TELEPHONE CALL RECORD PAGE 1 OF 1

DATE AND TIME: 06-01-2009, 10:00 am NAME: Mike Koosterman COMPANY: State Boiler Inspections PROJECT: IHDM Methodist West Hospital SUBJECT: Boiler Room Shut-down

CALLED US: PHONE NO.: 515-281-8064 FAX NO.: PROJECT NO.: 406281-3

WE CALLED: X

Question (BAF): When do water heaters require shut-down along with the boilers? Answer (MK): The determination on whether or not the water heaters are required to be shutdown along with the boilers has to do ASME Section 4 and the equipment "stamp". If the water heaters have "H" stamp they are required to be shut down and if they have a "HLW" stamp they are not required to be shut-down but they do recommend it

SIGNATURE: Bruce Farrell ROUTING:

COPIES TO: FILE: