.no+C (control figure)

L mm

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

505 730 1000 1495 1990 2980

715723 5 715724 2 715725 9 715726 6 715727 3 715728 0

716276 5 716277 2 716278 9 716279 6 716280 2 716281 9

250 330 440 620 800 1180

Use and installation

Mounted in ceiling with Expansion bolt alt. Concrete screw.

Internal cantilever arm W17/40 is mounted with a T-bolt.

On Vertical piece 20, mount Can- Vertical piece 20 may be tilever arm 50 using a T-bolt. equipped with a protective orange coloured End plug 28D.

103

End bracket WN17 WEF-0001 Used as vertical piece, for example mounted on Support bracket/joint W7 to achieve an invisible suspension.

End bracket WN17 *EAN-code=732167+Part.no+C (control figure) Use and installation

End bracket WN17 can be mounted as vertical piece on Support bracket/joint W7, use Screw set W36/W36C. The end brackets are joined with 2 Screw sets 22S. Max symmetrical load on the end bracket is 100 kg at a tightening torque of 10.4 Nm.

104

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Pre-galv. White80 Part. No. C*

Weight kg 100 pcs

733090 4

733091 1

733092 8

10

Angle bracket W8 WEF-0001 The angle bracket is mounted in the tray horizontally to a wall or vertically to a floor. The angle bracket can also be mounted as a pendant bracket in the lighting trunking. It can also be used as stabilizing angle.

Pre-galv. Part. No. C*

Angle bracket W8 716821 7 *EAN-code=732167+Part.no+C (control figure)

Hot dip galv. Part. No. C*

Pre-galv. White30 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

728883 0

729066 6

783124 1

6

Use and installation

2 Angle brackets W8 are mounted in Cable trays W1/40 or W3/40 using 2 Screw sets W38P for horizontal connection to wall and vertical connection to floor. Can be mounted with legs pointing inwards or outwards.

Angle bracket W8 mounted in bottom of lighting trunking with Screw set W36/W36C. Expansion bolts are used for installation in concrete walls. In sheet metal walls mounting is achieved with an Ogebe fixing type ED.

Horizontal installation of Cable tray W3/W1 on floor or vertically on wall. The angle bracket W8 can be turned to reduce the distance to floor or wall.

Horizontal installation of Cable tray W3 on floor or vertically on wall. The angle bracket W8 can be turned to reduce the distance to floor or wall.

The Angle bracket W8 is mounted to achieve clearance from wall or where there is a large asymmetric load on the tray at pendant installation. Mounted at a distance of 1.5-2 m.

Angle bracket mounted in bottom of lighting trunking with Screw set W36/W36C as pendant attachment.

105

Angle bracket W8S WEF-0001 To be used for various installations of Pendant/Fixing rail 24/34, support brackets etc.

Pre-galv. Part. No. C*

Angle bracket W8S 728071 1 *EAN-code=732167+Part.no+C (control figure)

Hot dip galv. Part. No. C*

Pre-galv. White80 Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

726873 3

726874 0

783126 5

8

Use and installation

Vertical piece 2 or Pendant/ Fixing rail 24/34 can be mounted with Angle bracket W8S directly into the lighting trunking. Use Screw set 22S.

Support bracket 3 can be Support bracket W1940/ W1960 mounted in ceilings with Angle can be mounted on Ceiling bracket W8S and Screw set 22S. bracket 5 with Angle bracket W8S and Screw set 22S.

Clamp suspension of cable tray can be made with Pendant/Fixing rail 24/34, Angle bracket W8S and Screw set 22S.

Angle bracket W8S can be used for installations in Pendant/Fixing rail 24/34. Use Screw set 22S. An easy way to build stands for electrical cabinets.

106

Support bracket/joint W7 can be mounted directly on Vertical piece 2 with Angle bracket W8S and Screw set 22S. Does not apply to widths used for joining only.

Support bracket W1940/ W1960 can be mounted on Vertical piece 2 with Angle bracket W8S and Screw set 22S.

Fixing tray N for casting-in WEF-0001 Pieces of Polystyrene at both ends makes it possible to adjust the height of the tray.

Fixing tray N-300 for casting-in Fixing tray N-400 for casting-in *EAN-code=732167+Part.no+C (control figure)

A mm

Pre-galv. Part. No. C*

Weight kg 100 pcs

330 430

782695 7 782696 4

1800 2200

Use and installation

Fixing tray N for casting-in mounted in the mould.

Fixing tray N adjusted onto the mould (from out- or inside).

The length is adjustable to ceiling and floor by moving the pieces of Polystyrene, total height min 2400-max 3000 mm.

The mesh tray mounted into the Fixing tray N is used for mounting of cables.

107

Lashing wire WEF-0011 For lashing of wires in mesh trays.

HTR-2303 Lashing wire, stainless steel, white PVC HTR-2313 Lashing wire, stainless steel, black PVC HT-2304 Lashing wire, white PVC HT-2314 Lashing wire, black PVC *EAN-code=732167+Part.no+C (control figure)

Diam mm

Breaking load kg

Part. No. C*

Weight kg 100 m

1.25 1.25 1.5 1.5

92 92 25 25

713686 5 713687 2 713684 1 713685 8

1.3 1.3 1.8 1.8

Use and installation

Lashing wire is used for mounting in mesh trays.

Ceiling mesh tray WN2 WEF-0001

For installation in ceilings. Wire Ø4.4 mm.

2000

B

A

A

B

Electro-galv. Part. No. C*

Ceiling mesh tray WN2 100 60 727991 3 *EAN-code=732167+Part.no+C (control figure) Use and installation

Mounted in ceilings with Ceiling bracket WN16.

108

Mounted under desks with Ceiling bracket WN16.

Hot dip galv. Part. No. C*

Stainl. steel (AISI316) Part. No. C*

Electro-galv. White80 Part. No. C*

Weight kg 100 pcs

727992 0

727993 7

727994 4

100

Ceiling bracket WN16 For installation of Ceiling mesh tray WN2.

WEF-0001

Electro-galv. Part. No. C*

Hot dip galv. Part. No. C*

Stainl. steel (AISI316) Part. No. C*

Electro-galv. White80 Part. No. C*

Weight kg 100 pcs

727996 8

727997 5

727998 2

5

Ceiling bracket WN16 727995 1 *EAN-code=732167+Part.no+C (control figure) Use and installation

Ceiling mesh tray WN2 must be mounted with Ceiling bracket WN16.

Ceiling mesh tray WN2 mounted under desks with Ceiling bracket WN16.

Earth clamp W79 Suitable for mounting on Junction box plate W24. Used for protective earthing.

Earth clamp W79 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Electro-galv. Part. No. C*

Weight kg 100 st

716640 4

0.2

Use and installation

Earth clamps W79 are intended for use when the earthing of mounting plates for the installation of machines complying with regulations for use of high tension current is required. The junction box plate’s (mounting plate’s) oval holes facilitate the moving of the Earth clamp W79 so that it is always located under the machine casing. If the machine’s earth clamp is not approved for splicing of earth cable, this must pass in unbroken state through the machine’s earth clamp to the earth clamp in the junction box plate. Wibe Junction box plate W24 and Earth clamp W79 are approved by the National Electrical Inspectorate 850513 in accordance with annotation S24-138/85.

109

Cover plate W16 WEF-0001 Mounted with Screw set W36/W36C under 90˚ bends, T- and X-junction if one needs to level out differences in levels between tray and junction.

A mm

Cover plate W16-70 70 Cover plate W16-100 100 Cover plate W16-200 200 Cover plate W16-300 300 Cover plate W16-400 400 *EAN-code=732167+Part.no+C (control figure) Use and installation

Mounted with Screw set W36/ W36C under X-junction W13/40 if one needs to level out differences in height between tray and bend.

110

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

1.5 1.5 1.5 1.5 1.5

718036 3 718037 0 718038 7 718039 4 718040 0

729154 0 729155 7 729156 4 729157 1 729158 8

6 12 48 108 192

Dividing strip 39 WEF-0001 Mounted to divide a cable tray or lighting trunking into two or more channels in order to separate different types of cables and pipes. Mounted with Support band W6.

Dividing strip 39/24 Dividing strip 39/55

Plate thickness mm

H mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Pre-galv. White80 Part. No. C*

Weight kg 100 pcs

0.6 0.6

24 55

718835 2 725785 0

782787 9

717950 3 725786 7

46 73

Plate thickness

Dividing strip 39/24 0.6 Dividing strip 39/55 0.6 *EAN-code=732167+Part.nr+C (control figure)

H mm

Hot dip galv. Part. No. C*

Stainl. steel (AISI316L) Part. No. C*

Weight kg 100 pcs

24 55

731747 9 732983 0

725593 1 725594 8

46 73

Use and installation

Used to separate tray or trunking in two or more ducts thereby separating control cables from other cables and pipes. The hole structure at distances of 250 mm permits two fixing opportunities with Support bands W6 even after cutting.

111

Insert piece W39 WEF-0021 Insert piece W39 is used to join Dividing strips W39.

Insert piece W39 *EAN-code=732167+Part.no+C (control figure)

Plastic Part. No. C*

Weight kg 100 pcs

716824 8

3

Use and installation

Insert piece W39 is used to join Dividing strips W39 and is mounted on Support bracket/joint W7 or Internal cantilever arm W17/40. When mounting over Internal cantilever arm W17/40, break away plastic bit from component.

Support band W6 WEF-0001 The Support band W6 is mounted to fix the lateral position of one or several Dividing strips 39.

Support band W6-70 Support band W6-100 Support band W6-200 Support band W6-300 Support band W6-400 Support band W6-500 Support band W6-600 *EAN-code=732167+Part.no+C (control figure)

L mm

Pre-galv. Part. No. C*

Weight kg 100 pcs

67 97 197 297 397 497 597

718828 4 718829 1 718830 7 718831 4 718832 1 718833 8 718834 5

1.0 1.4 2.8 4.3 5.7 7.2 8.6

Use and installation

Support band W6 is mounted to fix one or more Dividing strips 39 laterally. The holes in the support band and the locking pins in Dividing strip 39 allow for a fixed division with intervals of 25 mm.

112

Tele-conduit 36 WEF-0001 With knock-out holes Tele-conduit is installed where a separate tray is required for low-tension cables.

B mm

C mm

Pre-galv. Part. No. C*

Hot dip galv. Part. No. C*

Pre-galv. White80 Part. No. C*

Weight kg 100 pcs

Tele-conduit 36-50 42 Tele-conduit 36-100 92 Tele-conduit 36-200 192 *EAN-code=732167+Part.no+C (control figure)

50 100 200

725065 3 725066 0 725067 7

731748 6 731749 3 731750 9

725068 4 725069 1 725070 7

94 142 238

Use and installation

Make a hole for cable passage by pushing out the washer from below with a screw driver or similar.

113

Cover W5 WEF-0001 Length 2000 mm. The cover is used for screening control cables and in dusty and dirty premises.

Cover W5-60 Cover W5-70 Cover W5-100 Cover W5-150 Cover W5-200 Cover W5-300 Cover W5-400 Cover W5-500 Cover W5-600

t mm

B mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

0.7 0.7 0.7 0.7 0.7 0.7 1.0 1.0 0.7

61 71 101 151 201 301 401 501 601

732213 8 732214 5 732215 2 732216 9 732217 6 732218 3 732219 0 732220 6 732221 3

734133 7 729015 4 729016 1 733134 5 729017 8 729018 5 729019 2 729020 8 729021 5

90 100 140 190 250 360 680 840 700

t mm

B mm

Cover W5-60 1.0 61 Cover W5-70 1.0 71 Cover W5-100 1.0 101 Cover W5-150 1.0 151 Cover W5-200 1.0 201 Cover W5-300 1.0 301 Cover W5-400 1.0 401 Cover W5-500 1.0 501 Cover W5-600 1.0 601 *EAN-code=732167+Part.no+C (control figure)

Hot dip galv. Part. No. C*

ZINKPOX® White80 Part. No. C*

Weight kg 100 pcs

732261 9 732262 6 732263 3 732264 0 732265 7 732266 4 732267 1 732268 8 732269 5

782362 8 782363 5 782364 2 782365 9 782366 6 782367 3 782368 0 782369 7 782370 3

140 160 210 290 370 540 710 880 1050

Use and installation

Used for screening of control cables and in dusty and dirty premises.

114

Covers must be mounted on cable trays with Cover clamp W62.

Cover clamp W62 WEF-0001 Used for fixing covers on Trays W1 and W3 as well as on Lighting trunking W70/W71.

Cover clamp W62 *EAN-code=732167+Part.no+C (control figure)

Stainl. steel (AISI304) Part. No. C*

Weight kg 100 pcs

730186 7

0.8

Use and installation

Cover clamp W62 used for fixing the covers on Cable tray W1 and W3 as well as on Lighting trunkings W70 and W71.

Start by pressing the Cover clamp W62 over the sides of the cover. Then snap the cover over the folded edges of the tray. 6 Cover clamps W62 are needed per cover.

115

Combi bracket 53 Used for mounting cable trays, mesh trays and cable ladders on seemed roofing sheet etc.

WEF-0001,-0031

Hot dip galv. Part. No. C*

Combi bracket 53 Insulating plate 54 *EAN-code=732167+Part.no+C (control figure)

Plastic Part. No. C*

Weight kg 100 pcs

787223 7

26 2

782353 6

Breaking load* Type of roofing sheet

Insulating plate

Permitted load

Bandsheet Prelac Copper sheeting Bandsheet Prelac Copper sheeting

No Yes No Yes

F1=100 kg F2=50 kg F3=100 kg F4=50 kg

* Loading values and fixing of roof sheet - follow the supplier´s recommendations Test have been made of: Bandsheet Prelaq BLX t=0.6 SSAB tunnplåt Copper sheeting annealed SS 5015-80 t=0.6 Tightening torque at test=60Nm Use and installation

Combi bracket 53 mounted on seamed roofing sheet.

Alternative mounting of Combi bracket 53.

In order to avoid contact between Combi bracket 53 and copper sheeting, Insulating plate 54 must be used.

Alternative mounting of Combi bracket 53 and Insulating plate 54.

Cable ladder mounted across the seams of the roofing sheets with Combi bracket 53, Wall bracket 11/25 and Screw set 22S.

Cable ladder mounted along the seams of the roofing sheets with Combi bracket 53, Wall bracket 11/25, Screw set 22S, Pendant/ Fixing rail 24/48 and T-bolt 26F.

Mesh tray mounted along the seams of the roofing sheets with Combi bracket 53 and accessories from the Mesh tray program.

Mesh tray mounted across the seams of the roofing sheets with Combi bracket 53 and accessories from the Mesh tray program.

116

Strip fixing W44 WEF-0022 The Strip fixing W44 enables strapping of cables in an unperforated tray.

Strip fixing W44 *EAN-code=732167+Part.no+C(control figure)

Plastic (black) Part. No. C*

Weight kg 100 pcs

718469 9

1.0

Use and installation

The Strip fixing W44 is provided with double sided adhesive tape and is attached to the tray bottom. Alternatively, blind rivets or self-tapping screws can be used. When mounting with double sided adhesive tape, the surface on the tray bottom must be wiped clean. Loads may not be applied until after 24 hours. Full adhesion is obtained after 72 hours in 21˚C. Ideal application temperature is 21˚-38˚C. Application below normal room temperature is not recommended. Each Strip fixing W44 can be split up in 2 to 6 pieces. Supplied with 50 pieces in a plastic bag.

Protection strip W48 Used to protect the cables from damage.

Protection strip W48 *EAN-code=732167+Part.no+C (control figure)

WEF-0030

Plastic Part. No. C*

Weight kg 100 pcs

787211 4

6.1

Use and installation

When cutting a cable tray you can mount Protection strip W48 to protect the cables from damage.

117

Luminaire bracket W50 For mounting light fittings between two parallel Cable trays W1/W3 or Lighting trunking W70/W71. Dimension H is specified when ordering.

H mm

Luminaire bracket W50 ** *EAN-code=732167+Part.no+C (control figure) **Selected with respect to height of the light fittings ***H=100 mm

WEF-0001

Plate thickness mm

Pre-galv Part. No. C*

Pre-galv. White80 Part. No. C*

Weight kg 100 pcs

2.5

720520 2

720785 5

25***

Use and installation

Repair paint Galvafroid for repair of damaged places on pre-galvanized or hot dip galvanized cable trays and accessories. Repair paint for minor damages of powder coated products.

Anti-corrosive paint "Galvafroid", tin Repair paint White RAL 9003 Gloss 30, spray bottle Repair paint White RAL 9010 Gloss 80, spray bottle *EAN-code=732167+Part.no+C (control figure)

WEF-0013, 0016

Volume l

Part. No. C*

Weight kg 100 pcs

0.3 0.4 0.4

717637 3 739713 6 728027 8

86 60 60

Use and installation

Galvafroid used to increase the protection of cut or damaged places.Applied with a colour brush.

118

Repair paint in spray bottle for repainting of minor paint damages.

Screw set 22S For mounting of Ceiling bracket 5 on Pendant/Fixing rail 24/34 and Cantilever arm 80 on Vertical piece 7 or Wall bracket 80 etc.

Screw set 22S (bolt MVBF8x16+nut M6MF8) *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv. Part. No. C*

Stainl. steel (AISI316) Part. No. C*

Weight kg 100 pcs

713694 0

725582 5

1.9

Spring nut M8 For permanent mounting of fittings (instrument cabinets etc.) on Pendant/Fixing rail 24/48.

Spring nut M8 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv. Part. No. C*

Weight kg 100 pcs

716407 3

2.7

Mounting set W78 For mounting of Threaded rod M10 W76 in plate or light concrete ceilings.

WEF-0001

Mounting set W78 (washer diam.50+nut M6M10) *EAN-code=732167+Part.no+C (control figure)

Hot dip galv. Part. No. C*

Weight kg 100 pcs

717069 2

5.5

Screw set W36 For mounting of pendant attachments in Support bracket/Joint W7.

WEF-0001

Electro-galv. Part. No. C*

Stainl. steel (AISI316) Part. No. C*

Weight kg 100 pcs

715646 7

725581 8

1.2

Screw set W36 (bolt MVBF8x16+nut M6MF8) *EAN-code=732167+Part.no+C (control figure)

Screw set W36C Slotted screw used for mounting of pendant attachments in Support bracket/joint W7.

Screw set W36C (Slotted screw M8x16+nut M6MF 8 toothed) *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Electro-galv. Part. No. C*

Weight kg 100 pcs

783500 3

1.8

119

Screw set W37 For assembly of Pendant attachment W21 and Ceiling attachment W31 with Pendant rail W32. For joining of Pendant rail W32.

Screw set W37 (bolt MVBF 8x35+nut M6MF 8) *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Electro-galv. Part. No. C*

Stainl. steel (AISI316) Part. No. C*

Weight kg 100 pcs

716799 9

725586 3

2.8

Screw set W38P Used for mounting of joints, bends, junctions, Shade ledge W26 and Integrated ceiling support channel W27. Screw set W38P pierces through lacquered surfaces securing potential balancing. N. B. The joints must be unlacquered. Patented.

Electro-galv. Part. No. C*

Dacromet Part. No. C*

Screw set W38P 735177 0 733258 8 *Ean-code=732167+Part.no+C (control figure) **White laquered screw head

WEF-0001

Electro-galv. White60** Part. No. C*

Weight kg 100 pcs

782216 4

0.4

Screw set W34 For mounting Tray W3 on Cantilever arm 50. For mounting Junction box plate W24 in Tray W3, Lighting trunking W70 and W71. For mounting Locking clamp W77 or Angle bracket W8 onto Pendant rail W32. For assembly of Angle bracket W8 (light fitting bracket). For joining of Installation Trays W4 and installations with Profile W-swing 2.

Screw set W34 (bolt MSCS 6x12+nut M6MF6) *EAN-code=732167+Part.nr+C (control figure)

WEF-0001

Dacromet Part. No. C*

Electro-galv. Part. No. C*

Stainl. steel (AISI316) Part. No. C*

Weight kg 100 st

734646 2

718473 6

725589 4

0.8

Screw W40 For locking of T-joint W29 in open junctions.

Screw W40 (screw RXS ST 5.5x13-H) *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Electro-galv Part. No. C*

Weight kg 100 pcs

721868 4

0.3

Locking plug W41 For quick locking of joints, bends and branches in cable trays and lighting trunking.

Locking plug W41 *EAN-code=732167+Part.no+C (control figure)

120

WEF-0004

Plastic Part. No. C*

Weight kg 100 pcs

718645 7

0.1

T-bolt 26F WEF-0002 Used for mounting with Pendant/Fixing rails.

D A L T-bolt 26F/M8 T-bolt 26F/M10 (For P/F-rail 24/48) D

L mm

T-bolt 26F M8 30 T-bolt 26F M10 30 T-bolt 26F M8 40 T-bolt 26F M10 40 T-bolt 26F M8 50 T-bolt 26F M10 50 *EAN-code=732167+Part.no+C (control figure)

A mm

Electro-galv. Part. No. C*

Hot dip galv. Part. No. C*

Stainl. steel (AISI316) Part. No. C*

Weight kg 100 pcs

24 24 34 34 44 44

734983 8 734864 0 734984 5 734865 7 734985 2 734866 4

734744 5 716794 4 734745 2 716795 1 734746 9 716796 8

734986 9 728596 9 734987 6 728597 6 734988 3 728598 3

4.5 7 5 7.5 5.5 8

Max permitted extraction force T-bolt 26F M8/M10 + P/F-rail 24/48 +Washer 8,4x19x1,5

T-bolt 26F M8 + P/F-rail 24/48 + Washer 9x35x2

T-bolt 26F M10 + P/F-rail 24/48 + Washer 9x35x2

Use and installation

Installation of Pendant/Fixing rail on floor (or wall) with Angle bracket 5L and T-bolt.

Check the position mark on the bolt to ensure the right position of the T-bolt in the rail.

T-bolt M8 makes it possible to mount through the perforation of Pendant/Fixing rail 24/48.

121

Expansion bolts Electro-galvanized, hot dip galvanized or stainless steel AISI316. For installation of all Wibe cantilever arms and vertical pieces.

D mm

L mm

G mm

WEF-0001

Electro-galv Part. No. C*

Hot dip galv. Part. No. C*

Stainless steel (AISI316) Part. No. C*

Expansion bolt M6x40** 6 40 18 782222 5 782237 9 782252 2 Expansion bolt M6x65** 6 65 28 782223 2 782238 6 782253 9 Expansion bolt M8x50** 8 50 24 782224 9 782239 3 782254 6 Expansion bolt M8x95** 8 95 41 782225 6 782240 9 782255 3 Expansion bolt M8x120** 8 120 66 782226 3 782241 6 782256 0 Expansion bolt M10x60 10 60 29 782227 0 782242 3 782257 7 Expansion bolt M10x80 10 80 34 782228 7 782243 0 782258 4 Expansion bolt M10x100 10 100 54 782229 4 782244 7 782259 1 Expansion bolt M12x85 12 85 35 782230 0 782245 4 782260 7 Expansion bolt M12x100 12 100 50 782231 7 782246 1 782261 4 Expansion bolt M12x145 12 145 82 787052 3 787053 0 787054 7 Expansion bolt M16x110 16 110 53 782232 4 782247 8 782262 1 Expansion bolt M16x125 16 125 63 782233 1 782248 5 782263 8 Expansion bolt M16x150 16 150 76 782234 8 782249 2 782264 5 Expansion bolt M20x170 20 170 55 782235 5 782250 8 782265 2 Expansion bolt M20x220 20 220 55 782236 2 782251 5 782266 9 * EAN-code=732167+Part.no+C (control figure) ** M6 and M8 are delivered with an extra washer with a larger diameter. This washer must be mounted close to the cantilever arm or vertical piece. The smaller standard washer must be put on top of the bigger washer close to the nut.

Use and installation

D1= Drill diameter M = Installation depth B = Min. drilling depth T = Material thickness Data for installation

Dim M6x40 M6x65 M8x50 M8x95 M8x120 M10x60 M10x80 M10x100 M12x85 M12x100 M12x145 M16x110 M16x125 M16x150 M20x170 M20x220

122

D1 mm 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20

B mm 35 50 45 65 65 60 70 70 80 80 80 105 105 105 150 150

M mm 30 50 35 55 55 40 60 60 50 75 75 100 100 100 120 120

T mm 5 15 5 30 55 5 10 30 5 20 60 5 20 45 20 70

Tightening moment Nm 7 7 20 20 20 35 35 35 55 55 55 100 100 100 240 240

Weight kg 100 pcs

1.04 1.54 2.22 3.61 4.35 4.44 5.32 6.28 8.17 9.23 12.5 18.57 20.4 23.9 44.83 57.02

Expansion bolts WEF-0001 Extraction force

Permitted extraction force in kN for various concrete qualities Dim

Installation depth mm

C25

Concrete class C30

C35

C40

M6 M6 M6 M8 M8 M8 M10 M10 M12 M12 M12 M16 M20

30 40 50 35 40 55 40 60 50 75 80 100 120

1.4 2.3 3.2 1.6 2.0 3.3 2.2 4.0 3.1 6.5 7.5 9.4 12.3

1.6 2.8 3.5 1.8 2.4 3.8 2.5 4.5 3.5 7.4 8.5 10.7 14.0

1.8 2.9 3.7 2.0 2.5 4.0 2.8 5.0 3.9 7.8 9.0 12.0 15.7

2.0 3.0 4.0 2.3 2.9 4.7 3.1 5.6 4.4 9.3 10.5 13.4 17.4

Transverse force

Permitted transverse force in kN for various concrete qualities Dim

Installation depth mm

C25

Concrete class C30

C35

C40

M6 M6 M6 M8 M8 M8 M10 M10 M12 M12 M12 M16 M20

30 40 50 35 40 55 40 60 50 75 80 100 120

1.1 1.6 2.2 1.4 2.0 3.8 1.6 5.7 2.2 9.6 10.6 12.3 15.9

1.3 2.1 2.4 1.6 2.2 4.0 1.8 6.0 2.5 9.9 11.0 12.8 17.0

1.5 2.2 2.6 1.8 2.4 4.2 2.0 6.2 2.7 10.2 11.4 13.2 17.5

1.6 2.3 2.8 1.9 2.5 4.4 2.2 6.5 3.0 10.5 12.2 13.7 19.3

123

Fixing system

124

Concrete screw MMS-S For installation with cantilever arms and vertical pieces. Concrete screw with hexagonal head and special thread constructed for safe fixing in concrete or brickwork. Suitable for fixing of tubes, electrical installations, rails, handrails, machines, ventilating ducts, wood constructions. ❑ Easy to install ❑ High extraction values are obtained due to the special thread. The drill diameter is the same as the root diameter of the screw which gives a solid fixing inside the hole. ❑ Can be dismounted and reinstalled without reduced extraction force. ❑ A weaker drill can be used compared to using anchor, expansion bolt, screw and plug. ❑ Suitable in environments which are fire classified. Use and installation

Installation of cantilever arms.

Installation of vertical pieces.

Concrete screw MMS-S Electro-galvanized

WEF-0001

A = Drill diameter B = Min. installation depth C = Min. drilling depth F = Extraction force kN** T = Transverse force kN N = Width of jaws **For concrete class C25 Part. No. C*

F kN

T kN

N mm

ØxL mm

A mm

B mm

C mm

Number/ package

Weight kg 100 pcs

MMS-S 6x401

787067 7

2.40

2.2

10

6x40

5

30

50

200

0.74

MMS-S

6x501

787047 9

2.80

2.2

10

6x50

5

30

50

100

0.92

MMS-S

6x601

787048 6

2.80

2.2

10

6x60

5

30

50

100

1.03

MMS-S 7.5x352

781550 0

2.50

4.8

13

7.5x35

6

30

50

100

1.2

MMS-S 7.5x402

781551 7

2.50

4.8

13

7.5x40

6

30

50

100

1.3

MMS-S 7.5x502 MMS-S 10x60 MMS-S 10x70 MMS-S 10x80 MMS-S 12x80

781552 4

3.00

4.8

13

7.5x50

6

30

50

100

1.4

781553 1 781554 8 781555 5 781556 2

6.10 6.10 7.20 8.00

7.8 7.8 7.8 7.8

16 16 16 18

10x60 10x70 10x80 12x80

8 8 8 10

55 55 55 60

75 75 75 80

50 50 50 25

3.2 3.4 4.0 6.0

1 Washer 7.0x16x1.5 Electro-galv. is included 2 Washer 8.4x19x1.5 Electro-galv. is included

*EAN-code=732167+Part.no+C (control figure)

125

Concrete screw MMS-S Hot dip galvanized

WEF-0001

A = Drill diameter B = Min. installation depth C = Min. drilling depth F = Extraction force kN** T = Transverse force kN N = Width of jaws **For concrete class C25 Part. No. C*

F kN

T kN

N mm

ØxL mm

A mm

B mm

C mm

Number/ package

Weight kg 100 pcs

MMS-S 6x401

790356 6

2.40

2.2

10

6x40

5

30

50

200

0.74

MMS-S 6x501

790357 3

2.80

2.2

10

6x50

5

30

50

100

0.92

MMS-S 6x601

790358 0

2.80

2.2

10

6x60

5

30

50

100

1.03

MMS-S 7.5x352

790359 7

2.50

4.8

13

7.5x35

6

30

50

100

1.2

MMS-S 7.5x402

790360 3

2.50

4.8

13

7.5x40

6

30

50

100

1.3

MMS-S 7.5x502 MMS-S 10x60 MMS-S 10x70 MMS-S 10x80 MMS-S 12x80

790361 0

3.00

4.8

13

7.5x50

6

30

50

100

1.4

790362 7 790363 4 790364 1 790365 8

6.10 6.10 7.20 8.00

7.8 7.8 7.8 7.8

16 16 16 18

10x60 10x70 10x80 12x80

8 8 8 10

55 55 55 60

75 75 75 80

50 50 50 25

3.2 3.4 4.0 6.0

1 Washer 7.0x16x1.5 Hot dip galv. is included 2 Washer 8.4x19x1.5 Hot dip galv. is inclcluded

*EAN-code=732167+Part.no+C (control figure)

Concrete screw MMS-S Stainless steel AISI316 Concrete screw with soldered phosphatized carbon steel tip.

WEF-0001

L2 L1 A = Drill diameter B = Min. installation depth C = Min. drilling depth F = Extraction force kN** T = Transverse force kN N = Width of jaws **For concrete class C25

MMS-S 7.5x50/653 MMS-S 10x70/85 MMS-S 12x80/100

Part. No. C*

F kN

T kN

N mm

ØxL1/L2 mm

A mm

B mm

C mm

Number/ package

Weight kg 100 pcs

781557 9

3.00

4.8

13

7.5x50/65

6

30

85

50

1.9

781558 6 781559 3

7.20 8.10

7.8 7.8

16 18

10x70/85 12x80/100

8 10

55 60

105 120

50 25

4.4 7.6

3Washer 8.4x24x2.0 AISI316 is incl.

*EAN-code=732167+Part.no+C (control figure)

126

Concrete screw MMS-S FL Electro-galvanized Concrete screw with flange.

WEF-0001

A = Drill diameter B = Min. installation depth C = Min. drilling depth F = Extraction force kN** T = Transverse force kN D = Flange diameter N = Width of jaws **For concrete class C25 Part. No. C*

MMS-S FL 6x40 790394 8 MMS-S FL 6x50 790395 5 MMS-S FL 6x60 790396 2 MMS-S FL 7.5x50 790397 9 MMS-S FL 7.5x70 790398 6 MMS-S FL 10x70 790399 3 MMS-S FL 10x80 790400 6 MMS-S FL 12x90 790401 3 MMS-S FL 12x100 790402 0 *EAN-code=732167+Part.no+C (control figure)

F kN

T kN

N mm

ØxL mm

D mm

A mm

B mm

C mm

Number/ package

Weight kg 100 pcs

2.40 2.80 2.80 3.00 3.00 6.10 7.20 8.00 8.00

2.2 2.2 2.2 4.8 4.8 7.8 7.8 7.8 7.8

10 10 10 13 13 16 16 18 18

6x40 6x50 6x60 7.5x50 7.5x70 10x70 10x80 12x90 12x100

15.0 15.0 15.0 17.5 17.5 19.0 19.0 22.0 22.0

5 5 5 6 6 8 8 10 10

30 30 30 30 30 55 55 60 60

50 50 50 50 50 75 75 80 80

100 100 100 50 50 25 25 25 25

0.8 1.0 1.1 1.6 2.0 3.9 4.5 7.7 8.5

Concrete screw MMS-S FL Hot dip galvanized Concrete screw with flange.

WEF-0001

A = Drill diameter B = Min. installation depth C = Min. drilling depth F = Extraction force kN** T = Transverse force kN D = Flange diameter N = Width of jaws **For concrete class C25 Part. No. C*

MMS-S FL 6x40 790376 4 MMS-S FL 6x50 790377 1 MMS-S FL 6x60 790378 8 MMS-S FL 7.5x50 790379 5 MMS-S FL 7.5x70 790380 1 MMS-S FL 10x70 790381 8 MMS-S FL 10x80 790382 5 MMS-S FL 12x90 790383 2 MMS-S FL 12x100 790384 9 *EAN-code=732167+Part.no+C (control figure)

F kN

T kN

N mm

ØxL mm

D mm

A mm

B mm

C mm

Number/ package

Weight kg 100 pcs

2.40 2.80 2.80 3.00 3.00 6.10 7.20 8.00 8.00

2.2 2.2 2.2 4.8 4.8 7.8 7.8 7.8 7.8

10 10 10 13 13 16 16 18 18

6x40 6x50 6x60 7.5x50 7.5x70 10x70 10x80 12x90 12x100

15.0 15.0 15.0 17.5 17.5 19.0 19.0 22.0 22.0

5 5 5 6 6 8 8 10 10

30 30 30 30 30 55 55 60 60

50 50 50 50 50 75 75 80 80

100 100 100 50 50 25 25 25 25

0.8 1.0 1.1 1.6 2.0 3.9 4.5 7.7 8.5

127

Concrete screw MMS-PAN Electro-galvanized For installation of Pendant strip W33. Panheaded concrete screw, electro-galvanized and yellow chromated. Torx-recess.

WEF-0001

A = Drill diameter B = Min. installation depth C = Min. drilling depth E = Screw head diameter F = Extraction force kN** T = Transverse force kN **For concrete class C25 Part.No. C*

F kN

MMS-PAN 5x30 787049 3 0.8 MMS-PAN 5x50 787050 9 1.4 MMS-PAN 6x30 781560 9 2.40 MMS-PAN 7.5x45 781561 6 3.20 MMS-PAN 10x70 781562 3 7.20 *EAN-code=732167+Part.no+C (control figure)

T kN

Torx

ØxL mm

A mm

B mm

C mm

E mm

Number/ package

Weight kg 100 pcs

1.4 1.4 2.2 4.8 7.8

T-20 T-20 T-30 T-40 T-40

5x30 5x50 6x30 7.5x45 10x70

4 4 5 6 8

25 25 25 30 55

45 45 45 50 75

7.9 7.9 11.5 13 17

200 200 200 100 50

0.32 0.5 0.65 1.10 3.40

Use and installation

Installation of Pendant strip W33. Mounting with JR-clamp.

Concrete screw MMS-PAN SH WEF-0001

Electro-galvanized For installation of Ceiling attachment W31 or Tube pendant attachment W73. Concrete screw with extra big panhead, electro-galvanized and yellow chromated. Torx-recess.

A = Drill diameter B = Min. installation depth C = Min. drilling depth E = Screw head diameter F = Extraction force kN** T = Transverse force kN **For concrete class C25 Part. No. C*

MMS-PAN SH 7.5x45 781696 5 *EAN-code=732167+Part.no+C (control figure) Use and installation

Installation of Ceiling attachment W31.

128

F kN

T kN

Torx

ØxL mm

A mm

B mm

C mm

E mm

Number/ package

Weight kg 100 pcs

3.00 4.8

T-30

7.5x45

6

30

50

17

100

1.4

Concrete screw MMS-ST Electro-galvanized WEF-0001 For installation of eye nuts. The screw is specially developed for safe fixing in concrete. Suitable for tube installations, electrical installations, rails, handrails, machines, ventilating ducts, wood constructions. A = Drill diameter B = Min. installation depth C = Min. drilling depth E = Length of thread engagement F = Extraction force kN** T = Transverse force kN N = Widths of jaws M = English thread **For concrete class C25 T kN

N mm

DxL1 mm

L2 mm

M

A mm

B mm

C mm

E mm

Number/ package

Weight kg 100 pcs

MMS-ST 7.5x70 781563 0 3.20 4.8 MMS-ST 10x80 781564 7 6.51 7.8 *EAN-code=732167+Part.no+C (control figure)

10 13

7.5x70 10x80

53 65

M8 M10

6 8

30 55

50 75

13 10

50 50

1.8 3.5

Part. No. C*

F kN

Use and installation

Installation of eye nut.

Concrete screw MMS-I Electro-galvanized For installation of Pendant M8 or M10. ❑ High extraction values are obtained due to the special thread. The drill diameter is the same as the root diameter of the screw which gives a solid fixing inside the hole. ❑ Can be dismounted and reinstalled without diminished extraction force. ❑ A weaker drill and less drilling depth can be used compared to using anchor, expansion bolt, screw and plug. ❑ Suitable in environments which are fire classified.

WEF-0001

A = Drill diameter B = Min. installation depth C = Min. drilling depth F = Extraction force kN** T = Transverse force kN N = Widths of jaws M = Metrisk gänga **For concrete class C25 T kN

N mm

DxL1 mm

MMS-I 7.5x55 781565 4 3.20 4.8 *EAN-code=732167+Part.no+C (control figure)

13

7.5x93

Part. No. C*

F kN

L2 mm

M

A mm

B mm

C mm

Number/ package

Weight kg 100 pcs

M8/M10

6

30

50

100

1.9

Use and installation

Installation of Threaded rod M8 or M10.

129

Eye screw MMS-R Electro-galvanized For installation of wires in ceiling.

WEF-0001

A = Drill diameter B = Min. installation depth C = Min. drilling depth F = Extraction force kN** T = Transverse force kN **For concrete class C25

Part. No. C*

F kN

MMS-R 6x40 781566 1 2.80 *EAN-code=732167+Part.no+C (control figure)

T kN

ØxL mm

A mm

B mm

C mm

Number/ package

Weight kg 100 pcs

2.2

6x40

5

30

50

250

0.76

Light concrete screw Electro-galvanized For installation in porous concrete. Torx-recess.

WEF-0001

B = Min. installation depth E = Head diameter F = Permitted extraction force kN

Part. No. C*

Light concrete screw 8x100 790412 9 *EAN-code=732167+Part.no+C (control figure)

F kN

Torx

ØxL mm

B mm

E mm

Number/ package

Weight kg 100 pcs

0.67

T-40

8x100

95

14.8

50

2.4

Expansion nail WEF-0001

Electro-galvanized/ Aluminium For fixing of light details in concrete.

A = Drill diameter B = Min. installation depth C = Min. drilling depth

Expansion nail 5x22 *EAN-code=732167+Part.no+C (control figure)

Part. No. C*

ØxL mm

A mm

B mm

C mm

Number/ package

Weight kg 100 pcs

790413 6

5x22

5

20

30

250

0.5

Mounting tool for Eye screw MMS-R Electro-galvanized.

Mounting tool for Eye screw MMS-R *EAN-code=732167+Part.no+C (control figure)

130

WEF-0001

Part. No. C*

Number/ package

Weight kg 100 pcs

781567 8

1

5.5

Bitro adapter Electro-galvanized + plastic. The Bitro adapter must be installed direct on Hammer drill SDS PLUS. Drilling machine can be used. Suitable for drilling only in C25 concrete.

Bitro adapter 5, yellow Bitro adapter 6, green Bitro adapter 8, red Bitro adapter 10, blue *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

For drill mm

D mm

L mm

Number/ package

Weight kg 100 pcs

781568 5 781569 2 781570 8 781571 5

5 6 8 10

10 10 12 14

73 73 80 80

1 1 1 1

2.5 3.0 4.0 5.0

Use and installation

Turn off the hammer function of the drilling machine. Install the Bitro adapter on the drill. Check that the adapter locks the drill to avoid turning. Put in Torxbits or Magnetic socket or Square peg + Socket 16/18. When removing the adapter tilt it lightly and pull the bit, magnetic socket or the square peg.

When mounting use a drilling machine with torque regulator. Otherwise be very careful. If you let the machine continue to run when the screw is in bottom it is very easy to destroy the tip of the drill or that the drill gets stuck or broken. The risk increases with the length of the drill.

Magnetic socket for Concrete screw MMS-S Untreated steel.

WEF-0001

Magnetic socket 10x45 Magnetic socket 13x45** **Can also be used for MMS-I. *EAN-code=732167+Part.no+C (control figure)

Part. No. C*

Dim mm

D mm

Number/ package

Weight kg 100 pcs

781572 2 781573 9

10x45 13x45

10 13

1 1

2.5 3.0

Socket for Concrete screw MMS-S Untreated steel. To be used together with Square peg.

Part. No. C*

Socket 16 781574 6 Socket 18 781575 3 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Dim mm

D mm

Number/ package

Weight kg 100 pcs

16x34 18x34

16 18

1 1

6.0 10.0

131

Bits holder Stainless steel AISI304.

Bits holder 11x60 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/ package

Weight kg 100 pcs

781576 0

1

2.5

Square peg Untreated steel. To be used with Socket 16 and 18.

Square peg 3/8x50 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/ package

Weight kg 100 pcs

781577 7

1

2.0

Torxbits Untreated steel. To be used with Concrete screw MMS-PAN SH.

Torxbits TX 30x25 Torxbits TX 40x25 *EAN-code=732167+Part.no+C (control figure)

132

WEF-0001

Part. No. C*

Number/ package

Weight kg 100 pcs

788552 7 788553 4

2 2

0.5 0.6

Hammer drill SDS PLUS Untreated steel.

Hammer drill SDS PLUS 4x110 Hammer drill SDS PLUS 5x110 Hammer drill SDS PLUS 5x160 Hammer drill SDS PLUS 5.5x110 Hammer drill SDS PLUS 5.5x160 Hammer drill SDS PLUS 6x110 Hammer drill SDS PLUS 6x160 Hammer drill SDS PLUS 6x210 Hammer drill SDS PLUS 7x160 Hammer drill SDS PLUS 7x210 Hammer drill SDS PLUS 8x160 Hammer drill SDS PLUS 8x210 Hammer drill SDS PLUS 10x160 Hammer drill SDS PLUS 10x210 Hammer drill SDS PLUS 12x210 Hammer drill SDS PLUS 16x300 Hammer drill SDS PLUS 20x450

WEF-0001

Part. No. C*

Dim mm

Cutting length of the drill mm

Number/ package

Weight kg 100 pcs

787021 9 781631 6 781632 3 787022 6 787023 3 781633 0 781634 7 781635 4 787025 7 787026 4 781636 1 781637 8 781638 5 781639 2 787027 1 787028 8 787029 5

4x110 5x110 5x160 5.5x110 5.5x160 6x110 6x160 6x210 7x160 7x210 8x160 8x210 10x160 10x210 12x210 16x300 20x450

50 50 100 50 100 50 100 150 100 150 100 150 100 150 150 230 370

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

3.0 3.5 4.0 4.0 4.0 4.5 5.0 5.5 5.5 6.0 6.0 6.5 7.5 9.0 9.5 20.0 56.0

4x 75 5x 85 5x150 5.5x 85 5.5x150 6x100 6x150 7x100 7x150 7x300 8x150 8x200 10x150 10x200 12x200 16x300 20x400

40 50 60 50 90 60 90 60 90 220 90 135 90 135 135 220 230

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

2.0 2.5 2.0 2.0 2.0 2.0 4.0 4.0 4.0 8.0 4.0 6.0 6.0 8.0 10.0 26.0 62.0

Masonry drill WBL/WBE Tungsten carbide tip.Tool steel shank with plated finish. Masonry drill WBE 4x 75 787030 1 Masonry drill WBE 5x 85 787031 8 Masonry drill WBL 5x150 787032 5 Masonry drill WBE 5.5x 85 787033 2 Masonry drill WBL 5.5x150 787034 9 Masonry drill WBE 6x100 787035 6 Masonry drill WBL 6x150 787036 3 Masonry drill WBE 7x100 787037 0 Masonry drill WBL 7x150 787038 7 Masonry drill WBL 7x300 787039 4 Masonry drill WBL 8x150 787040 0 Masonry drill WBL 8x200 787041 7 Masonry drill WBL 10x150 787042 4 Masonry drill WBL 10x200 787043 1 Masonry drill WBL 12x200 787044 8 Masonry drill WBL 16x300 787045 5 Masonry drill WBL 20x400 787046 2 *EAN-code=732167+Part.no+C (control figure)

133

Concrete screws - Loadings Mounting of Wibe concrete screws To use Wibe concrete screws is both safe and easy. No special tools or machines are required. The screw performs an exact adapted thread in the bedding which means that no control of the tightening moment is required. The extraction force of a Wibe concrete screw is better than that of an expansion bolt with the same diameter You can choose a smaller diameter of a concrete screw than that of an expansion bolt and still receive the same extraction force. The same concrete screw can be re-used. Mounting instruction

Use a drill suitable to the screw. Drill the hole.

Switch off the hammer function. Mount the Bitro adapter on the drill. Pull in a bit or socket suitable for the screw to be used.

Mount with drilling machine. Wibe concrete screws can also be mounted with regular hand tools as box sockets.

1. Drill a hole with the same diameter as the root of the screw (for 6 mm drill 5 mm, for 7.5 mm drill 6 mm, for 10 mm drill 8 mm and for 12 mm drill 10 mm). The drill depth must be at least 20 mm deeper than the installation depth. 2. Blow the hole free from dust. 3. Mount the concrete screw close to the application bedding, no defined tightening moment is required. Note – don´t tighten the screw with a higher moment than stated on the package or technical data. Extraction forces, in kN, depending on installation depth in uncracked concrete C25. Calculated values with a safety factor of 3.0. Installation depth mm

25 30 35 40 45 50 55 60 70 80

MMS-5

MMS-6

MMS-7.5

0.8 1.4

2.02 2.40 2.50 2.80 2.80 2.80

2.15 2.50 2.60 3.00 3.20 4.10 6.10 6.51

2.80

MMS-10

3.50 3.80 4.00 4.30 6.10 7.20 7.90

MMS-12

5.50 6.30 7.20 8.00 8.10 10.00

Transverse forces Concrete screw MMS Dimensioned transverse force in kN. Concrete screw

Screw diameter mm Breaking torsional moment (Nm) Recommended max tightening moment (Nm)

MMS-5

MMS-6

MMS-7.5

MMS-10

MMS-12

1.4

2.2

4.8

7.8

7.8

5 12 10

6 24 10

7.5 28 20

10 80 50

12 120 80

Spacing The above values are valid when the distance from the nearest corner or free edge to the screw is at least 10 x screw diameter. The spacing between two screws must be minimum 20 x screw diameter.

134

Low density anchor TLF Hot dip galvanized For fixing in light concrete or clinker concrete. For medium or heavy installations. Unique advantages: ❑ Long expansion area and heavy expansion – very high loading values ❑ The expansion can be directed - superior loading values even at small edge distances. ❑ Very quick installation – drives in and expands with a hammer and Hammer tool TLF-S

DxL mm

D1 mm

Drill diameter mm

Number/ package

Weight kg 100 pcs

8x 65 12x100 12x145 16x130

13 20 20 25

8 12 12 16

50 25 25 10

1.4 4.7 6.2 10.0

Part. No. C*

Low density anchor TLF 8x65** 781782 5 Low density anchor TLF 12x100 781783 2 Low density anchor TLF 12x145 781784 9 Low density anchor TLF 16x130 781785 6 **One Hammer tool is incl. in each package. *EAN-code=732167+Part.no+C (control figure) Loading - All loadings refer to mounting in light concrete Y 500

Max Tightening moment M=Nm

Extraction force F1 kN

Transverse force kN

1 6 6 10

0.3 0.6 0.6 0.6

0.3 0.6 0.6 0.6

TLF 8x65 mounted with wood screw TKX Fzb SPAX-5x35 TLF 12x100 mounted with hexagon head wood screw T6S 4.6 Fzv 8x40 TLF 12x145 mounted with hexagon head wood screw T6S 4.6 Fzv 8x40 TLF 16x130 mounted with hexagon head wood screw T6S 4.6 Fzv 10x40 Max permitted load F on Cantilever arm 50

50-200

TLF 8x 65 TLF 12x100 TLF 12x145 TLF 16x130

WEF-0006

50-300

50-400

50-500

50-600

Kg

kN

Kg

kN

Kg

kN

Kg

kN

Kg

kN

26 26 26

0.26 0.26 0.26

25 25 25

0.25 0.25 0.25

22 22 22

0.22 0.22 0.22

23 23 23

0.23 0.23 0.23

21 21 21

0.21 0.21 0.21

Use and installation

Drill with recommended drill diameter, see above. (Without pre-drilling in quality Y400 and Y450).

Low density anchor TLF installed with Hammer tool TLF-S. Put the hammer tool into the installation hole of the low density anchor and bolt the anchor.

Lower the distance.

Expand the anchor by means of the Hammer tool.

135

Hammer tool TLF-S Untreated steel. For driving in and expansion of the Low density anchor TLF.

Hammer tool TLF-S 12x100 Hammer tool TLF-S 12x145 Hammer tool TLF-S 12x130 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

L mm

Number/ package

Weight kg 100 pcs

781842 6 781843 3 781844 0

180 225 220

1 1 1

23 24 42

Use and installation

Put the Hammer tool into the Lower the distance. installation hole of the Low density anchor and bolt the fixing (without pre-drilling in quality Y400 and Y450).

Expand the anchor by means of the Hammer tool.

Sleeve TLF-H12 Hot dip galvanized. To be used together with Low density anchor TLF 12x100 or 12 x145 in order to raise the transverse force performance.

Sleeve TLF-H12 *EAN-code=732167+Part.no+C (control figure)

Part. No. C*

Number/ package

Weight kg 100 pcs

781867 9

25

1.3

Use and installation

Put the sleeve on the Low density anchor. (See instructions for Low density anchor TLF).

136

WEF-0001

Bolt the Low density anchor with the sleeve in level with the wall.

Adapter TLF-A12 Electro-galvanized. To be used together with Low density anchor TLF 12x100 or 12x145 in order to receive an interior M10 thread. Suits Pendant M10.

Adapter TLF-A12 *EAN-code=732167+Part.no+C (control figure)

WEF-0007

Part. No. C*

Number/ package

Weight kg 100 pcs

781868 6

10

2.1

Use and installation

Screw the Adapter into the expanding Low density anchor.

Pendant M10 fits in the Adapter.

Angled bracket TLF-F12 Pre-galvanized. To be mounted with Low density anchor TLF 12x100 or 12x145 and can be used as fixing for band or wire installations.

Angled bracket TLF-F12 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/ package

Weight kg 100 pcs

781869 3

25

2.6

Use and installation

Mount the Angled bracket on the Low density anchor. (See instructions for Low density anchor TLF).

Bolt the Low density anchor with the Angled bracket into the bedding and check that it is secured.

137

Express hanger SVH Stainless steel AISI316. For fixing in concrete, natural stone, solid brick or plate. Used for installation of armatures close to the ceiling (with locking block) as well as for hanging of integrated ceilings, armatures, electrical-, tube- or ventilating equipment. Mounting tool SVH-T, for mounting to the right installation depth, is included in the package. Cover plate is included only for SVH-E1.

Part. No. C*

Express hanger SVH-E1 781870 9 Express hanger SVH-E2** 781871 6 **Cover plate not included. *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Drill mm

Min. drilling depth mm

Number/ package

Weight kg 100 pcs

8 8

30 30

100 500

0.3 0.3

Loading Permitted load capacity at safety factor 3 at extraction Concrete C25 kN Solid brick kN

Express hanger SVH-E1 Express hanger SVH-E2

1.0 1.0

0.5 0.5

Use and installation

Hole must be drilled with a 8 mm drill, drilling depth minimum 30 mm. Drive in the Express hanger with the Mounting tool SVH-T. The installation depth always turns out to be the right.

The short and stiff wire ends grip effectively into the sides of the hole resulting in a safe and strong fixing.

Mounting of wires. Cover plate hides the hole.

Express hanger SVH can also be used for installation of Fixing strip TRB and TGB.

When the fixing strip is turned into position it self-locks. Can also be locked with screw, rivet or lashing wire for extra security.

At a visible installation, hide the hole with a cover plate. Delivered together with SVH-E1.

138

Mounting close to the ceiling with Securing spring SVH-L.

Securing spring SVH-L Stainless steel AISI304. For installation of armatures close to ceiling.

Securing spring SVH-L *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/ package

Weight kg 100 pcs

781872 3

25

0.20

Use and installation

For installation of armatures close to the ceiling. Maximum loading per securing spring is 4 kg.

Mounting tool SVH-T Electro-galvanized. For installation of Express hanger SVH.

Mounting tool SVH-T *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/ package

Weight kg 100 pcs

781873 0

10

1.8

Use and installation

For installation of Express hanger SVH. The installation depth will always turn out to be the right.

139

Fixing strip TGB Pre-galvanized. For pendant installation and clamping Cold-rolled and galvanized sheet metal, perforated for easy installations. For fixing tools as Express hanger SVH or Low density anchor TLF with Angled bracket TLF-F12.

Fixing strip TGB 11x0.7 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/ Package

Weight kg 100 pcs

781874 7

1 (25m)

105

Use and installation

Can be mounted with Express hanger SVH.

Can be mounted with Low density anchor TLF and Angled bracket TLF-F12.

Can easily be mounted with other suitable fixing tools.

Fixing strip TRB Stainless steel AISI304. For pendant installation and clamping. Stainless steel band AISI304 for qualified installations in all type of environments. Express hanger SVH or Low density anchor TLF with Angled bracket TLF-F12 can be used as fixing tools.

Fixing strip TRB 11x0.7 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/ package

Weight kg 100 pcs

781875 4

1 (10m)

42

Use and installation

Can be mounted with Express hanger SVH.

140

Can be mounted with Low density anchor TLF and Angled bracket TLF-F12.

Can easily be installed with other suitable fixing tools.

Fixings - Ogebe The Ogebe fixing is a patented fixing intended for use when mounting plating with a thickness of 0.7-0.9 mm and 13 mm gypsum board. Pendants, cantilevers and holed strips can be mounted with these fittings. Technical data Material Material treatment Surface treatment Maximum load

Cold-rolled sheet steel SS 1142–32 Case-hardened Electro-galvanized See load tables

Nut Bolt Washer

Locking Nut M8, SMS 2165 FZB M8 x 16 mm FZB SRB 13.5 x 26 x 2 mm FZB

ø12 mm 0,7–0,9 mm

Drill a 12 mm dia. hole. A 10 mm drill can be used if one increases the hole dia. by slanting the electric drill.

Place the accompanying washer over the thin legs. Insert the legs through the drilled hole and fold the broader legs towards each other. If sealing is required, a standard sealing mass from building retailers can be used.

Mount the pendant, bracket or holed strip with the enclosed bolts and nuts. (The nut should always be a locking nut).

Breaking load The load applied at an equi-distance between 2 beams 600 mm apart. The values are taken from Swedish National Testing Institute Report 8410.0032 1984-09-28.

Fixing type E

Fixing types D, ED

Fixing type Eg

F3

F3

F1

F1

F3

F2

F3

F1

F3

F2

F3

F2

141

Ogebe fixing type E WEF-0001 The Ogebe fixing type E is used for mounting in 0.7-0.9 mm sheeting or board material. The following can be mounted: hole straps, pendants, ducts and pipings etc.

Ogebe fixing type E *EAN-code=732167+Part.no+C (control figure)

Electro-galv. Part. No. C*

Weight kg 100 pcs

716474 5

4.8

Use and installation

Mounting of Pendant rail W32.

Mounting of Pendant rail W32 with Ogebe fixing type E direct in lighting trunking.

Mounting of Ceiling attachment W31 on Ogebe fixing type E.

Mounting of hole strap.

Stand installation on wall.

Suspension of duct or pipe.

Mounting of holed beam.

A wire can be mounted directly in the Ogebe fixing type E.

The Ogebe fixing type E can be mounted direct into Support bracket/joint W7.

142

Ogebe fixing type D WEF-0001 The Ogebe fixing type D is used for mounting in 0.7-0.9 mm sheeting or board material. The following can be mounted: pendant fittings etc.

Ogebe fixing type D *EAN-code=732167+Part.no+C (control figure)

Electro-galv. Part. No. C*

Weight kg 100 pcs

716475 2

6.8

Use and installation

Mounting of ceiling attachment W31 on fixture, type D. Use Screw set W36 or W36C.

Ogebe fixing type D or ED can be mounted in lighting trunking as light fitting.

143

Ogebe fixing type ED WEF-0001 The Ogebe fixing type ED is used for mounting in 0.7-0.9 mm sheeting or board material. The following can be mounted: suspension devices, light fittings etc.

Ogebe fixing type ED *EAN-code=732167+Part.no+C (control figure)

Electro-galv. Part. No. C*

Weight kg 100 pcs

716477 6

5.8

Use and installation

Mounting of Pendant attachment W21 or Tube pendant attachment W73 with Ogebe fixing type ED. Use screw set W36/W36C.

When mounting Ceiling attachment W31 on cable trays/lighting trunking, the load can be distributed onto two or more fixings. This allow for lateral adjustment.

Mounting of light fittings in plate metal ceiling.

144

Stand installation on wall. Use Screw set W36/W36C.

Installation of holed beam. Use Screw set W36/W36C.

Ogebe fixing type D or ED can be mounted in lighting trunking as light fitting.

Ogebe fixing type Eg WEF-0001 The Ogebe fixing type Eg is intended for mounting in single gypsum boards.

Eg

Ogebe fixing type Eg *EAN-code=732167+Part.no+C (control figure)

Electro-galv. Part. No. C*

Weight kg 100 pcs

716478 3

5.6

Use and installation

Eg mounted in single gypsum board.

Stand installation on wall.

145

Integrated ceilings Ceilings from Wibe provide undreamt of possibilities to build different types of system ceilings with very high demands on functionality. You build using reliable, reputable components which are easy to install and combine in an almost neverending number of variations.

146

,

Acoustic lamina We can supply acoustic lamina for baffle frames, wire baskets and ceilings with T-profiles. There are several manufacturers on the market offering lamina of varying thicknesses, colours, suface coverings and structures.

It is possible to select the colour of your choice Cable trays, lighting trunking, mounting fittings and accessories come in standard version in pre-galvaniced or pre-galvanized with white paint finish (RAL 9010) design in accordance with the Zinkpox method. A celling often gives a room its character.Exploit the possibilities

The lamina comply with current standardes for fire-protection and are available with various sound absorption factors.

of choosing a coulor scheme for your ceiling thereby creating a pleasing atmosphere. We can supply the whole of our programme in RAL colour of your choice and with lustre you desire.

147

Open ceilings

4 7 8

3

2 7 3

1

6

9

3

3

5

2 5

3

1

1

Components 1. Cable tray W1 2. Support bracket/joint W7 3. Tube pendant attachment W73 4. Pendant strip W33 5. T-joint W9 (alt. W29) 6. Junction box plate W24 7. Screw set W36 8. Screw set W38P 9. Threaded rod M10 W76

148

9

Ceilings with sound baffles

4 8 5 8 7 3 2

10

10

4 8 5

2

10

8 3

10

9 9 9 6

1

1 2 38 1

10

1 6

Components 1. Cable tray W1 2. Support bracket/joint W7 3. Pendant attachment W21 4. Ceiling attachment W31 5. Pendant rail W32 6. T-joint W9 (alt. W29) 7. Screw set W37 8. Screw set W38P 9. Sound baffles 10. Position retainer W43

149

Ceilings with wire baskets

9

4 8 5

3 7

4

1

8 5

3 2

6 10 2 6 10 1 1

Components 1. Cable tray W1 2. Support bracket/joint W7 3. Pendant attachment W21 4. Ceiling attachment W31 5. Pendant rail W32 6. T-joint W9 (alt. W29) 7. Junction box plate W24 8. Screw set W37 9. Screw set W38P 10. Wire baskets

150

Ceilings in corridor

4

2 3 7

6 1

5

30

B

1

3

4

5 2 8

1

5

Components 1. Cable trays and Lighting trunking 2. Suspension 3. Junction box plate 4. Support bracket/joint 5. Baffles, baskets etc. 6. W-swing profiles 7. W-swing wall bracket 8. Shade ledges, angle strips, integrated ceiling support channels and wall trays B= please state when ordering

151

Sound baffles Wibe baffle frames are constructed of side and gable sections which are cut to measure and mounted in accordance with customer requirements. Baffles with hooks

Baffles with rings

Baffles with hooks The bottoms of the baffles and trays are on the same level. Hinged hooks The hooks allow the baffles to be lowered. However, this necessitates that the space between tray and baffle may not be less then 25 mm. Clearence hooks The hooks provide clearence and define the space between tray and baffle.

Baffles with suspension rings The rings are adapted to the W-swing profiles used in corridor installations. In this type of installation the baffles end up lower than the tray bottom.

Absorbents The baffles are provided with optional acoustic lamina. There are several producers in the market who can offer acoustic lamina in various thickness, colours and design. Ordering When ordering please specify the following measurements: L = Length of baffle B = Width of baffle C = Clearence measurement

Installation with Profile W-sving 2 on Wall bracket W-sving 2. Suspended baffle.

Installation of suspended baffle in Profile W-swing 3.

Installation with tray and Profile W-swing 5. Suspended baffle.

Installation with tray and Profile W-swing 1. Suspended baffle.

152

Position retainer 2 Position retainers W43 per baffle must be mounted diagonally. Mounting When installing the baffles directly in the trays normally 2 Hinged hooks are fitted to the one end of the baffles and 2 Clearence hooks in the other. At installation without distance between baffle and tray 4 Hinged hooks must be used. Material Made of pre-galvanized sheet steel + powder coated white. Other colours can be quoted.

Installation of suspended baffle in Profile W-swing 2 mounted on Profile W-swing 4A.

Wire baskets Wire baskets are an alternative to baffles. They provide an open and airy atmosphere. In shops and stores they provide good possibilities for hanging advertisements, bargain offers and decorations. The grating can be manufactured of wire with different diameters. Note that the shape of the mesh can either be square or rectangular.

Material Automatic welding of steel.

Design The welded grating is aesthetically attractive by simplicity, stability and plasticity. Abundance of variation due to the mesh pattern 50x50. Bigger mesh sizes can be offered. Standard pattern 50x50x4 mm.

Ordering Please state the following L = Length of basket (mm) B = Width of basket (mm)

Surface treatment Powder coated

153

154

Accessories Sound baffles The following accessories are included in an unassembled sound baffle: 4 Corners, 2 Hinged hooks, 2 Clearence hooks, 2 Side profiles and 2 Gable profiles. Hinged hooks and clearence hooks can be replaced with suspension rings when necessary. The baffles are easy to assemble without any tool.

Gable profile WEF-0001

Gable profile 570 Gable profile 1170 *EAN-code=732167+Part.no+C (control figure)

Length mm

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

570 1170

728802 1 728803 8

13.6 27.9

Side profile WEF-0001

Side profile for hook

Side profile for suspension ring

Side profile for hook Side profile for hook Side profile for hook Side profile for hook Side profile for hook Side profile for hook Side profile for hook Side profile for hook Side profile for hook *EAN-code=732167+Part.no+C (control figure) Please state length of profile when ordering

Length mm

Pre-galv. White30 Part. No. C*

571-625 626-749 750-999 1000-1170 1171-1249 1250-1400 1401-1750 1751-1990 1991-2400

739535 4 739536 1 739537 8 739538 5 739539 2 739540 8 739541 5 739542 2 739543 9

Weight kg 100 pcs

Clearance hook WEF-0001

Clearance hook 25 Clearance hook 30 Clearance hook 40 Clearance hook 50 *EAN-code=732167+Part.no+C (control figure)

Distance between baffle and tray mm

Electro-galv. Part. No. C*

Weight kg 100 pcs

25 30 40 50

720252 2 720253 9 720254 6 720255 3

2.0 2.0 2.0 2.0

155

Hinged hook WEF-0001

Hinged hook 25-30 Hinged hook 40 Hinged hook 50 *EAN-code=732167+Part.no+C (control figure)

Distance between baffle and tray mm

Electro-galv. Part. No. C*

Weight kg 100 pcs

25-30 40 50

720260 7 720261 4 720262 1

2.0 2.0 2.0

Suspension ring WEF-0001

Suspension ring 575 Suspension ring 1175 *EAN-code=732167+Part.no+C (control figure)

Length mm

Electro-galv. Part. No. C*

Weight kg 100 pcs

575 1175

728804 5 728805 2

7 14

Reinforced profile WEF-0001

Reinforced profile 570 Reinforced profile 1170 *EAN-code=732167+Part.no+C (control figure)

Length mm

White30 Part. No. C*

Weight kg 100 pcs

570 1170

733995 2 733996 9

13.6 27.9

Corner WEF-0001

Corner *EAN-code=732167+Part.no+C (control figure)

156

Pre-galv Part. No. C*

Weight kg 100 pcs

720286 7

2.5

Gypsum clip Used to mount gypsum wallboards in baffle frames.

WEF-0001

Gypsum clip *EAN-code=732167+Part.no+C (control figure)

Steel strip Part. No. C*

Weight kg 100 pcs

732241 1

0.4

Use and installation

Gypsum boards in Wibes baffle frames must have dimensions that are 20 mm smaller than the size of the baffle. The clip will keep the board in place.

Lock the gypsum clip by pressing down the tab. The gypsum clip suits a 9 mm thick board.

Normally it is enough with 4 gypsum clips pro baffle. The clips must be mounted diagonally.

Position retainer W43 Support W42 WEF-0017

Position retainer W43 Two pcs are mounted per baffle.

Support W42 Mounted in T-joint W9 as a support for cables.

Position retainer W43 Support W42 *EAN-code=732167+Part.no+C (control figure)

White plastic Part. No. C*

Weight kg 100 pcs

718245 9 718214 5

0.4 0.4

Use and installation

Position retainer W43 holds the sound baffles in the correct position. W 43 is snapped tight into the edge of the cable tray or lighting trunking.

Support W42 is mounted at T-joint W9 to prevent the cables from gliding out over the corner of the cable tray or lighting trunking. W42 is snapped tight into the edge of the tray.

157

Frame clip W90 Enables clip mounting in baffle frame.

Frame clip W90 (screw RXS Combi B6x19, fzb) *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Pre-galv. Part. No. C*

Weight kg 100 pcs

723021 1

1.0

Mounting of decoration strip etc.

Use and installation

The Frame clip W90 is clamped tight under the edge of the section.

Mounting of light fittings on Reinforced profile.

Installation of air component.

T-section is easily mounted with Frame clips W90 in the baffle frames.

In large frames an extra support for the absorbent lamina can be required. Install a T-section with 2 Frame clips W90.

Light fitting mounted in baffle frame. 2 T-profiles mounted with 4 Frame clips W90.

158

Ceilings in corridor

159

Profile W-swing 1/40 A profile that will simplify service and maintenance, used for mounting on trays with edge height 40 mm. 600 mm c/c is standard. Other c/c measurements can be manufactured on request.

Profile W-swing 1 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

White30 Part. No. C*

Weight kg 100 pcs

729196 0

210

Use and installation

Installation with tray on both sides and Profile W-swing 1 hanging on tray

Installation with tray and Profile W-swing 1. Suspended baffles,

edge. Suspended baffle, folding in both directions.

folding in both directions. The trays have pendular suspension from ceiling.

Profile W-swing 1/60 A profile that will simplify service and maintenance, used for mounting on trays with edge height 60 mm. 600 mm c/c is standard. Other c/c measurements can be manufactured on request.

Profile W-swing 1/60 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

White30 Part. No. C*

Weight kg 100 pcs

786871 1

200

Use and installation

Installation with tray on both sides and Profile W-swing 1 hanging on tray

Installation with tray and Profile W-swing 1. Suspended baffles, folding in

edge. Suspended baffle, folding in both directions.

both directions. The trays have pendular suspension from ceiling.

160

Profile W-swing 2 A profile that will simplify service and maintenance. 600 mm c/c is standard. Other c/c measurements can be manufactured on request.

Profile W-swing 2 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

728866 3

730162 1

110

Use and installation

Installation with Profile W-swing 2 on Wall bracket W-swing 2. Suspended baffle, folding in both directions.

Ceiling installation with Profile W-swing 2. Suspended baffle, folding in both directions.

When joining, Ceiling bracket W31 can be both joint and ceiling bracket. Mounted with Screw set W34.

Profile W-swing 2 can be suspended in Pendant strip W33. Mounted with Screw set W34.

Profile W-swing 2 can be suspended in Pendant attachment W21. Mounted with Screw set W34.

161

Wall bracket W-swing 2 WEF-0001 Used for installation with Profile W-swing 2.

Wall bracket W-swing 2 *EAN-code=732167+Part.no+C (control figure)

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

721175 3

729067 3

16

Use and installation

Wall bracket W-swing 2 mounted on pendant or direct on wall.

162

Profile W-swing 2 mounted on Wall bracket W-swing 2 with Screw set W34. The profile can easily be adjusted in the oval holes of the wall bracket and the profile. Infinitely variable lengthwise and ± 20 mm towards wall.

Profile W-swing 3 WEF-0001 A profile that will simplify service and maintenance. 600 mm c/c is standard. Other c/c measurements can be manufactured on request.

Profile W-swing 3 *EAN-code=732167+Part.no+C (control figure)

White30 Part. No. C*

Weight kg 100 pcs

729198 4

277

Use and installation

Installation with tray and Profile W-swing 1, Wall bracket W-swing 2 with Profile W-swing 2 and pendant with Profile W-swing 3. Hanging baffles, folding in both directions

When joining, Ceiling bracket W31 can be both joint and ceiling bracket. Mounted with Screw set W34.

Profile W-swing 3 can be suspended in Pendant attachment W21. Mounted with Screw set W34.

Profile W-swing 3 can be suspended in Pendant strip W33. Mounted with Screw set W34.

163

Profile W-swing 4A WEF-0001 A profile that will simplify service and maintenance. 600 mm c/c is standard. Other c/c measurements can be manufactured on request.

Profile W-swing 4A *EAN-code=732167+Part.no+C (control figure)

White30 Part. No. C*

Weight kg 100 pcs

731618 2

150

Use and installation

For suspension of baffles, Profile W-swing 4A is used in combination with Profile W-swing 2. Mounted with Screw set W34.

Profiles W-swing 2 och W-swing W-swing 4A can be suspended 4A mounted with Screw set W34. in Pendant attachment W21.

W-swing 4A can be suspended in Pendant strip W33.

When joining, Ceiling bracket W31 can be both joint and ceiling bracket. Mounted with Screw set W34.

164

Profile W-swing 5 A profile that will simplify service and maintenance. 600 mm c/c is standard. Other c/c measurements can be manufactured on request.

WEF-0001

White30 Part. No. C*

Weight kg 100 pcs

729200 4

200

Profile W-swing 5 *EAN-code=732167+Part.no+C (control figure) Use and installation

Installation with tray and Profile W-swing 5. Baffle in level with tray and folding in both directions.

Shade ledge W26/40 Used as a support for ceilings mounted between cable trays with edge height 40 mm.

Shade ledge W26/40 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

1.0

717990 9

729192 2

154

Use and installation

Shade ledge W26/40 is hung over the side edge of the cable tray.

Shade edge W26/40 is used as a support for ceilings mounted between cable trays. Also suitable for Lighting trunking W70/ W71. Mounted along the side edges of the cable tray or the lighting trunking.

Shade list W26/40 is locked tight in the tray by pinching the ends in under the tray edge with pliers.

165

Shade ledge W26/60 Used as a support for ceilings mounted between cable trays with edge height 60 mm.

Shade edge W26/60 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

1.0

718559 7

782661 2

185

Use and installation

Shade ledge W26/60 is hung over the side edge of the cable tray.

Shade edge W26/60 is used as a support for ceilings mounted between cable trays. Mounted along the side edges of the cable tray.

Shade list W26/60 is locked tight in the tray by pinching the ends in under the tray edge with pliers.

Integrated ceiling support channel W27/40 Used as a support for ceilings mounted between cable trays with edge height 40 mm.

Integrated ceiling support channel W27/40 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

1.0

714008 4

729193 9

130

Use and installation Integrated ceiling support channel W27/40 is hung over and mounted along the side edge of the cable tray and is used as a support for ceilings mounted between cable trays. Also suitable for Lighting trunking W70/W71.

166

Integrated ceiling support channel W27/40 is locked tight in the tray by pinching the ends in under the tray edge with pliers.

Integrated ceiling support channel W27/60 Used as a support for ceilings mounted between cable trays with edge height 60 mm.

WEF-0001

Plate thickness mm

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

1.0

718556 6

782662 9

160

Integrated ceiling support channel W27/60 *EAN-code=732167+Part.no+C (control figure) Use and installation

Integrated ceiling support channel W27/60 is used as a support for ceilings mounted between cable trays. Mounted along the side edge of the cable tray.

Integrated ceiling support channel W27/60 is locked tight in the tray by pinching the ends in under the tray edge with pliers.

Angle strip W46 Used as a support for ceiling installations.

Plate thickness mm

Angle strip W46 0.6 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

718608 2

729194 6

52

Use and installation

Angle strip W46 is mounted directly onto wall, column or similar as a support for baffles or ceiling lamina.

167

Wall tray W60/40 Wall tray with edge height 60 mm used for mounting of ceiling in corridor. The tray is mounted directly onto the wall.

L mm

Wall tray W60/40 2000 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

718383 8

729195 3

135

Use and installation

Wall tray W60 is mounted directly onto the wall.

Mounting of ceiling in corridor when canalisation on one side is required but with the same functionality as for cable trays on both sides.

Wall tray W60/60 Wall tray with edge height 60 mm used for mounting of ceiling in corridor. The tray is mounted directly onto the wall.

Plate thickness mm

Wall tray W60/60 1.0 *EAN-code=732167+Part.no+C (control figure)

WEF-0001

Pre-galv. Part. No. C*

Pre-galv. White30 Part. No. C*

Weight kg 100 pcs

787182 7

782783 1

333

Use and installation

Wall tray W60/60 is mounted directly onto the wall.

168

Mounting of ceiling in corridor when canalisation on one side is required but with the same functionality as for cable trays on both sides.

Installation examples

Use Vertical piece 2F at installa- Example of corridor installation. This way of mounting reduce the tions in corridors with gypsum obliquity of the cable tray. walls. The installation can easily be adjusted both vertically and horizontally and will not be effected of vibrations in the walls.

Example of installation with uneven loadings. The installation has been reinforced with lashing wires. The wire can be fixed to the ceiling or the ceiling bracket.

Internal cantilever arm can be mounted right over support bracket/joint.

Mounting of Pendant rail W32 with Ogebe fixing type E direct in lighting trunking.

Ogebe fixing type D or ED can be mounted in lighting trunking as light fitting.

The Ogebe fixing type E can be mounted direct into Support bracket/joint W7.

169

170

171

172

Management system - Quality and Environment

Wibe has a third-party certified management system for quality and environment in accordance with ISO 9001:2000 and ISO 14001:2004

AB WIBE Box 401, SE-792 27 MORA, Sweden Telephone +46 250 280 00, Telefax +46 250 188 55 e-mail: [email protected], www.wibe.se

Related Documents