Emax power breakers
Po
we Em r b ax re ak e
ABB’s Emax series of low voltage power circuit breakers embodies over half a century’s experience and technological development in power circuit breakers. The Emax offers a series of breakers that is totally innovative in its technological design, ease of installation and use, making it the ideal solution for the growing requirements of designers, switchboard and switchgear manufacturers, installers, OEMs and users. The Emax power circuit breakers are UL Listed and meet the ANSI and IEC Standards for low voltage power circuit breakers.
ABB Emax power circuit breakers are available in five different models with rated continuous current from 800A to 6300A and rated short-circuit current range from 42kA to 200kA (480V). Technical catalog 1SDC200005 D0201 is available upon request.
16
Emax
Power breakers
rs
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.1 1SXU000023C0202
rs ax ake m E bre er ow
Selection Guide General ratings and specifications
P
E1
UL 1066 Levels of performance Frame Size
Capacity of neutral pole for four-pole circuit breakers Rated short circuit current 240V 480V 600V Rated short time current
E2
E1
E3
E2
E3
B-A 800 1200 — — — — 100
N-A 800 1200 — — — — 100
B-A 1600 — — — — — 100
N-A 800 1200 1600 — — — 100
S-A 800 1200 1600 — — — 100
H-A 800 1200 1600 — — — 100
N-A 2000 2500 — — — — 100
S-A 800 1200 1600 2000 2500 3200 100
H-A 800 1200 1600 2000 2500 3200 100
V-A 800 1200 1600 2000 2500 3200 100
X-A 800 1200 1600 2000 — — —
42 42 42 42
50 50 50 50
42 42 42 42
65 50 50 50
65 65 65 65
85 85 65 65
65 50 50 50
85 65 65 65
85 85 85 65
125 125 100 85
200 200 14 14
B 800 1000 1250 1600 — — — 100
N 800 1000 1250 1600 — — — 100
B 1600 2000 — — — — — 100
N 1000 1250 1600 2000 — — — 100
S 800 1000 1250 1600 2000 — — 100
L 1250 1600 — — — — — 100
N 2500 3200 — — — — — 100
S 1000 1250 1600 2000 2500 3200 — 100
H 800 1000 1250 1600 2000 2500 3200 100
V 800 1250 1600 2000 2500 3200 — 100
L 2000 2500 — — — — — 100
[kA] [kA] [kA] [kA]
42 42 42 42
50 50 50 50
42 42 42 42
65 65 55 55
85 85 65 65
130 110 85 85
65 65 65 65
75 75 75 75
100 100 100 85
130 130 100 100
130 110 85 85
[kA] [kA] [kA] [kA] [kA]
42 42 42 42 42
50 50 50 50 50
42 42 42 42 42
65 65 55 55 55
85 85 65 65 65
130 110 65 65 10
65 65 65 65 65
75 75 75 75 75
85 85 85 85 75
100 100 85 85 85
130 110 65 65 15
[A] [A] [A] [A] [A] [A] [%Iu] [kA] [kA] [kA] [kA]
IEC 60947-2 Levels of performance Currents: rated uninterrupted current (at 40°C) Iu
16
Capacity of neutral pole for four-pole circuit breakers Rated ultimate breaking capacity under short circuit Icu 220/230/380/400/415V 440V 500/525V 660/690V Rated service breaking capacity under short circuit Ics 220/230/380/400/415V 440V 500/525V 660/690V Rated short time withstand current Icw (1s)
[A] [A] [A] [A] [A] [A] [A] [%Iu]
UL 1066 and IEC 60947-2 3
Overall dimensions Fixed: H = 418mm/16.46 in; D = 302 mm/11.89 in W (3 poles/4 poles) W (3 poles/4 poles)
[mm] [in]
296/386 11.65/15.2
Draw out: H = 461mm/18.15 in; D = 396.5 mm/15.61 in W (3 poles/4 poles) [mm] 324/414 W (3 poles/4 poles) [in] 12.76/16.3 Weights (circuit breaker complete with trip unit, RH terminals, CS, excluding accessories) Fixed 3 poles/4 poles [Kg] 45/54 3 poles/4 poles [lbs] 99/119 Draw out 3 poles/4 poles [Kg] 70/82 3 poles/4 poles [lbs] 154/181 1 four poles only 2 100% neutral protection 3 For X Versions, see page 16.7.
16.2 1SXU000023C0202
296/386 11.65/15.2
404/530 15.91/20.82
324/414 12.76/16.3
432/558 17.01/21.97
50/61 110/134
66/80 145/176
78/93 172/205
104/125 229/275
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po
we Em r b ax re ak e
Selection guide General ratings and specifications
rs
E4
UL 1066
E4
Capacity of neutral pole for four-pole circuit breakers Rated short circuit current 240V 480V 600V Rated short time current
E6 H-A/f
S-A
H-A
V-A
L-A
H-A
V-A
L-A
X-A
3200 3600 — — — — 50
3200 3600 — — — — 50
3200 3600 — — — — 50
3200 3600 — — — — 50
3200 3600 — — — — 100
4000 5000 — — — — 50
4000 5000 — — — — 50
4000 5000 — — — — 50
4000 5000 — — — — 50
4000 5000 — — — — 100
4000 5000 — — — — 100
85 65 65 65
100 85 85 85
100 100 100 100
125 125 100 100
100 85 85 85
125 85 85 100
125 125 100 100
150 150 100 100
200 200 100 100
125 85 85 100
200 200 1000 100
S 4000 — — — — — — 50
H 3200 4000 — — — — — 50
V 3200 4000 — — — — — 50
S/f 1 4000 — — — — — — 100
H/f 1 3200 4000 — — — — — 100
H 4000 5000 6300 — — — — 50
V 3200 4000 5000 6300 — — — 50
H/f 1 4000 5000 6300 — — — — 100
[kA] [kA] [kA] [kA]
75 75 75 75
100 100 100 85
150 150 130 100
80 80 75 75
100 100 100 100
100 100 100 100
150 150 130 100
100 100 100 100
[kA] [kA] [kA] [kA] [kA]
75 75 75 75 75
100 100 100 85 100
150 150 130 100 100
80 80 75 75 80
100 100 100 100 85
100 100 100 100 85
125 125 100 100 85
100 100 100 100 100
Levels of performance Frame Size
E6
[A] [A] [A] [A] [A] [A] [%Iu] [kA] [kA] [kA] [kA]
1
H-A/f 1 X-A/f 1
IEC 60947-2 Levels of performance Currents: rated uninterrupted current (at 40°C) Iu
Capacity of neutral pole for four-pole circuit breakers Rated ultimate breaking capacity under short circuit Icu 220/230/380/400/415V 440V 500/525V 660/690V Rated service breaking capacity under short circuit Ics 220/230/380/400/415V 440V 500/525V 660/690V Rated short time withstand current Icw (1s)
[A] [A] [A] [A] [A] [A] [A] [%Iu]
16
UL 1066 and IEC 60947-2 3
Overall dimensions Fixed: H = 418mm/16.46 in; D = 302 mm/11.89 in W (3 poles/4 poles) W (3 poles/4 poles)
[mm] [in]
566/656 22.28/25.83
Draw out: H = 461mm/18.15 in; D = 396.5 mm/15.61 in W (3 poles/4 poles) [mm] 594/684 W (3 poles/4 poles) [in] 23.39/26.93 Weights (circuit breaker complete with trip unit, RH terminals, CS, excluding accessories) Fixed 3 poles/4 poles [Kg] 97/117 3 poles/4 poles [lbs] 214/258 Draw out 3 poles/4 poles [Kg] 147/165 3 poles/4 poles [lbs] 324/363 1 four poles only 2 100% neutral protection 3 For X Versions, see page 16.7.
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
7462 29.37
782/908 30.79/35.78
10342 40.71
7742 30.47
810/936 31.89/36.85
10622 41.81
1252 276
140/160 308/353
1852 408
2002 441
210/240 463/529
2752 607
16.3 1SXU000023C0202
rs ax ake m E bre er ow
General information Catalog number explanation Emax breaker
P
D 3 V
E
H B A H 0 A 0 0 0 X X Locking provisions: X = none; A = keylock (open) B = button guard C = padlock provision (open) D = withdrawable position lock (connected, test, and disconnected positions E = withdrawable position lock (test, and disconnected positions) F= A+B; G=A+C; H=A+D; J=A+E; K=B+D; L=B+E; M=C+D; N=C+E; P=A+B+D; Q=A+B+E; R=A+C+D; S=A+C+E; T=heavy duty padlock provision (open); U=A+T; V=T+D; W=T+E; Y=A+T+D; Z=A+T+E Accessories: X=none; A=mechanical counter; B = bell alarm C=bell alarm w/remote reset 24-30VAC/DC D=bell alarm w/remote reset 110-130VAC/DC E=bell alarm w/remote reset 220-240VAC/DC F= A+B; G=A+C; H=A+D; J=A+E Undervoltage trip: 0= none 50/60Hz & VDC: A=24VDC C=48V E=110-120V G=220-240V J= 380-400VAC Second shunt trip: L= 24VDC N=48V Q=110-120V S=220-240V U=380-400VAC
B=30V D=60V F=125-127V H=250V K=440-480VAC M=30V P=60V R=125-127V T= 250V V=440-480VAC
Shunt trip: 0 = none 50/60Hz & VDC: A=24VDC; B=30; C=48; D=60; E=110-120; F=125-127; G=220-240, H=250; J=380-400VAC; K=440-480VAC; L=special low Z=120-127VAC/DC Spring charging motor: (includes spring charged signal, P/N does not show) 0=none, A=24-30VAC/VDC, B=48-60VAC/VDC, C=110-130VAC/VDC, D=220-250VAC/VDC, E=spring charged signal only Contacts: A=4 aux B=10 aux D=UV energ. N.O. F=A & D G=A & E H=B & D (15 auxiliary contacts available as separate accessory)
E=UV energ. NC J = B & E
Closing coil: 0=none 50/60Hz & VDC: A=24VDC; B=30; C=48; D=60; E=110-120; F=125-127; G=220-240; H=250; J=380-400VAC; K=440-480VAC
16
Trip unit accessories: (not compatible with PR121/P) A=PR120/K4C; B=PR120/V (bottom; supplied as std on PR123/P); C=PR120/D-M; D=PR120/D-BT; E=A+B; F=A+C; G=A+D; H=A+B+C; I=A+B+D; J=B+C+D; K=A+C+D; L=A+B+C+D; M=B+C; N=PR120/V (top); P=A+N; Q=A+N+C; R=A+N+D; S=N+C+D; T=A+N+C+D; U=N+C; V=B+D; W=N+D; 0=none Trip unit: A=PR121/P, LI; B=PR121/P, LSI; C=PR121/P, LSIG; D=non-automatic; E=PR122/P, LI; F=PR122P, LSI G=PR122/P, LSIG; H=PR122/P, LSIRc1 J=PR123/P, LSI + PR120/V; K=PR123/P, LSIG + PR120/V Version: B=UL fixed3; D=UL drawout, less cradle; F=IEC fixed3; W=IEC drawout, less cradle Rating plug: A=400; B=600/630; C=800; D=1000; E=1200/1250; F=1600; G=2000; H=2500; J=30002; K=3200, L=36002; M=4000; N=5000; P=63001; 0=None (Non-automatic only) Frame ampere rating: : A=800; B=1200/1250; C=1600; D=2000; E=2500; F=3200; G=3600; H=4000; J=5000, N=63001; P=10001 Breaking capacity: B=basic; N=normal; S=standard; H=high; V=very high; L=limiting; Q=1000VAC, R=750VDC (3P) 1000VDC (4P)5; X=200kA4 Frame size: 1=E1, 3P; 2=E2, 3P; 3=E3, 3P; 4=E4, 3P; 6=E6, 3P; A=E1, 4P; B=E2, 4P, C=E3, 4P; D=E4, 4P; (50% neutral); F=E6, 4P (50% neutral); G=E4, 4P (100% neutral); H=E6, 4P (100% neutral)
1 IEC only 2 UL only 3 Horizontal terminals are standard except for the E3 3200A; for vertical terminals, see page 16.36 for conversion kit. 4 Available as E3 up to 2000A and E6 up to 5000A. 5 Consult factory.
16.4 1SXU000023C0202
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
General information Catalog number information Emax, cradle (fixed part) D 3 S
2 5
Po
we Em r b ax re ak e
rs
V A X
Options5:
X=none R=DC rated (750V 3P, 1000V 4P)1
Contacts: 0=none A=5 position auxiliaries, TOC B=10 position auxiliaries, TOC
Terminal types: (1st letter is upper terminal, 2nd letter is lower terminal) UL/IEC: H=rear horz. (H=HH); V=rear vert. (V=VV); A=HV; B=VH IEC ONLY: F=front; L=rear flat; F=FF; L=LL; C=HF; D=FH; E=HL; G=LH; J=VF; K=FV; M=VL; N=LV; P=FL; Q=LF
Max. ampere rating: UL: 12=1200 (E1); 16=1600 (E2); 20=2000 (E3)3; 25=2500 (E3); 32=3200 (E3)4, 36=3600 (E4); 50=5000 (E6) IEC: 16=1600 (E1); 20=2000 (E2); 32=3200 (E3); 40=4000 (E4); 63=6300 ( E6)
Version: UL: N=E1B-A; E1N-A; E2B-A; E2N-A; H=E2S-A; E2H-A; E4S-A; E4H-A; E4H-A/f; E6H-A; E6H-A/f; S=E3N-A; E3S-A; V=E3H-A; E3V-A; L=E4V-A; E4L-A; X=E3X-A2; E6V-A; E6L-A; E6X-A IEC: C=IEC Cradle
Frame size: 1=1, 3P; 2=2, 3P; 3=3, 3P; 4=4, 3P; 6=6, 3P; A=1, 4P; B=2, 4P; C=3, 4P; D=4, 4P (50% neutral); F=6, 4P (50% neutral); G=4, 4P (100% neutral); H=6, 4P (100% neutral)
16
1 IEC only 2 Available as E3 up to 2000A 3 Vertical only up to 2000A 4 Vertical only 5 Consult factory for pricing
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.5 1SXU000023C0202
rs
ax ke UL circuitSelection Emax breakersguide Em rea er
w Po
b
UL Circuit Breakers
Rated maximum voltage Rated voltage
Test voltage (1 min. 50/60 Hz)
[V]
[V]
[kV]
635
600
2.2
Frequency
[Hz]
Version
Fixed (F) - Draw out (W)
Number of poles
1SDC200008F0201
Voltages
1SDC200007F0201
Common data
50 - 60
3-4
E1 Level of performance Currents Frame size
[A] [A] [A] [A] [A] [A] [%Iu]
E2
B-A
N-A
B-A
N-A
S-A
H-A
800 1200
800 1200
1600
800 1200 1600
800 1200 1600
800 1200 1600
100
100
100
100
42 42 42 42
65 50 50 50
65 65 65 65
85 85 65 65
80 70 30
80 70 30
80 70 30
80 70 12
Capacity of neutral pole for four-pole circuit breakers 100 100 Rated short circuit current 240 V [kA] 42 50 480 V [kA] 42 50 600 V [kA] 42 50 Rated short time current [kA] 42 50 Trip units PR121/P PR122/P PR123/P Trip times Make time (max) [ms] 80 80 Break time (I<ST current) (max) [ms] 70 70 Break time (I>ST current) (max) [ms] 30 30 Overall dimensions Fixed: H = 418 mm/16.46 in - D = 302 mm/11.89 in * W (3 poles/4 poles) [mm] 296/386 W (3 poles/4 poles) [in] 11.65/15.2 Draw out: H = 461 mm/18.15 in - D = 396.5 mm/15.61 in ** W (3 poles/4 poles) [mm] 324/414 W (3 poles/4 poles) [in] 12.76/16.3 Weights (Circuit breaker complete with trip unit, RH terminals, CS, excluding accessories) Fixed 3 poles/4 poles [kg] 45/54 3 poles/4 poles [lbs] 99/119 Draw out 3 poles/4 poles [kg] 70/82 3 poles/4 poles [lbs] 154/181
16
296/386 11.65/15.2 324/414 12.76/16.3
50/61 110/134 78/93 172/205
(1) four poles only. * for E3X-A: H = 438 mm/ 17.24 in - D = 302 mm/ 11.89 in ** for E3X-A: H = 481 mm/ 18.94 in - D = 396.5 mm/ 15.61 in
E1 B-A / N-A Continuous current rating Iu
Mechanical life with regular ordinary maintenance Operation frequency Electrical life
Operation frequency
E2 B-A / N-A / S-A / H-A
[A]
800
1200
800
1200
1600
[No. Operations x 1000]
20
20
20
20
20
[Operations/hour]
30
30
30
30
30
[No. Operations x 1000]
10
10
10
10
10
[Operations/hour]
30
30
30
30
30
(2) 10 for E3X-A. (3) 1.5 for E3X-A.
16.6 1SXU000023C0202
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po
we Em r b ax re ak e
1SDC200011F0201
rs
1SDC200010F0201
1SDC200009F0201
Selection guide UL Circuit Breakers
E3
E4
E6
N-A
S-A
H-A
V-A
X-A
S-A
H-A
V-A
L-A
2000 2500
800 1200 1600 2000 2500 3200 100
800 1200 1600 2000 2500 3200 100
800 1200 1600 2000
3200 3600
3200 3600
3200 3600
3200 3600
100
800 1200 1600 2000 2500 3200 100
100
50
50
50
65 50 50 50
85 65 65 65
85 85 85 65
125 125 100 85
200 200 14 14
85 65 65 65
100 85 85 85
80 70 30
80 70 30
80 70 30
80 70 30
80 70 30
80 70 30
80 70 30
H-A/f
H-A/f (1) X-A/f(1)
H-A
V-A
L-A
X-A
3200 3600
4000 5000
4000 5000
4000 5000
4000 5000
4000 5000
4000 5000
50
100
50
50
50
50
100
100
100 100 100 100
125 125 100 100
100 85 85 85
125 85 85 100
125 125 100 100
150 150 100 100
200 200 100 100
125 85 85 100
200 200 100 100
80 70 30
80 70 30
80 70 30
80 70 30
80 70 30
80 70 30
80 70 30
80 70 30
80 70 30
(1)
404/530 15.91/20.82
566/656 22.28/25.83
746 29.37
782/908 30.79/35.78
1034 40.71
432/558 17.01/21.97
594/684 23.39/26.93
774 30.47
810/936 31.89/36.85
1062 41.81
66/80 145/176
70/84 154/185
97/117 214/258
125 276
140/160 308/353
185 408
104/125 229/275
106/128 233/282
147/165 324/363
200 441
210/240 463/529
275 607
E4 S-A / H-A / V-A / L-A / H-A/f
E3 N-A / S-A / H-A / V-A
E6 H-A / V-A / L-A / X-A / H-A/f / X-A/f
800
1200
1600
2000
2500
3200
3200
3600
4000
15(2)
15(2)
15(2)
15(2)
15
15
8
8
8
8
30
30
30
30
30
30
30
30
30
30
10(3)
10(3)
10(3)
8(3)
8
8
5
5
5
3
30
30
30
30
30
30
30
30
30
30
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16
5000
16.7 1SXU000023C0202
rs ax ake m E bre er ow
Non-automatic switches UL
P
The switches share the same frames and accessories as the circuit breakers, with the only difference the absence of the trip unit. The switch is available in both three-pole and four-pole fixed and draw out version and is identified by the code "/MS" (on the label). The electrical characteristics of the switches are given in the following table.
Frame size
Number of Poles Capacity of neutral pole for four-pole circuit breakers Rated voltage Rated maximum voltage Test voltage (1 min. 50/60 Hz) Frequency Rated short time current Version
[A] [A] [A] [A] [A] [A] [%Iu] [V] [V] [kV] [Hz] [kA]
E1B-A/MS 800 1200 — — — — 3/4 100 600 635 2.2 50-60 42 F -W
E1N-A/MS 800 1200 — — — — 3/4 100 600 635 2.2 50-60 50 F -W
E2B-A/MS 1600 — — — — — 3/4 100 600 635 2.2 50-60 42 F -W
E2 N-A/MS 800 1200 1600 — — — 3/4 100 600 635 2.2 50-60 50 F -W
E2S-A/MS 800 1200 1600 — — — 3/4 100 600 635 2.2 50-60 65 F -W
E3N-A/MS 2000 2500 — — — — 3/4 100 600 635 2.2 50-60 650 F -W
E3S-A/MS 800 1200 1600 2000 2500 3200 3/4 100 600 635 2.2 50-60 650 F -W
16
16.8 1SXU000023C0202
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po
we Em r b ax re ak e
Non-automatic switches UL
Frame size
Number of Poles Capacity of neutral pole for four-pole circuit breakers Rated voltage Rated maximum voltage Test voltage (1 min. 50/60 Hz) Frequency Rated short time current Version
[A] [A] [A] [A] [A] [A] [%Iu] [V] [V] [kV] [Hz] [kA]
E4S-A/MS 3200 3600 — — — — 3/4 50 600 635 2.2 50-60 65 F -W
E4H-A/MS 3200 3600 — — — — 3/4 50 600 635 2.2 50-60 85 F -W
rs
E4V-A/MS 3200 3600 — — — — 3/4 50 600 635 2.2 50-60 100 F -W
E4H-Af/MS 3200 3600 — — — — 4 50 600 635 2.2 50-60 85 F -W
E6H-A/MS 4000 5000 — — — — 3/4 50 600 635 2.2 50-60 100 F -W
E6H-Af/MS 4000 5000 — — — — 4 100 600 635 2.2 50-60 100 F -W
16
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.9 1SXU000023C0202
rs ax ake m E bre er ow
Electronic trip units Rating plugs for UL circuit breakers
P
Rating plugs Type of circuit breaker
E1B-A E2B-A E2N-A
E2S-A
E2H-A
E3N-A E3S-A
E3H-A
E3V-A
E4S-A E4H-A E4V-A
16
E4L-A E6H-A E6V-A E6L-A
Rated current Iu
In [A] 400
600
800
800 1200 1600 800 1200 1600 800 1200 1600 800 1200 1600 2000 2500 800 1200 1600 2000 2500 3200 800 1200 1600 2000 2500 3200 800 1200 1600 2000 2500 3200 3200 3600 3200 3600 3200 3600 3200
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
1000
1200
1600
2000
2500
3000
3200
• •
• •
•
• •
• •
•
• •
• •
•
• • • •
• • • •
• • •
• •
•
• • • • •
• • • • •
• • • •
• • •
• •
•
•
• • • • •
• • • • •
• • • •
• • •
• •
•
•
• • • • • • • • • • • •
• • • • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • •
• • • • • • • • •
• • • • • • • •
• • • • • • • •
3600
4000
5000
•
• • •
3600
•
•
•
•
•
•
•
•
•
•
4000
•
•
•
•
•
•
•
•
•
•
5000
•
•
•
•
•
•
•
•
•
•
4000
•
•
•
•
•
•
•
•
•
•
5000
•
•
•
•
•
•
•
•
•
•
4000
•
•
•
•
•
•
•
•
•
•
5000
•
•
•
•
•
•
•
•
•
•
• • •
1 See page 16.29 for rating plugs sold separately.
16.10 1SXU000023C0202
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po
we Em r b ax re ak e
Fixed breakers, 3 pole UL
rs
Fixed breakers Manually Operated
Electrically Operated
Set of Three Vertical Terminals
UL
Frame Amps
Interrupting Ratings kA, 480V
E1B-A08 E1N-A08 E2N-A08 E2S-A08 E2H-A08 E3S-A08 E3H-A08 E3V-A08 E3X-A08 E1B-A12 E1N-A12 E2N-A12 E2S-A12 E2H-A12 E3S-A12 E3H-A12 E3V-A12 E3X-A12
800 800 800 800 800 800 800 800 800 1200 1200 1200 1200 1200 1200 1200 1200 1200
42 50 50 65 85 65 85 125 200 42 50 50 65 85 65 85 125 200
$ 6,815 6,933 7,729 8,458 8,664 8,755 8,931 9,926 11,678 7,321 7,429 7,819 8,712 8,835 8,780 9,048 9,953 11,709
$ 9,176 9,294 10,090 11,819 11,025 11,116 11,292 12,287 14,039 9,682 9,790 10,180 11,073 11,196 11,141 11,409 12,314 14,070
$ 644 644 690 690 690 790 790 790 790 644 644 690 690 690 790 790 790 790
E2B-A16 E2N-A16 E2S-A16 E2H-A16 E3S-A16 E3H-A16 E3V-A16 E3X-A16
1600 1600 1600 1600 1600 1600 1600 1600
42 50 65 85 65 85 125 200
7,871 9,082 9,764 10,019 9,797 10,352 11,387 13,396
10,232 11,443 12,125 12,380 12,158 12,713 13,748 15,757
690 690 690 690 790 790 790 790
E3N-A20 E3S-A20 E3H-A20 E3V-A20 E3X-A20
2000 2000 2000 2000 2000
50 65 85 125 200
10,032 11,053 13,602 14,962 17,603
12,393 13,414 15,963 17,323 19,964
790 790 790 790 790
E3N-A25 E3S-A25 E3H-A25 E3V-A25
2500 2500 2500 2500
50 65 85 125
14,778 16,451 17,708 19,479
17,139 18,812 20,069 21,840
790 790 790 790
E3S-A32 E3H-A32 E3V-A32 E4S-A32 E4H-A32 E4V-A32 E4L-A32
3200 3200 3200 3200 3200 3200 3200
65 85 125 65 85 100 150
23,242 23,929 26,488 21,102 21,566 24,047 27,812
25,603 26,290 28,849 23,463 23,927 26,408 30,173
E4S-A36 E4H-A36 E4V-A36 E4L-A36
3600 3600 3600 3600
65 85 100 150
23,939 27,302 28,666 29,203
26,300 29,663 31,027 31,564
1,664 1,664 1,664 1,664
E6H-A40 E6V-A40 E6L-A40 E6X-A40
4000 4000 4000 4000
85 125 150 200
31,528 43,932 50,399 53,052
33,889 46,293 52,760 55,413
2,783 2,783 2,783 2,783
E6H-A50 E6V-A50 E6L-A50 E6X-A50
5000 5000 5000 5000
85 125 150 200
43,221 51,684 55,439 58,356
45,582 54,045 57,800 60,717
2,783 2,783 2,783 2,783
6 Vertical Terminals are Standard 1,664 1,664 1,664 1,664
Standard features – manually operated UL breaker • • • • • • • • •
Rear horizontal terminals except where noted PR121 trip unit with LI protection functions Manual mechanical close and open pushbuttons CB open/closed mechanical indicator Spring charged/discharged mechanical indicator 2NO & 2NC auxiliary contacts for open/closed position indication Lifting plates Current transformers Terminal box
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule ED1 - ED6
16.11 1SXU000023C0202
16
rs ax ake m E bre er ow
Fixed breakers, 4 pole UL
P
Fixed breakers UL
16
Interrupting Ratings kA, 480V
Manually Operated
E1B-A08 E1N-A08 E2N-A08 E2S-A08 E2H-A08 E3S-A08 E3H-A08 E3V-A08 E3X-A08
800 800 800 800 800 800 800 800 800
42 50 50 65 85 65 85 125 200
$ 9,200 9,323 9,662 10,587 10,851 10,970 11,197 12,495 15,765
$ 11,561 11,684 12,023 12,948 13,212 13,331 13,558 14,856 18,126
$ 870 870 935 935 935 1,067 1,067 1,067 1,067
E1B-A12 E1N-A12 E2N-A12 E2S-A12 E2H-A12 E3S-A12 E3H-A12 E3V-A12 E3X-A12
1200 1200 1200 1200 1200 1200 1200 1200 1200
42 50 50 65 85 65 85 125 200
9,883 10,038 10,556 11,826 11,903 11,853 12,215 13,436 15,807
12,244 12,399 12,917 14,187 14,264 14,214 14,576 15,797 18,168
870 870 935 935 935 1,067 1,067 1,067 1,067
E2B-A16 E2N-A16 E2S-A16 E2H-A16 E3S-A16 E3H-A16 E3V-A16 E3X-A16
1600 1600 1600 1600 1600 1600 1600 1600
42 50 65 85 65 85 125 200
10,626 12,261 12,978 13,121 13,226 13,975 15,373 18,085
12,987 14,622 15,339 15,482 15,587 16,336 17,734 20,446
935 935 935 935 1,067 1,067 1,067 1,067
E3N-A20 E3S-A20 E3H-A20 E3V-A20 E3X-A20 E3N-A25 E3S-A25 E3H-A25 E3V-A25
2000 2000 2000 2000 2000 2500 2500 2500 2500
50 65 85 125 200 50 65 85 125
13,543 14,922 18,363 20,199 23,763 19,950 22,209 23,906 26,296
15,904 17,283 20,724 22,560 26,124 22,311 24,570 26,267 28,657
1,067 1,067 1,067 1,067 1,067 1,067 1,067 1,067 1,067
E3S-A32 E3H-A32 E3V-A32 E4S-A32 E4H-A32 E4H-A/f32 1 E4V-A32 E4L-A32
3200 3200 3200 3200 3200 3200 3200 3200
65 85 125 65 85 85 100 150
29,772 30,081 33,340 28,488 29,114 31,916 32,463 35,712
32,133 32,442 35,701 30,849 31,475 34,277 34,824 38,073
8 Vertical Terminals are standard 2,250 2,250 2,572 2,250 2,250
E4S-A36 E4H-A36 E4H-A/f36 1 E4V-A36 E4L-A36
3600 3600 3600 3600 3600
65 85 85 100 150
32,318 36,858 39,866 38,669 40,931
34,679 39,219 42,227 41,060 43,292
2,250 2,250 2,572 2,250 2,250
E6H-A40 E6H-A/f40 1 E6V-A40 E6L-A40 E6X-A40 E6X-A/f40
4000 4000 4000 4000 4000 4000
85 85 125 150 200 200
42,563 46,110 59,308 65,076 71,620 81,851
44,924 48,471 61,669 67,437 73,981 84,212
3,757 4,294 3,757 3,757 3,757 4,294
E6H-A50 E6H-A/f50 1 E6V-A50 E6L-A50 E6X-A50 E6X-A/f50
5000 5000 5000 5000 5000 5000
85 85 125 150 200 200
58,348 65,097 69,773 71,628 78,781 90,035
60,709 67,458 72,134 73,989 81,142 92,396
3,757 4,294 3,757 3,757 3,757 4,294
Standard features – manually operated UL breaker
Neutral pole rating
• • • • • • • • •
• E1 – E3 = 100% rating • E4 – E6 = 50% rating
Rear horizontal terminals except where noted PR121 trip unit with LI protection functions Manual mechanical close and open pushbuttons CB open/closed mechanical indicator Spring charged/discharged mechanical indicator 2NO & 2NC auxiliary contacts for open/closed position indication Lifting plates Current transformers Terminal box
Electrically Operated
Set of Four Vertical Terminals
Frame Amps
1 Special 100% neutral pole rating.
16.12 1SXU000023C0202
Discount schedule ED1 - ED6
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po
we Em r b ax re ak e
Withdrawable breakers, 3 pole UL
rs
Withdrawable breakers UL
Frame Amps
Interrupting Ratings kA, 480V
Manually Operated
Electrically Operated
Cradle w/Rear Horizontal Terminals
E1B-A08 E1N-A08 E2N-A08 E2S-A08 E2H-A08 E3S-A08 E3H-A08 E3V-A08 E3X-A08
800 800 800 800 800 800 800 800 800
42 50 50 65 85 65 85 125 200
$ 7,383 7,754 8,529 9,038 9,564 9,408 9,792 10,404 12,240
$ 9,744 10,115 10,890 11,399 11,925 11,769 12,153 12,765 14,601
$ 2,281 2,281 2,400 2,400 2,400 2,925 2,925 2,925 4,109
$ 644 644 690 690 690 790 790 790 790
E1B-A12 E1N-A12 E2N-A12 E2S-A12 E2H-A12 E3S-A12 E3H-A12 E3V-A12 E3X-A12
1200 1200 1200 1200 1200 1200 1200 1200 1200
42 50 50 65 85 65 85 125 200
8,375 8,690 8,814 9,242 9,687 9,520 9,633 10,596 12,467
10,736 11,051 11,175 11,603 12,048 11,581 11,994 12,957 14,828
2,281 2,281 2,400 2,400 2,400 2,925 2,925 2,925 4,109
644 644 690 690 690 790 790 790 790
E2B-A16 E2N-A16 E2S-A16 E2H-A16 E3S-A16 E3H-A16 E3V-A16 E3X-A16
1600 1600 1600 1600 1600 1600 1600 1600
42 50 65 85 65 85 125 200
9,320 10,483 11,506 11,726 10,931 11,445 12,590 14,812
11,681 12,844 13,867 14,087 13,292 13,806 14,951 17,173
2,400 2,400 2,400 2,400 2,925 2,925 2,925 4,109
690 690 690 690 790 790 790 790
E3N-A20 E3S-A20 E3H-A20 E3V-A20 E3X-A20
2000 2000 2000 2000 2000
50 65 85 125 200
11,386 12,700 14,262 15,688 18,456
13,747 15,061 16,623 18,049 20,817
2,925 2,925 2,925 2,925 4,109
790 790 790 790 790
E3N-A25 E3S-A25 E3H-A25 E3V-A25
2500 2500 2500 2500
50 65 85 125
17,767 20,315 22,622 24,884
20,128 22,676 24,983 27,245
2,925 2,925 2,925 2,925
790 790 790 790
E3S-A32 E3H-A32 E3V-A32 E4S-A32 E4H-A32 E4V-A32 E4L-A32
3200 3200 3200 3200 3200 3200 3200
65 85 125 65 85 100 150
25,310 26,009 27,177 23,800 24,447 25,863 31,205
27,671 28,370 29,538 26,161 26,808 28,224 33,566
7,259 7,259 7,259 6,259 6,259 6,259 6,259
6 Vertical Terminals are standard 1,664 1,664 1,664 1,664
E4S-A36 E4H-A36 E4V-A36 E4L-A36
3600 3600 3600 3600
65 85 100 150
26,863 30,865 31,948 42,215
29,224 33,226 34,309 44,576
6,259 6,259 6,259 6,259
1,664 1,664 1,664 1,664
E6H-A40 E6V-A40 E6L-A40 E6X-A40
4000 4000 4000 4000
85 125 150 200
34,676 46,570 51,407 54,113
37,037 48,931 53,768 56,474
7,398 7,398 7,398 7,398
2,783 2,783 2,783 2,783
E6H-A50 E6V-A50 E6L-A50 E6X-A50
5000 5000 5000 5000
85 125 150 200
46,402 57,078 59,375 62,500
48,763 59,439 61,736 64,861
7,398 7,398 7,398 7,398
2,783 2,783 2,783 2,783
Standard features – electrically operated breaker Moving part
Standard features – electrically operated breaker Fixed part
• • • • • • • • • • • • • •
• • • • •
PR121 trip unit with LI protection feature Spring charging motor Shunt trip Closing coil Manual mechanical close and open pushbuttons CB open/closed mechanical indicator Spring charged/discharged mechanical indicator 2NO & 2NC auxiliary contacts for open-closed position indication Lifting plates Current transformers Racking device with closed door Circuit breaker racking position indicator Sliding contacts Fail safe device (not available with YU)
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Set of Three Vertical Terminals
16
Safety shutters Rear horizontal terminals except where noted Sliding contacts Anti-insertion lock Ground connection
Discount schedule ED1 - ED6
16.13 1SXU000023C0202
rs ax ake m E bre er ow
Withdrawable breakers, 4 pole UL
P
Withdrawable breakers E1B-A08 E1N-A08 E2N-A08 E2S-A08 E2H-A08 E3S-A08 E3H-A08 E3V-A08 E3X-A08
800 800 800 800 800 800 800 800 800
Interrupting Ratings kA, 480V 42 50 50 65 85 65 85 125 200
E1B-A12 E1N-A12 E2N-A12 E2S-A12 E2H-A12 E3S-A12 E3H-A12 E3V-A12 E3X-A12
1200 1200 1200 1200 1200 1200 1200 1200 1200
E2B-A16 E2N-A16 E2S-A16 E2H-A16 E3S-A16 E3H-A16 E3V-A16 E3X-A16
UL
16
Frame Amps
Manually Operated
Electrically Operated
Cradle w/Rear Horizontal Terminals $ 3,079 3,079 3,240 3,240 3,240 3,949 3,949 3,949 4,109
Set of Four Vertical Terminals $ 870 870 935 935 935 1,067 1,067 1,067 1,067
$ 9,967 10,513 11,107 11,306 12,508 11,107 12,287 13,645 16,524
$ 12,328 12,874 13,468 13,667 14,869 13,468 14,648 16,006 18,885
42 50 50 65 85 65 85 125 200
11,306 11,262 11,899 12,596 12,846 12,447 13,005 14,305 16,830
13,667 13,623 14,260 14,957 15,207 14,808 15,366 16,666 19,191
3,079 3,079 3,240 3,240 3,240 3,949 3,949 3,949 4,109
870 870 935 935 935 1,067 1,067 1,067 1,067
1600 1600 1600 1600 1600 1600 1600 1600
42 50 65 85 65 85 125 200
12,582 14,152 14,515 14,800 14,757 15,451 16,996 19,996
14,943 16,513 16,876 17,161 17,118 17,812 19,357 22,357
3,240 3,240 3,240 3,240 3,949 3,949 3,949 4,109
935 935 935 935 1,067 1,067 1,067
1,067
E3N-A20 E3S-A20 E3H-A20 E3V-A20 E3X-A20
2000 2000 2000 2000 2000
50 65 85 125 200
15,371 17,145 19,254 21,179 24,916
17,732 19,506 21,615 23,540 27,277
3,949 3,949 3,949 3,949 4,109
1,067 1,067 1,067 1,067 1,067
E3N-A25 E3S-A25 E3H-A25 E3V-A25
2500 2500 2500 2500
50 65 85 125
23,985 27,425 30,540 33,594
26,346 29,786 32,901 35,955
3,949 3,949 3,949 3,949
1,067 1,067 1,067 1,067
E3S-A32 E3H-A32 E3V-A32 E4S-A32 E4H-A32 E4H-A/f32 1 E4V-A32 E4L-A32
3200 3200 3200 3200 3200 3200 3200 3200
65 85 125 65 85 85 100 150
24,789 33,369 33,884 32,130 33,003 34,067 34,915 40,123
27,150 35,730 36,245 34,491 35,364 36,428 37,276 42,484
9,679 9,679 9,679 8,450 8,450 9,657 8,450 8,450
E4S-A36 E4H-A36 E4H-A/f36 1 E4V-A36 E4L-A36
3600 3600 3600 3600 3600
65 85 85 100 150
36,265 41,668 43,659 43,130 48,173
38,626 44,029 46,020 45,491 50,534
8,450 8,450 9,657 8,450 8,450
2,250 2,250 2,572 2,250 2,250
E6H-A40 E6H-A/f40 1 E6V-A40 E6L-A40 E6X-A40 E6X-A/f40
4000 4000 4000 4000 4000 4000
85 85 125 150 200 200
46,813 53,123 62,870 66,386 73,053 83,489
49,174 55,484 65,231 68,747 75,414 85,850
9,987 11,414 9,987 9,987 9,987 11,414
3,757 4,294 3,757 3,757 3,757 4,294
E6H-A50 E6H-A/f50 1 E6V-A50 E6L-A50 E6X-A50 E6X-A/f50
5000 5000 5000 5000 5000 5000
85 85 125 150 200 200
63,643 68,799 77,055 80,156 84,375 96,429
65,004 71,160 79,416 82,517 86,736 98,790
9,987 11,414 9,987 9,987 9,987 11,414
3,757 4,294 3,757 3,757 3,757 4,294
Standard features – electrically operated breaker Moving part
Standard features – electrically operated breaker Fixed part
• • • • • • • • • • • • • •
• • • • •
PR121 trip unit with LI protection feature Spring charging motor Shunt trip Closing coil Manual mechanical close and open pushbuttons CB open/closed mechanical indicator Spring charged/discharged mechanical indicator 2NO & 2NC auxiliary contacts for open-closed position indication Lifting plates Current transformers Racking device with closed door Circuit breaker racking position indicator Sliding contacts Fail safe device (not available with YU)
16.14 1SXU000023C0202
8 Vertical Terminals are standard 2,250 2,250 2,572 2,250 2,250
Safety shutters Rear horizontal terminals Sliding contacts Anti-insertion lock Ground connection
Neutral pole rating • E1 – E3 = 100% rating • E4 – E6 = 50% rating
1 Special 100% neutral pole rating.
Discount schedule ED1 - ED6
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Non-automatic switches Fixed switches (without trip unit & c.t.s.), 3 pole UL
Po
we Em r b ax re ak e
rs
Fixed switches Manually Operated
Electrically Operated
Set of Three Vertical Terminals
UL
Frame Amps
Rated Short Time Current, kA
E1B-A/MS-08 E1N-A/MS-08 E2N-A/MS-08 E2S-A/MS-08 E3S-A/MS-08 E3V-A/MS-08
800 800 800 800 800 800
42 50 50 65 65 85
$ 5,086 5,334 7,230 7,498 7,053 9,050
$ 7,447 7,695 9,591 9,859 9,414 11,411
$ 644 644 690 690 790 790
E1B-A/MS-12 E1N-A/MS-12 E2N-A/MS-12 E2S-A/MS-12 E3S-A/MS-12 E3V-A/MS-12
1200 1200 1200 1200 1200 1200
42 50 50 65 65 85
5,592 5,627 6,090 7,348 6,944 9,407
7,953 7,988 8,451 9,709 9,305 11,768
644 644 690 690 790 790
E2B-A/MS-16 E2N-A/MS-16 E2S-A/MS-16 E3S-A/MS-16 E3V-A/MS-16
1600 1600 1600 1600 1600
42 50 65 65 85
6,142 7,353 8,550 7,961 10,731
8,503 9,714 10,911 10,322 13,092
690 690 690 790 790
E3N-A/MS-20 E3S-A/MS-20 E3V-A/MS-20
2000 2000 2000
50 65 85
8,196 9,217 14,564
10,557 11,578 16,925
790 790 790
E3N-A/MS-25 E3S-A/MS-25 E3V-A/MS-25
2500 2500 2500
50 65 85
12,942 14,615 17,658
15,303 16,976 20,019
790 790 790
E3S-A/MS-32 E3V-A/MS-32 E4S-A/MS-32 E4H-A/MS-32 E4V-A/MS-32 E4S-A/MS-36 E4H-A/MS-36 E4V-A/MS-36
3200 3200 3200 3200 3200 3600 3600 3600
65 85 65 85 100 65 85 100
20,091 21,148 18,733 19,197 24,305 21,570 24,933 29,258
22,452 23,509 21,094 21,558 26,666 23,931 27,294 31,619
6 Vertical Terminals are standard
E6H-A/MS-40
4000
100
28,946
31,307
2,783
E6H-A/MS-50
5000
100
40,639
43,000
2,783
1,664 1,664 1,664 1,664 1,664 1,664
Standard features – manually operated UL switch • • • • • •
Rear horizontal terminals except where noted Manual mechanical close and open pushbuttons CB open/closed mechanical indicator Spring charged/discharged mechanical indicator Lifting plates Terminal box
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16
Discount schedule ED1 - ED6
16.15 1SXU000023C0202
rs ax ake m E bre er ow
P
Non-automatic switches Fixed switches (without trip unit & c.t.s.), 4 pole UL
Fixed switches
16
Electrically Operated
Set of Four Vertical Terminals
$ 6,866 7,108 9,634 9,991 9,169 12,059
$ 9,227 9,469 11,995 12,352 11,530 14,420
$ 870 870 935 935 1,067 1,067
42 50 50 65 65 85
7,549 7,648 8,222 10,349 9,374 12,229
9,910 10,009 10,583 12,710 11,735 14,590
870 870 935 935 1,067 1,067
1600 1600 1600 1600 1600
42 50 65 65 85
8,282 9,927 12,042 10,747 13,950
10,653 12,288 14,403 13,108 16,311
935 935 935 1,067 1,067
E3N-A/MS-20 E3S-A/MS-20 E3V-A/MS-20
2000 2000 2000
50 65 85
11,065 12,443 18,933
13,426 14,804 21,294
1,067 1,067 1,067
E3N-A/MS-25 E3S-A/MS-25 E3V-A/MS-25
2500 2500 2500
50 65 85
17,472 19,730 23,452
19,833 22,091 25,813
1,067 1,067 1,067
E3S-A/MS-32 E3V-A/MS-32 E4S-A/MS-32 E4H-A/MS-32 E4H-A/f/MS-32 1 E4V-A/MS-32
3200 3200 3200 3200 3200 3200
65 85 65 85 85 100
26,118 27,492 25,290 25,916 27,899 31,597
28,479 29,853 27,651 28,277 30,260 33,958
8 Vertical Termianls are standard 2,250 2,250 2,572 2,250
E4S-A/MS-36 E4H-A/MS-36 E4H-A/f/MS-36 1 E4V-A/MS-36
3600 3600 3600 3600
65 85 85 100
29,120 33,660 36,372 38,035
31,481 36,021 38,733 40,396
2,250 2,250 2,572 2,250
E6H-A/MS-40 E6H-A/f/MS-40 1
4000 4000
100 100
39,077 42,260
41,438 44,621
3,757 4,294
E6H-A/MS-50 E6H-A/f/MS-50 1
5000 5000
100 100
54,863 59,535
57,224 61,896
3,757 4,294
UL
Frame Amps
Rated Short Time Current, kA
E1B-A/MS-08 E1N-A/MS-08 E2N-A/MS-08 E2S-A/MS-08 E3S-A/MS-08 E3V-A/MS-08
800 800 800 800 800 800
42 50 50 65 65 85
E1B-A/MS-12 E1N-A/MS-12 E2N-A/MS-12 E2S-A/MS-12 E3S-A/MS-12 E3V-A/MS-12
1200 1200 1200 1200 1200 1200
E2B-A/MS-16 E2N-A/MS-16 E2S-A/MS-16 E3S-A/MS-16 E3V-A/MS-16
Manually Operated
Standard features – manually operated UL switch
Neutral pole rating
• • • • • •
• E1 – E3 = 100% rating • E4 – E6 = 50% rating
Rear horizontal terminals except where noted Manual mechanical close and open pushbuttons CB open/closed mechanical indicator Spring charged/discharged mechanical indicator Lifting plates Terminal box
1 Special 100% neutral pole rating.
16.16 1SXU000023C0202
Discount schedule ED1 - ED6
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po Non-automatic switches we Em r a Withdrawable switches (without trip unit & c.t.s.), 3 pole breax ke rs UL Withdrawable switches UL
Frame Amps
Rated Short Time Current, kA
Manually Operated
Electrically Operated
Cradle w/Rear Horizontal Terminals
Set of Three Vertical Terminals
E1B-A/MS-08 E1N-A/MS-08 E2N-A/MS-08 E2S-A/MS-08 E3S-A/MS-08 E3V-A/MS-08
800 800 800 800 800 800
42 50 50 65 65 85
$ 5,654 6,355 7,407 7,560 7,931 9,360
$ 8,015 8,716 9,768 9,921 10,292 11,721
$ 2,281 2,281 2,281 2,281 2,925 2,925
$ 644 644 690 690 790 790
E1B-A/MS-12 E1N-A/MS-12 E2N-A/MS-12 E2S-A/MS-12 E3S-A/MS-12 E3V-A/MS-12
1200 1200 1200 1200 1200 1200
42 50 50 65 65 85
6,646 6,920 7,085 8,149 7,384 10,064
9,007 9,281 9,446 10,510 9,745 12,425
2,281 2,281 2,400 2,400 2,925 2,925
644 644 690 690 790 790
E2B-A/MS-16 E2N-A/MS-16 E2S-A/MS-16 E3S-A/MS-16 E3V-A/MS-16
1600 1600 1600 1600 1600
42 50 65 65 85
7,591 8,754 10,029 9,095 11,585
9,952 11,115 12,390 11,456 13,946
2,400 2,400 2,400 2,925 2,925
690 690 690 790 790
E3N-A/MS-20 E3S-A/MS-20 E3V-A/MS-20
2000 2000 2000
50 65 85
9,550 10,864 14,800
11,911 13,225 17,161
2,925 2,925 2,925
790 790 790
E3N-A/MS-25 E3S-A/MS-25 E3V-A/MS-25
2500 2500 2500
50 65 85
15,931 18,479 22,505
18,292 20,840 24,866
2,925 2,925 2,925
790 790 790
E3S-A/MS-32 E3V-A/MS-32 E4S-A/MS-32 E4H-A/MS-32 E4V-A/MS-32
3200 3200 3200 3200 3200
65 85 65 85 100
23,833 25,327 21,431 22,078 24,831
26,194 27,688 23,792 24,439 27,192
4,515 4,515 6,259 6,259 6,259
E4S-A/MS-36 E4H-A/MS-36 E4V-A/MS-36
3600 3600 3600
65 85 100
24,494 28,496 32,148
26,855 30,857 34,509
6,259 6,259 6,259
1,664 1,664 1,664
E6H-A/MS-40
4000
100
32,094
34,455
7,398
2,783
E6H-A/MS-50
5000
100
43,820
46,181
7,398
2,783
6 Vertical Terminals are standard 1,664 1,664 1,664
Standard features – manually operated switch Moving part
Standard features – manually operated switch Fixed part
• • • • • • • •
• • • • •
Manual mechanical close and open pushbuttons Circuit breaker open/closed mechanical indicator Spring charged/discharged mechanical indicator Lifting plates Racking device with closed door Circuit breaker racking position indicator Sliding contacts Fail-safe device (not available with YU)
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Safety shutters Rear horizontal terminals except where noted Sliding contacts Anti-insertion lock Ground connection
Discount schedule ED1 - ED6
16
16.17 1SXU000023C0202
rs ax ake m E bre er ow
Non-automatic switches Withdrawable switches (without trip unit & c.t.s.), 4 pole UL
P
Withdrawable switches
16
UL
Frame Amps
Rated Short Time Current, kA
Manually Operated
Electrically Operated
Cradle w/Rear Horizontal Terminals
Set of Four Vertical Terminals
E1B-A/MS-08 E1N-A/MS-08 E2N-A/MS-08 E2S-A/MS-08 E3S-A/MS-08 E3V-A/MS-08
800 800 800 800 800 800
42 50 50 65 65 85
$ 7,633 7,886 9,244 9,828 9,898 11,681
$ 9,994 10,247 11,605 12,189 12,259 14,042
$ 3,079 3,079 3,240 3,240 3,949 3,949
$ 870 870 935 935 1,066 1,066
E1B-A/MS-12 E1N-A/MS-12 E2N-A/MS-12 E2S-A/MS-12 E3S-A/MS-12 E3V-A/MS-12
1200 1200 1200 1200 1200 1200
42 50 50 65 65 85
8,972 8,996 9,565 10,594 9,968 13,084
11,333 11,357 11,926 12,955 12,329 15,445
3,079 3,079 3,240 3,240 3,949 3,949
870 870 935 935 1,066 1,066
E2B-A/MS-16 E2N-A/MS-16 E2S-A/MS-16 E3S-A/MS-16 E3V-A/MS-16
1600 1600 1600 1600 1600
42 50 65 65 85
10,248 11,818 12,516 12,278 15,060
12,609 14,179 14,877 14,639 17,421
3,240 3,240 3,240 3,949 3,949
935 935 897 1,066 1,066
E3N-A/MS-20 E3S-A/MS-20 E3V-A/MS-20
2000 2000 2000
50 65 85
12,893 14,666 19,240
15,254 17,027 21,601
3,949 3,949 3,949
1,066 1,066 1,066
E3N-A/MS-25 E3S-A/MS-25 E3V-A/MS-25
2500 2500 2500
50 65 85
21,507 24,947 29,257
23,868 27,308 31,618
3,949 3,949 3,949
1,066 1,066 1,066
E3S-A/MS-32 E3V-A/MS-32 E4S-A/MS-32 E4H-A/MS-32 E4H-A/f/MS-32 1 E4V-A/MS-32
3200 3200 3200 3200 3200 3200
65 85 65 85 85 100
28,599 30,181 28,932 29,805 31,237 32,280
30,960 32,542 31,293 32,166 33,598 34,641
6,083 6,083 8,450 8,450 9,657 8,450
E4S-A/MS-36 E4H-A/MS-36 E4H-A/f/MS-36 1 E4V-A/MS-36
3600 3600 3600 3600
65 85 85 100
33,067 38,470 43,786 45,592
35,428 40,831 46,147 47,953
8,450 8,450 9,657 8,450
2,250 2,250 2,572 2,250
E6H-A/MS-40 E6H-A/f/MS-40 1
4000 4000
100 100
43,327 46,217
45,688 48,578
9,987 11,414
3,757 4,294
E6H-A/MS-50 E6H-A/f/MS-50 1
5000 5000
100 100
59,157 63,669
61,518 66,030
9,987 11,414
3,757 4,294
8 Vertical Terminals are standard 2,250 2,250 2,572 2,250
Standard features – manually operated switch Moving part
Standard features – manually operated switches Fixed part
• • • • • • • •
• • • • •
Manual mechanical close and open pushbuttons Circuit breaker open/closed mechanical indicator Spring charged/discharged mechanical indicator Lifting plates Racking device with closed door Circuit breaker racking position indicator Sliding contacts Fail-safe device (not available with YU)
Safety shutters Rear horizontal terminals except where noted Sliding contacts Anti-insertion lock Ground connection
Neutral pole rating • E1 – E3 = 100% rating • E4 – E6 = 50% rating
1 Special 100% neutral pole rating.
16.18 1SXU000023C0202
Discount schedule ED1 - ED6
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po
Circuit breakers in accordance with IEC 6097-2
we Em r b ax re ak e
rs
E1
Poles 4p c.-b neutral current-carring capacity
Iu
(40 °C)
Ue Icu Ics Icw
(220...415V) (220...415V) (1s) (3s)
E2
E1B
Automatic circuit-breakers
[No.] [%Iu] [A]
800 1000 1250 1600
[V~] [kA] [kA] [kA] [kA]
E1N 3-4 100
690 42 42 42 36
E2B
E2S
E2L
E3N
E3S
3-4 100
800
690 50 50 50 36
E3
E2N
690 42 42 42 42
690 65 65 55 42
690 85 85 65 42
690 130 130 10 —
690 65 65 65 65
690 75 75 75 75
E3H 3-4 100
E3V
E3L
80012501600200025003200
690 100 85 75 65
690 130 100 85 65
690 130 130 15 —
Automatic circuit-breakers with full-size neutral conductor
Poles 4p c.-b neutral current-carring capacity Iu (40 °C) Ue Icu (220...415V) Ics (220...415V) Icw (1s) (3s)
[No.] [%Iu] [A] [V~] [kA] [kA] [kA] [kA]
Switch-disconnectors
Standard version
Standard version
Standard version
E1B/MS
E1N/MS
E2B/MS
E2N/MS
E2S/MS
E3N/MS
E3S/MS
E3V/MS
[No.] [A]
3-4 800100012501600
3-4 800-
3-4
3-4
3-4
3-4
3-4
[V~] [kA] [kA] [kA]
690 42 36 88.2
690 50 36 105
690 42 42 88.2
690 42 42 88.2
690 65 42 143
690 65 65 143
690 75 65 165
3-4 80012501600200025003200 690 85 65 286
Automatic circuit-breakers for applications up to 1150VAC
E2B/E
E2N/E
E3H/E
Poles Iu Ue Icu Ics Icw
3-4
3-4
3-4
1150 20 20 20
1150 30 30 30
1150 30 1 30 1 30 1
Poles Iu
(40 °C)
Ue Icw Icm
(1s) (3s) (220...440V)
(40 °C) (1150V) (1150V) (1s)
[No.] [A] [V~] [kA] [kA] [kA]
E2B/E MS E2N/E MS
Switch-disconnectors for applications up to 1150VAC
Poles Iu Ue Icu Ics
(40 °C) (1s) (1000V)
[No.] [A] [V~] [kA] [kA]
Switch-disconnectors for applications up to 1000VDC
Poles Iu UE
(40 °C)
Icw Icm
(1s) (750V) (1000V)
Iu
(40 °C)
[A]
Earthing switch with makeing capacity
Iu
(40 °C)
[A]
Earthing truck
Iu
(40 °C)
3-4
3-4
1150 20 40
1150 30 63
1150 50 105
E2N/E MS
E3H/E MS
3-4
3-4
750 (3p)1000(4p) 25 52.5 52.5
750 (3p)1000(4p) 40 105 105
E1 CS
E2 CS
E3 CS
1250
2000
3200
E1 MTP
E2 MTP
E3 MTP
E1B/E MS
[No.] 3-4 [A] 800-1250 [V~] 750 (3p)1000(4p) [kA] 20 [kA] 42 [kA] 42
Sectionalizing truck
[A]
E3H/E MS
3-4
1250
2000
3200
E1 MT
E2 MT
E3 MT
1250
2000
3200
16
1 The performance at 1000V is 50kA.
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.19 1SXU000023C0202
rs ax ake m E bre er ow
Circuit breakers in accordance with IEC 6097-2
P
E4
E4S
Automatic circuit-breakers
Poles
[No.]
4p c.-b neutral current-carring capacity
Iu Ue
E6H
E6V 3 -4
50
50
[A]
4000
3200-4000
3200-4000
4000-5000-6300
[V~]
690
690
690
690
690
Icu
(220...415V)
[kA]
75
100
150
100
150
Ics
(220...415V)
[kA]
75
100
150
100
125
Icw
(1s)
[kA]
75
100
100
100
100
(3s)
[kA]
75
75
75
85
85
E4S/f
E4H/f
Automatic circuit-breakers with full-size neutral conductor
E6H/f
Poles
[No.]
4
4
4
4p c.-b neutral current-carring capacity
[%Iu]
100
100
100
Iu
(40 °C)
Ue
[A]
4000
3200-4000
4000-5000-6300
[V~]
690
690
690
Icu
(220...415V)
[kA]
80
100
100
Ics
(220...415V)
[kA]
80
100
100
Icw
(1s)
[kA]
80
85
100
(3s)
[kA]
75
75
E4S/MS
E4H/MS
E4H/fMS
E6H/MS
[No.]
3 -4
3 -4
3 -4
3 -4
3 -4
[A]
4000
3200-4000
3200-4000
4000-5000-6300
4000-5000-6300
Switch-disconnectors
Poles Iu
(40 °C)
Ue
100 E6H/fMS
[V~]
690
690
690
690
690
Icw
(1s)
[kA]
75
100
85
100
100
(3s)
[kA]
75
75
75
85
85
Icm
(220...440V)
[kA]
165
220
220
220
220
Automatic circuit-breakers for applications up to 1150VAC
Poles Iu
E4H/E
[No.] (40 °C)
Ue
E6H/E
3 -4
3-4
[A]
3200-4000
4000-5000-6300
[V~]
1150
1150
Icu
(1150V)
[kA]
65
65
Ics
(1150V)
[kA]
65
65
Icw
(1s)
[kA]
65
65
E4H/E MS
E6H/E MS
3 -4
3-4
Switch-disconnectors for applications up to 1150VAC
Poles Iu
16
E6
E4V
3 -4
[%Iu]
(40 °C)
E4H
[No.] (40 °C)
Ue
[A]
3200-4000
4000-5000
[V~]
1150
1150
Icu
(1s)
[kA]
65
65
Ics
(1000V)
[kA]
143
143
E4H/E MS
E6H/E MS
Switch-disconnectors for applications up to 1000VDC
Poles Iu
[No.] (40 °C)
UE
3 -4
3-4
[A]
3200-4000
4000-5000-6300 750(3p) - 1000(4p)
[V~]
750(3p) - 1000(4p)
Icw
(1s)
[kA]
65
65
Icm
(750V)
[kA]
143
143
(1000V)
[kA]
143
143
Sectionalizing truck
Iu
(40 °C)
E4 CS
[A]
Earthing switch with makeing capacity
Iu
(40 °C)
[A]
Earthing truck
Iu
(40 °C)
16.20 1SXU000023C0202
[A]
E3H/E MS
E6 CS
4000
6300
E4 MTP
E6 MTP
4000
6300
E4 MT
E6 MT
4000
6300
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po
we Em r b ax re ak e
Fixed breakers, 3 pole IEC
rs
Fixed breakers IEC
Frame Amps
Interrupting Ratings kA, 415V
Manually Operated
Electrically Operated
Set of Three Vertical Terminals
Set of Three Front Terminals
E1B08 E1N08 E2S08 E3H08 E3V08
800 800 800 800 800
42 50 85 100 130
$ 6,027 6,199 6,968 7,709 7,825
$ 8,388 8,560 9,329 10,070 10,186
$ 644 644 690 790 790
$ 367 367 888 1,232 1,232
E1B10 E1N10 E2N10 E2S10 E3S10 E3H10
1000 1000 1000 1000 1000 1000
42 50 65 85 75 100
6,289 6,352 7,078 7,184 7,947 8,190
8,650 8,713 9,439 9,545 10,308 10,551
644 644 690 690 790 790
367 367 888 888 1,232 1,232
E1B12 E1N12 E2N12 E2S12 E2L12 E3S12 E3H12 E3V12
1250 1250 1250 1250 1250 1250 1250 1250
42 50 65 85 130 75 100 130
6,656 6,839 7,314 7,854 9,368 7,808 8,036 9,453
9,017 9,200 9,675 10,215 11,729 10,169 10,397 11,814
644 644 690 690 690 790 790 790
367 367 888 888 888 1,232 1,232 1,232
E1B16 E1N16 E2B16 E2N16 E2S16 E2L16 E3S16 E3H16 E3V16
1600 1600 1600 1600 1600 1600 1600 1600 1600
42 50 42 65 85 130 75 100 130
6,940 7,010 7,293 8,014 8,689 11,189 8,700 9,232 11,265
9,301 9,371 9,654 10,375 11,050 13,550 11,061 11,593 13,626
644 644 690 690 690 690 790 790 790
367 367 888 888 888 888 1,232 1,232 1,232
E2B20 E2N20 E2S20 E3S20 E3H20 E3V20 E3L20
2000 2000 2000 2000 2000 2000 2000
42 65 85 75 100 130 130
8,509 9,024 9,784 9,817 11,762 13,157 13,425
10,870 11,385 12,145 12,178 14,123 15,518 15,786
690 690 690 790 790 790 790
888 888 888 1,232 1,232 1,232 1,232
E3N25 E3S25 E3H25 E3V25 E3L25
2500 2500 2500 2500 2500
65 75 100 130 130
13,870 15,242 16,948 18,010 19,454
16,231 17,603 19,309 20,371 21,815
790 790 790 790 790
1,232 1,232 1,232 1,232 1,232
E3N32 E3S32 E3H32 E3V32 E4H32 E4V32 E6V32
3200 3200 3200 3200 3200 3200 3200
65 75 100 130 100 150 150
17,963 18,662 20,217 21,711 22,085 28,163 36,328
20,324 21,023 22,578 24,072 24,446 30,524 38,689
790 790 790 790 1,664 2,783 2,783
1,232 1,232 1,232 1,232 1,696 2,464 2,464
E4S40 E4H40 E4V40 E6H40 E6V40
4000 4000 4000 4000 4000
75 85 100 100 150
26,873 30,645 34,445 38,497 42,739
29,234 33,006 36,806 40,858 45,100
1,664 1,664 1,664 2,783 2,783
1,696 1,696 1,696 2,464 2,464
E6H50 E6V50
5000 5000
100 150
42,047 50,281
44,408 52,642
2,783 2,783
2,464 2,464
E6H63 E6V63
6300 6300
100 150
50,456 60,337
52,817 63,698
2,783 2,783
2,464 2,464
16
Standard features – manually operated breaker Fixed breaker • • • • • • • • •
Rear horizontal terminals PR121 trip unit with LI protection functions Manual mechanical close and open pushbuttons CB open/closed mechanical indicator Spring charged/discharged mechanical indicator 2NO & 2NC auxiliary contacts for open-closed position indication Lifting plates Current transformers Terminal box
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule ED1 - ED6
16.21 1SXU000023C0202
rs ax ake m E bre er ow
Fixed breakers, 4 poles IEC
P
Fixed breakers
16
IEC
Frame Amps
Interrupting Ratings kA, 415V
Manually Operated
Electrically Operated
E1B08 E1N08 E2S08 E3H08 E3V08
800 800 800 800 800
42 50 85 100 130
$ 7,475 7,688 8,960 9,213 10,353
$ 9,836 10,049 11,321 11,574 12,714
$ 837 837 897 1,027 1,027
$ 489 489 1,183 1,643 1,643
E1B10 E1N10 E2N10 E2S10 E3S10 E3H10
1000 1000 1000 1000 1000 1000
42 50 65 85 75 100
7,800 8,053 8,512 8,959 9,069 9,452
10,161 10,414 10,873 11,320 11,430 11,813
837 837 897 897 1,027 1,027
489 489 1,183 1,183 1,643 1,643
E1B12 E1N12 E2N12 E2S12 E2L12 E3S12 E3H12 E3V12
1250 1250 1250 1250 1250 1250 1250 1250
42 50 65 85 130 75 100 130
8,293 8,520 9,148 9,446 12,725 9,306 9,591 11,389
10,654 10,881 11,509 11,807 15,086 11,667 11,952 13,750
837 837 897 897 897 1,027 1,027 1,027
489 489 1,183 1,183 1,183 1,643 1,643 1,643
E1B16 E1N16 E2B16 E2N16 E2S16 E2L16 E3S16 E3H16 E3V16
1600 1600 1600 1600 1600 1600 1600 1600 1600
42 50 42 65 85 130 75 100 130
8,647 8,733 9,121 10,059 10,906 13,666 10,413 10,550 14,162
11,008 11,094 11,482 12,420 13,267 16,849 12,774 12,911 16,523
837 837 897 897 897 897 1,027 1,027 1,027
489 489 1,183 1,183 1,183 1,183 1,643 1,643 1,643
E2B20 E2N20 E2S20 E3S20 E3H20 E3V20 E3L20
2000 2000 2000 2000 2000 2000 2000
42 65 85 75 100 130 130
10,701 11,371 12,329 11,795 13,621 16,872 17,093
13,062 13,732 14,690 14,156 15,982 19,233 19,454
897 897 897 1,027 1,027 1,027 1,027
1,183 1,183 1,183 1,643 1,643 1,643 1,643
E3N25 E3S25 E3H25 E3V25 E3L25
2500 2500 2500 2500 2500
65 75 100 130 130
17,671 19,454 21,672 23,301 24,930
20,032 21,815 24,033 25,662 27,291
1,027 1,027 1,027 1,027 1,027
1,643 1,643 1,643 1,643 1,643
E3N32 E3S32 E3H32 E3V32 E4H32 E4H/f32 E4V32 E6V32
3200 3200 3200 3200 3200 3200 3200 3200
65 75 100 130 100 100 150 150
22,992 23,900 27,307 30,714 28,351 29,920 36,153 45,410
25,353 26,261 29,668 33,075 30,712 32,281 38,514 47,771
1,027 1,027 1,027 1,027 2,163 2,472 2,163 3,618
1,643 1,643 1,643 1,643 2,260 2,583 2,260 3,286
E4S40 E4H40 E4H/f40 E4V40 E6H40 E6H/f40 E6V40
4000 4000 4000 4000 4000 4000 4000
75 85 85 100 100 100 150
34,610 39,516 41,652 42,923 48,122 50,528 53,424
36,971 41,877 44,013 45,284 50,483 52,889 55,785
2,163 2,163 2,472 2,163 3,618 4,135 3,618
2,260 2,260 2,583 2,260 3,286 3,756 3,286
E6H50 E6H/f50 E6V50
5000 5000 5000
100 100 150
52,558 56,142 62,852
54,919 58,503 65,213
3,618 4,135 3,618
3,286 3,756 3,286
E6H63 E6H/f63 E6V63
6300 6300 6300
100 100 150
63,070 67,370 75,422
65,431 69,731 77,783
3,818 4,135 3,618
3,286 3,756 3,286
Standard features – manually operated breaker Fixed breaker • • • • • •
Rear horizontal terminals PR121 trip unit with LI protection functions Manual mechanical close and open pushbuttons Manual mechanical close and open pushbuttons CB open/closed mechanical indicator Spring charged/discharged mechanical indicator
1 Consult factory for special 100% neutral pole rating.
16.22 1SXU000023C0202
• • • •
Set of Four Vertical Terminals
Set of Four Front Terminals
2NO & 2NC auxiliary contacts for open-closed position indication Lifting plates Current transformers Terminal box
Neutral pole rating • E1 – E3 = 100% rating • E4 – E6 = 50% rating
Discount schedule ED1 - ED6
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po
we Em r b ax re ak e
Withdrawable breakers, 3 pole IEC
rs
Withdrawable breakers IEC
Frame Amps
Interrupting Ratings kA, 415V
Manually Operated
Electrically Operated
Cradle w/Rear Horizontal Terminals
Set of Three Vertical Terminals
E1B08 E1N08 E2S08 E3H08 E3V08
800 800 800 800 800
42 50 85 100 130
$ 6,501 6,877 7,883 8,125 8,246
$ 8,862 9,238 10,244 10,486 10,607
$ 2,281 2,281 2,400 2,925 2,925
$ 644 644 690 790 790
$ 367 367 888 1,232 1,232
E1B10 E1N10 E2N10 E2S10 E3S10 E3H10
1000 1000 1000 1000 1000 1000
42 50 65 85 75 100
7,337 7,684 8,007 8,127 8,585 8,749
9,698 10,045 10,368 10,488 10,946 11,110
2,281 2,281 2,400 2,400 2,925 2,925
644 644 690 690 790 790
367 367 888 888 1,232 1,232
E1B12 E1N12 E2N12 E2S12 E2L12 E3S12 E3H12 E3V12
1250 1250 1250 1250 1250 1250 1250 1250
42 50 65 85 130 75 100 130
7,757 8,101 8,626 9,151 12,180 8,760 8,897 9,363
10,118 10,462 10,987 11,512 14,541 11,121 11,258 11,724
2,281 2,281 2,400 2,400 2,400 2,925 2,925 2,925
644 644 690 690 690 790 790 790
367 367 888 888 888 1,232 1,232 1,232
E1B16 E1N16 E2B16 E2N16 E2S16 E2L16 E3S16 E3H16 E3V16
1600 1600 1600 1600 1600 1600 1600 1600 1600
42 50 42 65 85 130 75 100 130
8,222 8,304 9,097 10,234 11,371 14,704 10,674 11,100 15,126
10,583 10,665 11,458 12,595 13,732 18,281 13,035 13,461 17,487
2,281 2,281 2,400 2,400 2,400 2,400 2,925 2,925 2,925
644 644 690 690 690 690 790 790 790
367 367 888 888 888 888 1,232 1,232 1,232
E2B20 E2N20 E2S20 E3S20 E3H20 E3V20 E3L20
2000 2000 2000 2000 2000 2000 2000
42 65 85 75 100 130 130
10,987 11,182 11,377 11,361 13,256 13,864 17,817
13,348 13,543 13,738 13,722 15,617 16,225 20,178
2,400 2,400 2,400 2,925 2,925 2,925 2,925
690 690 690 790 790 790 790
888 888 888 1,232 1,232 1,232 1,232
E3N25 E3S25 E3H25 E3V25 E3L25
2500 2500 2500 2500 2500
65 75 100 130 130
15,220 17,896 19,528 21,210 22,892
17,581 20,257 21,889 23,571 25,253
2,925 2,925 2,925 2,925 2,925
790 790 790 790 790
1,232 1,232 1,232 1,232 1,232
E3N32 E3S32 E3H32 E3V32 E4H32 E4V32 E6V32
3200 3200 3200 3200 3200 3200 3200
65 75 100 130 100 150 150
22,337 23,340 23,724 25,367 23,842 25,731 38,539
24,698 25,701 26,085 27,728 26,203 28,092 40,900
2,925 2,925 2,925 2,925 6,259 6,259 7,398
790 790 790 790 1,664 1,664 2,783
1,232 1,232 1,232 1,232 1,696 1,696 2,464
E4S40 E4H40 E4V40 E6H40 E6V40
4000 4000 4000 4000 4000
75 85 100 100 150
30,399 34,540 38,681 44,177 50,140
32,760 36,901 41,042 47,701 52,501
6,259 6,259 6,259 7,398 7,398
1,664 1,664 1,664 2,783 2,783
1,696 1,696 1,696 2,464 2,464
E6H50 E6V50
5000 5000
100 150
45,541 53,341
47,902 55,702
7,398 7,398
2,783 2,783
2,464 2,464
E6H63 E6V63
6300 6300
100 150
64,163 78,427
66,524 80,788
7,398 7,398
2,783 2,783
2,464 2,464
Standard features – electrically operated breaker Moving part
Standard features – electrically operated breaker Fixed part
• • • • • • • • • • • • •
• • • • •
PR121 trip unit with LI protection functions Spring charging motor Shunt trip Closing coil Manual mechanical close and open pushbuttons CB open/closed mechanical indicator Spring charged/discharged mechanical indicator 2NO & 2NC auxiliary contacts for open-closed position indication Lifting plates Current transformers Racking device with closed door Circuit breaker racking position indicator Sliding contacts
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Set of Three Front Terminals
16
Safety shutters Rear horizontal terminals Sliding contacts Anti-insertion lock Ground connection
Discount schedule ED1 - ED6
16.23 1SXU000023C0202
rs ax ake m E bre er ow
Withdrawable breakers, 4 pole IEC
P
Withdrawable breakers
16
IEC
Frame Amps
Interrupting Ratings kA, 415V
Manually Operated
Electrically Operated
Cradle w/Rear Horizontal Terminals
Set of Four Vertical Terminals
E1B08 E1N08 E2S08 E3H08 E3V08
800 800 800 800 800
42 50 85 100 130
$ 7,717 8,605 9,998 10,398 10,554
$ 10,078 10,966 12,359 12,759 12,915
$ 2,572 2,572 3,192 3,890 3,890
$ 837 837 897 1,027 1,027
$ 489 489 1,183 1,643 1,643
E1B10 E1N10 E2N10 E2S10 E3S10 E3H10
1000 1000 1000 1000 1000 1000
42 50 65 85 75 100
9,621 9,717 10,155 10,307 10,988 11,103
11,982 12,078 12,516 12,668 13,349 13,464
2,572 2,572 3,192 3,192 3,890 3,890
837 837 897 897 1,027 1,027
489 489 1,183 1,183 1,643 1,643
E1B12 E1N12 E2N12 E2S12 E2L12 E3S12 E3H12 E3V12
1250 1250 1250 1250 1250 1250 1250 1250
42 50 65 85 130 75 100 130
10,649 11,098 11,372 11,772 14,395 11,906 12,229 15,445
13,010 13,459 13,733 14,133 17,763 14,267 14,590 17,806
2,572 2,572 3,192 3,192 3,192 3,890 3,890 3,890
837 837 897 897 897 1,027 1,027 1,027
489 489 1,183 1,183 1,183 1,643 1,643 1,643
E1B16 E1N16 E2B16 E2N16 E2S16 E2L16 E3S16 E3H16 E3V16
1600 1600 1600 1600 1600 1600 1600 1600 1600
42 50 42 65 85 130 75 100 130
10,812 11,375 11,395 12,873 13,460 17,501 12,472 13,304 18,408
13,173 13,736 13,756 15,234 15,821 22,625 14,833 15,665 20,769
2,572 2,572 3,192 3,192 3,192 3,192 3,890 3,890 3,890
837 837 897 897 897 897 1,027 1,027 1,027
489 489 1,183 1,183 1,183 1,183 1,643 1,643 1,643
E2B20 E2N20 E2S20 E3S20 E3H20 E3V20 E3L20
2000 2000 2000 2000 2000 2000 2000
42 65 85 75 100 130 130
13,851 15,661 16,825 14,873 16,784 19,212 22,714
16,212 18,022 19,186 17,234 19,145 21,573 25,075
3,192 3,192 3,192 3,890 3,890 3,890 3,890
897 897 897 1,027 1,027 1,027 1,027
1,183 1,183 1,183 1,643 1,643 1,643 1,643
E3N25 E3S25 E3H25 E3V25 E3L25
2500 2500 2500 2500 2500
65 75 100 130 130
20,380 22,816 24,938 27,125 29,312
22,741 25,177 27,299 29,486 31,673
3,890 3,890 3,890 3,890 3,890
1,027 1,027 1,027 1,027 1,027
1,643 1,643 1,643 1,643 1,643
E3N32 E3S32 E3H32 E3V32 E4S32 E4H32 E4H/f32 1 E4V32 E6V32
3200 3200 3200 3200 3200 3200 3200 3200 3200
65 75 100 130 75 100 100 150 150
29,555 29,893 32,017 34,141 33,317 32,589 33,523 47,423 49,722
31,916 32,254 34,378 36,502 35,678 34,959 35,884 49,784 52,083
3,890 3,890 3,890 3,890 8,324 8,324 9,513 8,324 9,839
1,027 1,027 1,027 1,027 2,163 2,163 2,472 2,163 3,618
1,643 1,643 1,643 1,643 2,260 2,260 2,583 2,260 3,286
E4S40 E4H40 E4H/f40 1 E4V40 E6H40 E6H/f40 1 E6V40
4000 4000 4000 4000 4000 4000 4000
75 85 85 100 100 100 150
41,350 44,409 45,478 45,930 48,486 50,911 58,496
43,711 46,770 47,839 48,291 60,857 53,272 60,857
8,324 8,324 9,513 8,324 9,839 11,245 9,839
2,163 2,163 2,472 2,163 3,618 4,135 3,618
2,260 2,260 2,583 2,260 3,286 3,756 3,286
E6H50 E6H/f50 1 E6V50
5000 5000 5000
100 100 150
58,680 66,853 56,568
61,041 69,214 71,181
9,839 11,245 9,839
3,618 4,135 3,618
3,286 3,756 3,286
E6H63 E6H/f63 E6V63
6300 6300 6300
100 100 150
82,888 94,017 101,432
85,249 96,378 103,793
9,839 9,839 9,839
3,618 4,135 3,618
3,286 3,756 3,286
Standard features – electrically operated breaker Moving part
• Circuit breaker racking position indicator • Sliding contacts
• • • • • • • • • • •
• • • • •
PR121 trip unit with LI protection functions Spring charging motor Shunt trip Closing coil Manual mechanical close and open pushbuttons CB open/closed mechanical indicator Spring charged/discharged mechanical indicator 2NO & 2NC auxiliary contacts for open-closed position indication Lifting plates Current transformers Racking device with closed door
1 Special 100% neutral pole rating.
16.24 1SXU000023C0202
Set of Four Front Terminals
Standard features – electrically operated breaker Fixed part Safety shutters Rear horizontal terminals Sliding contacts Anti-insertion lock Ground connection
Neutral pole rating • E1 –E3 = 100% rating • E4 – E6 = 50% rating
Discount schedule ED1 - ED6
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Non-automatic switches Fixed switches (Without trip unit & c.t.s.), 3 pole IEC
Po
we Em r b ax re ak e
rs
Fixed switches, 3 pole IEC
Frame Amps
Rated Short Time Current, kA
Manually Operated
Electrically Operated
Set of Three Vertical Terminals
Set of Three Front Terminals
E1B/MS08 E1N/MS08 E3V/MS08
800 800 800
42 50 85
$ 4,298 4,903 5,883
$ 6,659 7,264 8,244
$ 644 644 790
$ 367 367 1,232
E1B/MS10 E1N/MS10 E2N/MS10 E2S/MS10 E3S/MS10
1000 1000 1000 1000 1000
42 50 55 65 75
4,816 5,101 5,502 5,799 5,921
7,177 7,462 7,863 8,160 8,282
644 644 690 690 790
367 367 888 888 1,232
E1B/MS12 E1N/MS12 E2N/MS12 E2S/MS12 E3S/MS12 E3V/MS12
1250 1250 1250 1250 1250 1250
42 50 55 65 75 85
4,927 5,203 5,585 5,887 5,972 7,089
7,288 7,564 7,946 8,248 8,333 9,450
644 644 690 690 790 790
367 367 888 888 1,232 1,232
E1B/MS16 E1N/MS16 E2B/MS16 E2N/MS16 E2S/MS16 E3S/MS16 E3V/MS16
1600 1600 1600 1600 1600 1600 1600
42 50 42 55 65 75 85
5,203 5,307 5,564 6,285 6,722 6,864 8,145
7,564 7,668 7,925 8,646 9,083 9,225 10,506
644 644 690 690 690 790 790
367 367 888 888 888 1,232 1,232
E2B/MS20 E2N/MS20 E2S/MS20 E3S/MS20 E3V/MS20
2000 2000 2000 2000 2000
42 55 65 75 85
6,780 7,295 8,280 7,981 9,451
9,141 9,556 10,641 10,342 11,812
690 690 690 790 790
888 888 888 1,232 1,232
E3N/MS25 E3S/MS25 E3V/MS25
2500 2500 2500
65 75 85
12,034 13,406 14,246
14,395 15,767 16,607
790 790 790
1,232 1,232 1,232
E3N/MS32 E3S/MS32 E3V/MS32 E4H/MS32
3200 3200 3200 3200
65 75 85 100
16,127 16,826 17,901 18,688
18,488 19,187 20,262 21,049
790 790 790 790
1,232 1,232 1,232 1,232
E4S/MS40 E4H/MS40 E6H/MS40
4000 4000 4000
75 100 100
24,504 28,276 33,114
26,865 30,637 35,475
1,664 1,664 2,783
1,696 1,696 2,464
E6H/MS50
5000
100
39,465
41,826
2,783
2,464
E6H/MS63
6300
100
47,874
50,235
2,783
2,464
16
Standard features – manually operated switch • • • • • •
Rear horizontal terminals Manual mechanical close and open pushbuttons Circuit breaker open/closed mechanical indicator Spring charged/discharged mechanical indicator Lifting plates Terminal box
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule ED1 - ED6
16.25 1SXU000023C0202
rs ax ake m E bre er ow
Non-automatic switches Fixed switches (Without trip unit & c.t.s.), 4 pole IEC
P
Fixed switches, 4 pole
16
IEC
Frame Amps
Rated Short Time Current, kA
Manually Operated
Electrically Operated
E1B/MS08 E1N/MS08 E3V/MS08
800 800 800
42 50 85
$ 5,533 6,251 7,501
$ 7,894 8,612 9,862
$ 837 837 1,027
$ 489 489 1,643
E1B/MS10 E1N/MS10 E2N/MS10 E2S/MS10 E3S/MS10
1000 1000 1000 1000 1000
42 50 55 65 75
6,139 6,503 6,705 7,350 7,666
8,500 8,864 9,066 9,711 10,027
837 837 897 897 1,027
489 489 1,183 1,183 1,643
E1B/MS12 E1N/MS12 E2N/MS12 E2S/MS12 E3S/MS12 E3V/MS12
1250 1250 1250 1250 1250 1250
42 50 55 65 75 85
6,351 6,633 7,206 7,462 7,221 9,178
8,712 8,994 9,567 9,823 9,582 11,539
837 837 897 897 1,027 1,027
489 489 1,183 1,183 1,643 1,643
E1B/MS16 E1N/MS16 E2B/MS16 E2N/MS16 E2S/MS16 E3S/MS16 E3V/MS16
1600 1600 1600 1600 1600 1600 1600
42 50 42 55 65 75 85
6,633 6,766 7,179 8,117 8,636 8,328 10,444
8,994 9,127 9,540 10,478 10,997 10,689 12,805
837 837 897 897 897 1,027 1,027
489 489 1,183 1,183 1,183 1,643 1,643
E2B/MS20 E2N/MS20 E2S/MS20 E3S/MS20 E3V/MS20
2000 2000 2000 2000 2000
42 55 65 75 85
8,759 9,429 10,059 9,710 12,141
11,120 11,790 12,420 12,071 14,502
897 897 897 1,027 1,027
1,183 1,183 1,183 1,643 1,643
E3N/MS25 E3S/MS25 E3V/MS25
2500 2500 2500
65 75 85
15,586 17,369 18,432
17,947 19,730 20,793
1,027 1,027 1,027
1,643 1,643 1,643
E3N/MS32 E3S/MS32 E3V/MS32 E4H/MS32 E4H/f MS32 1
3200 3200 3200 3200 3200
65 75 85 100 100
20,907 21,815 23,184 24,146 26,368
23,268 24,176 25,545 26,507 28,729
1,027 1,027 1,027 2,163 2,472
1,643 1,643 1,643 2,260 2,583
E4S/MS40 E4H/MS40 E4H/f MS40 1 E6H/MS40 E6H/f MS40 1
4000 4000 4000 4000 4000
75 100 85 100 100
31,815 36,721 39,196 39,352 43,116
34,176 39,082 41,557 41,713 45,477
2,163 2,163 2,472 3,618 4,135
2,260 2,260 2,583 3,286 3,756
E6H/MS50 E6H/f MS50 1
5000 5000
100 100
49,479 56,638
51,480 58,999
3,618 4,135
3,286 3,756
E6H/MS63 E6H/f MS63 1
6300 6300
100 100
59,991 68,802
62,352 71,163
3,618 4,135
3,286 3,756
Standard features – manually operated switch
Neutral pole rating
• • • • • •
• E1 – E3 = 100% rating • E4 – E6 = 50% rating
Rear horizontal terminals Manual mechanical close and open pushbuttons Circuit breaker open/closed mechanical indicator Spring charged/discharged mechanical indicator Lifting plates Terminal box
Set of Four Vertical Terminals
Set of Three Front Terminals
1 Special 100% neutral pole rating.
16.26 1SXU000023C0202
Discount schedule ED1 - ED6
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
P
ow Em Non-automatic switches er ax Withdrawable switches (Without trip unit & c.t.s.), 3 pole break er s IEC Withdrawable switches, 3 pole IEC
Frame Amps
Rated Short Time Current, kA
Manually Operated
Electrically Operated
Cradle w/Rear Horizontal Terminals
Set of Three Vertical Terminals
Set of Three Front Terminals
E1B/MS08 E1N/MS08 E3V/MS08
800 800 800
42 50 85
$ 4,772 4,952 7,060
$ 7,133 7,313 9,421
$ 2,281 2,281 2,925
$ 644 644 790
$ 367 367 1,232
E1B/MS10 E1N/MS10 E2N/MS10 E2S/MS10 E3S/MS10
1000 1000 1000 1000 1000
42 50 55 65 75
5,051 5,152 5,770 5,857 6,716
7,412 7,513 8,131 8,218 9,077
2,281 2,281 2,400 2,400 2,925
644 644 690 690 790
367 367 888 888 1,232
E1B/MS12 E1N/MS12 E2N/MS12 E2S/MS12 E3S/MS12 E3V/MS12
1250 1250 1250 1250 1250 1250
42 50 55 65 75 85
6,028 5,255 6,897 7,718 6,924 7,237
8,389 7,616 9,258 10,079 9,285 9,598
2,281 2,281 2,400 2,400 2,925 2,925
644 644 690 690 790 790
367 367 888 888 1,232 1,232
E1B/MS16 E1N/MS16 E2B/MS16 E2N/MS16 E2S/MS16 E3S/MS16 E3V/MS16
1600 1600 1600 1600 1600 1600 1600
42 50 42 55 65 75 85
6,831 6,968 7,368 8,505 8,331 8,838 9,160
9,192 9,329 9,729 10,866 10,692 11,199 11,521
2,281 2,281 2,400 2,400 2,400 2,925 2,925
644 644 690 690 690 790 790
367 367 888 888 888 1,232 1,232
E2B/MS20 E2N/MS20 E2S/MS20 E3S/MS20 E3V/MS20
2000 2000 2000 2000 2000
42 55 65 75 85
9,258 9,453 9,648 9,525 10,737
11,619 11,814 12,009 11,886 13,098
2,400 2,400 2,400 2,925 2,925
690 690 690 790 790
888 888 888 1,232 1,232
E3N/MS25 E3S/MS25 E3V/MS25 E3N/MS32 E3S/MS32 E3V/MS32 E4H/MS32
2500 2500 2500 3200 3200 3200 3200
65 75 85 65 75 85 100
13,384 16,060 16,611 20,501 21,540 22,281 24,011
15,745 18,421 18,972 22,862 23,865 24,642 26,372
2,925 2,925 2,925 2,925 2,925 2,925 6,259
790 790 790 790 790 790 1,664
1,232 1,232 1,232 1,232 1,232 1,232 1,696
E4S/MS40 E4H/MS40 E6H/MS40
4000 4000 4000
75 100 100
28,030 32,171 36,789
30,391 34,532 39,150
6,259 6,259 6,259
1,664 1,664 2,783
1,696 1,696 2,464
E6H/MS50
5000
100
42,959
45,320
7,398
2,783
2,464
E6H/MS63
6300
100
61,581
63,942
7,398
2,783
2,464
Standard features – manually operated switch Moving part
Standard features – manually operated switch Fixed part
• • • • • • •
• • • • •
Manual mechanical close and open pushbuttons Circuit breaker open/closed mechanical indicator Spring charged/discharged mechanical indicator Lifting plates Racking device with closed door Circuit breaker racking position indicator Sliding contacts
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16
Safety shutters Rear horizontal terminals Sliding contacts Anti-insertion lock Ground connection
Discount schedule ED1 - ED6
16.27 1SXU000023C0202
rs ax ake m E bre er ow
Non-automatic switches Withdrawable switches (Without trip unit & c.t.s.), 4 pole IEC
P
Withdrawable switches, 4 pole
16
IEC
Frame Amps
Rated Short Time Current, kA
Manually Operated
Electrically Operated
E1B/MS08 E1N/MS08 E3V/MS08
800 800 800
42 50 85
$ 5,775 6,314 7,501
$ 8,136 8,675 9,862
E1B/MS10 E1N/MS10 E2N/MS10 E2S/MS10 E3S/MS10
1000 1000 1000 1000 1000
42 50 55 65 75
6,440 6,569 7,033 7,139 8,696
E1B/MS12 E1N/MS12 E2N/MS12 E2S/MS12 E3S/MS12 E3V/MS12
1250 1250 1250 1250 1250 1250
42 50 55 65 75 85
E1B/MS16 E1N/MS16 E2B/MS16 E2N/MS16 E2S/MS16 E3S/MS16 E3V/MS16
1600 1600 1600 1600 1600 1600 1600
E2B/MS20 E2N/MS20 E2S/MS20 E3S/MS20 E3V/MS20 E3N/MS25 E3S/MS25 E3V/MS25
Cradle w/Rear Horizontal / Flat Terminals
Set of Four Vertical Terminals
Set of Four Front Terminals
$ 2,572 2,572 3,890
$ 837 837 1,027
$ 489 489 1,643
8,801 8,930 9,394 9,500 11,057
2,572 2,572 3,192 3,192 3,890
837 837 897 897 1,027
489 489 1,183 1,183 1,643
8,707 9,168 9,430 9,610 9,821 10,312
11,068 11,529 11,791 11,971 12,182 12,673
2,572 2,572 3,192 3,192 3,890 3,890
837 837 897 897 1,027 1,027
489 489 1,183 1,183 1,643 1,643
42 50 42 55 65 75 85
8,888 9,065 9,453 10,931 11,733 10,387 11,762
11,249 11,426 11,814 13,292 14,094 12,748 14,123
2,572 2,572 3,192 3,192 3,192 3,890 3,890
837 837 897 897 897 1,027 1,027
489 489 1,183 1,183 1,183 1,643 1,643
2000 2000 2000 2000 2000 2500 2500 2500
42 55 65 75 85 65 75 85
11,909 13,719 14,241 12,788 15,119 18,295 20,731 21,625
14,270 16,080 16,602 15,149 17,480 20,656 23,092 23,986
3,192 3,192 3,192 3,890 3,890 3,890 3,890 3,890
837 897 897 1,027 1,027 1,027 1,027 1,027
1,183 1,183 1,183 1,643 1,643 1,643 1,643 1,643
E3N/MS32 E3S/MS32 E3V/MS32 E4H/MS32 E4H/fMS32 1
3200 3200 3200 3200 3200
65 75 85 100 100
27,470 27,808 28,996 30,738 32,273
29,831 30,169 31,357 33,099 34,634
3,890 3,890 3,890 8,324 9,513
1,027 1,027 1,027 2,163 2,472
1,643 1,643 1,643 2,260 2,583
E4S/MS40 E4H/MS40 E4H/f MS40 1 E6H/MS40 E6H/f MS40 1
4000 4000 4000 4000 4000
75 100 100 100 100
38,555 41,614 45,598 43,359 45,527
40,916 43,975 47,959 45,720 47,888
8,324 8,324 9,513 9,839 11,245
2,163 2,163 2,472 3,618 4,135
2,260 2,260 2,583 3,286 3,756
E6H/MS50 E6H/f MS50
5000 5000
100 100
55,601 62,290
57,962 64,651
9,839 11,245
3,618 4,135
3,286 3,756
E6H/MS63 E6H/f MS63 1
6300 6300
100 100
79,809 88,561
82,170 90,922
9,839 11,245
3,618 4,135
3,286 3,756
Standard features – manually operated switch Moving part
Standard features – manually operated switch Fixed part
• • • • • • •
• • • • •
Manual mechanical close and open pushbuttons Circuit breaker open/closed mechanical indicator Spring charged/discharged mechanical indicator Lifting plates Racking device with closed door Circuit breaker racking position indicator Sliding contacts
Safety shutters Rear horizontal terminals Sliding contacts Anti-insertion lock Ground connection
Neutral pole rating • E1 – E3 = 100% rating • E4 – E6 = 50% rating
1 Special 100% neutral pole rating.
16.28 1SXU000023C0202
Discount schedule ED1 - ED6
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po
we Em r b ax re ak e
Air circuit breakers Installed optional features UL & IEC
rs
1.20 Trip Units1 Catalog number
Factory installation price adder
PR121/P-LI PR121/P-LSI PR121/P-LSIG
— $ 515 1,208
— $ 1,604 2 2,297 2
PR122/P-LI PR122/P-LSI PR122/P-LSIRc (IEC only) PR122/P-LSIG
1,686 2,210 3,189 2,904
2,775 3,299 4,278 3,993
PR123/P-LSI (Standard with PR120/V) PR123/P-LSIG (Standard with PR120/V)
6,631 7,323
7,720 8,412
Field installable price
1.21 Rating Plugs UL
E1
E2
E3
DE0400RP DE0600RP DE0800RP DE1000RP DE1200RP DE1600RP DE2000RP DE2500RP DE3000RP DE3200RP DE3600RP DE4000RP DE5000RP
X X X X X
X X X X X X
X X X X X X X X X X
IEC
E1
E2
E3
DE0400RP DE0630RP DE0800RP DE1000RP DE1250RP DE1600RP DE2000RP DE2500RP DE3000RP DE3200RP DE4000RP DE5000RP DE6300RP
X X X X X X
X X X X X X X
X X X X X X X X X X
E4
E6
X X X X X X X X X
X X X X X X X X X X X
E4
E6
X X X X X X X X X
X X X X X X X X X X X
Field installable price
125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125
16
1 Must order rating plug separately when ordering trip unit separately. 2 Requires PRO30/B to be purchased separately. See item 49 on page 16.36.
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule EDX
16.29 1SXU000023C0202
rs ax ake m E bre er ow
P
Air circuit breakers Installed optional features UL & IEC
1.22 Auxiliary Units Catalog number
PR010/T PR021/K PR120/K4 PR120/K4C PR120/V PR120/D-M PR120/D-BT BT030
Description
Configuration Test Unit Signaling Unit Signaling Module 4 output with independent terminals Signaling Module 4 + 1 input with common terminal Voltage Measuring Module Communication Module (Modbus RTU) Bluetooth Wireless Communication Module internal Bluetooth Wireless Communication Module external
List price
$ 12,500.00 5,000.00 2,500.00 2,500.00 2,125.00 5,000.00 2,500.00 3,335.00
16
1 Standard connection when ordered with breaker.
16.30 1SXU000023C0202
Discount schedule EDX
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po
we Em r b ax re ak e
Air circuit breakers Installed optional features UL & IEC
rs
23. – 30. Electrical and mechanical accessories Item
Factory Field installation installation catalog list price number adder
23a. Shunt trip coil (included in the electrically operated breaker) Rated voltage 24V 30V 48V 60V 110/120V $ 374 125/127V 220/240V 250V 380/400V 440/480V
KE6S0 KE6S9 KE6S8 KE6S7 KE6S6 KE6S5 KE6S4 KE6S3 KE6S2 KE6S1
Field installation list price
$ 374
23b. Second shunt trip coil (includes accessory support) 1
24V 30V 48V 60V 110/120V 456 125/127V 220/240V 250V 380/400V 440/480V
KE6S0-2 KE6S9-2 KE6S8-2 KE6S7-2 KE6S6-2 KE6S5-2 KE6S4-2 KE6S3-2 KE6S2-2 KE6S1-2
456
24. Closing coil (included in the electrically operated breaker) Rated voltage 24V 30V 48V 60V 110/120V 374 125/127V 220/240V 250V 380/400V 440/480V
KE6C0 KE6C9 KE6C8 KE6C7 KE6C6 KE6C5 KE6C4 KE6C3 KE6C2 KE6C1
374
25. Spring charging motor with limit switch and electrical indication charged spring (included in the electrically operated breaker) Rated voltage 24/30V 48/60V 1613 100/130V 220/250V
KE6M9 KE6M7 KE6M5 KE6M3
1613
73
KE6SC
73
Rated voltage 24V 30V 48V 60V 110/120V 456 125/127V 220/240V 250V 380/400V 440/480V
KE6U0 KE6U9 KE6U8 KE6U7 KE6U6 KE6U5 KE6U4 KE6U3 KE6U2 KE6U1
456
27. Energized undervoltage release signalling contact Auxiliary contact normally open 82 Auxiliary contact normally closed
KE6UE10 KE6UE01
Spring charged signal only
26. Instantaneous under voltage trip release
82
1 Order as alternative to UV trip.
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule EDX
16.31 1SXU000023C0202
16
rs ax ake m E bre er ow
P
Air circuit breakers Installed optional features UL & IEC
Item
Factory Field installation installation catalog list price number adder
Field installation list price
28. Auxiliary contacts for breakers 1 Rated 5A-250VAC / 0.3A –125VDC 28a. 4 auxiliary open/closed contacts (PR121/ on-automatic switch) 28b. 4 auxiliary open/closed contacts for digital signals (PR121/non-automatic switch) 28c. 4 auxiliary open/closed contacts (2NO+2NC+2PR122-3) 28d. 4 auxiliary open/closed contacts (2NO+2NC+2PR122-3) for digital signals 28e. 10 auxiliary open/closed contacts (PR121/non-automatic switch) 28f. 10 auxiliary open/closed contacts for digital signals (PR121/non-automatic switch) 28g. 10 auxiliary open/closed contacts (5NO+5NC+2PR122-3) 28h. 10 auxiliary open/closed contacts (5NO+5NC+2PR122-3) for digital signals 28i. 15 additional auxiliary contacts for field installation on fixed breakers (connected to breaker with flexible cable) 28j. 15 additional auxiliary contacts for field installation on withdrawable breakers (connected to breaker with flexible cable) 2 29. Auxiliary contacts for switches 29a. 2NO + 2NC 29b. 5NO + 5NC
– 297 – 297 753 753 753 753 1507
KE6A4 KE6A4D KE6A4-PR122/3 KE6A4-PR122/3D KE6A10 KE6A10D KE6A10-PR122/3 KE6A10-PR122/3D KE6A15
$ 297 297 297 297 1050 1050 1050 1050 1507
1507
KE6A15-W
1507
297 1050
KE6A4 KE6A10
297 1050
30. – 33. Electrical and mechanical accessories Item
30.
Factory Field installation installation catalog list price number adder
Auxiliary contacts for service/test/disconnected position indication Cradle mounted 30a . 5 auxiliary contacts 30b. 10 auxiliary contacts for E1/2 3 pole 30c. 10 auxiliary contacts for E1/2 4 pole 30d. 10 auxiliary contacts for E3 3 pole 30e. 10 auxiliary contacts for E3 4 pole 30f. 10 auxiliary contacts for E4/6 3/4 pole
Field installation list price
377 753 753 753 753 753
KE6PS1 KE2PS3 KE2PS4 KE3PS3 KE3PS4 KE6PS2
377 753 753 753 753 753
31. Mechanical operation counter
418
KE6MC
418
32. Bell alarm Electrical signalling of overcurrent release tripped, Bell alarm contact
348
DE6TBA
348
DE6TBAR4 DE6TBAR5 DE6TBAR9
545
33.
Bell alarm w/remote reset 33a. Electrical signalling of overcurrent release tripped with remote reset 220-240V AC/DC 33b. Electrical signalling of overcurrent release tripped with remote reset 110-130V AC/DC 545 33c. Electrical signalling of overcurrent release tripped with remote reset 24-30V AC/DC
16
1 For field installation, order auxiliary contacts for corresponding trip unit/ 2 Order as alternative to various types of interlock and kirk key lock. For mounting on fixed breaker, also requires accessory 32 (KE6MLP).
16.32 1SXU000023C0202
Discount schedule EDX
non-automatic switch.
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po
Air circuit breakers Optional features UL & IEC
we Em r b ax re ak e
rs
34. – 39. Locks and interlocks Item
34. Button guard 35.
Factory Field installation installation catalog list price number adder
$ 48
Key lock in open position 35a. Key lock N. 20005 1 35b. Key lock N. 20006 35c. Key lock N. 20007 202 35d. Key lock N. 20008 35e. Key lock different keys
Field installation list price
KE6PG
$ 48
DE6KL2 DE6KL3 DE6KL4 DE6KL5 DE6KL1
202
36a. Padlocking button cover (padlocks not supplied) 3 - 4mm locks
162
KE6PD1
162
36b. 3 - 5/16 locks
350
KE6PDHD1
350
DE6PL2 DE6PL3 DE6PL4 DE6PL5 DE6PL1
202
37.
Key and padlocking device to lock the breaker in disconnected, test or connected position (position lock) 37a. Key + padlocking 20005 37b. Key + padlocking 20006 37c. Key + padlocking 20007 202 37d. Key + padlocking 20008 37e. Key + padlocking different keys
38. Accessory to lock the breaker in test or disconnected position only 2 Position lock
212
KE6PLA
212
39. Padlocking device for the safety shutters on the cradle Cradle padlock
N/A
KE6SP
43
16
1 Keylock number when factory installed is N3004222. 2 Also requires position lock (accessory 37).
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.33 1SXU000023C0202
rs ax ake m E bre er ow
External accessories Current transformers, UL & IEC
P
40a. Neutral current transformer (required for 4 wire ground fault systems) For breaker Amps
Catalog number
List price
E1 – E2
400A 800A 1000A 1200A KE2NCT 1250A 1600A 2000A
$ 406
E3
400A 800A 1000A 1200A 1250A KE3NCT 1600A 2000A 2500A 3200A
414
E4
1600A 2000A 2500A KE4NCT 1 3200A 3600A 4000A
818
E6
3200A 4000A KE6NCT 1 5000A 6300A
834
16
1 KE4NCT & KE6NCT are 100% rated. For 50% rated neutrals on E4 & E6, use KE2NCT & KE3NCT
16.34 1SXU000023C0202
Discount schedule EDX
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Po
we Em r b ax re ak e
External accessories Mechanical interlocks1
rs
41. Mechanical interlocks (base plate for fixed circuit breaker) For breaker Interlock type
E1 – E6
Catalog number
All
KE6MLP
List price
$ 241
NOTE: order for fixed circuit breaker only; order one accessory for each fixed breaker.
42. Interlock for fixed circuit breaker/fixed part of withdrawable circuit breaker (cable attachment plate) For breaker Interlock type
E1 – E6
Catalog number
A, B, D C
KE6MLA KE6MLC
List price
$ 628
NOTE: order one accessory for each fixed circuit breaker/fixed part of withdrawable circuit breaker
43. Interlock for fixed circuit breaker/moving part of withdrawable circuit breaker (internal interlocking shaft) For breaker Interlock type
Catalog number
E1 – E2 E3 E4, 3 pole All E4, 4 pole/ E6, 3 pole E6, 4 pole
KE2ML KE3ML KE4ML-3 KE6ML-3 KE6ML-4
List price
$ 145
NOTE: order one accessory for each fixed circuit breaker/mobile part of withdrawable circuit breaker
44. Interlock cables For breaker Interlock type
E1 – E6
A B C D
Horizontal Catalog number
Vertical Catalog number
KE6MLC-HA KE6MLC-HB KE6MLC-HC KE6MLC-HD
KE6MLC-VA KE6MLC-VB KE6MLC-VC KE6MLC-VD
List price
$ 97 193 193 193
NOTE: order one type of cable for each interlock
16
1 Order as an alternative to the Accessory number 15 auxiliary contact (see page 16.32) and kirk key lock.
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule EDX
16.35 1SXU000023C0202
rs ax ake m E bre er ow
External accessories Other items
P
45. Electronic time delay for undervoltage release 1 Item
45.
Delay
Time delay Voltage 24/30V 48V 60V 0.5-1-1.5-2-3.5 s 110/125V 220/250V
Field installation catalog number
KE6TL9 KE6TL8 KE6TL7 KE6TL5 KE6TL3
List price
$ 428
46. Transparent front cover (IP54) For breaker
46. Cover
E1 – E6
Catalog number
KE6DC
List price
$ 557
47. Kirk key lock adaptor plate (in open position) For breaker
47.
Kirk key lock adaptor plate 47a. E1 – E2 fixed breaker, 3-4 pole 47b. E1 – E2 withdrawable breaker, 3-4 pole 47c. E3 fixed breaker, 3-4 pole 47d. E3 withdrawable breaker, 3-4 pole 47e. E4 fixed breaker, 3 pole 47f. E4 withdrawable breaker, 3 pole 47g. E6 fixed breaker, 3 pole 47h. E6 withdrawable breaker, 3 pole 47i. E4 fixed breaker, 4 pole 47j. E4 withdrawable breaker, 4 pole 47k. E6 fixed breaker, 4 pole 47l. E6 withdrawable breaker, 4 pole
Catalog number
KE6KKC-E2F KE6KKC-E2W KE6KKC-E3F KE6KKC-E3W KE6KKC-E4F KE6KKC-E4W KE6KKC-E6F KE6KKC-E6W KE6KKC-E4F-F KE6KKC-E4W-4 KE6KKC-E6F-4 KE6KKC-E6W-4
List price
$ 1436 1195 1436 1195 1436 1195 1436 1195 1436 1195 1436 1195
NOTE: Provision for kirk lock (kirk key lock not included; use lock Type F – 1 inch bolt projection in withdrawn position).
48. Kit for converting fixed breaker with rear horizontal terminals to rear vertical (set of three terminals) Item
16
48.
Conversion kit 48a. 1/2 3p F HR > F VR E1-A 48b. 1/2 3p F HR > F VR E2-A 48c. 1/2 3p F HR > F VR E3-A (12, 16, 20) 48d. 1/2 3p F HR > F VR E3-A (25) 48e. 1/2 3p F HR > F VR E4-A 48f. 1/2 3p F HR > F VR E6-A
Catalog number
KE1FHRVR KE2FHRVR KE3FHRVR KE3F25HRVR KE4FHRVR KE6FHRVR
List price
$ 644 690 790 790 1664 2783
49. – 50. Test kits Item
49. Hand-held battery (standard w/PR122 & 123) 50. Test and configuration unit SACE PR010/T
PR030/B PR010/T
51. – 54. Spare parts
Item
51. 52. 53. 54.
Catalog number
Racking crank Door escutcheon Support plate for auxiliary releases Lifting plates
Catalog number
1SDA038092R1 1SDA038096R1 1SDA038339R1 1SDA038093R1
List price
275 12,500
List price
$ 122 153 244 224
1 IEC only.
16.36 1SXU000023C0202
Discount schedule EDX
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
Approximate dimensions (for UL version) 1 E1, fixed with horizontal rear terminals 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.37 1SXU000023C0202
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E1, fixed with horizontal rear terminals 4 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.38 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E1, withdrawable with horizontal rear terminals 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.39 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E1, withdrawable with horizontal rear terminals 4 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.40 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E1 - E2, withdrawable with vertical rear terminals 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.41 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E1 - E2, withdrawable with vertical rear terminals 4 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.42 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E2, fixed with horizontal rear terminals 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.43 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E2, fixed with horizontal rear terminals 4 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.44 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E2, withdrawable with horizontal rear terminals 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.45 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E2, withdrawable with horizontal rear terminals 4 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.46 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E3, fixed with horizontal rear terminals 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.47 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E3, fixed with horizontal rear terminals 4 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.48 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E3, withdrawable with horizontal rear terminals 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.49 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E3, withdrawable with horizontal rear terminals 4 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.50 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E3 (2500A), withdrawable with vertical rear terminals 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.51 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E3 (2500A), withdrawable with vertical rear terminals 00.00 4 pole 00.00
Inches [Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.52 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E3 (1200A/1600A/2000A), withdrawable with Vertical rear terminals, 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.53 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E3 (1200A/1600A/2000A), withdrawable with Vertical rear terminals, 4 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.54 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E3 (3200A), fixed with Vertical rear terminals, 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.55 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E3 (3200A), fixed with Vertical rear terminals, 4 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.56 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E3 (3200A), withdrawable with Vertical rear terminals, 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.57 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E3 (3200A), withdrawable with Vertical rear terminals, 4 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.58 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E3X Draw-out with Vertical rear terminals, 3 pole, 800-1200A
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.59 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E3X Draw-out with Vertical rear terminals, 3 pole, 1600-2000A
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.60 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E3X Fixed with Vertical rear terminals, 3 pole, 800-2000A
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.61 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E3X Draw-out with Vertical rear terminals, 4 pole, 1600-2000A
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.62 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E3X Fixed with Vertical rear terminals, 4 pole, 800-2000A
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.63 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E4, fixed with horizontal rear terminals 3 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.64 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E4, fixed with horizontal rear terminals 4 pole (50% neutral)
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.65 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E4, fixed with horizontal rear terminals 4 pole (100% neutral)
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.66 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E4, withdrawable with horizontal rear terminals 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.67 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E4, withdrawable with horizontal rear terminals 4 pole (50% neutral)
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.68 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E4, withdrawable with horizontal rear terminals 4 pole (100% neutral)
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.69 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E4, withdrawable with vertical rear terminals 3 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.70 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E4, withdrawable with vertical rear terminals 4 pole (50% neutral)
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.71 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E4, withdrawable with vertical rear terminals 4 pole (100% neutral)
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.72 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E6, fixed with horizontal rear terminals 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.73 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E6, fixed with horizontal rear terminals 4 pole (50% neutral)
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.74 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E6, fixed with horizontal rear terminals 4 pole (100% neutral)
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.75 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E6, withdrawable with horizontal rear terminals 3 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.76 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E6, withdrawable with horizontal rear terminals 4 pole (50% neutral)
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.77 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E6, withdrawable with horizontal rear terminals 4 pole (100% neutral)
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.78 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E6, withdrawable with vertical rear terminals 3 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.79 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E6, withdrawable with vertical rear terminals 4 pole (50% neutral)
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.80 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E6, withdrawable with vertical rear terminals 4 pole (100% neutral)
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.81 1SXU000023C0201
rs ax ake m E bre er ow
P
Approximate dimensions (for UL version) 1 E1 - E6, fixed with vertical rear terminals 3 pole
00.00
Inches
00.00
[Millimeters]
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
16.82 1SXU000023C0201
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
00.00
Inches
00.00
[Millimeters]
Approximate dimensions (for UL version) 1 E1 - E6, fixed with vertical rear terminals 4 pole
Po
we Em r b ax re ak e
rs
16
1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.83 1SXU000023C0201
rs ax ake m E bre er ow
Emax Circuit Breaker Submittal Sheet Request for Quote Form
P
Date
Customer Name
From
Account No.
Location
Contact Name
Phone No.
Location
Fax No.
Phone No.
Comments
Fax No.
00.00
Inches
00.00
[Millimeters]
RFQ No. Due Date
Close Date
Quantity 1=1, 3P
4=4, 3P
B=2, 4P
F=6, 4P 50% neutral
2=2, 3P
6=6, 3P
C=3, 4P
G=4, 4P 100% neutral
3=3, 3P
A=1, 4P
D=4, 4P 50% neutral
H=6, 4P 100% neutral
B=basic
S=standard
V=very high
X=200kA
N=normal
H=high
L=limiting (IEC only)
A=800
D=2000
G=3600
N=6300 (IEC only)
B=1200/1250
E=2500
H=4000
P=1000 (IEC only)
C=1600
F=3200
J=5000
A=400
E=1200/1250
J=3000 (UL only)
N=5000
B=600/630
F=1600
K=3200
P=6300 (IEC only)
C=800
G=2000
L=3600 (UL only)
D=1000
H=2500
M=4000
0=None (non-automatic only
B = fixed, UL
F=Fixed, IEC
Q = 1000VAC
D = drawout, UL, less cradle
W=drawout, IEC, less cradle
R = 750VDC (3P) 1000VDC (4P)
A = PR121/P, LI
D = non-automatic
G = PR122/PD, LSIG
B = PR121/P, LSI
E = PR122/P, LI
H = PR122/PD, LSIRc
C = PR121/P, LSIG
F = PR122/P, LSI
J = PR123/P,LSI+PR120/V
0 = none
F=A+C
M=B+C
T=A+N+C+D
A = PR120/K4C
G=A+D
N = PR120/VT
U=N+C
B = PR120/VB std. on PR123/P
H=A+B+C
P=A+N
V=B+D
C = PR120/D-M
J=B+C+D
Q=A+N+C
W=N+D
D = PR120/D-BT
K=A+C+D
R=A+N+D
E=A+B
L=A+B+C+D
S=N+C+D
Closing coil:
0 = none
C = 48
F = 125 – 127
J = 380 – 400VAC
50/60Hz & VDC:
A = 24VDC
D = 60
G = 220– 240
K = 440 – 480VAC
B = 30
E = 110 – 120
H = 250
A = 4 aux
D = UV energ.NO
G=A&E
B = 10 aux
E = UV energ.NC
H=B&D
F=A&D
J=B&E
Frame Size
Breaking Capacity
Frame Ampere Rating
Rating Plug:
Version
Trip unit:
16
Trip unit accessories:
Contacts:
Spring charging motor: (includes spring charged signal, P/N does not show)
16.84 1SXU000023C0201
D
0 = none
C = 110-130VAC/VDC,
A = 24 – 30VAC/VDC,
D = 220 – 250VAC/VDC,
B = 48 – 60VAC/VDC
E = spring charged signal only
K = PR123/ P,LSIG+PR120/V
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
0 = none
Shunt trip:
C = 48VAC/DC
F = 125 – 127VAC/DC
J = 380 – 400VAC
A = 24VDC
D = 60VAC/DC
G = 220– 240VAC/DC
K = 440P–o480VAC E
Undervoltage trip: 00.00 Inches
0 = none
C = 48VAC/DC
F = 125 – 127VAC/DC
J = 380 – 400VAC
00.00& VDC: [Millimeters] 50/60Hz
A = 24VDC
D = 60VAC/DC
G = 220– 240VAC/DC
K = 440 – 480VAC
OR
B = 30VAC/DC
E = 110 – 120VAC/DC
H = 250VAC/DC
N = 48VAC/DC
R = 125 – 127VAC/DC
U = 380 – 400VAC
L = 24VDC
P = 60VAC/DC
S = 220– 240VAC/DC
V = 440 – 480VAC
M = 30VAC/DC
Q = 110 – 120VAC/DC
T = 250VAC/DC
X = none
F=A+B
A = mechanical counter
G=A+C
B = bell alarm
H=A+D
C = bell alarm w/remote reset 24-30VAC/DC
J=A+E
50/60Hz & VDC:
EmaxB =Circuit Breaker Submittal Sheet 30VAC/DC E = 110 – 120VAC/DC H = 250VAC/DC Request for Quote Form
Second Shunt trip: 50/60Hz & VDC:
Accessories:
w
m br ea
er ax L = low Z 120-127VAC/DC ke
rs
D = bell alarm w/remote reset 110-130VAC/DC E = bell alarm w/remote reset 220-240VAC/DC Locking Provisions
X = none
F=A+B
M=C+D
T = Heavy duty padlock, KE6PDHD1
A = Keylock
G=A+C
N=C+E
U=A+T
B = button guard
H=A+D
P=A+B+D
V=T+D
C = padlock provision (open)
J=A+E
Q=A+B+E
W=T+E
D = withdrawable position lock (connected, test and disconnected positions)
K=B+D
R=A+C+D
Y=A+T+D
E = withdrawable position lock ( test and disconnected positions)
L=B+E
S=A+C+E
Z=A+T+E
1 = 1, 3P
6 = 6, 3P
D = 4, 4P (50% neutral)
2 = 2, 3P
A = 1, 4P
F = 6, 4P (50% neutral)
3 = 3, 3P
B = 2, 4P
G = 4, 4P (100% neutral)
4 = 4, 3P
C = 3, 4P
H = 6, 4P (100% neutral)
C = IEC cradle
UL cradle
Cradles Frame Size:
Version:
N = E1B-A; E1N-A; E2B-A E2N-A
L = E4V-A; E4L-A
H = E2S-A; E2H-A; E4S-A; E4H-A; E4H-A/f; E6H-A; E6H-A/f
X = E3X-A2; E6V-A; E6LA; E6X-A
S = E3N-A; E3S-A; V=E3H-A; E3V-A 12 = 1200 (E1) UL
25 = 2500 (E3) UL
50 = 5000 (E6) UL
32 = 3200 (E3) IEC
16 = 1600 (E2) UL
32 = 3200 (E3) UL
12 = 1250 (E1) IEC
40 = 4000 (E4) IEC
20 = 2000 (E3) UL
36 = 3600 (E4) UL
20 = 2000 (E4) IEC
63 = 6300 (E6) IEC
Terminal Types:
H = HH
A = HV
E = HL (IEC only)
M = VL (IEC only)
(1st letter is upper terminal, 2nd letter is lower terminal) H= Rear Horizontal/V = Rear Vertical/F = Front/L = Rear Flat
V = VV
B = VH
G = LH (IEC only)
N = LV (IEC only)
F = FF (IEC only)
C = HF (IEC only)
J = VF (IEC only)
P = FL (IEC only)
L = LL (IEC only)
D = FH (IEC only)
K = FV (IEC only)
Q = LF (IEC only)
Maximum Ampere Rating:
Contacts:
16
0 = none A = 5 position auxiliaries, TOC B = 10 position auxiliaries, TOC
Options:
X = none
R = DC rated (750 V 3P, 1000V 4P) IEC only
Approved By:
Date:
Accepted By:
Date:
Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com
16.85 1SXU000023C0201