Ultimate Pipe Calculation V1.0.xls

  • June 2020
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Ultimate Pipe Calculation V1.0.xls as PDF for free.

More details

  • Words: 454
  • Pages: 3
Coefficients

DATE: Supercedes:

Excel Calculation Tool

Pipe sections Worksheet designed by: Tom Smales Adapted to U Thermo range by : Paul Delouche Description:

This excel calulation tool provides an approximate estimation of the heat loss and surface temperature of the insulation system. This basic tool can be used to estimate the product performance and thickness required when choosing the appropriate insulation materials. The results are purely indicative.and the design of the complete insulation system and final choices made concerning the products used and the thicknesses to be installed are entirely the responsability of the designer

Conductivity =a+b*T+c*T2+d*T3 coefficients λ

Temperatures Thermal conductivity (λ lambda)

Product U Thermo Pipe

a

b

3.25E-02

7.04E-05

50

100

150

200

300

400

500

U Thermo Pipe**

0.037

0.043

0.051

0.060

0.083

0.111

0.143

°C W/m.K

c

d

3.58E-07 -1.11E-10

Product for comparison (values to enter)

** in blue, values measured according to EN 8 497 in accredited laboratory

Comparison of the thermal conductivity of the U Thermo pipe with chosen product

Lambda (W/m.K)

0.24

U Thermo Pipe

0.22

Product for comparison (polynomial tendancy curve)

0.2 0.18 0.16 0.14 0.12 0.1 0.08 0.06 0.04 0.02 0

0

100

200

300

400

500

600

Temperature (°C)

Isover, a division of Saint-Gobain Construction Products South Africa (Pty) Ltd Iron Road, New Era, Springs, 1560 Tel: (011) 360-8200 Fax: (011) 813-4414 Web Address: www.isover.co.za

Page 1

700

800

Coefficients

2010.07.21 2004 version

surface temperature of the e and thickness required when

and final choices made esponsability of the designer

600 0.180

700 0.219

s measured according to EN 8 497 in accredited laboratory

product

600

700

800

(Pty) Ltd 13-4414

Page 2

DATE: Supercedes:

2010.07.21 2004 version

Pipe sections calculation Calculation for a single Pipe section Worksheet designed by: Tom Smales Adapted to U Thermo range by : Paul Delouche

Client Date Project reference

U Thermo Pipe

PARAMETER

TERM Tp

UNIT °C

600

Ambient air temperature

Ta

°C

25

Enter actual ambient temperature

External surface temperature

Ts

°C

84

Enter required insulation surface temperature

Mean temperature of insulation

Tm

°C

342

Thickness of insulation Thermal conductivity Safety factor Surface heat transfer coefficient

d λ

mm W/m.K %

Surface temperature of pipe

Pipe diameter

f dp

Lagged pipe diameter

ds

Factor Heat flow External surface temperature

VALUE

100 0.094 0% 5.7

mm

160

mm ln (ds/dp)

360

Q' Ts

REMARKS Enter actual pipe temperature

Use this cell as the 'by changing cell' in GOAL SEEK

Aluminium=5.7, Galvanised=6.3, Unclad=10 Enter actual pipe external diameter

0.811

W/m

376.3

°C

83.4

Use this cell as the 'set cell' in GOAL-SEEK

Isover, a division of Saint-Gobain Construction Products South Africa (Pty) Ltd Iron Road, New Era, Springs, 1560 Tel: (011) 360-8200 Fax: (011) 813-4414 Web Address: www.isover.co.za

Related Documents

Pipe Calculation
June 2020 4
Pipe
November 2019 34
Pipe
November 2019 37