MCCONNELL DOWELL SOUTH EAST ASIA PTE LTD MCD Management System
CONSTRUCTION EXECUTION PROCEDURE CONCRETE REPAIR WORKS Doc No:
2755-MCD-CON-CEP-0034
Client:
Project:
DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN
Location:
TUAS, SINGAPORE
Project No:
2755
Revision History Rev
Date
Description
Author
Reviewer
A
10 Apr 2017
B C
Approver
Issue for Review and Approval
M. Villaroza
P. Rajendra
D. Pau
09 Jun 2017
Issue for Review and Approval
M. Villaroza
P. Rajendra
D. Pau
10 Jul 2017
Cast back repair method included
M. Villaroza
P. Rajendra
D. Pau
This document remains the property of McConnell Dowell Corporation. Its contents are confidential and shall not be reproduced, destroyed or given away without the express, written permission of McConnell Dowell Corporation. The electronic version of this document in MMS Database on designated server(s) is the Master Copy and is a controlled document. Unless specifically noted thereon, other copies of this document are uncontrolled. Based on MMS Template MMS # 600-J001-100 Rev11 25Mar2015.
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
TABLE OF CONTENTS 1
PURPOSE
3
2
scope
3
3
ACRONYMS
3
4
RESPONSIBILITIES
4
5
REFERENCES
4
6
CONSTRUCTION METHODOLOGY
5
6.1 summary 6.2 work method 6.3 MATERIAL DATA SUMMARY 6.4. permits
5 6 10 10
7
ACTIVITY SCHEDULE / MILESTONES
12
8
CONSTRUCTION RESOURCES
12
8.1 8.2 8.3
KEY PROJECT PERSONNEL personnel & Training Requirements Subcontractors & Suppliers
12 12 13
8.4
Plant & equipment
13
INSPECTION & TESTING
13
9 10
OHS&E HAZARD IDENTIFICATION, RISK ASSESSMENT & CONTROL
14
11
HAZARDOUS MATERIAL / SUBSTANCES
16
12
APPENDICES
17
13
REVIEW & APPROVAL
17
APPENDIX A: i. ii. iii. APPENDIX B:
QA / QC Documents Request for Inspection – Notification 017-F002-2755 Concrete Repair Checklist F028-600-2755 Summary list of Approved Material Submission (MAR) JSEA
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 2 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
1 PURPOSE The purpose of this Construction Execution Procedure (CEP) is to identify and provide specific requirements and procedure for most types of concrete repairs. It also details the safety measures required to ensure that the works are conducted in accordance with the client’s safety requirements. However due to the nature of the works, this CEP may be altered to suit the work. In such an event the client will be informed either verbally or in writing.
2 SCOPE The scope of work applicable to this Construction Execution Procedure outlines the repair works for unsound concrete in the Permanent Reinforced Concrete Structure and Patching of Formwork Tie-rod Cone Holes
3 ACRONYMS The scope of work applicable to this Construction Execution Procedure outlines the repair works for unsound concrete in the Permanent Reinforced Concrete Structure and Patching of Formwork Tie-rod Cone Holes. CEP
Construction Execution Procedure
COP
Code of Practice
ENV
Environment
EPI
Environmental Protection Instruction
IFC
Issued for Construction
ITC
Inspection and Test Checklist
ITP
Inspection and Test Plan
JSEA Job Safety and Environmental Analysis OHS
Occupational Health and Safety
PEP
Project Execution Plan
SOP
Safe Operating Procedures
SWI
Safe Work Instructions
SWMS Safe Work Method Statement
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 3 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
4 RESPONSIBILITIES Responsibility
Who
Final approval of this CEP.
David Pau
Nominated responsible “Owner” of this CEP. They are required to ensure regular review of this document when aspects of the document need amending.
Prasad Rajendra
Nominated as responsible for managing the construction works associated with this CEP.
Mika Tuoriniemi
Nominated as responsible for managing the construction works associated with this CEP.
Erwin Lee
Nominated as responsible for managing the construction works associated with this CEP.
Aatish Rumjeet
Nominated as responsible for managing the construction works associated with this CEP.
Verdy Nurtanio
Nominated as responsible for managing the quality control associated with this CEP.
Moises Villaroza
5 REFERENCES Construction Codes & Standards WSH relevant Code of Practice Construction Drawings & Specifications General Specification Particular Specification Material & Workmanship Specification Relevant Legislation / Code of Practice / Standards Relevant OHS Act(s)
WSH Act
Relevant OHS Regulation (s)
WSH (Risk Management) Regulations WSH (Construction) Regulations
Relevant OHS COP/ Standards Relevant Environment Act(s)
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 4 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
Construction Codes & Standards Relevant Environment Regulations(s) Relevant Environment COP / Standards Other(s), specify: Project Documents Project Execution Plan PEP Attachment 13-1 Project HSE Risk Register PEP Att. 2-1A Project Legal & Other Requirements – OHS PEP Att. 2-1B Project Legal & Other Requirements – ENV
6 CONSTRUCTION METHODOLOGY 6.1
SUMMARY Repair procedures have been prepared for eight possible types of repair to precast units and cast in situ works as listed below. The damaged area will be repaired using one of the products, which has been specified for each area. 1. Concrete Chipped off With No Exposure of Reinforcement 2. Concrete Chipped off With Exposure of Reinforcement 3. Voids on Surface (Blow Holes) 4. Recess for Lifting Hook 5. Cone Holes 6. Honey Combing a. Type A Trowellable Method (Honeycomb 5mm to 50mm deep) b.
Flowable Method (Honeycomb 51mm to 100mm deep)
c. Pressure Grout Method (Honeycomb 101mm to 200mm deep d. Cast back Method (Honeycomb / Other Defects more than 200mm deep) 7. Crack width below < 0.20mm 8. Cracks width 0.30mm and above
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 5 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
6.2
WORK METHOD 1. Concrete Chipped off With No Exposure of Reinforcement
Hack off and remove all loose parts from the affected area and feather the edges.
Clean surface and remove any dust.
Wet surface with water but ensure there is no free surface water before application of grout and apply bonding agent ‘Fosroc Nitobond AR’.
Apply the repair mortar Sto Crete NSG / NSG-S.
‘Sika ANTISOL – S’ or ‘Stocryl SCC Supreme’ curing compound is then used.
All works will be recommendations.
performed
in
accordance
with
the
manufactures
2. Concrete Chipped off With Exposure of Reinforcement
Hack off and remove all loose parts from the affected area to 20mm behind exposed reinforcing and feather the edges.
Put up formwork at the affected area to hold repair materials in shape if necessary.
Apply reinforcement protection primer ‘Fosroc Nitoprime Zincrich’ to the exposed reinforcement (if grouting will be done after 24 hours).
Wet surface with water but ensure there is no free surface water before application of bonding agent ‘Fosroc Nitobond AR’.
Apply the repair mortar ‘Sto Crete NSG / NSG-S’.
‘Sika ANTISOL – S’ or ‘Stocryl SCC Supreme’ curing compound is then used.
All works will be recommendations.
performed
in
accordance
with
the
manufactures
3. Voids on Surface (Blow Holes)
Remove all loose parts from the affected area.
Moisten the exposed concrete surface.
The surface must be free from standing water, oil and grease. Dust, dirt and other foreign particles must also be removed.
Wet the surface and then the blowholes are filled in with cement paste (Portland cement) applied by trowel with excess removed to maintain a smooth finish.
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 6 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
4. Recess for Lifting Hook
Cut off lifting strand from base of the recess, with minimal 50mm deep without damaging reinforcement.
The surface must be free from standing water, oil and grease. Dust, dirt and other foreign particles must also be removed. .
Apply reinforcement protection primer ‘Fosroc Nitoprime Zincrich’ to the exposed reinforcement (if grouting will be done after 24 hours).
Wet surface with water but ensure there is no free surface water before application of bonding agent ‘Fosroc Nitobond AR’.
Apply the repair mortar ‘Sto Crete NSG / NSG-S’.
‘Sika ANTISOL – S’ or ‘Stocryl SCC Supreme’ curing compound is then used.
5. Cone Holes
Remove plastic cones.
The surface must be free from standing water, oil and grease. Dust, dirt and other foreign particles must also be removed.
Wet the surface and apply the mortar ‘Sto Crete NSG / NSG-S’.
‘Sika ANTISOL – S’ or ‘Stocryl SCC Supreme’ curing compound is then used.
6. Honey Combing / Spalling A. Trowellable Method (Honeycomb 5mm to 50mm deep)
All areas where exposed aggregate is present, cleaning and hacking back to sound concrete.
Sound concrete is described as fully compacted and monolithic without the presence of voids or loose aggregate.
Wet surface with water but ensure there is no free surface water before application of bonding agent ‘Fosroc Nitobond AR’.
Apply the repair mortar Sto Crete NSG / NSG-S’.
‘Sika ANTISOL – S’ or ‘Stocryl SCC Supreme’ curing compound is then used.
All works will be recommendations.
performed
in
accordance
with
the
manufactures
B. Flowable Method (Honeycomb 51mm to 100mm deep)
Use marker pen to draw a line around the defective area.
Saw cut 5 to 10mm deep along the marked line to avoid feathered edges.
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 7 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
Use a breaker to remove all the unsound concrete. Continue hacking until sound homogeneous concrete is reached.
Clean-off the prepared area with water to remove all dust. Remove all rust from exposed rebar using wire brush.
Apply reinforcement protection primer ‘Fosroc Nitoprime Zincrich’ to the exposed reinforcement
Wet surface with water but ensure there is no free surface water before application of bonding agent ‘Fosroc Nitobond AR’.
Put up formwork at the affected area to hold repair materials in shape if necessary.
Flow the repair mortar ‘Sto Crete NSG/ NSG-S from one side only to avoid air entrapment’.
‘Sika ANTISOL – S’ or ‘Stocryl SCC Supreme’ curing compound is then used.
All works will be recommendations.
performed
in
accordance
with
the
manufactures
C. Pressure Grout Method (Honeycomb 101mm to 200mm deep)
Use marker pen to draw a line around the defective area.
Saw cut 5 to 10mm deep along the marked line to avoid feathered edges.
Use a breaker to remove all the unsound concrete. Continue hacking until sound homogeneous concrete is reached.
Clean-off the prepared area with water to remove all dust. Remove all rust from exposed rebar using wire brush.
Pre-wet the substrate surface to saturate and clear any excess water.
Apply ‘Fosroc Nitobond AR’ bonding agent to the substrate.
Fix chicken wire mesh to the existing rebar and pack with 4 to 10mm aggregates, if required, additional rebars to be drilled to allow fixing of chicken wire mesh
Fix the formwork to the surface to be grouted with provision of air release vents to the top part and grout inlet hose to the bottom part. All edges to be made leakproof using sponge in between the formwork and the concrete surface
Mix StoCrete NSG / NSG-S as per manufacturer specifications.
Pump the grout using a hand pump fitted with a gauge through the inlet hose until the grout overflows from the air release vents
Close the air vent hose and maintain a pressure of 1 bar for 30 seconds to ensure grout has filled up all the voids
Disconnect the inlet hose from the pump and block the hose
Leave to cure until grout is set and remove the formwork
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 8 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
Apply ‘Stocryl SCC Supreme’ curing compound with a paint brush after removing the formwork
D. Cast Back Method. (Honeycomb / Other Defects more than 200mm deep)
Use marker pen to draw a line around the defective area.
Saw cut 5 to 10mm deep along the marked line to avoid feathered edges.
Use a breaker to remove all the unsound concrete. Continue hacking until sound homogeneous concrete is reached.
Clean-off the prepared area with water to remove all dust. Remove all rust from exposed rebar using wire brush.
Pre-wet the substrate surface to saturate and clear any excess water.
Apply Fosroc Nitobond AR’ or Stocrete SBR-HD bonding agent to the substrate.
Fix the surface to be concreted with a funnel top edge (as necessary). Formwork to be higher than the surface to be repaired. All edges to be made leak-proof using sponge in between the formwork and the concrete surface
Cast back with Approved Concrete Mix Design or approved NSGrout
Leave to cure until concrete / NS Grout is set, before removing the formwork
Use a grinder to remove excess concrete on top part and sides and make surface even
Apply Stocryl SCC-Supreme curing compound with a roller or spray after removing the formwork
7. Shrinkage Cracks (width less than or equal to 0.2mm) Cracks in the precast wall panels with widths below 0.20mm will be repaired as follows:
The surface must be free from standing water, oil and grease. other foreign particles must also be removed.
Dry pack OPC cement will be brushed into all the cracks.
Water will be applied to the dry packed surface and brushed in to the dry packed cracks to from a seal.
Dust, dirt and
8. For concrete crack width 0.3mm and above Cracks in the precast wall panels and Cast-in Situ with widths of 0.30mm and above shall be repaired using UNIFOR “UF Grout” for dry Crack Repair by Epoxy Injection as per the following procedure:
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 9 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
6.3
Surface Preparation. Remove dust particles , laitance with wire brush and or using compressed air. Sealing of Surface and Adhesive of Plug. Seal crack at lengths, stopping at intervals of 300mm for plug adhesion using UF seal (Interval length depends on crack and depth). UF Seal Curing. Allow UF Seal to cure. 9refer to material specifications). Installation of Injector. Install injector by screwing onto the plugs. UF Grout Injection. Inject UF grout into container using grease/ footpump. Stop when pressure indicator rises to 3.kg/cm2. Proceed to next injector UF Grout Curing. Allow UF Grout to cure. Finishing. Remove injector and grind off sealing material.
MATERIAL DATA SUMMARY
Patching of Formwork Tierod Cone Holes 1) StoCrete NSG / NSG-S (Patching Material) 2) StoCrete SBR-HD / Fosroc Nitobond AR (Bonding Agent) 3) StoCryll SCC-SUPREME / Sika Antisol (Curing Compound)
Patching of Honeycomb 5mm to 50mm Deep, Patching, Chipping & Spalling 1) StoCrete NSG / NSG-S (Patching Material) 2) StoCrete SBR-HD / Fosroc Nitobond AR (Bonding Agent) 3) StoCryll SCC-SUPREME / Sika Antisol (Curing Compound)
Repair of Honeycomb 51mm to 100mm Deep and 101mm to 200mm deep Pressure Grouting 1) StoCrete NSG / NSG -S (Grouting Material) 2) StoCrete SBR-HD / Fosroc Nitobond AR (Bonding Agent) 3) StoCryll SCC-SUPREME/ Sika Antisol (Curing Compound) 4) Fosroc Nitoprime Zincrich (Protection primer to the exposed reinforcement
bars, as required)
Repair of Honeycomb more than 200mm 1) Approved Concrete Mix Design / Approved NS Grout (StoCrete NSG /NSG-S)
Repair of Concrete crack width 0.3mm and above 1) Unifor UF Grout Epoxy Resin (Crack Injection System)
6.4. PERMITS
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 10 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
Permit-To-Work (Lifting, Hot Work Permit, Working at Height) of McConnell Dowell as and when required.
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 11 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
7 ACTIVITY SCHEDULE / MILESTONES The concrete repair works shall be carried out as and when required.
8 CONSTRUCTION RESOURCES 8.1
KEY PROJECT PERSONNEL
The Project Manager or Construction Manager or delegate will appoint a Supervisor to oversee each or a few related activities. It will be ensured that the Supervisor will be experienced in the associated work, will be able to read drawings, be competent in reporting, and be conversant with the technical, safety and environmental specifications, guidelines or requirements. Table 7A Personnel requirements
Function / Role
Name
Project Manager
David Pau
92987313
Construction Manager
Prasad Rajendra
91795789
QA / QC Manager
Moises Villaroza
90111571
Precast Manager
Mika Tuoriniemi
87995883
Senior Project Engineer
Erwin Lee
96916298
Project Engineer
Aatish Rumjeet
91470306
Project Engineer
Verdy Nurtanio
92447851
8.2
Contact Details
PERSONNEL & TRAINING REQUIREMENTS
All equipment shall be operated by suitably qualified and experienced personnel. Specialised labour requirements for the works will involve: Table 7B Personnel & Training requirements
Function / Role
Qualification / licence Required
Skilled Supervisor
Work at height Certificate
Work at height training
Skilled Worker
Work at height Certificate
Work at height training
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
Activity specific Training Required
PAGE 12 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
8.3
SUBCONTRACTORS & SUPPLIERS
Table 7C – Sub-contractors and suppliers
Scope of works
Name of Subcontractor / Suppliers
Contact Details
Contact Person
Concrete repair works
McConnell Dowell
Mika Tuoriniemi
87995883
Concrete repair works
McConnell Dowell
Erwin Lee
96916298
Concrete repair works
McConnell Dowell
Aatish Rumjeet
91470306
Concrete repair works
McConnell Dowell
Verdy Nurtanio
92447851
Concrete repair works
McConnell Dowell
Moises Villaroza
90111571
8.4
PLANT & EQUIPMENT
Plant and equipment associated with the works will be in good working order and have the capacity to safely and efficiently do the work required. The type, size and number of machines used will depend on the quantity of material, scheduling and access restrictions. Necessary plant inspections and operator competency assessments will be undertaken as part of the Project Safety Management Plan. The following list outlines the plant and equipment expected for the associated scope: Table 7D Powered Plant & Equipment required for the works
Powered Plant and Equipment required for the works:
Type of Works
(e.g. EWP / Crane / Forklift / etc)
Mortar / Grout Mixer
Concrete Repair works
Drilling Machine/Breaker Machine
Concrete Repair works
Air compressor
Concrete Repair works
Injection Pump
Concrete Repair works
9 INSPECTION & TESTING ITP(s) documents will be prepared to summarise inspection and testing protocols. At predetermined stages of works, the appropriate inspections or tests shall be undertaken and submitted as specified. Subsequent works will then proceed upon meeting the specified criteria. The following ITP(s) will be used to manage the quality of the works: Table 6A Inspection & Test Plan List
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 13 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
ITP Number
2755-MCD-QAC-ITP0013
Person or organisation responsible for preparation
Title / scope
CONCRETE REPAIR WORK
PROJECT / SITE ENGINEERS
10 OHS&E HAZARD IDENTIFICATION, RISK ASSESSMENT & CONTROL H Hazard identification, risk assessment and control will be principally managed and documented through use of the PEP Att. 13-1 HSE Risk Register (MMS# 020-Y001-7566). Relevant SWI’s, SOPs and EPIs will be implemented and followed. JSEA / SWMS’s will be prepared to cover specific risks associated with the works. Development and implementation of the JSEA / SWMS and the associated documentation (SWI’s; SOP’s; EPIs; etc...) will be undertaken with the personnel involved in the works. These documents can then be viewed by the Client’s representative prior to work commencement. All personnel will complete the project site induction before being allowed access to the works. Operator competency will be recorded and plant inspections will be undertaken prior to any activity commencing. Daily start up meetings will be conducted and documented by Supervisors to ensure all safety measures are in place for the day’s activities.
Table 11A OHS&E Hazard Identification, Risk assessment & Control
JSEA/SWMS Title / Activity description (What)
Development Responsibility (Role)
Due By
JSEA X012-020-7566 Concrete Repair works
Mika Tuoriniemi
Dec 2017
JSEA X012-020-7566 Concrete Repair works
Erwin Lee
Dec 2017
JSEA X012-020-7566 Concrete Repair works
Aatish Rumjeet
Dec 2017
JSEA X012-020-7566 Concrete Repair works
Verdy Nurtanio
Dec 2017
JSEA X012-020-7566 Concrete Repair works
Moises Villaroza
Dec 2017
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 14 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
Table 11B Required SWI for Activities / Tasks
Activity description (What)
SWI (No. + Name)
Preparation work
K005-Using Electrically Operated Tools K082-Personal Protective Equipment K044-Exposure to Noise K041-Housekeeping-Access & Egress
Working at Height
K036-Working at Height K082-Personal Protective Equipment K041-Housekeeping-Access & Egress
Manual Handling
K081-Manual Handling
Construction noise
K044-Exposure to Noise
Table 11C Environmental Aspects Identification, Risk Assessment & Controls
Implementation Responsibility (Role/Subcontractor)
Aspect (What)
Control (How)
Flora
Not applicable
Fauna
Not applicable
Weed and pest control
L031-Vector Control - Mosquito
Water quality
Not applicable
Erosion and Sediment control
Not applicable
Noise
PEP Noise Management Plan K044-Exposure to Noise
ECO
Dust
Supress with water PEP Safety management plan
ECO / Supervisor
Waste
Not applicable
Ground Contamination
L007-Storage, Maint. & Refuelling Machinery
Cultural Heritage
Not applicable
Other
Not applicable
ECO
ECO / Supervisor
Note: the above list is not intended to be exhaustive, and is limited to the scope of work as identified at the time of the Risk Register Workshop.
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 15 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
11 HAZARDOUS MATERIAL / SUBSTANCES Table 12A Hazardous materials / Substance list
Hazardous Materials / Substance
Specific task / activity it is required for
Fosroc Nitobond AR
Refer to submitted SDS via Material Approval (MAR)
Fosroc Nitoprime Zincrich
Refer to submitted SDS via Material Approval (MAR)
StoCrete NSG-H
Refer to submitted SDS via Material Approval (MAR)
StoCryl SCC
Refer to submitted SDS via Material Approval (MAR)
Davco Grout 280
Refer to submitted SDS via Material Approval (MAR)
Sika ANTISOL - S
Refer to submitted SDS via Material Approval (MAR)
Unifor UF Grout
Refer to submitted SDS via Material Approval (MAR)
Note: the above list is not intended to be exhaustive, and is limited to the scope of work as identified at the time of the Risk Register Workshop.
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 16 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
12 APPENDICES APPENDIX A: QAQC Documents i.
Request for Inspection – Notification 017-F002-2755
ii.
Concrete Repair Checklist F028-600-2755
iii.
Summary list of Approved Material Submission (MAR)
APPENDIX B: JSEA
13 REVIEW & APPROVAL Position
Name
Prepared By:
QAQC Engineer
Mark Condes
Reviewed By:
Quality Manager
Moises Villaroza
Reviewed By:
Precast Manager
Mika Tuoriniemi
Reviewed By:
Project Engineer - R2
Erwin Lee
Reviewed By:
Project Engineer – R3
Aatish Rumjeet
Reviewed By:
Project Engineer - TVB
Verdy Nurtanio
Reviewed By:
Safety Manager
Hairy Ghani
Reviewed By:
Construction Manager
Prasad Rajendra
Approved By:
Project Manager
David Pau
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
Signature
Date
PAGE 17 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
APPENDIX A QA / QC Documents
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 18 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL
CONSTRUCTION EXECUTION PROCEDURE 2755-MCD-CON-CEP-0034 REVISION C DATE 10 JULY 2017
APPENDIX B Job Safety & Environmental Analysis (JSEA)
McCONNELL DOWELL SEA PTE LTD PROJECT NO. 2755 DESIGN AND BUILD OF ROAD ACCESS AT TUAS VIEW BASIN NATIONAL ENVIRONMENT AGENCY (NEA)
PAGE 19 OF 19 COMMERCIAL-IN-CONFIDENCE McCONNELL DOWELL