VITOSOL
System Design Guidelines
Vitosol 200-F
Viessmann solar collectors – the right solution for every application Using solar energy to heat domestic hot water and to provide a backup for space heating
5167 156 v3.1
05/2008
Vitosol 300-T Model SP3
Vitosol 200-F
Flat plate solar collector for installation on pitched and flat roofs, and for freestanding installation
Vitosol 300-T
Vacuum tube solar collector, based on the heat pipe principle, for installation on sloped and flat roofs and for freestanding installation
Safety, Installation and Warranty Requirements
Safety, Installation and Warranty Requirements Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections). H Licensed professional heating
contractor The installation, adjustment, service, and maintenance of this equipment must be performed by a licensed professional heating contractor. Please see section entitled “Important Regulatory and Installation Requirements”.
"
H Grounding/lightning protection of the
solar system In the lower part of the building, install an electrical conductor on the solar circuit’s piping system in compliance with local regulations. Connection of the solar system to a new or existing lightning protection or the provision of local grounding should only be carried out by a licensed professional, who must take into account the prevailing conditions on site.
CAUTION Avoid scratching or sudden shocks to glass cover of the solar panel.
CAUTION Never step on collectors or solder in close proximity to the glass surface of the solar panel. H Applicability
H Product documentation
Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel. For a listing of applicable literature, please see section entitled “Important Regulatory and Safety Requirements”.
"
H Advice to owner
Once the installation work is complete, the heating contractor must familiarize the system operator/ultimate owner with all equipment, as well as safety precautions/requirements, shut-down procedure, and the need for professional service annually. H Warranty
Observe maximum load and distance from edge before installing the substructure to the roof. If necessary, consult with a structural engineer to determine if the structure is suitable for installing solar collectors. The collectors must be securely mounted so that the mountings can withstand intense wind conditions and local snow loads.
CAUTION
IMPORTANT Pool water or potable water cannot be pumped directly through the Vitosol collectors. Damage to collectors caused by corrosion, freezing or scaling will void warranty.
Gloves and eye protection must be worn when handling solar panels.
CAUTION Solar panel connection pipes and solar heating fluid can become hot enough to cause severe burns. Extreme caution must be taken if panels have been in a stagnant condition (no flow of fluid).
5167 156 v3.1
Information contained in this and related product documentation must be read and followed. Failure to do so renders warranty null and void.
CAUTION
Vitosol solar collectors are designed for use in closed loop heating systems for domestic hot water heating, space heating and pool heating via a heat exchanger. The use of Viessmann heat transfer medium “Tyfocor-HTL” is strongly recommended.
2
Contents
Contents Safety General Information Basic Principles of Solar Technology
Page Safety Instructions Important Regulatory and Installation Requirements About these Instructions Product Information Important Regulatory and Installation Requirements Subsidies, Permits and Insurance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Solar Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 HExploiting solar energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 H Solar radiation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 H Global radiation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 H Exploiting solar energy with collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 H Influence of alignment, inclination and shade on energy yield . . . . . . . . . 10 H Inclination and orientation of collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 H Angle of inclination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Overall System Optimisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Specification
Construction and Function of Collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 H Vitosol 200-F – flat panel collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 H Vitosol 300-T – vacuum tube collector based on the heat pipe principle 14 Collector Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Solar coverage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Collector Installation and Mounting Details . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 H Installation options for different collector types . . . . . . . . . . . . . . . . . . . . . 18 H Vitosol 200-F flat panel collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 H Support weight requirements - Vitosol 300-T . . . . . . . . . . . . . . . . . . . . . . . . 24 General Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Notes on Planning and Operation
Calculating the Required Absorber Surface Area . . . . . . . . . . . . . . . . . . . . . . 27 H Calculating the absorber surface area and DHW cylinder capacity . . . . . 27 H Calculating the absorber surface area for space heating . . . . . . . . . . . . . . 28
5167 156 v3.1
Sizing Pipe Diameters and Circulation Pump . . . . . . . . . . . . . . . . . . . . . . . . . . 31 H Sizing pipe diameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 H Installation examples for Vitosol 200-F, models SV2 and SH2 . . . . . . . . 35 H Collector pressure drop information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 H Sizing pipe circulation pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 H Technical information on the Solar-Divicon . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Safety Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 H Liquid capacity of solar heating system components . . . . . . . . . . . . . . . . . 37 H Diaphragm expansion vessel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 H Technical data for the expansion tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 H Pressure relief valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 H High limit safety cut-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 H Thermostatic mixing valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3
Contents
Contents (continued)
Page General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 H How to implement the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 System Design 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 H Dual-mode DHW heating with Vitocell-B 100 or Vitocell-B 300 DHW tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 System Design 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 H Dual-mode DHW heating and space heating backup with heating water storage tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 System Design 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 H Dual-mode DHW heating with two DHW tanks . . . . . . . . . . . . . . . . . . . . . . 50 System Design 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 H Dual-mode DHW and swimming pool water heating . . . . . . . . . . . . . . . . . 53 System Design Extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 H System with bypass circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 H Bypass circuit with solar cell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 H System with energy-saving mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Appendix
Calculation Example Based on the Viessmann ”ESOP” Program . . . . . . . . 58 H Solar heating systm with dual-coil DHW tank . . . . . . . . . . . . . . . . . . . . . . . 58 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
5167 156 v3.1
System Designs
4
Safety
Important Regulatory and Installation Requirements Codes The installation of solar heating systems might be governed by individual local rules and regulations for this type of product, which must be observed. The installation of this unit shall be in accordance with local codes. Always use latest editions of codes. Mechanical room Ensure the mechanical room complies with the requirements of the system design guideline and/or technical data manual. The solar storage tank must be installed in a mechanical room which is never subject to freezing temperatures. If not in use and danger of freezing exists in the mechanical room, ensure water in tank is drained.
Working on the equipment The installation, adjustment, service, and maintenance of this equipment must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of solar heating systems. There are no user serviceable parts on this equipment.
Please carefully read this manual prior to attempting installation. Any warranty is null and void if these instructions are not followed. This product must be installed observing not only the necessary product literature (see list), but also all local, provincial/state plumbing and building codes, as they apply to this product and all periphery equipment. For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product. We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire.
The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. These include pumps, valves, air vents, thermostats, temperature and pressure relief controls, etc.
Ensure main power supply to equipment, the heating system, and all external controls has been deactivated. Take precautions in both instances to avoid accidental activation of power during service work. Leave all literature at the installation site and advise the system operator/ultimate owner where the literature can be found. Contact Viessmann for additional copies.
5167 156 v3.1
Technical literature Literature applicable to all aspects of the Vitosol: - Technical Data Manual - Installation Instructions - Start-up/Service Instructions - Operating Instructions and User’s Information Manual - System Design Guidelines
5
General Information
About these Instructions Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include ”WARNING”, ”CAUTION”, and ”IMPORTANT”. See below.
WARNING Indicates an imminently hazardous situation which, if not avoided, could result in substantial product/property damage, serious injury or loss of life.
CAUTION Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/property damage.
IMPORTANT
Warnings draw your attention to the presence of potential hazards or important product information.
Cautions draw your attention to the presence of potential hazards or important product information.
Helpful hints for installation, operation or maintenance which pertain to the product.
This symbol indicates that additional, pertinent information is to be found in the adjacent column.
This symbol indicates that other instructions must be referenced.
Product Information Vitosol 200-F, Models SV2, SH2 Flat panel solar collector with 25 ft.2 / 2.3 m2 collector area. Max. stagnation temperature 430°F / 221°C Max. operating pressure 87 psig / 6 bar
Max. stagnation temperature 302°F / 150°C Max. operating pressure 87 psig / 6 bar
6
5167 156 v3.1
Vitosol 300-T, SP3 Series Vacuum tube solar collector with 22 and 32 ft.2 / 2 and 3 m2 collector area.
Basic Principles of Solar Technology
Subsidies, Permits and Insurance Solar heating systems for DHW or swimming pool heating are subsidised by many regional and local authorities. Request information about subsidies from your local authority. Further information is available from our sales offices.
Your local planning office will be able to advise you about whether solar heating systems need planning permission.
The sun has provided the earth with light and heat for billions of years. Without it, our existence on earth would be impossible. We have been using the sun’s heat since time immemorial. In summer, it heats our buildings directly, while in winter we make use of solar energy stored in the form of wood, coal, oil and gas, to provide heat for our buildings and domestic hot water. To protect fuel reserves, the heating industry has committed itself to finding more responsible ways of handling these precious resources, which have accumulated naturally over millions of years. One rational way of achieving this aim is to make direct use of solar energy by means of collectors.
Thanks to the use of highly sophisticated collectors and a perfectly matched overall system, the economic use of solar energy is no longer a futuristic vision, but a proven everyday reality. Considering that fuel prices will continue to rise in the years ahead, investing in a solar heating system can be viewed as a ”genuine” investment in the future.
Viessmann solar collectors are tested for impact resistance, incl. hail impact, in accordance with DIN EN 12975-2. Nevertheless, we would recommend you include the collectors in your building insurance, to protect you from losses arising from any extraordinary natural phenomenon. Our warranty excludes such losses.
Solar Energy
5167 156 v3.1
Exploiting solar energy
7
Basic Principles of Solar Technology
Solar Energy
(continued)
Solar radiation Solar radiation represents a flow of energy irradiated uniformly in all directions by the sun. Of that energy, an output of 429 Btu/h/ft.2 or 1.36 kW/m2, the so-called solar constant, hits the outer earth’s atmosphere.
S
RT
Diffused celestial radiation Direct solar radiation Wind, rain, snow, convection Convection losses Conduction losses
Heat radiation of the absorber Heat radiation of the glass cover Useful collector output Reflection RT Return S Supply
Global radiation
direct radiation diffused radiation
5000 4000 3000 2000 1000 0 Jan.
Feb.
March
April
May
June
July
Aug.
Sept.
Oct.
Nov.
Dec.
After penetrating the earth’s atmosphere, the solar radiation is reduced by reflection, dispersion and absorption by dust particles and gaseous molecules. That portion of this radiation which passes unimpeded through the atmosphere to strike the earth’s surface is known as direct radiation. The portion of the solar radiation which is reflected and/or absorbed by dust particles and gas molecules and irradiated back strikes the earth’s surface indirectly is known as diffused radiation. The total radiation striking the earth’s surface is the global radiation Eg, i.e., global radiation = direct radiation + diffused radiation. In the latitudes of North America, the typical global radiation under optimum conditions (clear, cloudless sky at midday) amounts to a max. of 317 Btu/h/ft.2 or 1 000 W/m2. With solar collectors, as much as 75 % of this global radiation can be utilised, depending on the type of collector.
8
5167 156 v3.1
Solar irradiation in Wh/(m2 x d)
6000
Basic Principles of Solar Technology
Solar Energy
(continued)
Exploiting solar energy using solar collectors The useful energy which a collector can absorb depends on several factors. The main factor is the total solar energy available.
The amount of global energy varies from location to location (see maps below).
The type of collector, as well as its inclination and orientation, are also very important (see page 10). If the solar installation is to be operated economically, careful dimensioning of the system components is also essential.
Annual global radiation in Canada
2.5 - 3
Btu/ft2/day 787-945
kwh/m2/day
3 - 3.3 kwh/m2/day
945-1040
kwh/m2/day
1040-1134
3.6 - 3.9 kwh/m2/day 3.9 - 4.2 kwh/m2/day
1134-1228 1228-1323
4.2 - 4.4 kwh/m2/day
1323-1386
4.4 - 4.7 kwh/m2/day
1386-1481
3.3 - 3.6
> 4.7 kwh/m2/day
>1481
5167 156 v3.1
Annual global radiation in the United States
3 - 4 kwh/m2/day
Btu/ft2/day 945-1260
4 - 5 kwh/m2/day
1260-1575
5 - 6 kwh/m2/day
1575-1890
6 - 7 kwh/m2/day
1890-2205
Note: Average mean daily global radiation on a south-facing surface tilted at an angle equal to the latitude of the location.
9
Basic Principles of Solar Technology
Solar Energy
(continued)
Influence of alignment, inclination and shade on energy yield
Optimum alignment and inclination North
West
East
South
Example: 30°; 45° south-west
Annual irradiation in %
Angle of inclination
The solar generator provides the highest annual solar yield for a DHW system when facing south with an inclination of approx. 30 to 35 degrees to the horizontal plane. However, the installation of a solar heating system is still viable even when the installation deviates quite significantly from the above (south-westerly to south-easterly alignment, 25 to 55 degrees inclination). The graph illustrates the loss of yield resulting from an installation of the collector array which is less than perfect. The graph also indicates that a shallower inclination is more favourable, if the collector surface cannot be pointed south. A solar heating system with a 30º inclination and an alignment of 45º south-westerly still achieves 95% of its optimum yield. Even with an east-westerly alignment, you can still expect 85% with a roof inclination between 25º and 40º. A more steeply sloped installation would be more favourable in winter, but the system achieves two thirds of its yield during the summer months. On the other hand, an angle of inclination less than 20 degrees should be avoided, otherwise the solar generator will become too contaminated, or snowcovered. Installing the collector array on different roofs requires complex hydraulic interconnections between the individual collectors. Every array is equipped with a separate collector temperature sensor and a separate pump line. The increase in energy yield is therefore offset by the higher installation costs, resulting in a significantly reduced cost:benefit ratio.
Position and size the collector array so that the influence of neighbouring structures, trees, power lines, etc., which throw shadows over the array, is minimised. Also consider how neighbouring properties will be likely to develop over a period of 20 years, as regards additional buildings, plants and saplings. 10
5167 156 v3.1
Shade reduces energy yield
Basic Principles of Solar Technology
Solar Energy
(continued)
Inclination and orientation of collectors To achieve optimum energy absorption, the collectors must be oriented towards the sun. The angle of inclination and the azimuth angle are the dimensions used to determine the orientation of the collectors. Angle of inclination Angle of inclination α
IMPORTANT The angle of inclination for Vitosol 300-T collectors must be at least 25º in order to guarantee circulation of the evaporator liquid in the heat pipe
The angle of inclination a is the angle between the horizontal and the collector plane. For pitched roof installations, the angle of inclination is determined by the slope of the roof. The largest amount of energy can be captured by the collector’s absorber when the collector plane is aligned at right angles to the irradiation of the sun. Because the angle of irradiation depends on the time of day and the time of year, the collector plane should be aligned according to the position of the sun during the phase of maximum energy supply. In practice, angles of inclination of between 30 and 45º have proven to be ideal. For most installations in North America, for example, an angle of inclination of between 25 and 70º is advantageous, depending on the period of use. Lower angles of inclination are better for applications where more energy is required in the summer months (i.e. pool heating). Higher angles of inclination are better for applications where more energy is required in the winter months. Capturing the maximum amount of energy throughout the year can be achieved using an angle of inclination equal to the latitude of the building site. This is ideal for domestic hot water heating applications. Azimuth angle
Example:
5167 156 v3.1
Deviation from south: 15º east
Collector plane Azimuth angle
The azimuth angle describes the deviation of the collector plane from south; the collector plane aligned to the south is the azimuth angle = 0º. Because solar irradiation is at its most intensive at midday, the collector plane should be oriented as closely as possible to the south. However, deviations from south up to 45º south-east or south-west have minimal impact on annual energy production. 11
Basic Principles of Solar Technology
Overall System Optimization A high-quality solar collector cannot by itself guarantee the optimum operation of a solar installation. This depends more on the complete system solution as a whole. Viessmann supplies all the components required for a solar heating system:
H a control unit that is tailored to the
individual solar heating system, H a DHW tank incorporating a solar heat exchanger low inside the tank, H a preassembled pump station with all necessary hydraulic components, H design details aimed at achieving fast-responding control and therefore maximum yields from the solar heating system.
Correctly designed solar heating systems with well matched system components can cover 50 to 80 % of the annual energy demand for DHW heating in detached and semi-detached houses. We will be pleased to assist you with the design of solar heating systems. The elements of a solar heating system are shown in the diagram.
T
T
T
DHW
S
R
I
DCW
*1
12
Brass elbow c/w sensor well Dual-mode DHW tank I Tank temperature sensor Air separator Solar control unit Flexible connection pipe
Collector temperature sensor Fast air-vent, c/w shutoff valve *1 R Return to collector S Supply from collector
Install at least one air-vent valve (quick-acting air-vent valve or a manual vent valve, see page 43) at the highest point of the system.
5167 156 v3.1
Solar collector Solar-Divicon (pumping station) Overflow container Expansion vessel Solar manual filling pump System fill manifold valve
Specification
Construction and Function of Collectors Vitosol 200-F flat panel collector Vitosol 200-F flat plate solar collector is available as: H Vertical version Model SV2 and horizontal version Model SH2, each offering 2.3 m2 / 25 ft2 absorber surface. The main component of Vitosol 100 is the Sol-Titanium coated copper absorber. It ensures high absorption of solar radiation and low emission of thermal radiation. A copper pipe through which the heat transfer medium flows is fitted to the absorber. The heat transfer medium channels the absorber heat through the copper pipe. The meander-shaped direct flow absorber of models SV2 and SH2 provides an extremely even flow through each individual collector in the collector arrays. The absorber is surrounded by a highly insulated collector housing which minimises collector heat losses. The high quality thermal insulation provides temperature stability and is free from gas emissions. The cover comprises a solar glass panel. The glass has a very low iron content, thereby reducing reflection losses. Continuous profiled seal (vulcanised) Solar glass cover, 3.2 mm thick Meander-shaped copper pipe Copper absorber Melamine resin foam
Mineral fiber Aluminum frame sections Aluminum-zinc bottom panel Connection pipe
The collector housing comprises a powder-coated aluminium frame (recycled aluminium), within which the solar glass panel is permanently sealed. Model SV2 and SH2 Up to twelve collectors can be joined to form a single collector array. For this purpose, the standard delivery includes flexible connection pipes, sealed with O-rings. A general connection kit with clamping ring connections enables the collector array to be readily attached to the pipes of the solar circuit. The collector temperature sensor is installed in the solar circuit flow via a sensor well set.
Technical Data Vitosol 200-F, SV2/SH2 Gross Area
Absorber Area
Aperture Area
Dimensions
m2
ft2
m2
ft2
m2
ft2
mm
in
kg
lb
SV2
2.51
27.0
2.32
25
2.33
25.1
1056x 2380x90
41¾x 93¾x3½
52
115
SH2
2.51
27.0
2.32
25
2.33
25.1
2380x90x 1056
93¾x41¾x x3½
52
115
5167 156 v3.1
Model
Weight
13
Specification
Construction and Function of Collectors
(continued)
Vitosol 300-T vacuum tube collector
Vitosol 300-T vacuum tube collectors are available in two types: 20 tube version, 30 tube version The tube shape gives the collector great stability and high impact resistence. Re-evacuation of the tubes is not necessary as the tubes have a permanent airtight seal. The vacuum in the glass tubes ensures optimum heat insulation. Convection losses between the glass tube and the absorber are almost completely eliminated. This enables the utilisation of even low radiation levels (diffused radiation). The performance of the collector does not drop off as significantly in cold weather as a flat plate collector. On average, approximately 30% to 50% higher annual solar energy gain than flat plate collectors can be expected. Built into each vacuum tube is a Sol-Titanium coated copper absorber. It is a highly selective surface that ensures high absorption of solar radiation and low emission of thermal radiation.
Condenser Double pipe heat exchanger
Technical Data Vitosol 300-T, 2m2/3m2 Model Gross Area
Absorber Area
Aperture Area
Dimensions
Weight
mm
m2
ft2
m2
ft2
m2
in
kg
lb
2m2
2.83
30.5
2.05
22
2.11 22.7 1419x 1996x 122
55¾x 78½x 4¾
45
99
3m2
4.24
45.6
3.07
33
3.17 34.1 2126x 1996x 122
83¾x 78½x 4¾
68
150
14
ft2
Please note: The angle of inclination must be at least 25º to guarantee circulation of the evaporator liquid inside the heat exchanger.
5167 156 v3.1
Evacuated glass tube Heat pipe Absorber
A heat pipe filled with an evaporator liquid is arranged on the absorber. The heat pipe is connected to the condenser via a flexible coupling. The condenser is mounted in a double pipe heat exchanger. This involves a so-called ”dry connection”, i.e. pipes can be rotated or replaced even when the installation is filled and under pressure. Heat is transferred from the absorber to the heat pipe. This lets the liquid evaporate. The vapour then rises to the condenser. The heat is transferred to the passing heat transfer medium by the double-pipe heat exchanger containing the condenser which causes the vapour to condense. The condensate flows back into the heat pipe and the process is repeated.
Specification
Construction and Function of Collectors
(continued)
Vitosol 300-T (continued) Absorber surface areas of up to 6 m2 can be joined to form a single collector array. For this purpose, the standard delivery includes flexible connection pipes, sealed with O-rings. A connection kit with clamping ring connections enables the collector array to be readily connected to the pipes of the solar circuit. The collector temperature sensor is installed in a sensor mounting on the flow pipe in the connection housing of the collectors.
102mm / 4” Legend
5167 156 v3.1
Groove for retaining clip
15
Specification
Collector Efficiency Some of the solar radiation striking the glass of the collectors is ”lost” due to reflection and absorption. The optical efficiency ηo takes these losses into account. When the collectors heat up, they transfer heat to the environment as the result of conduction, radiation and convection. These thermal losses are allowed for by the heat loss factors k1 and k2 .
The heat loss factors and optical efficiency combine to form the collector efficiency curve which can be calculated on the basis of the following formula:
η = η o − k 1 ⋅ ∆T − k2 ⋅ ∆T Eg Eg
2
Eg= radiation intensity (W/m2) ∆ T = Temperature difference between ambient air and collector fluid ºC
If the difference between the collector and ambient temperature is zero, the collector loses no heat to the environment, and the efficiency η is at its maximum level; this is known as the optical efficiency ηo. The thermal capacity is a measure of the thermal inertia of the collector, and shows the response behaviour of the collector when heating and cooling. A low thermal capacity is of advantage with wide ranging temparature and weather conditions typical in northerly climates. The table below lists comparative values for the optical efficiency and the heat loss factors as tested in European certification labs. Vitosol 200-F and 300-T are both tested and certified in North America to SRCC OG-100.
Collector type
Vitosol 200-F Vitosol 300-T *1
Opt. efficiency level *1 in i % ηo 79.3 82.5
Heat loss factors k1 in W/(m2 · K) 3.95 1.19
k2 in W/(m2 · K2) 0.0122 0.009
Spec. thermal capacity p y kJ/( 2 · K) kJ/(m 6.4 5.4
ηo based on absorber area
H
0.9 0.8 0.7 0.6 0.5 0.4 0.3
Efficiency
0.2
0
0 10 20 30 40 50 60 70 80 90 100 Temperature difference in degrees C between ambient air and collector fluid
Vitosol 300-T Vitosol 200-F
16
5167 156 v3.1
0.1
Specification
Solar Coverage The solar coverage value indicates what percentage of the energy required annually for domestic hot water applications can be covered by the solar heating system. The absorber surface area should be sized so that the ”production” of surplus heat is just about avoided during the summer months. The higher the solar cover rate, the lower the efficiency, since a high cover rate has the effect of raising the temperature level of the solar circuit. This results in increased heat losses and lower seasonal efficiency.
Absorber surface in m2
Vitosol 200-F
0
13
26
40
53
66
79
ltrs/day 106 USG/day
92
The diagrams show the coverage values that can be achieved with the various collector types, based on H the meteorological records for a typical location at 49° latitude, H south-facing roofs, H a roof pitch of 45º and H a DHW temperature of 113°F / 45ºC in the standby tank. This data represents approximate guide values.
DHW consumption Vitosol 300-T
Absorber surface in m2
USG/day
0
13
26
40
53
66
79
Note: Solar fractions will be higher for locations in southern parts of the USA due to higher levels of radiation.
ltrs/day 106 USG/day
92
DHW consumption
Influence of various parameters on solar coverage Reference system 100 litres/day
76
300 litres/day
52
400 litres/day
45
Collector inclination 30°
61 61
Collector inclination 60° 45
Westerly orientation South-west orientation
56
*1
Vacuum tubes Hannover
77 55
Freiburg
69 0
20
5167 156 v3.1
Solar cover rate in %
*1
Reference system:
62
40
60
H 4-person household with hot water
consumption of 53 USG/day / 200 litres/day H 2 Vitosol 200-F collectors, model SV2 and SH2 H 45º roof inclination H South-facing roof orientation H Dual-mode DHW cylinder, 300 litres H Meteorological records for a typical location at 49° latitude The bars indicate the expected coverage values for deviations from the reference system. 80
For comparable absorber surface area.
17
Specification
Collector Installation and Mounting Installation options for different collector types
Viessmann offers universal mounting systems to simplify installation. The mounting systems are suitable for virtually all forms of roofs, as well as installation on flat roofs or ground mounted free-standing installations.
Fitting
Collector type
Pitched roofs
A Vitosol 200-F, model SV2 Vitosol 300-T B Vitosol 200-F, model SH2
Flat roofs
C Vitosol 200-F, model SV2, SH2 Vitosol 300-T
Freestanding installation
D Vitosol 200-F, model SV2, SH2 Vitosol 300-T
Sloped roofs - rooftop installation Required roof area
A
mm
A
in
B
mm
B
Vitosol 200-F, type SV2
2380
93 3/4 1056 + 16*1
41 5/8 + 5/8*1
Vitosol 200-F, type SH2
1056
41 5/8 2380 + 16*1
93 3/4 + 5/8*1
Vitosol 300-T, type SP3, 2m2
2031
80
1418 + 102*1
55 3/4 + 4*1
Vitosol 300-T, type SP3, 3m2
2031
80
2127 + 102*1
83 3/4 + 4*1
*1
18
Add this value for every additional collector.
in
5167 156 v3.1
Collector Type
Specification
Collector Installation and Mounting
(continued)
Vitosol 200-F flat panel collector Flat collectors are ideally suited for domestic hot water and swimming pool heating applications.
Model SH2 has been specially designed for installation on flat roofs and for freestanding installation.
Both vertical and horizontal types are suitable for installation on pitched roofs. The selection of method of installation is influenced by the structural characteristics of the building.
Viessmann offers a universal fastening system to simplify installation. The fastening system is suitable for virtually all forms of roof and roofing.
Installation kits are available for installing collectors on flat roofs. An engineering evaluation is required to establish additional superimposed loads from wind or snow, as described in the local building code. Retain the services of a professional structural engineer to calculate additional live loads due to the installation of solar collectors on the roof.
Sloped Roofs Installation Details
a
b 40 10
c
5167 156 v3.1
Collector Lag bolt Mounting rail Roof bracket
Collector
Dimension
Model SV2
inches mm inches mm
Model SH2
a
b 93¾ 2 380 41¾ 1 138
c 74¾ - 82½ 1 900 - 2 100 19½ - 35½ 500 - 900
3½ 89 3½ 89
19
Specification
Collector Installation and Mounting
(continued)
Flat roof installation H Collectors secured against lifting
A collector system must be secured by additional weights against slippage and lifting (see table on the following page). Slippage is the movement of the collectors on the roof surface due to wind, because of insufficient friction between the roof surface and the collector system.
require less ballast weight, but additional attachment to the roof or building structure with wires, cables or other sufficient means. Min. 6 ft/ 2m
The collectors should be installed with an angle of inclination of 35º to 45º if the load capacity of the roof allows this. Maintain a minimum distance of 2m/6ft from the roof edge in all installations. Outside of this area you may experience significant increases in wind turbulance. The system will also be hard to access if modifications are required. If the roof size dictates a modification of the array distribution, ensure that arrays of the same size are created.
H Collectors secured against slippage
require more ballast weight, but no additional attachment to the roof or substructure.
Roof edge Min. 6 ft/ 2m Collector array
Determining the collector row distance “z” When installing several collector rows in sequence, exact dimensions (dimension “z”) must be maintained to prevent unwanted shade. Determine angle of the sun β.
This should be chosen so that the midday sun on Dec. 12 can fall onto the collector without creating shade. In North America, this angle is dependent upon latitude and is between 13º (Edmonton) and 41º (Miami).
Example Boston is located approx. 42.5º latitude. Angle of the sun β= 90º-23.5º-latitude (23.5º should be accepted as the constant) 90º-23.5º-42.5º = 24º l · sin (180 º - ( α+ β )) z = sin β Vitosol 200-F, type SV2
l
l
α
β
z =
z z l
α β
= Collector row distance = Collector height (see page 13 and 14)
= Collector angle of inclination = Angle of the sun
Collector row distance ”z” (all dimensions in mm) Vitosol 200-F Collector type
β = 24º (Boston)
2385mm sin (180 º - 69 º) 0 sin 24º
z = 5474mm
Vitosol 300-T
Type SV2 Angle of inclination α
Type SH2 Angle of inclination α
Angle of inclination α
Angle of sun β
35º
45º
35º
45º
35º
45º
55º
15.0º
7059
7880
3140
3550
5991
6772
7349
17.5º
6292
7035
2799
3130
5340
5970
6419
20.0º
5712
6320
2541
2812
4848
5363
5716
22.5º
5256
5758
2338
2561
4461
4886
5164
25.0º
4887
5303
2174
2359
4148
4500
4716
27.5º
4582
4926
2038
2191
3888
4180
4346
20
5167 156 v3.1
α
l = 2380mm α= 45º
Specification
Collector Installation and Mounting
(continued)
Vitosol 200-F flat panel collector (continued) Please refer to Vitosol 200-F Installation instructions for additional information on collector mounting on 5285 710.
IMPORTANT An evaluation by a professional structural engineer is required to calculate additional live loads due to the installation of solar collectors on a roof.
Vitosol 200-F, type SV2 and SH2 Collector angle of inclination - 25º or 45º Ballast to be applied and maximum load on the substructures of flat roofs to DIN 1055 Collector angle of inclination
25º
Installation height above ground m
45º
Ballast against slippage*1 Ballast against lifting*1 Ballast against slippage
Ballast against lifting
up to 8
up to 8
8 to 20
20 to 100
up to 8
8 to 20
20 to 100
up to 8
8 to 20
20 to 100
8 to 20
20 to 100
Ballast to be applied Type SV2
kg
315
554
793
144
304
465
508
842
1213
128
224
346
Type SH2
kg
323
561
800
155
315
476
492
845
1198
132
254
375
*1 See description on page 20. Collector supports The collector supports are pre-assembled. They consist of foot support A, bearing supports and adjustment pieces. The upper adjustment pieces contain holes for adjusting the angle of inclination. Connection cross ties are required for 1 to 6 collectors connected in a series.
Type SV2 Foot support hole dimensions 80
80
50
75
11
75
897
1795
1620
50
722
11
Type SH2 Foot support hole dimensions
100
5167 156 v3.1
A Foot support
100
A
21
Specification
Collector Installation and Mounting
(continued)
Vitosol 200-F A
Installation on substructures
A Connection cross ties
X Y
Z *1 X
*1 For calculating dimension “z”, see page 20 Installation with ballast
A
A Connection cross ties
X Y
Z *1
X
Collector type
x
SV2
590
23 1/4
481
19
SH2
1920
75 5/8
481
19
22
mm x
in y
mm y
in
5167 156 v3.1
*1 For calculating dimension “z”, see page 20
Specification
Collector Installation and Mounting
(continued)
Vitosol 300-T sloped roof installation details
230mm / 9” 340mm / 13.4”
1650mm / 65”
Deviations from south can be compensated by axial rotation of the vacuum tubes.
1600mm / 63”
Collector Roof bracket Roof joist Collector installation rail with tube mountings Roof sheathing complete with shingles Lag bolt
1419mm/55 3/4” 102mm / 4”
3m2 version
2126mm/83 3/4”
5167 156 v3.1
2m2 version
23
Specification
Collector Installation and Mounting
(continued)
Flat roof support weight requirements - Vitosol 300-T Collector angle of inclination of 25º Weight of supports
Installation height above ground
ft. m
Weight of supports lbs per support A kg per support A lbs per support B kg per support B
Secured against slippage*1 up to 26 26 to 66 up to 8 8 to 20 2m2 3m2 2m2 3m2 Version Version Version Version 168 256 284 430 76 116 129 195 225 102
342 155
392 178
593 269
Secured against lifting*1 up to 26 26 to 66 up to 8 8 to 20 2m2 3m2 2m2 3m2 Version Version Version Version 57 90 112 176 26 41 51 80 141 64
220 100
276 125
421 191
*1 See description on page 20. Support A Support B
B
A
Model
2m2 Version
3m2 Version
inches mm Dimension Y inches mm Surface area (X x Y) ft.2 m2 Weight of lbs collector kg
76¼ 1940 56¾ 1440 30 2.80 99 45
76¼ 1940 84½ 2149 44½ 4.15 150 68
5167 156 v3.1
Dimension X
24
Specification
Collector Installation and Mounting
(continued)
Flat roof support weight requirements - Vitosol 300-T (continued) Collector angle of inclination of 45º Weight of supports Secured against slippage ft. up to 26 26 to 66 8 to 20 m up to 8 2m2 3m2 2m2 3m2 Version Version Version Version 344 390 586 lbs per support A H 20 225 156 177 266 kg per support A 102 564 633 948 lbs per support B 377 256 287 430 kg per support B 171
Installation height above ground Weight of supports
Secured against lifting up to 26 26 to 66 up to 8 8 to 20 2m2 3m2 2m2 3m2 Version Version Version Version --------161 73
245 111
302 137
454 206
Support A Support B
B
A
Model
2m2 Version
3m2 Version
inches mm Dimension Y inches mm Surface area (X x Y) ft.2 m2 Weight of lbs collectors kg
60¼ 1530 56¾ 1440 24 2.20 99 45
60¼ 1530 84½ 2149 35 3.27 150 68
5167 156 v3.1
Dimension X
25
Specification
General Installation Instructions H Vitosol solar collectors are hailproof.
Nevertheless we recommend to include bad weather and hail damage coverage into your home owners insurance package. Our warranty does not cover such damages.
H Please observe local building code
guidelines for maximum load restrictions on the substructure and for necessary distance to roof edge.
H Make sure to remove snow off
collectors if more than 20” / 50 cm have accumulated.
H Mount collectors carefully, so that
even during storm and bad weather mounting clamps can absorb any tension.
H An access door or skylight should be
provided in the roof in the vicinity of the collectors to facilitate inspection and maintenance work.
H When there is a relatively large
distance between the collector panel and the roof ridge, a snow board must be installed above the collector panel in regions where heavy snowfalls can be expected.
H Filling the solar heating systems with
Viessmann “Tyfocor-HTL” heat transfer medium is highly recommended. Other heat transfer fluids may be suitable if they have the same temperature range (-35ºC / -31ºF to 170ºC / 338ºF) and are non-toxic.
H Use high temperature insulation
materials. In pump idle mode and with strong solar irradiation, collectors could reach an idle temperature of over 200ºC / 392ºF. Protect pipe insulation and sensor cables against attack by birds and animals.
H Grounding and lightning protection of
5167 156 v3.1
the solar heating system An electrically conductive connection of the pipework system of the solar circuit should be implemented in the lower part of the building in accordance with local regulations. Connection of the collector system to a new or existing lightning protection system or the provision of local grounding should only be carried out by a licensed professional, taking local conditions into account.
26
Notes on Planning and Operation
Calculating the Required Absorber Surface Area Calculating the absorber surface area and DHW tank capacity Absorber surface area Estimates based on meteorological conditions such as annual global radiation, cloud cover etc. are sufficiently accurate for practical purposes. In order to obtain a comprehensive summary of the solar coverage for domestic hot water heating, it is recommended that this estimate should form the basis of a calculation carried out using a solar computer simulation. Viessmann can provide design support and computer simulations upon request. Contact your local Viessmann sales representative. The cover rate determined by this program should be 50 to 60 % for relatively small systems (detached house), and at least 40 % for larger systems (apartment block). Guide values for estimating the required absorber surface area can be drawn from the table on page 30. The absorber surface area calculated on the basis of this table has proved to be accurate in practice.
The basis for designing a solar DHW heating system is the DHW daily demand. It can be estimated based on the following table: DHW Demand Vp litres/(d · person) For DHW temps temps. 45ºC 60ºC Residential properties*1 High demands Average demands Low demands
50 - 80 30- 50 15 - 30
35-56 21-35 11-21
DHW tank capacity (solar storage) The following values can be used as a basis for calculating the cylinder storage capacity: The total available solar DHW tank capacity (dual-coil tank or preheating tank) should be sized on the basis of 1.5 to 2 times the daily requirements. For fluctuating DHW demand use larger storage (daily demand x2). For relatively constant demand use value 1.5. The minimum solar storage tank volume should be based on 50 liter/m2/ 1.25gal/ft2 collector absorber area.
Typical Solar Storage and Collector Selection Daily DHW Demand @ 50ºC/120ºF
Solar Tank Capacity
Vitosol 200-F Flat Plate Collectors SH2/SV2
Vitosol 300-T Tube Collectors
2
120L 32 gal.
200L 53 gal.
1
1x2m2
3-4
180-240L 48-63 gal.
300L 79 gal.
2
1x3m2
5-6
300-360L 79-95 gal.
450L 120 gal.
3
1x2m2 + 1x3m2
5167 156 v3.1
# People in household
27
Notes on Planning and Operation
Calculating the Required Absorber Surface Area System for space heating backup - DHW cylinder and collector 100
A
75
E
25
B D C
A B C D E
Nov.
Dec.
Oct.
Aug.
Sep.
Jul.
Jun.
May
Mar. Apr.
Feb.
0 Jan.
Energy requirement or gain (%)
50
Space heating requirement for one house (typical construction) Space heating requirement for one low energy house Hot water requirement Solar energy yield at 5 m2 absorber surface (2 flat collectors) Solar energy yield at 15 m2 absorber surface (6 flat collectors)
For buildings with a higher energy demand the coverage drops lower. Use the Viessmann ESOP calculation program when making sizing calculations. Max. connectable collector area when using Vitocell tanks must follow the chart on page 31.
5167 156 v3.1
Concentrating exclusively on the central heating demand can lead to problematic oversizing of the system. For low energy houses (heat demand less than 50 kWh/(m2p.a.), solar coverage of 20 to 25% refers to the total energy demand, incl. provision for DHW heating.
The period when the greatest amount of solar energy is available does not coincide with the time when the most heat is required. While the heat consumption for DHW heating is relatively constant throughout the year, only very little solar energy is available at the times when the heat demand for central heating is at its highest (see diagram). A relatively large absorber area is required to provide central heating backup. In summer, this can result in stagnation in the solar circuit. Systems for heating backup require additional storage tanks and controls. The basis for sizing a solar heating system for central heating backup is the space heating demand of the building during spring, autumn and in winter, as well as the heating demand in summer (i.e. the demand for DHW heating). Heat demand in summer, e.g to avoid condensation in cellars, to use underfloor heating in bathrooms, increases the demand. For efficient operation of a solar central heating backup, the collector area should be 2 to 2.5 times larger than the DHW heat demand in summer requires. To avoid excessive summer time temperature stagnation avoid using collector areas greater than 3 times what would be used for DHW requirements only.
28
Notes on Planning and Operation
Calculating the Required Absorber Surface Area
(continued)
Swimming pool water heating system - heat exchanger and collector
A solar heating system in no way alters this typical temperature pattern. The solar application leads to a definite increase in the base temperature. Subject to the ratio between the pool surface and the collector area, a different temperature can be reached. The adjacent diagram shows with which ratio of aperture or absorber area to the pool surface what average temperature increase can be reached. This ratio is independent of the collector type used due to the comparably low collector temperatures and the operating period (summer). For this reason, unglazed collectors are most often used for outdoor pools.
Average pool temperature in 0C
Open-air swimming pools are mainly used between May and September [in northern USA]. The energy demand required depends mainly on the leakage rate, evaporation, loss (water must be replenished cold) and the transmission heat loss. Through using a cover, the evaporation and consequently the energy demand of the pool is reduced to a minimum. The largest energy input comes direct from the sun, which shines onto the pool surface. Therefore the pool has a ”natural” base temperature which can be shown in the adjacent diagram as an average pool temperature over the operating time.
Note Revising and maintaining the pool temperature at a higher base level using a conventional heating system does not alter this ratio. However, the pool will be heated up much more quickly. 25 20 15 10 5 0
Average temperature increases in degrees C/day
Open-air swimming pools
Jan Feb MarApr May Jun Jul Aug Sep Oct Nov Dec
Location Boston 40m2 Upper surface 1.5m deep protected position covered at night
8 7 6 5 4 3 2 1 0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 Ratio-absorber area to the pool surface (open-air swimmimg pool)
5167 156 v3.1
Indoor swimming pools Indoor swimming pools generally have a higher target temperature than open-air pools and are used throughout the year. If, over the course of the year, a constant pool temperature is required, indoor swimming pools must be heated in dual-mode. To avoid sizing errors, the energy demand of the pool must be measured. For this, suspend heating the water for 48 hours and determine the temperature at the beginning and end of the test period. The daily energy demand can therefore be calculated from the temperature difference and the capacity of the pool. For new builds, the heat demand of the swimming pool must be calculated.
On a summer day (clear skies), a collector system used to heat a swimming pool in northern USA produces energy of approx. 4.5kWh/m2 absorber area. Calculation example for Vitosol 200-F Pool surface: 36 m2 Average pool depth: 1.5m Pool capacity: 54m3 Temperature loss on 2 days: 2ºC Daily energy demand: 54m3⋅1K⋅1.16
kWh K m3
Collector area:
62.6 kWh
=13.9m2 4.5 kWh/m2
This corresponds to 6 collectors. For a first approximation (cost estimate), an average temperature loss of 1C/day can be used. With an average pool depth of 1.5m an energy demand of 1.74kWh/day is required to maintain the base temperature. It is therefore sensible to use approx. 0.4m2 absorber area per m2 of pool surface.
= 62.6kWh
29
Notes on Planning and Operation
Calculating the Required Absorber Surface Area
(continued)
Guide values for sizing solar heating systems (continued) H Absorber surface area (data based on meteorological records for a site at 49° latitude)
Application
Required absorber surface area A for coverage of
DHW heating Detached & semi-detached houses Multi-occupancy dwellings
60 % Vitosol 200-F
ft.2/person m2/person ft.2/person m2/person
40 up to 50 % Vitosol 200-F
Vitosol 300-T
13 - 16 1.2 - 1.5 8.6 - 11.8 0.8 - 1.1
8.6 - 10.8 0.8 - 1.0 6.5 - 8.6 0.6 - 0.8
10.8 - 13 1.0 - 1.2 6.5 - 8.6 0.6 - 0.8
Vitosol 300-T 6.5 0.6 4.3 0.4
-
8.6 0.8 6.5 0.6
Information regarding the DHW cylinder When sizing the solar heating system, observe the max. aperture area which may be connected to the different DHW cylinders. At a design output of 600W/m2 and a temperature difference between DHW temperature (at the height of the solar
DHW Tank
Capacity
heat exchanger, lower indirect coil) and solar circuit return (lower than 10ºC), the max. number of collectors mentioned in the table (values apply to all Viessmann collectors) should not be exceeded.
If a higher system temperature range is acceptable, then the number of collectors can be no more than doubled.
Max. connectable number of collectors Vitosol 200-F
Vitosol 300-T 2m2
Vitosol 300-T 3m2
300 L/79 gal.
4
5
3
Vitocell-B 100/300
450 L/120 gal.
7
7
5
Vitocell-V 100/300
200 L/53 gal. 300 L/79 gal. 450 L/120 gal.
3 4 7
4 5 7
3 3 5
5167 156 v3.1
Vitocell-B 100/300
30
Notes on Planning and Operation
Sizing Pipe Diameters and Circulation Pump Solar heating system operating modes
Volume flow in the collector array Generally, very low flow rates are required for Vitosol collectors. This results in small pipe and pump requirements. There are different operating modes, which depend on the total area of collectors installed, and piping requirements. At the same irradiation level, and consequently the same collector output, a higher flow rate means a lower temperature spread in the collector circuit; a lower flow rate means a higher temperature spread. With a high temperature spread, the average collector temperature increases, i.e the operating efficiency of the collector drops accordingly. Therefore, with lower flow rates the use of electrical energy (pump size) reduces and a smaller size connection pipe is possible. To safeguard a safe flow rate and a turbulent flow, Vitosol flat-plate collectors require a flow rate of at least 15 liters/(h.m2). Vitosol tube collectors require at least 25 liters/(h.m2). Generally, when setting the collector volume flow, the necessary volume flow of the connected heat exchanger should also be taken into account. 1. High-flow mode For solar heating systems up to 270º ft.2 / 25 m2 absorber surface area, we recommend the high flow operation. This reduces the temperature spread between supply and return. The higher flow rate requires a slightly larger pipework size, and larger pump sizes.
H A smaller pump capacity is required
resulting in lower electrical consumption.
In the low-flow operating mode, the pipes can be sized on the basis of a flowrate of H Vitosol 200-F: approx. 15 liters/h per m2 absorber surface area (approx. 0.07 gpm/m2 absorber surface area). H Vitosol 300-T: approx. 25 litrers/h per
m2 absorbed surface area (approx. 0.11gpm/m2 absorber surface area).
With both collector models, a uniform flow rate through all collectors is guaranteed if the Viessmann piping layout drawings are followed. To reduce the amount of installation work required for the piping, it is advisable to connect two rows of collectors with all piping connections on one side of the array. Pipe installation information To minimise the pressure drop through the piping of the solar heating systems, the flow velocity in the copper pipe should not exceed 3.5ft/s. We recommend flow velocities between 1.3 and 2.3ft/s. At these flow velocities, pressure drops of between 1 and 2.5 mbar/m pipe length occur.
IMPORTANT Do not use galvanized pipes, galvanized fittings or graphitised gaskets. Hemp should be used only in conjunction with pressure and temperature-resistant sealant.
IMPORTANT The components used must be resistant to the heat transfer medium (for composition, see the datasheet for the specific collector).
IMPORTANT The thermal insulation of external piping must be resistant to temperature, UV radiation and to attack by birds or animals. Insulate internal ”hot” pipework according to current practice (fire protection, touch protection), e.g. using high-temperature resistant insulation, as offered by Armacell.
For the installation of the collectors, we recommend the use of commercial copper pipe and red bronze fittings or stainless steel pipe. The cross-sections should be sized as for a conventional heating system on the basis of flow rate and velocity (see the tables below).
5167 156 v3.1
In the high-flow operating mode, the pipes can be sized on the basis of a flowrate of H Vitosol 200-F: approx. 40 liters/h per m2 absorber surface area (approx. 0.18 gpm/m2 absorber surface area). H Vitosol 300-T: 60 liters/h per m2 absorber surface area (0.27 gpm/m2 absorber surface area). 2. Low-flow mode For large solar installations (larger than 270 ft.2 / 25 m2 absorber surface area), low flow mode operation can be used.. Advantages of the low-flow mode: H A high temperature level is reached quickly in the collector circuit. H The low flow rate in the collector circuit means that much smaller pipe sizes are required. 31
Notes on Planning and Operation
Sizing Pipe Diameters and Circulation Pump
(continued)
Sizing pipe diameters (continued) Vitosol 200-F (high-flow operating mode), 40 liters/(h.m2) or 0.18gpm/m2 Number of collectors Model SV2 and SH2 Volume flow gpm liters/min Flow velocity ft./s m/s Pressure drop in the ft. of pipework head/ft. mbar/m
2
3
4
0.8 3.1
1.2 4.6
1.6 6.2
5 2.1 7.8 1.3 to 2.3 0.4 to 0.7
6
8
10
12
2.5 9.3
3.3 12.4
4.1 15.5
4.9 18.6
0.11 to 0.27 1.0 to 2.5
Vitosol 300-T (high-flow operating mode), 60 liters/(h.m2) or 0.3gpm/m2 Absorber surface area
m2
Volume flow
gpm liters/min ft./s m/s ft. of head/ft. mbar/m
Flow velocity Pressure drop in the pipework
2
3
4
5
0.53 2
0.8 3
1.1 4
1.3 5
6
8
10
12
15
2.1 8
2.6 10
3.2 12
4.0 15
6
8
10
12
0.8 0.92 2.9 3.5 0.7 to 1.3 0.2 to 0.4
1.25 4.7
1.53 5.8
1.85 7.0
1.6 6 1.3 to 2.3 0.4 to 0.7 0.11 to 0.27 1.0 to 2.5
Vitosol 200-F (low-flow operating mode), 15 liters/(h.m2) or 0.07gpm/m2 Number of collectors Model SV2 and SH2 gpm Volume flow liters/min Flow velocity ft./s m/s
2
3
4
0.3 1.2
0.5 1.8
0.6 2.3
5
Pressure drop in the ft. of pipework head/ft. mbar/m
0.11 to 0.27 1.0 to 2.5
Vitosol 300-T (low-flow operating mode), 25 liters/(h.m2) or 0.11gpm/m2 Absorber surface area
m2
Volume flow
gpm liters/min ft./s m/s ft. of head/ft. mbar/m
Flow velocity
3
4
5
0.21 0.8
0.3 1.2
0.45 1.7
0.6 2.1
6 0.7 2.5 0.7 to 1.3 0.2 to 0.4
8
10
12
15
0.9 3.3
1.1 4.2
1.3 5.0
1.64 6.2
0.11 to 0.27 1.0 to 2.5 5167 156 v3.1
Pressure drop in the pipework
2
32
Notes on Planning and Operation
Sizing Pipe Diameters and Circulation Pump
(continued)
Installation examples (hydraulic connection) Vitosol 200-F, type SV2/SH2 High -flow operation Installation of collectors, connection on alternate sides, max. 12 collectors. Ø 28x1 C
Installation of collectors, single-sided connection, max. 10 collectors. C
A
Ø 28x1
A max. 12
max. 10
B
B
Ø 28x1
Ø 28x1
Supply (hot) Return Air vent valve (shut-off type)
Low-flow operation Installation of collectors, connection on alternate sides, max. 10 collectors. Ø 18x1 C
Installation of collectors, single-sided connection, max. 8 collectors. C
max. 10 B
A
Ø 18x1
A max. 8
B
Ø 18x1
Ø 18x1
Supply (hot) Return Air vent valve (shut-off type)
Vitosol 300-T, type SP3 Installation on pitched roofs (max. 6 per array) Connection from the left (preferred option) C A B
Connection from the right C A B
Ø 18x1
Ø 18x1
5167 156 v3.1
Supply (hot) Return Air vent valve (shut-off type)
33
Notes on Planning and Operation
Sizing Pipe Diameters and Circulation Pump
(continued)
Collector pressure drop information (relative to water, approx. 30% higher for Tyfocor HTL @ 40ºC)
” w.c. mbar 800 2000
1000
200 160
500 400
120
300
80
200
40
20
100
50 40
12
30 0.5
80
200
40
100
32
80
24 20 16
60 50 40
12
30
8
20
4
10
3.2
8
2.4 2
6 5
1.6
4
1.2
3
0.8
2
Pressure drop
Pressure drop
400
1 0.3
2 3 4 5 l/min 0.5 0.8 1.11.3 gpm Waterflow
mbar
Vitosol 300-T vacuum tube collector “ w.c.
Vitosol 200-F, flat plate collector model SV2 and SH2
1 1 0.3
2
3
4
5
6
0.5 0.8 1.1 1.3 1.6
10
ltr/h
2.6
GPM
Waterflow
1 1 2 1 2
34
2m2 3m2 model 2m2 model 2m2 and 1 x model 3m2 model 3m2
For calculation of total pressure drop
H Collectors connected in series:
Total pressure drop = sum of the individual resistance values H Collectors connected in parallel: Total pressure drop = individual pressure drop (assuming all individual resistance values are equal). 5167 156 v3.1
Calculating pressure drop The total pressure drop of the solar heating system consists of: H collector resistance values, H pipe resistance values, H individual resistance values of the fittings and H individual resistance values of the fittings and H resistance values of the heat exchanger in the DHW tank.
x x x x x
Notes on Planning and Operation
Sizing Pipe Diameters and Circulation Pump
(continued)
Sizing the circulation pump If the flowrate and pressure drop of the entire system are known, the pump is selected on the basis of the pump characteristics. Variable-speed pumps which can be matched to the system by switching are the most suitable. To simplify the installation and selection of the pumps and safety equipment, Viessmann supplies the Solar-Divicon. The Solar-Divicon comprises H pre-assembled and sealed valves and safety assembly, H flow regulating valve with meter to control the solar heating system during commissioning and operation, H flow check valves, H system pump (2 sizes available), H pressure gage, H 2 thermometers, H 2 isolation valves, H pressure relief valve, 87 psig / 6 bar.
Two models of Solar-Divicon are available: Model DN 20 H up to 12 Vitosol 200-F collectors H up to 20 m2 absorber surface area with Vitosol 300-T, Model DN 25 H up to 18 Vitosol 200-F collectors H up to 30 m2 absorber surface area with Vitosol 300-T. Final determination of which Solar-Divicon model to use must be based on system layout and pipe sizes used.
IMPORTANT The Solar-Divicon and the solar pump line are not suitable for direct contact with swimming pool water or potable water.
IMPORTANT Always install Solar-Divicon at a lower height than the collectors to prevent steam from entering the expansion vessel in the event of stagnation.
IMPORTANT For systems which are installed in the roof space or involve short pipe lengths, a preliminary vessel should be provided if necessary.
1 2 3 4 5 6 7 8 9
Pressure relief valve, 87 psig/6 bar Expansion tank connection Pressure gage, 0-6 bar/0-87 psig Temperature gage c/w integrated shut-off valves and flow check valves Pump Flow meter Insulation door Flush and fill manifold Air separator (locked under insulation)
VL Flow RL Return Shut-off valve Thermometer Non-return valve Solar circuit circulation pump Flow rate indicator
A B C
5167 156 v3.1
D A E VL
RL
The solar circuit pump line is constructed as the pump line of the Solar-Divicon. 35
Notes on Planning and Operation
Sizing Pipe Diameters and Circulation Pump
(continued)
Technical information on the Solar-Divicon
Solar-Divicon
Model
Circulation pump (Model: Wilo) Rated voltage
V
Maximum delivery
GPM
Maximum head
ft.
Flow meter (setting range)
USG/min
DN 20
DN 25
STAR S 16 U 15
STAR S 21 U 25
AC 115
AC 115
16
16.7
20.7
21.1
0.5 to 5
1 to 10
1 to 20
5 to 40
87 6 248 120
87 6 248 120
Flow meter (setting range)
ltrs/min
Pressure relief valve
psig, bar
Maximum operating temperature
°F, °C
Maximum operating pressure
psig, bar
87 6
87 6
inches mm inches mm inches mm
1/2
3/ 4
Connections (Compression fittings Ø): Solar circuit Solar expansion tank Safety relief valve
22 3/ 4 22 3/ 4 22
22
3/ 4
22
3/ 4
22
Characteristics
Pump model DN 25
5167 156 v3.1
Pump model DN 20
36
Notes on Planning and Operation
Safety Equipment Liquid capacity of solar heating system components USG liters USG liters USG liters USG liters
0.48 1.83 0.65 2.48 0.32 1.20 0.47 1.80
Solar-Divicon (pumping station for the collector circuit)
USG liters
0.08 0.30
Vitocell-B 100
USG liters
79 300
120 450
Heating water capacity of bottom coil
USG liters
2.6 10
3.3 12.5
Vitocell-B 300
USG liters
79 300
79 300
Heating water capacity of bottom coil
USG liters
2.9 11
3.9 15
Vitocell-V 300, Tank capacity (with indirect coil/s) Heating water capacity of coil
USG liters USG liters
Vitosol 200-F,
model SV2
Vitosol 200-F,
model SH2
Vitosol 300-T,
model 2m2 model 3m2
Tank capacity
Dimension USG/ft. pipe
53 200 3.2 11.9
79 300 2.9 11
120 450 4 15
3/ ” 8
½”
¾”
1”
1¼”
1½”
0.0083
0.013
0.027
0.045
0.068
0.095
5167 156 v3.1
Copper pipe, type M Water content
Tank capacity
37
Notes on Planning and Operation
Safety Equipment h Static height T
A
h DHW
B C
D G
Information regarding stagnation System idle periods, e.g. due to defects or incorrect operation, can never be ruled out. For this reason solar heating systems must be protected according to the current technical standards against the potential difficulties which may arise from idle periods, i.e. systems cannot be damaged or cause damage if idle periods occur. Collectors and connection pipes are designed for the maximum expected temperatures in case of stagnation. Temperatures over 170ºC / 338ºF have a detrimental effect on the process medium. When designing the collector array it should be ensured that the system can “breathe” properly (e.g. do not route solar pipes above the collector array).
VL RL E
T F
KW
Collector Safety valve Solar-Divicon Pre-cooling vessel (see below) Diaphragm expansion vessel Dual-mode DHW cylinder High limit safety cut-out (see page 41)
Information regarding the heat transfer medium Heat transfer media containing glycol can be damaged, if they are subjected for long periods of temperatures above 170ºC / 338ºF. This can lead to the system suffering from sludge and hard deposits, particularly in conjunction with other contaminants (flux and oxidized deposits). Therefore, after completing the installation, thoroughly flush out the system. After filling the system with process medium, ensure that heat is transferred inside the system, i.e. that
longer periods of stagnation are prevented. System must be air-tight as glycol deterioration is always worse in presence of O2 molecules. Check the glycol every 2 years. Information regarding pre-cooling vessels Pre-cooling vessels or stratification cylinders in solar heating systems protect the diaphragm expansion vessel from over heating if stagnation occurs. The installation of such vessels is recommended if the content of the pipework between the collector array Content litres
and the expansion vessel is lower than 50% of the capacity of the correctly sized expansion vessel. The reference value is the total volume which evaporates in idle conditions. Sizing: Capacity of the correctly sized expansion vessel less the content of the return line between the collector array and the expansion vessel. Determining the capacity of the pre-cooling vessel: 1.5 x collector content x number of collectors.
Number of collectors Vitosol SV2 Vitosol SH2 Vitosol 300-T 2m2 Vitosol 300-T 3m2
12 38
4
3
6
4
5167 156 v3.1
RL Return VL Flow
The solar heating system must be protected in respect to temperature, pressure and discharge of liquid in accordance with local regulations. The collector circuit must be protected in such a way that at the highest possible collector temperature (= idle temperature) no heat transfer medium can escape from the safety valve. This is achieved through the appropriate sizing of the expansion vessel and matching of the system pressure. For total pipework lengths shorter than 10m/32ft, we recommend the installation of a pre-cooling vessel and diaphragm expansion vessel into the hot supply pipe and only the pressure relief valve into the return pipe.
Notes on Planning and Operation
Safety Equipment
(continued)
Diaphragm expansion tank
A
B Delivered condition (3 bar/45 psig pressure)
A
A
D
E
C
C
Solar heating system filled without heat effect
Process medium Nitrogen filling
Under max. pressure at the highest process medium temperature
Nitrogen buffer Safety water seal, min. 3l/0.8gal
Specification - Viessmann expansion tank A B Øa Øa
Construction and operation A diaphragm expansion tank is a sealed expansion vessel whose gas space (nitrogen filling) is separated from the liquid space (heat transfer medium) by a diaphragm and whose inlet pressure is subject to the system height. To safely prevent steam being created during the operating stage, collectors must indicate a pressure of at least 15 psig / 1 bar in their cold state. The expansion tank inlet pressure is then higher by an amount of 0.45 psig x static height (h) in ft. or 0.1 bar x static height (h) in m. In hot conditions, the system pressure rises by approx. 15 to 30 psig/1 to 2 bar. Maximum idle temperature of collectors: Vitosol 200-F, Models SV2, SH2 Flat panel solar collector with 25 ft.2 / 2.3 m2 collector area. Max. shutdown temperature 430°F / 221°C Max. operating pressure 87 psig /6 bar
b
Vitosol 300-T, SP3 Series Vacuum tube solar collector with 22 and 32 ft.2 / 2 and 3 m2 collector area. Max. shutdown temperature 302°F / 150 °C Max. operating pressure 87 psig /6 bar
b
To ensure that no heat transfer medium can escape from the pressure relief valve, the expansion tank must be sufficiently large to accommodate the liquid content of the collector when steam forms (stagnation).
IMPORTANT Expansion tank
Content litres
A
18 25 40 50 80
5167 156 v3.1
B
Operating pressure bar 10 10 10 10 10
Øa mm
b mm
Connection Weight R kg
280 280 354 409 480
370 490 520 505 566
¾” ¾” ¾” 1” 1 1”
7.5 9.1 9.9 12.3 18.4
The cold fill inlet pressure (gas space) must be adjusted on site as follows: 15 psig + 0.45 psig x static height in ft 1 bar + 0.1 bar x static height in m The system operating pressure must be 4.5 to 7.5 psig/0.3 to 0.5 bar higher than the inlet pressure of the diaphragm expansion tank. The waterseal should be 0.005x the total liquid content of the system but not less than 3 liters.
39
Notes on Planning and Operation
Safety Equipment
(continued)
Technical data for the expansion tank (continued)
(V v + V 2 + z ⋅ V k) ⋅ (p e + 1) VN = pe − p st
Whereby VN = nominal capacity of the diaphragm expansion tank in liters Vv = safety water seal (here heat transfer medium) in litres Vv = 0.005 · VA in litres (min. 3 litres) VA = liquid capacity of the entire system (see page 42). pst = nitrogen inlet pressure of expansion vessel in bar pst =1 bar + 0.1 · h h =static head of the system in m (see drawing on page NO TAG) z = number of collectors Vk = collector capacity in litres (see page 37). V2 = volume increase when the system heats up V2 =
VA · β
=expansion quotient ( β= 0.13 for Viessmann heat transfer medium from –20 to 120ºC) pe = permissible end pressure in bar pe =psi – 0.1 · psi psi =safety valve blow off pressure b
WARNING Do not use expansion tanks that are not designed for solar heating systems. Temperatures during stagnation periods can reach extremely high levels, which could result in serious injuries from hot system fluid discharging from pressure relief valve.
WARNING Do not undersize expansion tank.
40
Calculation example Solar heating system with: 2 Vitosol 200-F, type SV2 @ 1.83 litres Liquid capacity: VA = 25 litres Static head: h = 5 m Permissible final pressure: pe = 5.4 bar (ü) (Safety valve blow off pressure: 6 bar) VN =
(V v + V 2 + z ⋅ V k) ⋅ (p e + 1) p e − p st
Vv =VA · 0.005 Vv =0.125 litres, selected 3 litres (see previoys page). V2 =VA · b V2 =3.25 litres pst =1.5 bar + 0.1 bar/m · 5 m pst =2.0 bar VN =
(3 + 3.25 + 2 ⋅ 1.83) ⋅ (5.4 + 1) 5.4 − 1.5
VN =16.3 litres Due to the possibility of steam collecting in the solar circuit pipe, we recommend multiplying the calculated value VN by a safety factor of 1.5. Select a 25 liter expansion vessel.
Selection table for expansion tanks, subject to collector model (in conjunction with a 6 bar safety valve) These details provide only guide values; a final calculation must be carried out. Vitosol 200-F, model SV2 Number of System Static collectors capacity head VA h (m) liters 2 20 5 10 3 25 5 10 4 32 5 10 5 35 5 10 Vitosol 200-F, model SH2 Number of System Static collectors capacity head VA h m liters 2 20 5 10 3 30 5 10 4 35 5 10 5 40 5 10 Vitosol 300-T Absorber System surface capacity area VA m2 liters 3 16 4
18
5
23
6
25
9
35
Static head h (m) 5 10 5 10 5 10 5 10 5 10
Expansion tank capacity liters 25 25 40 40 40 50
Expansion tank capacity liters 25 40 40 40 50 50 80
Expansion tank capacity liters 18 18 18 25 25 40
5167 156 v3.1
The nominal capacity of the expansion vessel is calculated according to the equation
Notes on Planning and Operation
Safety Equipment
(continued)
Pressure relief valve The operating pressure of the pressure relief valve is the maximum system pressure +10 %. The pressure relief valve must comply with all local codes. The pressure relief valve must be matched to the output of the collector or the collector assembly and be able to handle their maximum output of 900w/m2.
IMPORTANT When use is made of water containing antifreeze or synthetic heat transfer media which are miscible with water (e.g. Viessmann heat transfer medium) and whose boiling point is higher than that of water, the blow off and discharge pipes must be run to an open container capable of accommodating the total capacity of the collectors. Use only pressure relief valves designed for a maximum of 87 psig / 6 bar and 248ºF / 120ºC bearing the markings ”S” (solar) as part of the product identification.
IMPORTANT Solar-Divicon is equipped with a pressure relief valve for max. 87 psig / 6 bar and 248ºF / 120ºC. High limit safety cut-out The Vitosolic 200 solar control unit is equipped with an electronic limit thermostat which is preset in the factory to 167ºF / 75ºC and can be adjusted. For systems with a sufficiently large DHW capacity, this protection is adequate, as the maximum operating temperature does not exceed 23ºF / 11ºC.
Example: Vitosol 200-F flat collector x 4=, approx. 7 m2 absorber surface area DHW cylinder with 300 litres capacity 300 = 40 litres/m2, 7.5
e.g. no high limit safety cut-out required.
5167 156 v3.1
An additional mechanical high limit safety cut-out is required, if the DHW tank capacity is less than 40 liters/m2 collector surface area.
41
Notes on Planning and Operation
Safety Equipment
(continued)
Thermostatic mixing valve Solar storage tank Thermostatic anti-scald mixing valve
DHW
A thermostatic mixing valve is required for all solar systems to prevent domestic hot water temperatures higher than 140 ºF / 60 ºC (local codes may require different temperature settings). Install an anti-scald mixing valve designed for potable domestic hot water systems.
DCW
WARNING
5167 156 v3.1
The domestic hot water temperature must be limited to 140 °F / 60 °C by installing a mixing device, e.g. a thermostatic anti-scald mixing valve.
42
Notes on Planning and Operation
Accessories
22
Solar manual filling pump
R ½”
38
.
22
R1”
approx. 166
Quick-acting air-vent valve (with tee)
Threaded elbow
160 (220) 65
15 220
290 40
For installation at the highest point of the system. With shut-off valve and locking ring connection.
Flexible connection pipe
22
For the installation of the DHW tank temperature sensor into the tank return. Comes as standard equipment with Vitocell-B 100 tanks and is an accessory with Vitocell-B 300 tanks.
For replenishing and raising the pressure.
1000
approx. 225
22
22
Air separator Stainless steel corrugated pipe with thermal insulation and compression fitting connection. Comes with thermal insulation. Set of 2 per package.
111
5167 156 v3.1
For installation in the supply pipe of the solar circuit, preferably upstream of the inlet to the DHW tank. With automatic air-vent valve, shut-off valve and locking ring connection. This is not required if a Solar Divicon model DN 20 or DN 25 is used.
43
System Designs
General Information For our climatic zone: dual systems In our climatic zone, solar radiation is insufficient to cover the entire requirements for domestic hot water or swimming pool heating as well as space heating by means of solar energy. Therefore, a solar heating system for DHW or swimming pool water heating and/or central heating should always be combined with another heat generator. In dual systems, for example, an oil or gas-fired boiler supplies the additional heat required. How to implement the installation
WARNING With temperatures over 140°F / 60°C, the DHW temperature must be limited to 140°F / 60°C by installing a mixing device, e.g. a thermostatic mixing valve (DHW tank accessory).
Over the following pages, we have described methods of operation and used design suggestions to illustrate various installation ideas involving different equipment specifications. A summary is provided which lists essential control equipment. The temperatures stated are guide values; other values may be set to meet particular requirements. The circulation pumps referred to in these examples (standard delivery with Solar-Divicon) are AC pumps. DHW tank backup by the boiler is suppressed by the Vitosolic, when the anticipated heat requirement for DHW heating is expected to be covered by the solar heating system. This may require the use of the optional expansion boards. When connection between the Vitosolic and the boiler control (Vitodens programming unit, Vitotronic 300 or Dekamatik) is made via the KM-BUS, the setpoint temperature for boiler backup of DHW is reduced, stopping the boiler from coming on. Abbreviations used in the examples: Domestic cold water Domestic hot water Return Supply
5167 156 v3.1
DCW DHW R S
44
System Designs
System Design 1 Dual-mode DHW heating with Vitocell-B100 or Vitocell-B 300 DHW tanks - with Vitosolic 200 or GL 30 control DHW heating without solar energy
DHW heating with solar energy
The top part of the DHW tank is heated by the boiler. The DHW tank temperature sensor of the boiler control unit switches tank heating circulation pump .
When a temperature difference higher is than the value set in control unit measured between collector temperature sensor and tank temperature sensor , solar circuit circulation pump is switched ON and the DHW tank is heated up. The temperature in the DHW tank is limited by the electronic limit or by thermostat in control unit high limit safety cut-out (if required).
When the preset temperature is exceeded, these devices switch OFF . The solar circuit circulation pump electronic temperature limit is set at the factory.
Installation diagram 2
A
1
B
DHW C
4 D 28 E
F
S
5 5
R
6
21
7
3
5167 156 v3.1
G
Solar collector Solar-Divicon Taps *1
DCW
H
DHW circulation DHW circulation output of the boiler control unit or timer installed on site
Heating circuit Oil/gas-fired boiler DHW cylinder
High limit safety cut-out, see page 41.
45
System Designs
System Design 1
(continued)
Dual-mode DHW heating with Vitocell-B100 or Vitocell-B 300 DHW tanks - with Vitosolic 200 or GL 30 control (continued) Control equipment required Number Part no.
2
Description Control of DHW cylinder loading by solar energy Vitosolic 200 or GL 30 control Collector temperature sensor
3
DHW tank temperature sensor*1
1
4
Solar circuit circulation pump (standard equipment of Solar-Divicon, see page 35)
1
5
1
6
High limit safety cut-out (see page 41)*2 Control of DHW tank loading by the boiler DHW tank temperature sensor
7
Circulation pump for DHW tank loading
1
Item 1
*1Installation requires a threaded *2Accessory with Vitodens.
1 1
1
7134 552 7134 450 Included in standard equipment for item 1 Included in standard equipment for item 1 7133 454 or 7133 455 Supplied on site Included in standard equipment of boiler control unit *2 DHW tank accessory
elbow (standard delivery for Vitocell-B 100, accessory for Vitocell-B 300 ).
WARNING
5167 156 v3.1
The domestic hot water temperature must be limited to 140 °F / 60 °C by installing a mixing device, e.g. a thermostatic anti-scald mixing valve.
46
System Designs
System Design 2 Dual-mode DHW heating and space heating backup with heating water storage tank - with Vitosolic 200 DHW heating without solar energy
Space heating without solar energy
Space heating with solar energy
The upper indirect coil of the DHW tank is heated by a boiler. The DHW tank temperature sensor of the boiler control unit switches circulation pump to heat up the DHW tank.
Diverter valve remains at zero volts (setting ”AB-B”), if the differential temperature between heating water storage tank temperature sensor (discharge) and space heating return temperature sensor falls below the value set at control unit . No flow through the heating water storage tank takes place. The boiler provides heat to the heating circuit according to the heating curve set at the boiler control unit.
Heating water storage tank circuit and circulation circulation pump pump for storage tank heating are switched ON and the heating water storage tank is heated up, when a temperature difference higher than the differential temperature preset in control unit is measured between collector temperature sensor and storage tank temperature sensor . The temperature inside (re-loading) the heating water storage tank will be limited by the electronic limit thermostat in control unit . When the preset temperature is exceeded, this device switches the storage tank circuit circulation pump and OFF. Circulation pump is switched OFF for approx. 2 minutes, roughly every 15 minutes (adjustable time), to check whether the temperature at the collector temperature sensor is high enough to change over to DHW tank loading.
DHW heating with solar energy Solar circuit circulation pump is switched ON and the DHW is heated up, when a temperature difference higher than the value set in control unit is measured between collector temperature sensor and DHW temperature sensor . The temperature in the DHW is limited by the electronic limit thermostat in or by high limit safety control unit cut-out (if required). When the preset temperature is exceeded, these devices switch OFF . solar circuit circulation pump The electronic temperature limit is set at the factory.
5167 156 v3.1
Control unit switches diverter valve to position ”AB-A” and the space heating return water will be channelled into the boiler via the storage tank, if the temperature differential between storage tank temperature sensor (discharge) and space heating return temperature sensor exceeds that set at control unit . If the temperature of the pre-heated return water is insufficient, the boiler re-heats the water to the necessary flow temperature level.
47
System Designs
System Design 2
(continued)
Installation diagram 2
Refer to Viessmann sample layout drawing #5 for alternate layout. (contact Viessmann sales rep. for details)
A
B
C
1
4 qE
DHW D
S
R
5 5
6 qP 21
9
qT
7
AB
qR A
B
3 G
qW
Solar collector Solar-Divicon Solar pump line Taps
*1High
48
limit safety cut-out, see page 41.
H
K
DHW circulation DHW circulation output of the boiler control unit or timer installed on site
DCW
Heating water storage tank Oil/gas-fired boiler DHW tank 5167 156 v3.1
qQ
System Designs
System Design 2
(continued)
Dual-mode DHW heating and space heating backup with heating water storage tank - with Vitosolic 200 (continued) Control equipment required Number
Part no.
1 2
Description Control of DHW tank loading by solar energy Vitosolic 200 Collector temperature sensor
1 1
3
DHW tank temperature sensor*1
1
4
Solar circuit circulation pump (standard equipment of Solar-Divicon, see page 35)
1
5 8
1 1
6
High limit safety cut-out (see also page 41) Circulation pump (relayering) Control of DHW tank loading by the boiler DHW tank temperature sensor
7134 450 Included in standard equipment for item 1 Included in standard equipment for item 1 7133 454 or 7133 455 Supplied on site Supplied on site
7
Circulation pump for DHW tank loading
1
9 qP qQ
Space heating control with solar energy Return temperature sensor (heating circuit) Temperature sensor (storage tank), discharge Temperature sensor (storage tank, re-loading)
1 1 1
Item
qW qE qR qT *1A
Three-way diverter valve Solar circuit circulation pump for storage tank heating (part of the solar pump line, see page 35) Circulation pump for storage tank heating Heat exchanger
1
Included in standard equipment of the boiler control unit DHW tank accessory
1 1
7170 965 7170 965 Included in standard equipment for item 1 Supplied on site Supplied on site
1 1
Supplied on site Supplied on site
threaded elbow (standard delivery for Vitocell-B 100, accessory for Vitocell-B 300 ) is recommended for this installation.
Note: , circulation pump for storage tank and heat exchanger Heating water storage tank indirect-fired storage tank, c/w internal heat exchanger coil (e.g. Vitocell-V 100).
can all be replaced with an
WARNING
5167 156 v3.1
The domestic hot water temperature must be limited to 140 °F / 60 °C by installing a mixing device, e.g. a thermostatic anti-scald mixing valve.
49
System Designs
System Design 3 Dual-mode DHW heating with two DHW tanks - with Vitosolic 200 DHW heating without solar energy
DHW heating with solar energy
DHW tank 2 is heated by the boiler. The DHW tank thermostat with connected tank temperature sensor of the boiler control unit switches circulation to heat up the DHW tank. pump
is Solar circuit circulation pump switched ON and DHW tank 1 is heated up, when a temperature difference higher than the value set in control unit is measured between collector temperature sensor and tank temperature sensor . The temperature in DHW tank 1 is limited by the electronic limit or by thermostat in control unit high limit safety cut-out (if required). When the preset temperature is exceeded, this device switches OFF solar circuit circulation pump . The electronic temperature limit is set at the factory.
DHW circulation pump 8b (if installed) is switched ON and circulation pump 8a is switched OFF, so that the DHW circulation only affects DHW tank .
Circulation pump 8a is switched ON, when the temperature at sensor in DHW tank 1 exceeds that at sensor in DHW tank 2. The DHW circulation covers both DHW tanks. This feeds the water heated in DHW tank 1 into DHW tank 2. This way, DHW tank 2 is also heated by solar energy. DHW circulation pump 8b (if installed) for DHW tank 2 is controlled by the boiler control unit. Circulation pump 8a will be switched OFF if the temperature in DHW tank 2 rises above that in DHW tank 1.
WARNING
5167 156 v3.1
The domestic hot water temperature must be limited to 140 °F / 60 °C by installing a mixing device, e.g. a thermostatic anti-scald mixing valve.
50
System Designs
System Design 3
(continued)
Installation diagram (system with two DHW cylinders with indirect coils) 2
A
B
1
4
C
8a
D E 28 8b
F 5
S
5
R
DHW 21
DCW
2
qP 6
1
9
3
7 G
5167 156 v3.1
Solar collector Solar-Divicon Taps DHW circulation
*1High
H
DCW
K
DHW circulation output of the boiler control unit or timer installed on site Heating circuit
Oil/gas-fired boiler DHW tank 2 DHW tank 1
limit safety cut-out, see page 41.
51
System Designs
System Design 3
(continued)
Dual-mode DHW heating with two DHW tanks - with Vitosolic 200 (continued) Control equipment required Item
Description
Number
Part no.
1 2
Control of DHW tank 1 loading by solar energy Vitosolic 200 Collector temperature sensor
1 1
3
DHW tank temperature sensor*1
1
4
Solar circuit circulation pump (standard equipment of Solar-Divicon, see page 35)
1
5
High limit safety cut-out (see also page 41)
1
7134 552 Included in standard equipment for item 1 Included in standard equipment for item 1 7133 454 or 7133 455 Supplied on site
6
Control of DHW tank 2 loading by the boiler DHW tank temperature sensor
1
7
Circulation pump for DHW tank loading*3
1
8
DHW circulation changeover DHW circulation pump or circulation pump (relayering)
1
Supplied on site
9
Temperature sensor tank 1
1
qP
Temperature sensor tank 2
1
Included in standard equipment for item 1 7170 965
*1The screw-in elbow which is *2Accessory with Vitodens. *3Part of the standard delivery
Included in standard equipment of boiler control unit *2 Accessories DHW tank
available as an accessory for the DHW cylinder is recommended for installation purposes. with Vitodens (for types with DHW heating).
WARNING
5167 156 v3.1
The domestic hot water temperature must be limited to 140 °F / 60 °C by installing a mixing device, e.g. a thermostatic anti-scald mixing valve.
52
System Designs
System Design 4 Dual-mode DHW and swimming pool water heating - with Vitosolic 200 DHW heating without solar energy
DHW heating with solar energy
Swimming pool water heating
The top part of the DHW tank is heated by the boiler. The DHW tank temperature sensor of the boiler control unit switches tank heating circulation pump .
Solar circuit circulation pump for DHW is switched ON and the heating DHW tank is heated up, when a temperature difference higher than the value set in control unit is measured between collector temperature sensor and DHW tank temperature sensor .
Solar circuit circulation pump for DHW is switched OFF, and solar heating circuit circulation pump for swimming pool heating is switched ON, if the temperature at DHW tank is so high, that temperature sensor the temperature difference falls below the set differential temperature for DHW heating. The temperature at collector temperature sensor must then be higher by the temperature difference for swimming pool water heating set in control unit than the temperature at temperature sensor (swimming pool) . Swimming pool water limit thermostat switches circulation (max. limit) pump OFF when the desired set water temperature has been reached. Circulation pump is switched OFF for approx. 2 minutes roughly every 15 minutes (adjustable time), to check whether the temperature at the collector temperature sensor is high enough to change over to DHW tank loading.
Solar circuit circulation pump for DHW is switched OFF, and solar heating circuit circulation pump for swimming pool heating is switched ON (see ”Swimming pool water heating”), if the temperature at DHW tank temperature sensor is so high that the actual temperature difference falls below the set differential temperature. The temperature in the DHW tank is limited by the electronic limit thermostat in control unit or by (if high limit safety cut-out required). When the preset temperature is exceeded, these devices switch OFF solar circuit circulation pump . The electronic temperature limit is set at the factory.
When the solar energy is insufficient to heat the swimming pool water, the heating of the swimming pool water will be taken over by the oil/gas-fired boiler via temperature sensor in heat exchanger 2.
5167 156 v3.1
The filter time and any boiler backup should fall outside those times when heating by solar energy can be expected.
53
System Designs
System Design 4
(continued)
Installation diagram 2
A
B
C
1
qP
4
DHW D E F 28
S
G
R
5 5
6 8
21
7
3 H
qR L
DCW
K
qT
M
qE
2
qQ
N
9
1
O
*1High
54
limit safety cut-out, see page 41.
DHW circulation output of the boiler control unit or timer installed on site Heating circuit Oil/gas-fired boiler Dual-mode DHW tank
Swimming pool Heat exchanger 2 Heat exchanger 1 Filter system with pump
5167 156 v3.1
Solar collector Solar-Divicon Solar pump line Taps DHW circulation
System Designs
System Design 4
(continued)
Dual-mode DHW and swimming pool water heating - with Vitosolic 200 (continued) Control equipment required Number
Part no.
1 2
Description Control of DHW tank loading by solar energy Vitosolic 200 Collector temperature sensor
1 1
3
DHW tank temperature sensor*1
1
4
Circulation pump for the solar circuit (standard equipment of Solar-Divicon, see page 35)
1
5 8
High limit safety cut-out (see also page 41) Circulation pump
1 1
7134 552 Included in standard equipment for item 1 Included in standard equipment for item 1 7133 454 or 7133 455 Supplied on site Supplied on site
6
Control of DHW tank loading by the boiler DHW tank temperature sensor
1
7
Circulation pump for DHW tank loading
1
9
Control of swimming pool heating by solar energy Temperature sensor (swimming pool)
1
Item
qP qQ qE qR qT *1A
Solar circuit circulation pump for swimming pool heating (part of the solar pump line, see page 35) Swimming pool limit thermostat (max. limit) Control of swimming pool heating by the boiler Temperature sensor (heat exchanger 2) Limit thermostat (max. limit) Circulation pump for swimming pool water heating
Included in standard equipment of the boiler control unit DHW tank accessory
1
Included in standard equipment for item 1 Supplied on site
1
Supplied on site
1 1 1
7170 965 Supplied on site Supplied on site
threaded elbow (standard delivery for Vitocell-B 100, accessory for Vitocell-B 300) is recommended for this installation.
WARNING
5167 156 v3.1
The domestic hot water temperature must be limited to 140 °F / 60 °C by installing a mixing device, e.g. a thermostatic anti-scald mixing valve.
55
System Designs
System Design Extensions Bypass circuit To improve the start-up characteristics of the system or for systems with several collector arrays, operation with a bypass circuit is feasible. Version 1 - bypass circuit with collector temperature sensor and bypass sensor The Vitosolic 200 records the collector temperature via the collector temperature sensor. If the set temperature difference between the collector temperature sensor and the
cylinder sensor is exceeded, the bypass pump is switched ON. If the temperature difference between the bypass sensor and the cylinder
S1
R5
Note The pump of the Solar-Divicon is used as the bypass pump and the pump of the solar circuit pump line is used as the solar circuit pump.
R1
S3 VL
temperature sensor is exceeded by 2.5 K the solar circuit pump is switched ON and the bypass pump is switched OFF.
R1 R3 S1 S3
Solar circuit pump Bypass pump Collector temperature sensor Bypass sensor
RL
Version 2 - bypass circuit with solar cell (e.g. with an external heat exchanger) For this system version, the solar circuit pump takes on this additional function. The Vitosolic 200 records the solar intensity via the solar cell.
The solar circuit pump will be switched ON, if the set irradiation threshold is exceeded.
The pump will be switched OFF, if the irradiation falls below the set switching threshold (shutdown delay approx. 2 min).
CS
R1 S1 RL
5167 156 v3.1
VL
CS Solar cell R1 Solar circuit pump S1 Collector temperature sensor
56
System Designs
System Design Extensions
(continued)
System with energy-saving mode
Version 3 - bypass circuit with solar cell and collector temperature sensor The Vitosolic 200 records the solar intensity via the solar cell. If the set irradiation threshold is exceeded, the bypass pump is switched ON. The bypass pump is switched OFF
and the solar circuit pump will be switched ON, if the set temperature difference between the collector temperature sensor and cylinder temperature sensor is exceeded.
The bypass pump will also be switched OFF if the irradiation falls below the set switching threshold (shutdown delay approx. 2.5 min).
Note The pump of the Solar-Divicon is used as the bypass pump and the pump of the solar circuit pump line is used as the solar circuit pump.
CS
R5
R1
S1 RL
Solar cell Solar circuit pump Bypass pump Collector temperature sensor
5167 156 v3.1
VL
CS R1 R5 S1
57
Appendix
Calculation Example Based on the Viessmann “ESOP” Program
Solar heating system with dual-coil DHW tank 2 x Vitosol 200-F
200 litres/day 45 °C Azimuth: 0° Inclination: 45°
300 litres
11 kW
Results of simulation over a one-year period 59.8 % 36.2 % 2 214 kWh 6.12 MWh 2 975 kWh 274 m3 520 kg
5167 156 v3.1
DHW solar fraction System efficiency Heat yield of collector circuit Irradiation on reference surface Heat requirement for DHW heating Natural gas savings CO2 emissions avoided
58
Appendix
Calculation Example Based on the Viessmann “ESOP” Program
(continued)
Solar heating system with dual-coil DHW tank (continued)
Coverage 59.8%
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
Dec
Period: 1.1. – 31.12.
System parameters Collector circuit details 2 collectors Total surface area, gross: 5.42 m2 Angle of inclination: 45º
Model: Vitosol 200-F Net: 4.99 m2 Azimuth: 0º
DHW cylinder with two indirect coils Capacity: 300 l
Model: Vitocell-B 100 (300 litres)
DHW consumer Type: Detached house
200 l per day at 45 ºC set temperature, 365 days
Cold water
February: 8 ºC
Total annual global radiation: 1101.08 kWh/m2
5167 156 v3.1
Weather statistics A location at 49º latitude
August: 12 ºC
59
Appendix
Glossary Absorber Device contained inside a solar collector for absorbing radiation energy and transferring this as heat to a liquid. Absorption Absorption of radiation. Condenser Device in which vapour is precipitated as liquid. Convection Transfer of heat by a flowing medium. Convection creates energy losses caused by a difference in temperature, e.g. between the glass plate of the collector and the hot absorber. Dispersion Interaction of radiation with matter by which the radiation direction is altered; total energy and wavelength remain unchanged. Efficiency The efficiency of a solar collector is the input/output ratio of the collector. Relevant variables are, for example, the ambient and absorber temperatures. Emission Radiation of beams, e.g. light or particles.
Heat loss coefficients k1 and k2 k1 is the constant component of the heat loss of a collector and is usually designated as k value (unit: W/(m2 · K)). k2 is the quadratic component of the temperature-dependent heat loss (unit: W/(m2 · K2)). Any informative statement about the heat losses of a collector requires both values to be quoted. Heat pipe Closed, capillary container which contains a small quantity of highly volatile liquid. Heat transfer medium Fluid which picks up the useful heat in the absorber of the collector and transfers it to a user (heat exchanger).
Selective surface The absorber in the solar collector has been given a highly selective coating to improve its efficiency. This specially applied coating enables the absorption to be maintained at a very high level for the incident sunlight spectrum (approx.94 %). The emission of the long-wave heat radiation is largely avoided. The high-selectivity black chromium coating is very durable. Stagnation Condition of a collector when no heat is being conducted away by the heat transfer medium. Vacuum A space devoid of air.
Photovoltaic effect Gaining electrical energy from solar energy. Radiation energy Quantity of energy transmitted by radiation. Radiation level (irradiation) Radiation power, impacting per unit surface, expressed in W/m2, or Btu/h/ft.2.
5167 156 v3.1
Evacuation Evacuating air from a container. This reduces the air pressure and creates a vacuum.
60
61
5167 156 v3.1
62
5167 156 v3.1
63
5167 156 v3.1
Printed on environmentally friendly (recycled and recyclable) paper. Technical information subject to change without notice.
64
Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario • N2V 2G5 • Canada Tel. (519) 885-6300 • Fax (519) 885-0887 www.viessmann.ca •
[email protected]
5167 156 v3.1
Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island • 02886 • USA Tel. (401) 732-0667 • Fax (401) 732-0590 www.viessmann-us.com •
[email protected]