TRAN SMISS IO N LI NE
Character ist ic s • It is a metallic conductor system used to transfer electrical energy from one point to another using electrical current flow. • Nowadays, the transmission line is made of parallel-conductor (copper wire) and coaxial cable. • It consists of 2-wire line since transmission line for transverse electromagnetic TEM wave propagation always have 2 conductors. • The characteristic of Transmission Line are determined by its electrical properties : Conductivity & Insulator Dielectric Constant September 18, 2009
FKEE
Norizam
2
Types of Transmission Lines • • • •
September 18, 2009
Open-Wire Twin-Lead Twisted-Pair Coaxial
FKEE
Norizam
3
Metallic transmission lines
Open-wire
September 18, 2009
Twin lead
FKEE
Norizam
4
Metallic transmission lines Unshielded twisted-pair
September 18, 2009
FKEE
Norizam
5
Metallic transmission lines Coaxial cable
September 18, 2009
FKEE
Norizam
6
Metallic transmission lines Differential, or balanced, transmission system
Balanced lines have equal impedances from the two conductors to ground Twisted-pair and parallel lines are usually balanced
September 18, 2009
FKEE
Norizam
7
Ideal Transmission Line • No losses – conductors have zero resistance – dielectric has zero conductance – possible only with superconductors – approximated by a short line • No capacitance or inductance – possible with a real line only at dc – with low frequencies and short lines this can be approximated
September 18, 2009
FKEE
Norizam
8
The electrical properties determine the PRIMARY electrical constant: Series Resistance, R Series Inductance, L Shunt Capacitance, C Shunt Conductance, G The combined above parameter is called LUMPED PARAMETERS. Refer to Figure 12-14 & 12-15 in the textbook for the two-wire parallel transmission line and single section transmission line. The transmission line characteristic is called SECONDARY CONSTANT. The secondary constants are: 1. Characteristic Impedance 2. Propagation constant September 18, 2009
FKEE
Norizam
9
Two-wire parallel transmission line electrical equivalent circuit
September 18, 2009
FKEE
Norizam
10
Char acteri stic Impedance The characteristic Impedance, Zo is defined as : A transmission line must be terminated at purely resistive load for maximum power transfer.
Zo = Zo = Zo =
( R + jwL) / (G + jwC )
R/G
for Low Frequencies for high Frequencies
L/C
The conductance between 2 wires are determined by the shunt leakage resistance, Rs The load impedance, ZL must match with characteristic impedance, ZO September 18, 2009
FKEE
Norizam
11
Refer to figure 12-16 for Characteristic impedance of a transmission line of infinite section. The characteristic impedance can be calculated by using Ohm’s Law: Zo = Eo / Io where Eo is source voltage and Io is transmission line current
The characteristic impedance also can be calculated by its physical dimension:
September 18, 2009
FKEE
Norizam
12
Any transmission line that is terminated is a purely resistive Load in infinite line:
Zi = Zo No Reflected Wave V & I in phase Maximum Power Transfer from source to load
September 18, 2009
FKEE
Norizam
13
Propagation C
onsta nt
Propagation Constant is used to express the attenuation (signal loss) and the phase shift per unit length of a transmission line. It is defined as :
γ = α+ jβ γ = ( R + jwL)(G + jwC ) Where γ = propagation constant (unitless) α = attenuation coefficient (nepers per unit length) β = phase shift coefficient (radians per unit length) September 18, 2009
FKEE
Norizam
14
For an ideal line R and G are zero
j LC 0
purely imaginary and no attenuation
LC
September 18, 2009
FKEE
Norizam
15
Transmission Lines Losses • Conductor Losses •Increases with frequency due to skin effect
• Dielectric Heating Losses •Also increases with frequency • Radiation
Losses
• Not significant with good quality coax properly installed • Can be a problem with openwire cable • Coupling
Losses
• Corona Skin effect September 18, 2009
FKEE
Norizam
16
Transmission Lines Losses
September 18, 2009
FKEE
Norizam
17