Transformer On Load

  • May 2020
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Transformer On Load as PDF for free.

More details

  • Words: 798
  • Pages: 14
Transformer on Load Φ2

Φ

Φ

Φ2 Φ2’ I0 V

Φ

Φ I2

1

Load

Fig. 4

Phasor diagram for Transformer on Load V1

V

1

I1 I2 '

θ1 θ0

I1

I2 ' θ1 θ0

I0

I0

Φ

I2

Φ θ2

Load I2 is resistive

Load I inductive

I2

K=1

K=1

E

E2 Fig. 5

2

2

is

Actual transformer: Winding resistance & magnetic leakage R V

X

1

I1

1

X E

1

2

Z1 = R 1 + X 1

2

1

E

R

2

I2

2

V

2

2

Z2 = R 2 + X 2

2

2

R1 & R2 : resistances of primary & secondary windings respectively. X1 & X2 : leakage reactances of primary & secondary windings respectively.

Phasor diagram of actual transformer

a) I2 is resistive

b) I2 is inductive

c) I2 is capacitive

Transfer of resistances & reactances to any side •

The Cu loss by I2 in secondary = I22 R2. If R 2 ′is the equivalent resistance in the primary which would have caused the same loss as R2 in the secondary, then 2

2

I 2 R 2 = I1 R 2



R2 R2 ′ or, R 2 = = 2 k2  I1     I2 



Similarly, equivalent primary resistance as referred to secondary is ′ R1 = k 2R1

• Leakage reactances can also be transferred from one winding to other ; X2



X2 = 2 k

′ X1 = k 2 X1

Total resistance referred to primary is Total reactance referred to primary is

R 01 = R 1 + R 2

X 01 = X 1 + X 2

• Total impedance of transformer referred to primary is 2 2

Z 01 = R 01 + X 01





Similarly, total resistance referred to secondary is



R 02 = R 2 + R 1

Similarly, total reactance referred to secondary is



X 02 = X 2 + X 1

Similarly, total impedance of transformer referred to secondary is 2

Z 02 = R 02 + X 02

2

Z R

Impedance referred to secondary

02

02

X

02

Equivalent circuit of Transformer Φ

I1 V

E

1

E

1

I2 V

2

A) Circuit R

1

X

Iw V

1

R

0

I2 '

I1

1

I0

R

2

X

I2

2

Iμ X

0

E

1

E

2

B) Equivalent circuit of transformer

V

2

Z

L

2

Equivalent circuit of Transformer referred to primary R1

I0

Iw V1

I2'

I1

X1

R0

X2'

R 2'



X0

V2' ZL'

E2'= E1

E2/E1 = I1/I2 = K

I2'

I1

E2' = E2/K, R2' = R2/K2, X2' = X2/K2, V2' =V2/K, Z′L =ZL/K2

C) Equivalent circuit with secondary impedances transferred to primary I1

R1

I2'

X1

R2'

X2 '

I0

Iw V1

Iμ R0

I1

E2' = E1

X0

I2'

D) Approximate equivalent circuit

ZL '

V2'

Approximate Equivalent circuit with secondary impedances transferred to primary I1

R01 = R1+R 2'

X01= X1 + X2'

I 2'

I0 V1

R0

ZL

X0

V2' I1

I2'

'

Transformer tests •

The performance of a transformer can be calculated on the basis of its equivalent circuit which contains the 4 main parameters: 1. Equivalent resistance R01(or R02) 2. Equivalent leakage reactance X01 (or X02) 3. Core loss resistance R0 4. Magnetizing reactance X0.



These parameters are determined from the following tests: a) Open circuit test b) Short circuit test

Open circuit test W V1

A

V

V2=E2

Low Voltage winding

High Voltage winding

Open Circuit Test

• As the primary no-load current I0 is small, Copper loss is negligibly small in primary & nil in secondary. Hence, wattmeter reading represents the core loss under no load condition. • Core loss = W = input power on no-load = V1I0cosΦ0 => cosΦ0 = W/(V1I0) Hence, Iw = I0 cos Φ0 & Iμ=I0sin Φ0 Also, X0 = V1/ Iμ & R0 = V1/ Iw

Short Circuit test •

This test is conducted to determine: 1. Full-load copper loss 2. Equivalent resistance & reactance referred to metering side. W LV supply

A

V

High Voltage winding





Low Voltage winding

A low voltage (5 -10% of normal primary voltage) at correct frequency is applied to the primary winding & is continuously increased till full load currents flow both in primary & secondary. Since applied voltage is small, flux linking with core is very small & hence, iron loss can be neglected & reading of wattmeter gives total copper losses at full load. If Vsc is the voltage required to circulate rated load currents, then

Z 01 =

Vsc 2 2 2 ;W = I sc R01 ⇒ X 01 = Z 01 − R01 I sc

Related Documents

Transformer On Load
May 2020 3
Transformer
June 2020 13
Transformer
May 2020 16
Transformer
May 2020 25
Transformer
April 2020 22
Transformer
June 2020 13