Transformer on Load Φ2
Φ
Φ
Φ2 Φ2’ I0 V
Φ
Φ I2
1
Load
Fig. 4
Phasor diagram for Transformer on Load V1
V
1
I1 I2 '
θ1 θ0
I1
I2 ' θ1 θ0
I0
I0
Φ
I2
Φ θ2
Load I2 is resistive
Load I inductive
I2
K=1
K=1
E
E2 Fig. 5
2
2
is
Actual transformer: Winding resistance & magnetic leakage R V
X
1
I1
1
X E
1
2
Z1 = R 1 + X 1
2
1
E
R
2
I2
2
V
2
2
Z2 = R 2 + X 2
2
2
R1 & R2 : resistances of primary & secondary windings respectively. X1 & X2 : leakage reactances of primary & secondary windings respectively.
Phasor diagram of actual transformer
a) I2 is resistive
b) I2 is inductive
c) I2 is capacitive
Transfer of resistances & reactances to any side •
The Cu loss by I2 in secondary = I22 R2. If R 2 ′is the equivalent resistance in the primary which would have caused the same loss as R2 in the secondary, then 2
2
I 2 R 2 = I1 R 2
′
R2 R2 ′ or, R 2 = = 2 k2 I1 I2
•
Similarly, equivalent primary resistance as referred to secondary is ′ R1 = k 2R1
• Leakage reactances can also be transferred from one winding to other ; X2
′
X2 = 2 k
′ X1 = k 2 X1
Total resistance referred to primary is Total reactance referred to primary is
R 01 = R 1 + R 2
X 01 = X 1 + X 2
• Total impedance of transformer referred to primary is 2 2
Z 01 = R 01 + X 01
′
′
Similarly, total resistance referred to secondary is
′
R 02 = R 2 + R 1
Similarly, total reactance referred to secondary is
′
X 02 = X 2 + X 1
Similarly, total impedance of transformer referred to secondary is 2
Z 02 = R 02 + X 02
2
Z R
Impedance referred to secondary
02
02
X
02
Equivalent circuit of Transformer Φ
I1 V
E
1
E
1
I2 V
2
A) Circuit R
1
X
Iw V
1
R
0
I2 '
I1
1
I0
R
2
X
I2
2
Iμ X
0
E
1
E
2
B) Equivalent circuit of transformer
V
2
Z
L
2
Equivalent circuit of Transformer referred to primary R1
I0
Iw V1
I2'
I1
X1
R0
X2'
R 2'
Iμ
X0
V2' ZL'
E2'= E1
E2/E1 = I1/I2 = K
I2'
I1
E2' = E2/K, R2' = R2/K2, X2' = X2/K2, V2' =V2/K, Z′L =ZL/K2
C) Equivalent circuit with secondary impedances transferred to primary I1
R1
I2'
X1
R2'
X2 '
I0
Iw V1
Iμ R0
I1
E2' = E1
X0
I2'
D) Approximate equivalent circuit
ZL '
V2'
Approximate Equivalent circuit with secondary impedances transferred to primary I1
R01 = R1+R 2'
X01= X1 + X2'
I 2'
I0 V1
R0
ZL
X0
V2' I1
I2'
'
Transformer tests •
The performance of a transformer can be calculated on the basis of its equivalent circuit which contains the 4 main parameters: 1. Equivalent resistance R01(or R02) 2. Equivalent leakage reactance X01 (or X02) 3. Core loss resistance R0 4. Magnetizing reactance X0.
•
These parameters are determined from the following tests: a) Open circuit test b) Short circuit test
Open circuit test W V1
A
V
V2=E2
Low Voltage winding
High Voltage winding
Open Circuit Test
• As the primary no-load current I0 is small, Copper loss is negligibly small in primary & nil in secondary. Hence, wattmeter reading represents the core loss under no load condition. • Core loss = W = input power on no-load = V1I0cosΦ0 => cosΦ0 = W/(V1I0) Hence, Iw = I0 cos Φ0 & Iμ=I0sin Φ0 Also, X0 = V1/ Iμ & R0 = V1/ Iw
Short Circuit test •
This test is conducted to determine: 1. Full-load copper loss 2. Equivalent resistance & reactance referred to metering side. W LV supply
A
V
High Voltage winding
•
•
Low Voltage winding
A low voltage (5 -10% of normal primary voltage) at correct frequency is applied to the primary winding & is continuously increased till full load currents flow both in primary & secondary. Since applied voltage is small, flux linking with core is very small & hence, iron loss can be neglected & reading of wattmeter gives total copper losses at full load. If Vsc is the voltage required to circulate rated load currents, then
Z 01 =
Vsc 2 2 2 ;W = I sc R01 ⇒ X 01 = Z 01 − R01 I sc