Wire Size Specifier

  • Uploaded by: DennyHalim.com
  • 0
  • 0
  • October 2019
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Wire Size Specifier as PDF for free.

More details

  • Words: 1,247
  • Pages: 5
COPPER WIRE SPECIFIER BY R. JAMES & R. PEREZ INput Voltage= INput Amperage= INput Feet=

24.00 volts 10.00 amperes 250.00 feet of wire in the COMPLETE circuit INput Wire Gauge 2

Volts Thru= Volts Loss=

23.61 volts 0.39 volts

Power Input= Power Lost= Power Transferred= Efficiency in %= V lost in %

240.00 watts 3.91 watts 236.09 watts 98.37% 1.65%

Shunts Shunt length in feet

0.1Ω 0.01Ω 639.881 63.988 ma=mv*10 ma=mv*100

Feet/Ω 6398.81 Ω/Foot 0 Ω/Ft. X # of FT.=

0.001Ω 6.399 Amps=mv

0.0001Ω 0.640 Amp=mv*10

0.04

0.00001Ω 0.064 A=mv*100

12 Volt Wire Sizing Chart 15 .975

R O U N D T R I P W I R E L E N G T H in F E E T

Specification Voltage is 15.00 VDC Wiring is specified for a power efficiency  of 97.5% and/or correct ampacity

PV ARRAY CURRENT IN AMPERES. 6 12 15 18 21 24 30 36 25 13 10 10 9 8 7 6 6 30 13 10 9 8 7 7 6 5 35 12 9 8 7 7 6 5 4 40 11 8 7 7 6 5 4 4 45 11 8 7 6 6 5 4 3 50 10 7 7 6 5 4 4 3 60 10 7 6 5 4 4 3 2 70 9 6 5 4 4 3 2 1 80 8 5 4 4 3 2 1 1 90 8 5 4 3 3 2 1 0 100 7 4 4 3 2 1 1 0 125 7 4 3 2 1 1 0 ­1 150 6 3 2 1 0 0 ­1 ­2 175 5 2 1 0 0 ­1 ­2 ­3 200 4 1 1 0 ­1 ­1 ­2 ­3 225 4 1 0 ­1 ­1 ­2 ­3 250 4 1 0 ­1 ­2 ­2 ­3 275 3 0 ­1 ­2 ­2 ­3 300 3 0 ­1 ­2 ­3 ­3 325 2 ­1 ­2 ­2 ­3 350 2 ­1 ­2 ­3 ­3 375 2 ­1 ­2 ­3 400 1 ­1 ­2 ­3 425 1 ­2 ­3 450 1 ­2 ­3 475 1 ­2 ­3 500 1 ­2 ­3 600 0 ­3 700 ­1

42 48 54 60 66 72 78 84 90 96 102 108 114 120 5 4 4 4 3 3 2 2 2 1 1 0 0 0 4 4 3 3 2 2 2 1 1 1 0 0 0 0 4 3 3 2 2 1 1 1 0 0 0 0 ­1 ­1 3 2 2 1 1 1 0 0 0 ­1 ­1 ­1 ­1 ­1 3 2 1 1 1 0 0 0 ­1 ­1 ­1 ­2 ­2 ­2 2 1 1 1 0 0 ­1 ­1 ­1 ­1 ­2 ­2 ­2 ­2 1 1 0 0 ­1 ­1 ­1 ­2 ­2 ­2 ­3 ­3 ­3 ­3 1 0 0 ­1 ­1 ­2 ­2 ­2 ­3 ­3 ­3 ­3 0 ­1 ­1 ­1 ­2 ­2 ­3 ­3 ­3 0 ­1 ­2 ­2 ­2 ­3 ­3 ­3 ­1 ­1 ­2 ­2 ­3 ­3 ­2 ­2 ­3 ­3 ­3 ­3 ­3 Specification Voltage 15 VDC for 12 VDC PV Applications Wiring is specified for a power efficiency  of 97.5% and/or correct ampacity Codes The body of the table contains the Wire Gauge Number "0" Wire is designated by 0 "00" Wire is designated by ­1 "000" Wire is designated by ­2 "0000" Wire is designated by ­3 Wiring power efficiency is specified at 68°F.   If ambient temperature is > 90°F., use the next gauge larger wire

14

14 12 12 10

8

6

6

6

4

4

4

2

2

2

2

0

0

0

0

0

0

24 Volt Wire Sizing Chart 30 .975

R O U N D T R I P W I R E L E N G T H in F E E T

Specification Voltage is 30.00 VDC Wiring is specified for a power efficiency  of 97.5% and/or correct ampacity

PV ARRAY CURRENT IN AMPERES. 6 12 15 18 21 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 25 14 13 12 12 10 8 6 6 6 6 6 6 4 4 4 2 2 2 2 0 0 0 30 14 13 12 11 10 8 6 6 6 6 6 6 4 4 4 2 2 2 2 0 0 0 35 14 12 11 10 10 8 6 6 6 6 6 5 4 4 4 2 2 2 2 0 0 0 40 14 11 10 10 9 8 6 6 6 5 5 4 4 4 3 2 2 2 2 0 0 0 45 14 11 10 9 9 8 6 6 6 5 4 4 4 3 3 2 2 2 2 0 0 0 50 13 10 10 9 8 7 6 6 5 4 4 4 3 3 2 2 2 1 1 0 0 0 60 13 10 9 8 7 7 6 5 4 4 3 3 2 2 2 1 1 1 0 0 0 0 70 12 9 8 7 7 6 5 4 4 3 3 2 2 1 1 1 0 0 0 0 ­1 ­1 80 11 8 7 7 6 5 4 4 3 2 2 1 1 1 0 0 0 ­1 ­1 ­1 ­1 ­1 90 11 8 7 6 6 5 4 3 3 2 1 1 1 0 0 0 ­1 ­1 ­1 ­2 ­2 ­2 100 10 7 7 6 5 4 4 3 2 1 1 1 0 0 ­1 ­1 ­1 ­1 ­2 ­2 ­2 ­2 125 10 7 6 5 4 4 3 2 1 1 0 0 ­1 ­1 ­2 ­2 ­2 ­2 ­3 ­3 ­3 ­3 150 9 6 5 4 3 3 2 1 0 0 ­1 ­1 ­2 ­2 ­2 ­3 ­3 ­3 175 8 5 4 3 3 2 1 0 0 ­1 ­1 ­2 ­2 ­3 ­3 ­3 200 7 4 4 3 2 1 1 0 ­1 ­1 ­2 ­2 ­3 ­3 225 7 4 3 2 2 1 0 ­1 ­1 ­2 ­3 ­3 ­3 250 7 4 3 2 1 1 0 ­1 ­2 ­2 ­3 ­3 Specification Voltage 30 VDC 275 6 3 2 1 1 0 ­1 ­2 ­2 ­3 ­3 for 24 VDC PV Applications 300 6 3 2 1 0 0 ­1 ­2 ­3 ­3 325 5 2 1 1 0 ­1 ­2 ­2 ­3 Wiring is specified for a power efficiency  of 97.5% 350 5 2 1 0 0 ­1 ­2 ­3 ­3 and/or correct ampacity 375 5 Codes 2 1 0 ­1 ­1 ­2 ­3 400 4 1 1 0 ­1 ­1 ­2 ­3 The body of the table contains the Wire Gauge Number 425 4 1 0 ­1 ­1 ­2 ­3 "0" Wire is designated by 0 450 4 1 0 ­1 ­1 ­2 ­3 "00" Wire is designated by ­1 475 4 1 0 ­1 ­2 ­2 ­3 "000" Wire is designated by ­2 500 4 1 0 ­1 ­2 ­2 ­3 "0000" Wire is designated by ­3 600 3 0 ­1 ­2 ­3 ­3 700 2 Wiring power efficiency is specified at 68°F.   ­1 ­2 ­3 ­3 800 1 ­1 ­2 ­3 If ambient temperature is > 90°F., use the next gauge larger wire

14

14 12 12 10

8

6

6

6

4

4

4

2

2

2

2

0

0

0

0

0

0