Axisware Sylk Manual: Factorylink Driver For Square D Sy/link Manual

  • Uploaded by: Axisware LLC
  • 0
  • 0
  • April 2020
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Axisware Sylk Manual: Factorylink Driver For Square D Sy/link Manual as PDF for free.

More details

  • Words: 12,716
  • Pages: 54
Square D SY/LINK Driver for FactoryLink

Version 7.2

February 2004

Axisware Square-D SY/LINK Driver for FactoryLink

1

Contents 1 Overview......................................................................................................1 1.1 Software License.....................................................................................................1 1.2 Introduction.............................................................................................................1 1.3 Historical Note........................................................................................................1 1.4 SY/LINK Card Installation.....................................................................................1 1.5 Software Installation...............................................................................................1

2 Factorylink Application Configuration......................................................3 2.1 External Device Definition.....................................................................................3 2.1.1 Logical Port.............................................................................................3 2.1.2 Device Name...........................................................................................3 2.1.3 Function...................................................................................................3 2.1.4 Memory...................................................................................................3 2.1.5 Comment.................................................................................................4 2.2 Axisware SY/LINK Read/Write Control................................................................5 2.2.1 Table Name.............................................................................................5 2.2.2 Unsolicited Read.....................................................................................5 2.2.3 Exception Write......................................................................................5 2.2.4 Block Read Priority.................................................................................6 2.2.5 Block Read Trigger.................................................................................6 2.2.6 Block Read Disable.................................................................................6 2.2.7 Block Read Complete.............................................................................6 2.2.8 Block Read State.....................................................................................6 2.2.9 Block Write Priority................................................................................7 2.2.10 Block Write Trigger..............................................................................7 2.2.11 Block Write Disable..............................................................................7 2.2.12 Block Write Complete..........................................................................7 2.2.13 Block Write State..................................................................................7 2.3 Axisware SY/LINK Read/Write Information Table...............................................8 2.3.1 Tag Name................................................................................................8 2.3.2 Logical Station........................................................................................8 2.3.3 Data Table...............................................................................................8 2.3.4 Data Offset (Address).............................................................................9 2.3.5 Bit # or Length........................................................................................9 2.3.6 Data Type................................................................................................9 2.3.7 Message Priority.....................................................................................9 2.4 Axisware SY/LINK Logical Station Control........................................................10 2.4.1 Logical Port...........................................................................................10 2.4.2 Timeout (Tenths)...................................................................................10 2.4.3 Card Memory Address (Hex)................................................................10 2.4.4 Network Address (Hex)........................................................................10 2.4.5 Maximum Network Size.......................................................................11 2.4.6 Network Baudrate.................................................................................11 2.4.7 RS-422 Port Mode.................................................................................11 2.4.8 RS-422 Port Baudrate...........................................................................11 2.4.9 RS-422 Port Parity................................................................................11 2.4.10 RS-422 Port Data Bits.........................................................................11 2.4.11 Acknowledge Alarms (possible future)..............................................12 Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

2

2.4.12 Acknowledge Fault/Alert/Warning Register (possible future)...........12 2.4.13 Unsolicited Message Length...............................................................12 2.4.14 Message Tag........................................................................................12 2.5 Axisware SY/LINK Logical Station Information.................................................13 2.5.1 Error/Status Tag Name..........................................................................13 2.5.2 Logical Station (Decimal).....................................................................13 2.5.3 Device Type..........................................................................................13 2.5.4 Routing Levels......................................................................................14 2.5.5 Routing Drop Id 1 - 7............................................................................14 2.5.6 Comment...............................................................................................14

3 Appendices................................................................................................15 3.1 Appendix A: Installation of SY/LINK Card........................................................15 3.1.1 Sy/Link Segment Memory Addresses:..................................................15 3.1.2 Cable Connections................................................................................15 3.1.3 Network Configuration and Addressing...............................................15 3.2 Appendix B: Software Installation - OS/2...........................................................18 3.2.1 Before Starting Installation (OS/2 version)..........................................18 3.2.2 Driver Installation Instructions (OS/2).................................................19 3.2.3 Modifying the CONFIG.SYS File (OS/2)............................................20 3.2.4Softkey Protection Validation................................................................21 3.3 Appendix C: (Reserved).......................................................................................22 3.4 Appendix D: Software Installation - Windows 95/NT........................................23 3.4.1 Before Starting Installation - (Windows 95/NT version).....................23 3.4.2 Driver Installation Instructions (Windows 95/NT)...............................23 3.4.3 Softkey Protection Validation...............................................................25 3.5 Appendix E: (Reserved).......................................................................................26 3.6 Appendix F: Driver Status Codes........................................................................27 3.6.1 Application startup errors.....................................................................27 3.6.2 Run-time startup errors.........................................................................29 3.6.3 SoftKey protection messages................................................................29 3.6.4 Run-time errors.....................................................................................30 3.6.5 Unsolicited message processing errors.................................................30 3.7 Appendix G: Tables for Network and Alarm Errors...........................................33 3.7.1Network Error Table..............................................................................33 3.7.2Alarm Error Table..................................................................................35 3.8 Appendix H: Data Types and Conversions..........................................................36 3.9 Appendix I: SY/LINK Addressing.......................................................................39 3.9.1Data Tables............................................................................................39 3.9.2 Device Types.........................................................................................40 3.10 Appendix J: Unsolicited Reads..........................................................................41 3.10.1Unsolicited Alarms..............................................................................42 3.10.2Unsolicited Data...................................................................................43 3.11 Appendix K: FactoryLink Version Upgrade Procedures...................................44 3.12 Appendix L: Sample Application......................................................................45

4 Glossary of Terms.....................................................................................46 5 Contact information..................................................................................48

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

1

This document contains proprietary information of Axisware LLC (Axisware). This document is based on information available at the time of its publication. While efforts have been made to be accurate, the information contained herein does not purport to cover all details or variations in hardware or software, nor to provide for every possible contingency in connection with installation, operation, or maintenance. Features may be described herein which are not present in all hardware and software systems. Axisware assumes no obligation of notice to holders of this document with respect to changes subsequently made. Axisware makes no representation or warranty, expressed, implied, or statutory with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warranties of merchantability or fitness for purpose shall apply. All trademarks are the property of their respectve owners. All trademarks acknowledged.

Copyright 1995-1996 NOVA Technologies Copyright 1997-2000 Bullet Software Copyright 2000-2004 Axisware LLC All Rights Reserved

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

Axisware LLC

2

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

1

1 Overview 1.1 Software License Axisware LLC grants you a non-exclusive license to use the Software programs and related documentation for this product on a single processing unit. For each processing unit that executes the Software programs for this product you must have a unique serial number and Proof of License statement. No one other than a current Axisware employee or agent is permitted to modify or tamper with in any way the executable computer files(s) associated with this product. This license applies solely to the software contained in this product, and does not include any additional software or documentation provided by Axisware or other parties required for the proper operation of this product. This product uses a SoftKey protection method. Please consult the SoftKey manual for a discussion of the procedures to validate the SoftKey for this product.

1.2 Introduction This manual describes the installation and configuration of the Square D SY/LINK communication driver for FactoryLink . The installation of the SY/LINK card is also briefly described. The driver currently supports all standard SY/NET devices. Unsolicited messages, faults, alerts, and warnings are supported from all SY/MAX PLCs. Register status and force information may also be read from SY/MAX PLCs.

1.3 Historical Note This product was previously a Nova Technologies product and is now an Axisware product. The manual is correct in all technical detail except install instructions, which are detailed in the Utilities manual. Axisware has assumed all responsibilities for this product; if you see a reference to Nova Technologies consider it a reference to Axisware.

1.4 SY/LINK Card Installation The SY/LINK card must be installed in the computer in an open slot. Please consult Appendix A for information concerning the installation of the card, and also refer to your hardware manuals for complete information.

1.5 Software Installation If installing over a previous version of this driver, perform a multi-platform save of the FactoryLink application before the install and restore the application after installation. Please refer to FactoryLink documentation for details on multi-platform save and restore.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

2

In this document are appendices describing the software installation for this product on specific platforms. Please read the appropriate appendix before installing this product. Platform OS/2 Windows 95/NT

Appendix B D

When the driver software installation is completed, please refer to the SoftKey Manual for the instructions on running the Validate program. Failure to run Validate by the end of the 15-day grace period will result in a nonfunctioning driver. After this communications driver has been installed, updating to a newer version of FactoryLink may appear to cause operational problems. Please refer to Appendix K before updating FactoryLink.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

3

2 Factorylink Application Configuration 2.1 External Device Definition Access this table by selecting External Device Definition from the Configuration Manager main menu. This is one of the five configuration tables that must be configured The other tables are accessed by selecting Axisware SY/LINK Driver from the Configuration Manager main menu. This table identifies the computer’s ports and I/O cards through which the devices will communicate with FactoryLink. In this table identifiers are declared which make the external devices recognizable to FactoryLink. This panel contains seven fields or five fields depending on FactoryLink version. Here we describe only the applicable fields, you shuld ignore any fields not described here. Use the Tab key to move among the fields.

2.1.1 Logical Port Number assigned by the user to indicate a particular communication path. This number must be unique for each EDI driver used in the application. Valid entries: 0-999 Physical Card & Physical Port These fields are not used by this driver.

2.1.2 Device Name The four-character device name for the EDI driver that will use the related Logical Port. Valid entry:

SYLK

2.1.3 Function Type of communication used by the EDI driver for the related Logical Port. This field refers to the different types of EDI communication modes. Valid entry:

SYSPRG

2.1.4 Memory

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

4

The amount of memory in K-bytes used for the block storage size of the read and write information entered by the user. This entry refers only to the memory used by the driver for data storage for the related Logical Port. Valid entries: 4-63

2.1.5 Comment (Optional) Description for the current Logical Port. Used only for application documentation. Valid entry:

Axisware LLC

14 alphabetic or numeric characters

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

5

2.2 Axisware SY/LINK Read/Write Control This table specifies the tags used to control the reading and writing of the values specified in the Read/Write Information table (the controlling tags are the Read Trigger, Read Disable, Write Trigger, Write Disable). It also defines the tags that will report the status of reads and writes (the status tags are the Read Complete, Read State, Write Complete, Write State). Each line in this table refers to one Read/Write Information Table. After these fields have been configured, select "Next" or Ctrl-N to edit the Read/Write Information Table corresponding to the Control table selected by the cursor.

2.2.1 Table Name User assigned name of the Read/Write Information Table to be defined or modified. Valid entry: ASCII string incorporation up to 16 of the following character set: A-Z,a-z,@,$,_, or 0-9

2.2.2 Unsolicited Read Allows you to select whether or not the current table will be considered in the processing of an unsolicited message received from the PLC. Standard addressing is used to correlate the message from the PLC with the tags configured in the table. Please refer to Appendix N for additional information and examples. Valid entries:

Descriptions:

Yes Force No

Normal write to the real-time database Forced write to the real-time database Unsolicited reads are not processed

2.2.3 Exception Write Option determining whether or not a specific tag in the related Read/Write Information Table is written to the selected logical station whenever the real-time database value for that tag changes.

Axisware LLC

Valid entries:

Description:

Yes

A change of status of any element in the table generates a write of that element's value.

No

No exception processing.

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

6

2.2.4 Block Read Priority Priority influencing the order in which the EDI task handles the queuing of block read requests. If two requests are received simultaneously by EDI, the request with the highest priority (lowest number) is processed first. Valid entries: 1 - 4

(default = 1)

2.2.5 Block Read Trigger Digital tag whose value, when forced to 1 (ON), initiates a block read of the values specified in the related Read/Write Information Table. This trigger allows the block read operation to be initiated by some other task. Valid entry:

FactoryLink digital tag

2.2.6 Block Read Disable Digital tag used to determine whether or not a block read table will be processed. If the tag value is 0, the table is permitted to function normally; however, if the value is 1, the table will not respond to the Block Read Trigger defined above. Valid entry:

FactoryLink digital tag

2.2.7 Block Read Complete Digital tag whose value is force written to 1 (ON) by the EDI task whenever any block read operation for this table is completed. If this tag is specified then when the EDI task initializes, its value is force written to 1 (ON). Note:

Block Read Complete tags are valid only if a different table is used for each logical port. Valid entry:

FactoryLink digital tag

2.2.8 Block Read State Digital tag whose value is 0 (OFF) when a block read of the tags specified in this table is in progress and 1 (ON) otherwise. If this tag is specified then when the EDI task initializes, its value is force written to 1 (ON). Note:

Block Read State tags are valid only if a different table is used for each logical port. Valid entry:

Axisware LLC

FactoryLink digital tag

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

7

2.2.9 Block Write Priority Priority influencing the order in which the EDI task handles the queuing of block write and exception write requests. If two requests are received simultaneously by EDI, the request with the highest priority (lowest number) is processed first. Valid entries: 1-4

(default = 1)

2.2.10 Block Write Trigger Dgital tag whose value, when forced to 1 (ON), initiates a block write of the values specified in the related Read/Write Information Table. This trigger allows the block write operation to be initiated by some other task. Valid entry:

FactoryLink digital tag

2.2.11 Block Write Disable Dgital tag used to determine whether or not a block write table will be processed. If the tag value is 0, the table is permitted to function normally; however, if the value is 1, the table will not respond to the Block Write Trigger defined above. Valid entry:

FactoryLink digital tag

2.2.12 Block Write Complete Dgital tag whose value is force written to 1 (ON) by the EDI task whenever any block write operation for this table is completed. If this tag is specified then, when the EDI task initializes, its value is force written to 1 (ON). Note:

Block Write Complete tags are valid only if a different table is used for each logical port. Valid entry:

FactoryLink digital tag

2.2.13 Block Write State Dgital tag whose value is 0 (OFF) when a block write of the tags specified in this table is in progress and 1 (ON) otherwise. If this tag is specified then, when the EDI task initializes, its value is force written to 1 (ON). Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

Note:

8

Block Write State tags are valid only if a different table is used for each logical port. Valid entry:

FactoryLink digital tag

2.3 Axisware SY/LINK Read/Write Information Table The Read/Write Information Table links FactoryLink tags to specific addresses in the PLC represented by the Logical Station. Values are either read into the tags from the device or written from the real-time database tags to the device. These tables are sometimes referred to as overlay panels, or ovr panels. Each table has one entry (line) for it in the Read/Write Control Table. Note:

Please verify that the table name displayed at the bottom of the panel correctly shows the table to be modified.

After these fields have been completed, select "Next" or Ctrl-N to edit the Logical Station Control Table.

2.3.1 Tag Name Name of the FactoryLink tag to be updated as a result of the read operation or the tag from which information is taken to be written to the device. Valid entry:

FactoryLink tag (DIGITAL, ANALOG, LONGANA, FLOAT, MESSAGE)

2.3.2 Logical Station Number from the Logical Station Table identifying the particular combination of physical attributes that will define and govern the data transfer to and from the real-time tag. Valid entries: 0-999

2.3.3 Data Table Mnemonic defining the area of device memory to be accessed, or the manner in which the device is to be addresse Valid entries: Refer to Appendix I (SY/LINK Addressing).

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

9

2.3.4 Data Offset (Address) Numeric portion of device address. Specifies word offset or address of data to be accessed. Valid entries: Refer to Appendix I (SY/LINK Addressing).

2.3.5 Bit # or Length If a digital tag is used, this field is one based and is used to specify the bit offset in the selected word. If a message tag is used, the field specifies the number of bytes that are to be transferred between the message tag and the Logical Station. Please see Appendix I for additional information concerning the use of bit numbers to access the status bits for a PLC register. Valid entries: Digital tags 1 - 32 Message tags 1 - 128

2.3.6 Data Type Data type for information being read/written from/to the Logical Station. Valid entries: Refer to Appendix H (Data Types and Conversions)

2.3.7 Message Priority Priority of read or write operation. If an operation is given priority status, the operation will preempt other normal priority operations on the network.. Care should be taken when using priority messages, because the overall performance of the network can be adversely affected if too many priority messages are used.

Axisware LLC

Valid entry:

Descriptions:

NORMAL PRIORITY

Normal priority read or write High priority read or write

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

10

2.4 Axisware SY/LINK Logical Station Control This table is used to configure each logical port and its associated stations in the Logical Station Information table. It specifies which specific port is connected to the external device being defined. After completing these fields, select "Next" or Ctrl-N to edit the Logical Station Information Table corresponding to the table selected by the cursor.

2.4.1 Logical Port Number specified in the External Device Definition Table which represents a particular communications path. This number must also be referenced in the External Device Definition panel. Valid entries: 0-999

2.4.2 Timeout (Tenths) Number of tenths of seconds permitted for the driver to process a request. Valid entries: Actual value in tenths of seconds. 20 to 30 (or 2 - 3 seconds for most applications).

2.4.3 Card Memory Address (Hex) Address for memory shared by the SY/LINK card and the FactoryLink CPU. This number must match the address selected by the dip switches on the card. Valid entries: Hex memory address as selected by key file (D0000 recommended) CA000, CB000, CC000, CD000, CE000, CF000, D0000, D1000, D2000, D3000

2.4.4 Network Address (Hex) Network address for the FactoryLink computer. Must be unique on the network. Valid entries: 0 - 99 or 0 – 30. See the next field. (Maximum Network Size)

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

11

2.4.5 Maximum Network Size Three possible choices for the maximum network size are available, 30, 31, and 100. The default is 30. All devices on the network must be configured for the same size (number of drops). If less than 30 devices will be used, a significant speed increase can be attained by configuring for only 30 devices. However, some configurations will require that the maximum size of 100 be used. Valid entries: 30, 31 or 100

2.4.6 Network Baudrate The baudrate determines the speed with which data will be transmitted over the network. All devices on the network must be configured for the same baudrate. Before selecting a baudrate, please note the guidelines and restrictions indicated in section 4.0 Network Configuration and Connections in the SY/LINK manual by Square D Company. Valid entries: 62.5K, 125K, 250K, and 500K

2.4.7 RS-422 Port Mode This field is used to select the operating mode for the RS-422 port on the SY/LINK card. Valid entries: SY/MAX, NET2NET

2.4.8 RS-422 Port Baudrate The baudrate determines the speed data will be transmitted over the RS-422 line. The device connected to the 422 line must be configured for the same baudrate. Valid entry:

110, 300, 600, 1200, 2400, 4800, 9600 and 19200

2.4.9 RS-422 Port Parity The parity selects how the parity bit is used on the RS-422 port. The device connected to the 422 line must be configured for the same parity. Valid entry:

NONE, ODD, EVEN

2.4.10 RS-422 Port Data Bits

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

12

This field is used to select the number of data bits used on the RS-422 port. The device connected to the 422 line must be configured for the same number of data bits. Valid entry:

7-BITS, 8-BITS

2.4.11 Acknowledge Alarms (possible future) Reserved for possible future use. Valid entry:

NO

2.4.12 Acknowledge Fault/Alert/Warning Register (possible future) Reserved for possible future use. Valid entry:

1

2.4.13 Unsolicited Message Length Unsolicited messages received from other PLCs are written directly into register memory on the SY/LINK card. The driver does not have the capability of determining which device sent the data or how many words of data were sent. This field allows the user to specify the number of words the driver is to assume are received with each unsolicited message. Valid entry:

1 - 128

2.4.14 Message Tag (Optional) Message tag to which a text string will be written if an error is encountered in the processing of an EDI request. Valid entry:

Axisware LLC

FactoryLink message tag

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

13

2.5 Axisware SY/LINK Logical Station Information This table defines the logical station(s) accessible through a specific logical port defined in the Logical Station Control Table. Each logical station is tied to its physical station address and device type. This logical station information structure allows communications to multiple devices on a network using one logical port. Note:

Please verify that the table name displayed at the bottom of the panel is showing the table to be modified.

After these fields have been completed, "Exit" or F3 will allow you to return to the Configuration Manager main menu.

2.5.1 Error/Status Tag Name (Optional) Analog tag to which all error codes for this logical station are to be written. Valid entries: FactoryLink analog tag

2.5.2 Logical Station (Decimal) Number entered by user to represent a particular combination of a logical port and physical device. This number is referenced in the Read/Write Information Table to correlate specific addresses and tags with a physical device. Please note that this number must be unique for each device name (SYLK). Valid entries: 0-999

2.5.3 Device Type Type of device on the SY/NET network with which communications are to be established. Valid entries: "SCP_1XX" "SCP_3XX" "SCP_4XX" "SCP_5XXO" "SCP_5XX" "SCP_6XX" "SCP_7XX" “DLM_110” “DLM_120” “PCM_110” "SY/LINK" GENERIC

Axisware LLC

Description: Series 100 processors Series 300 processors Series 400 processors Series 500 processors (rev. 1 - 6) Series 500 processors (rev 7 and up) Series 600 processors Series 700 processors D-Log Data Controller Module D-Log Data Controller Module PID Loop Control Module SY/LINK card General device using routing exactly as specified in the next field

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

14

2.5.4 Routing Levels The number of drop addresses from the seven following fields to be considered as valid. The specified number of valid addresses will be copied to the routing portion of the SY/LINK card for each transaction involving the selected Logical Station. Please see page 38 of the SY/LINK manual and Appendix I of this manual for additional information concerning routing. Valid entries: 0-7

2.5.5 Routing Drop Id 1 - 7 These seven fields specify the actual route values that will be used to access a device on the network. Only the number of fields specified above will be actually used. Please see page 38 of the SY/LINK manual for additional information regarding routing. Valid entries: 0-254

2.5.6 Comment (Optional) Description for the current Logical Station. Used only for application documentation. Valid entry:

Axisware LLC

31 alphabetic or numeric characters

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

15

3 Appendices 3.1 Appendix A: Installation of SY/LINK Card The SY/LINK card must be installed in the computer in an open, full length slot. However, Prior to installing the SY/LINK card, the appropriate memory segment address must be properly set by the dip switches. The memory segment address is selected by the dip switches on the SY/LINK card. The four dip switches are set in accordance with pages 14 and 15 of the SY/LINK manual. The following chart illustrates the proper switch settings for all valid addresses. A segment memory address of D0000 (hex) is recommended.

3.1.1 Sy/Link Segment Memory Addresses: SW1 0 0 0 0 0 0 0 0 1 1

SW2 0 0 0 0 1 1 1 1 0 0

SW3 0 0 1 1 0 0 1 1 0 0

SW4 0 1 0 1 0 1 0 1 0 1

ADDRESS CA000 CB000 CC000 CD000 CE000 CF000 D0000 D1000 D2000 D3000

.

3.1.2 Cable Connections The required communication cabling is discussed on pages 23 through 33 of the SY/LINK manual. The standard configuration would be to connect the cable shipped with the SY/LINK board (part number S30600-162-50) to a "Tee" connector (Class 8030 Type CCK-212) on the network cable (Belden 9463 twinaxial cable, Square D designator: Class 8030 Type CC-201).

3.1.3 Network Configuration and Addressing The following scenarios show different configurations for connecting the SY/LINK card to PLCs. Note that the first actual routing level is automatically handled by the driver so only the remaining levels are entered in the Logical Station Information Table. All addresses used are for example purposes only. Going out through 422 port and going straight to the PLC:

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

SY/LINK Card

16

No NIM is used in this scenario.

Network Address = 5

The only time SY/MAX mode is used when using the 422 port is when going straight to the PLC.

RS-422 Port Mode = SY/MAX Routing is 005, 105 Use 1 for Routing Levels, 1 Drop ID of 105. (Note: The first routing is put in automatically by the driver. Therefore the station needs only 1 Drop ID.

Going out through 422 port and through the NIM to the PLC:

SY/LINK Card Network Address = 5 RS-422 Port Mode = NET2NET Routing is 005, 105, 005. Routing Levels = 2 2 Drop IDs of 105, 005 are used.

0 5

Address wheel must be 5 (matching the Network Address) if NET2NET mode is used. -- Set to SY/MAX

-- Set to Net2Net

(The driver automatically provides the first level.)

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

17

Going out through 422 port and through two NIMs to a PLC:

SY/LINK Card Network Address = 5 RS-422 Port Mode = NET2NET

0 5

0 7

Routing is 005, 105, 007. Routing Levels = 2 2 Drop IDs of 105 and 007 are used.

-- Set to SY/MAX

-- Set to SY/MAX

-- Set to Net2Net

Going out through network port to NIMs and PLCs on a network: Out Network Port

A

B

SY/LINK Card Network Address = 05 RS-422 Port Mode = (no entry required) To the first PLC (A) the routing is 005, 007. Routing Levels = 1 1 Drop ID of 007 . To the second PLC (B) the routing is 005, 108. Routing Levels = 1 1 Drop ID of 108.

Axisware LLC

0 7

0 8

-- Set to SY/MAX

-- Set to SY/MAX

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

18

3.2 Appendix B: Software Installation - OS/2

3.2.1 Before Starting Installation (OS/2 version) Updating From A Previous Version: If the driver software is an update from an older version of the Axisware driver, the following procedures must be followed for the software to be properly installed. First, the operator must exit from both the Run Manager and the Configuration Manager. Second, a multiplatform save file should be created. Third, the driver should be installed as described below. Fourth, restore the multiplatform save file created in step 2. Fifth, update the Configuration Manager tables for the Axisware driver (Logical Station Information). The install command file relies upon the environment variable $FLINK to complete the installation process. ($FLINK is used to refer to the environment variable “FLINK”, which points to the FactoryLink directory.) Before starting the install program you may want to manually set $FLINK if you want to have the files copied to a directory other than the default of C:\FLOS2. If $FLINK has not been defined when the install is started, you will be requested to exit and assign a value to $FLINK, and then restart the install program. $FLINK can be assigned a parameter by using the SET command (example: set flink=d:\flos2). Be sure to include the drive letter. During the installation, two ASCII text files will be modified by the installation program. The original copies of both files will be copied to a file with the same filename but a .NVA extension. The first file to be modified is $FLINK\AC\TITLES (where $FLINK is the FactoryLink directory). This file is used by the Configuration Manager to determine which tasks to list and also the order in which they are to be listed. The following line will be added to the TITLES file. (The line may be different, depending on your FactoryLink version.) sylk.ac EDI NOVA SY/LINK Driver If you have a backup file named $FLINK\AC\TITLES.NVA (possibly created by a previous install), the program will warn you during the install that it is about to be overwritten and will ask you if you want to exit, and manually save the .NVA file.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

19

The second file to be modified is $FLINK\CTGEN\CTLIST. This file is used by the CTGEN utility in the creation of the binary CT (configuration table) files used at run-time by FactoryLink. The following line will be added to the CTLIST file. sylk: sylkshdr sylksovr sylk_hdr sylk_ovr If you have a backup file named $FLINK\CTGEN\CTLIST.NVA (possibly created by a previous install), the program will ask you during the install if you wish to exit, and manually save a copy of this .NVA file before it is overwritten

3.2.2 Driver Installation Instructions (OS/2) It is important that you have followed the hardware installation procedures described in Appendix A before proceeding with the driver installation instructions. The driver software is loaded by inserting the driver diskette in drive A or B. At the OS/2 command prompt, make the drive containing the diskette the current working drive, type INSTALL and then press Enter. Note:

A source other than drive A or B can be used; e.g., from a directory on a hard drive, or across a network.

If a message is displayed stating that the INSTALL program is having difficulty finding the directory containing the FactoryLink program files, press a key to exit and use the set command to reset the $FLINK environment variable. The problem may be resolved by clearly stating the drive letter. At the OS/2 command prompt type set FLINK= followed by the drive letter (a-z), a colon (:), a backslash (\) and the directory name (s) giving the path to the FactoryLink program files. Examples: set FLINK=d:\work1\flos2 or set FLINK=t:\sect2\factory. Make sure that the only space in this command is between “set” and “FLINK”. After the “Axisware” screen appears the FactoryLink Path and FactoryLink Release Version are displayed. Press y and then the Enter (Return) key if the information is correct. The driver Serial Number and Release Type are then displayed. Press y and then the Enter (Return) key to continue. The following message will appear Copying configuration files to hard disk . . .

followed by a message relevant to obtaining authorization for the product, if required. The install program checks for a backup file named $FLINK\AC\TITLES.NVA. If found, the following message is displayed: This install program will update your file named $FLINK\AC\TITLES $FLINK\AC\TITLES.NVA (a backup file) already exists. To overwrite it, press y followed by Enter (Return).

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

20

By pressing n, you may Exit, manually save your .NVA backup file, and restart this program.. Enter either y or n followed by the Enter (Return) key ==>

The install program will then go through the same procedure before updating the file $FLINK\CTGEN\CTLIST. The install program checks for a backup file named $FLINK\CTGEN\CTLIST.NVA. If found, this message appears: This install program will update your file named $FLINK\CTGEN\CTLIST $FLINK\CTGEN\CTLIST.NVA (a backup file) already exists. To overwrite it, press y followed by Enter (Return). By pressing n, you may Exit, manually save your .NVA backup file, and restart this program. Enter either y or n followed by the Enter (Return) key ==>

The messages Updating listing of driver names. . .

and Updating CTLIST . . .

will be displayed while the backup (.NVA) versions are being created and the $FLINK\AC\TITLES and $FLINK\CTGEN\CTLIST files are updated. If one of the following error messages appear: !!!! Unable to update $FLINK\AC\TITLES file or

!!!! Unable to update $FLINK\CTGEN\CTLIST file

the lines to be added to these files can be typed in manually using a text editor. Refer to the section “Before Starting” (above) for the specific lines and where they are to be added. Please notice any additional messages displayed on the screen. When all of the necessary files have been copied the following message will appear: .....NOVA Installation Program Completed.

3.2.3 Modifying the CONFIG.SYS File (OS/2) This portion of the manual should only be consulted after the general installation has been completed. The device driver NOVAMEM.SYS must be loaded into memory when your system boots for the FactoryLink SY/LINK driver to function properly. After the Axisware installation diskette's INSTALL program is run, the CONFIG.SYS file must be modified manually, using a text editor, such as OS/2's System Editor "e". The following line (or one similar to it) must be added to the OS/2 CONFIG.SYS file. A directory that will contain the device driver NOVAMEM.SYS is automatically created when the software is installed from the

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

21

Axisware installation diskette. Assuming that $FLINK is set to c:\flos2, the line to be added to the CONFIG.SYS would be: DEVICE=C:\FLOS2\EDI\SYLK\NOVAMEM.SYS It is very important that only ONE reference to this device driver be made in the CONFIG.SYS file. Note:

The changes you make to your CONFIG.SYS file will not take effect until you reboot your system.

3.2.4Softkey Protection Validation Please refer to the SoftKey Manual and run the program Validate to ensure that your product does not expire at the end of the 15-day grace period. Specific steps are included in the Softkey Manual. Warning: The installation of this product is not complete until the Validate program is run.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

22

3.3 Appendix C: (Reserved) This appendix is reserved for future use.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

23

3.4 Appendix D: Software Installation - Windows 95/NT

3.4.1 Before Starting Installation - (Windows 95/NT version) Updating From A Previous Version: If the driver software is an update from an older version of the Axisware driver, the following procedures must be followed for the software to be properly installed. First, the operator must exit from both the Run Manager and the Configuration Manager. Second, a multiplatform save file should be created. Third, the driver should be installed as described below. Fourth, restore the multiplatform save file created in step 2. Fifth, update the Configuration Manager tables for the Axisware driver (Logical Station Information). The install command file relies upon the environment variable $FLINK to complete the installation process. ($FLINK is used to refer to the environment variable “FLINK”, which points to the FactoryLink directory.) Before starting the install program you may want to manually set $FLINK if you want to have the files copied to a directory other than the default of C:\FLNT. If $FLINK has not been defined when the install is started, you will be requested to exit and assign a value to $FLINK, and then restart the install program. $FLINK can be assigned a parameter by using the SET command (example: set flink=d:\flnt). Be sure to include the drive letter. During the installation, two ASCII text files will be modified by the installation program. The original copies of both files will be copied to a file with the same filename but a .NVA extension. The first file to be modified is $FLINK\AC\TITLES (where $FLINK is the FactoryLink directory). This file is used by the Configuration Manager to determine which tasks to list and also the order in which they are to be listed. The following line will be added to the TITLES file. (The line may be different, depending on your FactoryLink version.) sylk.ac EDI Axisware SY/LINK Driver If you have a backup file named $FLINK\AC\TITLES.NVA (possibly created by a previous install), the program will warn you during the install that it is about to be overwritten and will ask you if you want to exit, and manually save the .NVA file. The second file to be modified is $FLINK\CTGEN\CTLIST. This file is used by the CTGEN utility in the creation of the binary CT (configuration table) files used at run-time by FactoryLink. The following line will be added to the CTLIST file. sylk: sylkshdr sylksovr sylk_hdr sylk_ovr If you have a backup file named $FLINK\CTGEN\CTLIST.NVA (possibly created by a previous install), the program will ask you during the install if you wish to exit, and manually save a copy of this .NVA file before it is overwritten.

3.4.2 Driver Installation Instructions (Windows 95/NT)

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

24

It is important that you have followed the hardware installation procedures described in Appendix A before proceeding with the driver installation instructions. The driver software is loaded by inserting the driver diskette in drive A or B. After making the drive containing the diskette the current working drive, type INSTALL and then press Enter. (Do not use File… Run…from Windows NT's Program Manager or File Manager.) Note:

A source other than drive A or B can be used; e.g., from a directory on a hard drive, or across a network.

If the $FLINK environment entry is not defined, you will be asked if you want to accept a default setting for it. Press y to accept this default setting. If n is pressed, the program exits, and you may use the command required by your platform to specify the location of the FactoryLink program files (example: set FLINK=f:\flnt), and then restart. If a message is displayed stating that the INSTALL program is having difficulty finding the directory containing the FactoryLink program files, press a key to exit and use the set command to reset the $FLINK environment variable. The problem may be resolved by clearly stating the drive letter. At the command prompt type set FLINK= followed by the drive letter (a-z), a colon (:), a backslash (\) and the directory name (s) giving the path to the FactoryLink program files. Examples: set FLINK=d:\work1\flnt or set FLINK=t:\sect2\factory. Make sure that the only space in this command is between “set” and “FLINK”. After the “Axisware” screen appears the FactoryLink Path and FactoryLink Release Version are displayed. Press y and then the Enter (Return) key if the information is correct. The driver Serial Number and Release Type are then displayed. Press y and then the Enter (Return) key to continue. The following message will appear Copying configuration files to hard disk . . .

followed by a message relevant to obtaining authorization for the product, if required. The install program checks for a backup file named $FLINK\AC\TITLES.NVA. If found, the following message is displayed: This install program will update your file named $FLINK\AC\TITLES $FLINK\AC\TITLES.NVA (a backup file) already exists. To overwrite it, press y. By pressing n, you may Exit, manually save your .NVA backup file, and restart this program. Enter either y or n followed by the Enter (Return) key ==>

The install program will then go through the same procedure before updating the file $FLINK\CTGEN\CTLIST. The install program checks for a backup file named $FLINK\CTGEN\CTLIST.NVA. If found, this message appears:

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

25

This install program will update your file named $FLINK\CTGEN\CTLIST $FLINK\CTGEN\CTLIST.NVA (a backup file) already exists. To overwrite it, press y followed by Enter (Return). By pressing n, you may Exit, manually save your .NVA backup file, and restart this program. Enter either y or n followed by the Enter (Return) key ==>

The messages Updating listing of driver names. . .

and Updating CTLIST . . .

will be displayed while the backup (.NVA) versions are being created and the $FLINK\AC\TITLES and $FLINK\CTGEN\CTLIST files are updated. If one of the following error messages appear: !!!! Unable to update $FLINK\AC\TITLES file or

!!!! Unable to update $FLINK\CTGEN\CTLIST file

the lines to be added to these files can be typed in manually using a text editor. Refer to the section “Before Starting” (above) for the specific lines and where they are to be added. Please notice any additional messages displayed on the screen. When all of the necessary files have been copied the following message will appear: .....NOVA Installation Program Completed.

Be sure to restart your computer to ensure that the proper changes have been made.

3.4.3 Softkey Protection Validation Please refer to the SoftKey Manual and run the program Validate to ensure that your product does not expire at the end of the 15-day grace period. Specific steps are included in the Softkey Manual. Warning: The installation of this product is not complete until the Validate program is run.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

26

3.5 Appendix E: (Reserved) This appendix is reserved for future use.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

27

3.6 Appendix F: Driver Status Codes

3.6.1 Application startup errors The following error codes (alphabetized) may be reported to FactoryLink while the SY/LINK Driver tables are being processed at startup. These messages will appear within the Run-Time Manager window during the startup of the application. Messages that scroll off the screen may be redirected to an output file by opening an OS/2 or DOS window and, at the prompt, typing edistart -r -v > edi.out followed by the Enter (Return) key. When the process has completed, edit the file edi.out to view the error codes generated by FactoryLink Bitwise data anomaly Duplicate binary address encountered. Data anomaly Indicates that addresses and data types specify overlapping elements. DIGITAL tags may not be used with numerical types DIGITAL tags may only be used to read or write discretes. Invalid bit number specified The bit number must normally be between 1 and 16. If the register data table is used, a bit number between 17 and 32 may be used to specify status bits for that register. Invalid data table specified An invalid data table was selected for the indicated device type. Consult the key file in the Configuration Manager for a list of valid data tables. Invalid data type encountered See Appendix H for list of valid data types. Invalid device type specified The data file is corrupted and contains a device not recognized by the driver. Delete the indicated record and type in the record again, selecting a valid device type. Invalid string length If a message tag is used, the Bit #/Length field in the Read/Write Information Table represents the length (in bytes) of the message used in the transaction. This number must be between 1 and 255. High priority, digital writes are invalid Digital writes are completed with a maskable write operation. Only normal priority is permitted with this write function. Logical station X, invalid routing The logical station X which was specified in the current Read/Write Information Table contains invalid routing information. Check page 38 of the SY/LINK manual for additional information about routing. Logical station X not found Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

28

The logical station X was specified in the current Read/Write Information Table, but this logical station number was never defined in the Logical Station Information Table. Maximum element length exceeded Based on the PLC type and the specified operation, there is a defined maximum length for each element. This error will only occur when priority operations are used in conjunction with messages tags longer than 16 words. MESSAGE tags may not be used with numerical types Only the ASC data type may be used with MESSAGE tags. No tag given The indicated line of the Read/Write Information Table currently being processed does not contain a valid FactoryLink tag name. No tags, read/write packet not made The current Read/Write Information Table contained entries that caused a portion of the table to generate an error and consequently no DCT information was output. Only DIGITAL tags may be used with BIN Binary data may only be accessed with DIGITAL tags. Only MESSAGE tags may be used with ASC ASCII strings may only be read into MESSAGE tags. Ordering anomaly Indicates that the Read/Write Information Table currently being processed contains addresses such that the driver is unable to properly arrange all the entries. Out of Memory The driver was unable to internally allocate all the necessary memory. Allocate more memory in the External Device Definition Table. Positive word address required The word address specified in the Configuration Manager must be one or greater. Selected data table only valid for reads Register status and forcing information may only be read from the PLC. Any attempts to write this information will result in a network error. If, due to a special configuration, it is necessary to perform this write operation, the actual register may be specified with a register data table. Selected data table only valid for unsolicited Faults, alerts, and warnings may only be accessed from unsolicited tables. Please consult Appendix J for additional information concerning unsolicited messages. Word address exceeded range The maximum word address for all data tables other than registers is 8192.

Word address exceeded range for alarm

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

29

The maximum word address for all alarm data tables is 16. Consult Appendix J for a more complete discussion of alarms (Faults, Alerts, and Warnings) The following errors may be reported when the EDI task is started after all tables have been processed. All the following errors are immediately fatal. Check separately enclosed manual for all errors reported concerning the security key.

3.6.2 Run-time startup errors The following errors may be reported when the EDI task is started after all tables have been processed. All the following errors are immediately fatal. Check separately enclosed manual for all errors reported concerning the security key. Cannot open device (error: X) [OS/2 only] Unable to open the OS/2 device driver NOVAMEM.SYS. Check that this file is specified in the CONFIG.SYS file as indicated in Appendix B. Cannot get pointer from card driver (error : X) [OS/2 only] System call failed to return card pointer. Check that this file is specified in the CONFIG.SYS file as indicated in Appendix B. Failed to initialize SY/LINK card The SY/LINK card did not initialize as expected. Check all parameters specified on the Logical Station Control Table. The selected memory address is most likely the problem. The operator must verify that no other device or process is attempting to utilize the same memory segment as the SY/LINK card. Invalid card memory address Verify that the card memory address entered on the Logical Station Control Table is a valid selection from the key file. Invalid custom data length in Logical Port Def, Exiting Software key violation, Exiting SoftKey protectiono SoftKey protection may appear after the driver has been initialized by the EDI task. Please refer to the SoftKey manual if they appear. If SoftKey does not detect a problem the following message will be displayed.

3.6.3 SoftKey protection messages Messages relating to SoftKey protection may appear after the driver has been initialized by the EDI task. Please refer to the SoftKey manual if they appear. If SoftKey does not detect a problem the following message will be displayed. Serial #: XXXXXXX Single Processor Run Time License This is a normal informational message displaying the product name and your Serial Number.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

30

3.6.4 Run-time errors The following errors may be reported while the driver is processing the EDI requests. The text represents the error message returned to the message tag defined in the Logical Station Control Table. The number in parentheses is returned to the analog tag defined in the Logical Station Information Table. While the following errors are not immediately fatal, recurring errors should be evaluated and eradicated to maintain the integrity of the network. (-10)

Device failed to respond, routing: X The indicated device did not respond when polled. Check cabling, the device address, and the routing parameters X.

(-11)

Zero length buffer error A request has been made to the CPT module with a zero byte transaction length. This error should not occur, please contact Axisware.

(-12)

Buffer manipulation error Internal communication error between DSF and CPT module. Please contact Axisware if error persists.

(-13)

Module communication timeout Communication failure between modules. Increase timeout allowed in Logical Station Control Table. If error persists, contact Axisware.

(-14)

XXXX sylkdsf dsf_read()/dsf_write() error returned from dsf_t_q_mail() Internal queue handling error encountered. Contact Axisware with error.

(Y)

Network error returned Y, routing: X The error Y was returned when the specified transaction was attempted. Check that the desired operation is valid and that the routing X is valid. For error descriptions, please refer to the Network Error Table in this manual.

3.6.5 Unsolicited message processing errors The following errors may be reported while the driver is attempting to process unsolicited message requests. The text represents the error message returned to the message tag defined in the Logical Station Control Table. While the following errors are not immediately fatal, recurring errors should be evaluated and eradicated to maintain the integrity of the network EDI DSF pointer error Software error; contact Axisware with error message. General failure clearing alarm - error X Error X occurred when the driver was attempting to clear the alarm that had been received by the SY/LINK card. For error descriptions, please refer to the Alarm Error Table in this manual.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

31

General failure retrieving alarm - error X Error X occurred when the driver was attempting to process the alarm that had been received by the SY/LINK card. For error descriptions, please refer to the Alarm Error Table in this manual. Invalid tag type for unsolicited message Internal software error. Please contact Axisware with error. Linked list error Internal software error. Please contact Axisware with error. Maximum number of unsolicited reads exceeded A maximum number of 32,000 unsolicited reads may be configured. However, the practical limitation due to memory is about 6500. If this limit is reached, please contact Axisware. No unsolicited reads have been defined An unsolicited message has been received over the Genius network; however, no unsolicited messages were defined in the Configuration Manager. If unsolicited messages are to be used, at least one line on the Read/Write Control Table must specify unsolicited message support. Timeout clearing alarm The driver was attempting to clear a received alarm from the SY/LINK card. A timeout occurred during this operation. Increase the timeout value specified in the Logical Station Control Table. If the error persists, contact Axisware with the problem. Timeout retrieving alarm The driver was attempting to read a received alarm from the SY/LINK card. A timeout occurred during this operation. Increase the timeout value specified in the Logical Station Control Table. If the error persists, contact Axisware with the problem. Unable to allocate memory for all unsolicited messages Allocate more memory to EDI task. Please note that the current driver limits the number of unsolicited messages configured to about 6500 due to the segment size. If this limit is reached, please contact Axisware. Unable to establish unsolicited index Internal software error, contact Axisware. Unable to evaluate unsolicited message An unsolicited message was received over the network with an unexpected format. Check Appendix J for details concerning the processing of unsolicited messages. Undefined unsolicited message An unsolicited message directed toward the SY/LINK card was received. The address has not been configured as an unsolicited message in the Configuration Manager. Unsolicited message processing error X While an unsolicited message was being transferred from the SY/LINK card, error X was returned by the card. Attempt the same operation again. Verify all settings on the Logical Station Control Table. If the error persists, contact Axisware with the problem. For error descriptions, please refer to the Network Error Table in this manual. Unsolicited message processing timeout Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

32

Unsolicited messages must be read from the card after they are received. After having received a message, the request to the card for the message was refused. Increase the timeout permitted in the Logical Station Control Table. Contact Axisware if the error persists. Unsolicited queue overflow Appendix G: Tables for Network and Alarm Errors

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

33

3.7 Appendix G: Tables for Network and Alarm Errors When errors occur during certain operations the SY/LINK board stores a code that indicates the cause of the error. Errors that occur during communication operations are stored in location 21H-22H ("Error Flag"). These codes are listed in the Network Error Table. Errors caused by faulty parameters used to access alarm messages are presented in location 241H-242H. These codes are listed in the Alarm Error Table. User programs should be designed to check for error codes in these locations and to either alert the operator or perform other appropriate actions.

3.7.1Network Error Table Code 001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 018 019 020 021 022 023 024 025 026 027 028 029 030 031 032 033 034 035 036 037 038 039

Description Illegal protocol opcode Illegal intermediate code Illegal address attempted Illegal rack address attempted Instruction attempted which is not allowed Item being searched for cannot be found Attempt to alter data in a protected register Attempt to alter data in protected memory Attempt to alter data in a read-only register Attempt to exceed memory limitations Communications overflow Illegal CPU rack addressing Communications error The operation attempted is not allowed in run Communication overflow Register count too large for the processor Remote device inactive The rung number used is not allowed Illegal read parameter Illegal channel number Trying to change a forced bit Forcing function is inhibited Attempt to alter data in a forced register Attempt to force a non-forcible register CPU error, check register 8175 Rack addressing and user memory overlap Memory error - clear all operation required Illegal baud rate selected Attempt to send message with illegal route Attempt to alter protected memory - inhibit coil End of file encountered Operation not allowed in protected memory Data error UVPROM memory error Write protected Replace not allowed - use delete and insert Attempt to skip or read a file past last file Data view protected - cannot read Alarm already set

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink 040 041 042 043 044 045 046 047 048 049 050 051 053 054 055 060 061 062 063 064 065 066 067 068 069 070 071 072 079 080 081 082 083 084 085 086 087 088 089 090 091 092 093 094 095 096 097 098 099 100 101 102

34

Hardware memory security in effect Illegal register write Illegal file number Illegal operation attempted File not found Operation not allowed - D-LOG tape operation in progress Protected file Operation not allowed due to keyswitch position Programming MCR in subroutine area not allowed I/O, register or channel safeguarded Rack address not alterable while forcing active Missing module Illegal media format - erase track/clear memory required Illegal mark number File operation aborted Illegal mark number for GOTO or GOSUB Mark St. Sub cannot be inserted - append only Return rungs not allowed in ladder area Mark number previously used Operation not allowed in run - cannot delete return Operation not allowed - cannot delete mark St. Sub Operation not allowed - cannot delete mark having return Operation not allowed - return must have mark Operation not allowed - only one return per mark Operation not allowed in run - Gosub with no return Operation not allowed in run - Goto to mark with return Operation not allowed in run - cannot delete mark Operation not allowed in run - unused mark number Operation not allowed in run with programmable interrupt Insufficient data Unrecognized command Illegal parameter Illegal source parameter Illegal destination parameter Invalid filespec Invalid input channel Invalid output channel Device not available Serial link not established Hardware read fault Hardware write fault Read error Write error Directory read error Directory write error Directory space full Device space full File not found File access denied File already exists File already open File format error

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 133 135

35

File wrong type Open attempt to open file I/O attempt to unopen file Write attempt to read only file Record out of range Too many open files Operation aborted by user Source filespec required Destination filespec required Maximum open count for file Incompatible source device/file type Incompatible destination device/file type Device timeout Protected file Illegal file type Illegal device File type required Device required Channel required Route required Filename required Illegal offset Illegal count Source/destination cannot be same device Duplicate label File mismatch Invalid register address Invalid file name Write data error Insufficient data for write Invalid read parameter

3.7.2Alarm Error Table Code 001 002 003 004 005 006 007

Description Invalid opcode Invalid fault count Invalid alert count Invalid warning count Invalid fault acknowledgment register Invalid alert acknowledgment register Invalid warning acknowledgment register

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

36

3.8 Appendix H: Data Types and Conversions The driver supports the following FactoryLink tag types: DIGITAL ANALOG LONG ANALOG FLOATING POINT MESSAGE The driver also supports the following PLC data types: BIN INT2 INT4 BCD4 BCD8 FLT4 FLT8 ASC

(single data bit), (16 bit signed integer), (32 bit signed integer), (16 bit, 4 digit BCD), (32 bit, 8 digit BCD), (32 bit floating point - single precision), and (64 bit floating point - double precision). (ASCII strings)

DIGITAL BIN DIGITAL tags may only be converted to and from the BIN data type. If the requested binary PLC data type is on, the DIGITAL tag will be set to one. If the binary element is off, the DIGITAL tag will be set to zero. ANALOG INT2 The ANALOG tag is a 16 bit signed integer; therefore, no conversion is needed. INT4 The lowest 16 bits of the INT4 data type correspond directly with the 16 bits comprising the ANALOG tag. BCD4 After being read from the PLC, the BCD4 value is converted into a 16 bit integer. The value is then directly transferred without conversion into the ANALOG tag. BCD8 After being read from the PLC, the BCD8 value is converted into a 32 bit integer. The value is then handled as the INT4 data type above.

FLT4 Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

37

The whole number portion of the floating point number is transferred to the ANALOG tag. This conversion is accurate only if the whole number value is between -32767 and +32767. When converting back to a FLT4, a fractional portion of zero is assumed. FLT8 The whole number portion of the floating point number is transferred to the ANALOG tag. This conversion is accurate only if the whole number value is between -32767 and +32767. When converting back to a FLT8, a fractional portion of zero is assumed. LONG ANALOG INT2 The LONG ANALOG is a 32 bit signed integer; therefore, the 16 bits of the INT2 data type correspond to the lowest 16 bits of the LONG ANALOG tag. INT4 No conversion necessary; all 32 bits transfer directly. BCD4 After being read from the PLC, the BCD4 value is converted into a 16 bit integer. The value is then handled as the INT2 data type above. BCD8 After being read from the PLC, the BCD8 value is converted into a 32 bit integer. The value is then handled as the INT4 data type above. FLT4 The whole number portion of the floating point number is transferred to the LONG ANALOG tag. This conversion is accurate only if the whole number value is between -4.3e09 and +4.3e09. When converting back to a FLT4, a fractional portion of zero is assumed. FLT8 The whole number portion of the floating point number is transferred to the LONG ANALOG tag. This conversion is accurate only if the whole number value is between -4.3e09 and +4.3e09. When converting back to a FLT8, a fractional portion of zero is assumed. FLOATING POINT INT2 The INT2 value is converted into a standard IEEE 64 bit floating point value and then transferred directly into the FLOATING POINT tag. The fractional portion of the number is assumed to be zero. INT4 The INT4 value is converted into a standard IEEE 64 bit floating point value and then transferred directly into the FLOATING POINT tag. The fractional portion of the number is assumed to be zero. BCD4 After being read from the PLC, the BCD4 value is converted into a 16 bit integer. The value is then handled as the INT2 data type above. BCD8

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

38

After being read from the PLC, the BCD8 value is converted into a 32 bit integer. The value is then handled as the INT4 data type above. FLT4 The FLT4 value is converted from a standard IEEE 32 floating point number into a standard IEEE 64 bit floating point number. This value is then transferred directly into the FLOATING POINT tag. FLT8 The data is transferred directly; no conversion is necessary. MESSAGE ASC All data is read directly into the message tag from the specified device address. No conversion of any kind is employed.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

39

3.9 Appendix I: SY/LINK Addressing All addressing for the SY/LINK driver is word based. The driver supports three basic device types and four data tables for standard read/write operations. Each data table will be discussed first, followed by a brief discussion of the special considerations for each device type. Please consult page 38 of the SY/LINK manual for additional routing information if required.

3.9.1Data Tables REGISTER The register data table is the primary area of device memory that is accessed by the driver. SY/MAX devices consist of a maximum of 32767 words of addressable memory. Not all devices use all this memory; therefore, it is the responsibility of the operator to ensure that the memory map entered in the Configuration Manager is valid. The register memory is divided into 4 equal areas: general purpose registers (1 - 8192), status registers (8193 - 16384), force enable registers (16385 - 24576), and force status registers (24577 - 32767). Write and unsolicited read operations are only to be directed toward the general purpose registers; all other areas are read only. Example: Data Table: REGISTER REGISTER REGISTER REGISTER REGISTER

Offset: 100 101 8193 24577 102

Bit 0 0 0 0 4

Description: General purpose register 100 General purpose register 101 Status for register 1 Force status for register 1 General purpose register 102 bit 4

In addition to the above word operations, the status bits for a register may also be addressed as follows: Example: Data Table: REGISTER REGISTER

Offset: 100 101

Bit: 17 32

Description: Bit 1 of status for register 100 Bit 16 of status for register 101

STATUS The status data table contains status information for each of the general purpose registers. This data table only supports read operations. Write and unsolicited read operations are not allowed. The range of addressable offsets is 1 - 8192. Example: Data Table: STATUS STATUS STATUS STATUS

Offset: 100 101 424 1000

Description: Status for general purpose register 100 Status for general purpose register 101 Status for general purpose register 424 Status for general purpose register 1000

FRC_ENBL

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

40

The force enable table contains forcing information for each of the general purpose registers. If a bit in the force enable table is on (a one), that bit is either forced on or off depending on the value of that bit in the force status table. These registers are read only. Write and unsolicited read operations are not allowed. The range of addressable offsets is 1 - 8192. The highest addressable bit is 16. Example: Data Table: FRC_ENBL FRC_ENBL

Offset: 100 101

Bit: 10 12

Description: Force enable bit 10 of register 100 Force enable bit 12 of register 101

FRC_STAT The force status table contains forcing information for each of the general purpose registers. If a bit in the force status table is on (a one), that bit is forced on if the corresponding bit in the force enable table is also on. If a bit in the force status table is off (a zero), that bit is forced off if the corresponding bit in the force enable table is on. These registers are read only. Write and unsolicited read operations are not allowed. The range of addressable offsets is 1 - 8192. The highest addressable bit is 16. Example: Data Table: FRC_STAT FRC_STAT

Offset: 100 101

Bit: 10 12

Description: Force status bit 10 of register 100 Force status bit 12 of register 101

3.9.2 Device Types SCP-XXX This is a general mnemonic for all the PLCs supported by the driver. This device type should be used for all block reads from and all writes to network devices that are PLCs or functionally equivalent to a PLC. The only difference between the PLC types as far as the driver is concerned is the number of words that can be transferred for priority operations. These limitations are listed on page 59 and page 66 of the SY/LINK manual. If a device is used that is addressed in a fashion similar to a PLC, a device type of SCP-4XX or SCP-6XX could be used for a general form of interface. The first level of routing used when addressing these device types is the address assigned to FactoryLink on the Logical Station Control Table. The remaining routing levels are copied from the Logical Station Information Table; therefore, at least one level of routing must be specified in the Logical Station Information Table. SY/LINK This device type is used to directly address the SY/LINK card. The card has 512 registers that can be accessed by read or write operations just as any other PLC registers. However, any writes to these registers (even FactoryLink) will be flagged by the SY/LINK card as an unsolicited message. If unsolicited messages, other than alarms, are to be processed by the driver, a Logical Station must be configured with a device type of SY/LINK. Each message received will then be evaluated based on the records that are defined in unsolicited tables with that Logical Station. No routing levels should be specified in the Logical Station Information Table for this device type. GENERIC This device type assumes a maximum priority operation size of 128 words (the maximum). The primary difference for this device type is the way routing is handled. All routing levels are copied directly from the Logical Station Information Table. No routing information is taken from the Logical Station Control Table as it is for the PLC types. This allows for special routing if required by the application. Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

41

3.10 Appendix J: Unsolicited Reads Unsolicited messages can be configured to allow a PLC to send data to the FactoryLink real-time database without the PLC being polled by the EDI driver. This can be useful for logging PLC data that is not generated at predefined intervals such as alarm reporting or data that changes infrequently. Two different types of unsolicited messages can be received by FactoryLink: alarms and register data.. Several simple steps are required to configure the system to receive either type of unsolicited message. The first step is to set the column titled Unsolicited Read in the NOVA SY/LINK Read/Write Control Table to either "Forced" or "Yes". This will allow that specific table to be included in the driver's search for tags with which to associate the incoming data. The table for which unsolicited reads have been enabled may now be edited to associate FactoryLink real-time database elements to addresses in the PLC. The same addressing rules should be followed for unsolicited read tables as for the standard read or write tables. Note: The number of tags that are configured as unsolicited read tags directly affects the time that is required to process incoming requests; therefore, if speed is critical, only include the unsolicited read tags that are essential to the application.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

42

3.10.1Unsolicited Alarms The following section briefly describe the steps necessary to configure FactoryLink to receive alarms transmitted by a SCP-400. The NOVA SY/LINK Read/Write Information Table must be completed with a data table of either FAULT, ALERT, or WARNING. The data offset must be set to a number between 1 and 16. A data offset of 1 will return the alarm code, while larger numbers will index further into the returned data. Example: Data Table ALERT WARNING

Data Offset 1 3

Description Alarm code from any alert from related Logical Station Third word from any warning from related Logical Station

One of the two following lines of logic must also be added to the PLC. The write command permits more flexibility, while the alarm command is more straight forward. WRITE COMMAND ROUTE ROUTE STAT LOCAL REMOTE COUNT TWRTE2 15 10 S0300 S0100 S8201

5

STANDARD ALARM ROUTE ROUTE STAT REMOTE CODE TALRM2 15 10 S0300 S8201 00162

Both commands will write out of CPU port 2 to a NIM with a network address of 15. The final destination would be a FactoryLink terminal defined as device number 10. As a result of the first command, five words of data will be written from CPU registers starting at S0100 to the Alert registers (S8201+) on the SY/LINK card. As a result of the second command, an alarm code of 162 will be written from the CPU to the Alert register (S8201) on the SY/LINK card.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

43

3.10.2Unsolicited Data The following section briefly describes the steps necessary to configure FactoryLink to receive data transmitted by a SCP-400. The NOVA SY/LINK Read/Write Information Table must be completed with a data table of REGISTER and a data offset between 1 and 512. All other data tables are invalid for unsolicited read operations. The device type for the associated Logical Station, configured within the NOVA SY/LINK Logical Station Information Table, must have a device type of SY/LINK. A write from another PLC will flag the SY/LINK card that a write has occurred and also the first register involved in the write, but information concerning the device sending the data and the number of words transmitted is not available; therefore, the user must also configure the Logical Station Control Table so the Unsolicited Msg Length field indicates the number of words that the driver is to assume will be received with each unsolicited message. Example: Data Table: REGISTER REGISTER

Data Offset: 1 15

Description: Register 1 of the SY/LINK memory Register 15 of the SY/LINK memory

The following line of logic must also be added to the PLC. WRITE COMMAND ROUTE ROUTE STAT COUNT TWRTE2 15 10

LOCAL REMOTE S0300 S0100

S0001 15

The command will write out of CPU port 2 to a NIM with a network address of 15. The final destination would be a FactoryLink terminal defined as device number 10. As a result of the command, fifteen words of data will be written from CPU registers starting at S0100 to the SY/LINK registers starting at S0001. The FactoryLink tag associated with the first line of the example will be set equal to S0100 of the PLC. If the Unsolicited Msg Length parameter is greater than 15, the tag associated with the second line of the example will be set equal to S0114 of the PLC. However, if the Unsolicited Msg Length is less than 15, the first tag will still receive a value; but the second tag will be left unchanged.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

44

3.11 Appendix K: FactoryLink Version Upgrade Procedures After installing this communications driver, upgrading to a newer version of FactoryLink may appear to cause operational problems. This is due to the modifications to certain text files made by installing this product being overwritten during the install of the new FactoryLink version. However, these files can be reconfigured using a text editor. Before installing the FactoryLink upgrade it is important to do a multiplatform save of your application. After installing the FactoryLink upgrade, the following steps should be done before restoring the multiplatform save file of your application: Where $FLINK indicates the FactoryLink directory (example: FLINK=C:\FLWIN): 1. Edit the file $FLINK\AC\TITLES and add the following line: sylk.ac EDI NOVA SY/LINK Driver 2. Open the file $FLINK\CTGEN\CTLIST and add the following line: sylk: sylkshdr sylksovr sylk_hdr sylk_ovr 3. Please refer to the appropriate appendix for your platform for further information on modifications needed in the CONFIG.SYS or SYSTEM.INI files. The SAMPLE directory of the install cd-rom includes compressed multiplatform save files of a sample application for this driver. The sample application can be used to test communications, as well as serve as an example of how to prepare a FactoryLink application to use the driver. The sample application has examples of block reads, block writes, exception writes and unsolicited reads from a single PLC. Please refer to the "README.TXT" file in the SAMPLE directory for instructions on how to use the application.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

45

3.12 Appendix L: Sample Application

The SAMPLE directory of the install cd-rom includes compressed multiplatform save files of a sample application for this driver. The sample application can be used to test communications, as well as serve as an example of how to prepare a FactoryLink application to use the driver. The sample application has examples of block reads, block writes, exception writes and unsolicited reads from a single PLC. Please refer to the "README.TXT" file in the SAMPLE directory for instructions on how to use the application.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

46

4 Glossary of Terms configuration tables Where you establish the communication path and specify elements in the database. These tables work together to allow FactoryLink to exchange information from the database with the device. External Device Definition Table Configuration table that tells the application what type of devices are connected to the computer's ports and assigns them a logical port number. logical port Number entered by the user to represent a particular combination of a logical port and a physical device (PLC). Correlates specific addresses and tags with a physical device (PLC). logical station Number entered by the user to represent a particular combination of a logical port and a physical device (PLC). Correlates specific addresses and tags with a physical device (PLC). Logical Station Control Table Table used to configure each logical port and its associated stations in the Logical Station Information table. The Logical Station Control table specifies which specific port is connected to the external device being defined. Logical Station Information table Table which defines the logical station(s) accessible through a specific logical port defined in the Logical Station Control table. Each logical station is tied to its physical station address and device type. Proof of License An 8 1/2 by 11 certificate that must accompany the software indicated by its unique serial number when that product is sold or transferred to another company or entity. Read/Write Control Table Table used to configure each logical port and its associated stations in the Logical Station Information table. Each line in this table refers to one Read/Write Information table. Read/Write Information Table Configuration table that links FactoryLink tags to specific addresses in the PLC represented by the Logical Station. SoftKey Axisware' software protection system where no hardware key (dongle) is required.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

47

Validate The program run after the software is installed that checks for improper use of the product and enables the software to function past the grace period.

Axisware LLC

[email protected]

www.axisware.com

Axisware Square-D SY/LINK Driver for FactoryLink

48

5 Contact information Axisware LLC [email protected] http://www.axisware.com 3213 Peppertree Pl. Plano, TX 75074, USA T: 1-(214)-764-1876 F: 1-(214)-764-1878