By Sekhar Samy, CCI, and Dave Stemler, CCI 21st AOV Users’ Group Conference • Winter 2002, January 9-11 Clearwater Beach, FL, USA
22591 Avenida Empresa Rancho Santa Margarita, CA 92688 949.858.1877 w Fax 949.858.1878 w ccivalve.com 521
|
10/02 w ©2002 CCI w DRAG is a registered trademark of CCI.
Linear Piston Actuators
Operability of an actuator in a general sense just means that it can be
n Sekhar Samy, Control Components Incorporated, Rancho
important criteria listed above has been carefully considered before
Santa Margarita, California, USA; and Dave Stemler, Control Components Incorporated, Rancho Santa Margarita, California, USA.
selecting an operator.
21st AOV Users’ Group Conference, Winter 2002, January 9-11, Clearwater Beach, FL, USA
actuated when required to do so. It does not ensure that any of the
Repeatable tight shutoff There are no consistent guidelines for achieving the required level of tightness within the valve industry, so it is imperative that the user spell out quantitative criteria in ensuring that the actuator has sufficient thrust. In an ideal situation with perfectly machined seating
Introduction
surfaces even a small positive force is adequate for tight shutoff.
H
manufacturing tolerances. Over time a sealing surface goes through
igh Reliability of actuation is of paramount importance in the nuclear power industry. Pneumatic actuators form the largest
installed base with many in safety significant applications. This paper addresses the issues related to actuation, such as available Thrust, Stiffness, Sensitivity, Hysteresis, Dead band, Dynamic Stability and a sizing example.
This is not the case in real world applications, where there are normal wear and tear and would quickly deteriorate to allowing more leakage then desired. So while a valve may leak test to the specified class in the shop in mint condition, it may not provide the specified shutoff after some use. The important quantitative criterion is Pounds of thrust per Lineal Inch (PLI) of seating circumference. In the valve
This paper will also present comparisons between various types of
industry this value for an ANSI/FCI 70.2 Class IV shutoff varies from
linear actuators and their relative advantages and disadvantages. Also
40 to 400 PLI.
presented will be evaluation techniques for troubleshooting actuator problems and improving plant performance. Actuation Requirements In a nuclear power plant typically 90% of the control valve actuators are pneumatic. Hence, it is not surprising that the AUG and its participants expend considerable time in studying pneumatic actuators. The reason pneumatic actuator are widely used is primarily due to the fact that compressed air readily provides a large source of available power for valve actuators. Most valves do not move at once so the total power requirements at any given time in a plant can be easily met. Most importantly, this ready source of stored energy is also available during short-term outages. In critical service valve applications, in addition to reliable operability there are other important considerations: n
Repeatable Tight Shutoff
n
Optimal controllability during normal operating conditions (Resolution)
n
Good controllability during transients
n
Environmental Qualification
n
Compact with a low center of gravity, and a high weight to thrust
Just such a wide variation suggests that sufficient conservatism is necessary based on empirical study of contact stresses between sealing members and field observations. The Instrument Society of America (ISA) Guide (Ref 1) recommends a value of 300 PLI for Class IV shutoff. Optimal Controllability It is often overlooked that control valves are final control elements in process control. The best control systems cannot make up for limitations of a control valve. Small hysteresis and dead band, quick response to small changes in input signal are all key to good performance. The quantifiable measure for fine controllability is Resolution. Resolution is defined as the smallest possible change in position of the control valve. When a valve is asked to change position from a steady state of zero stem velocity, what is the smallest incremental travel possible? To answer this question the valve actuator system is modeled as an elastic spring mass system and analyzed. The smallest change in force is due to change from the static to dynamic friction as the valve makes a change in position. The friction under consideration is due to valve plug piston seals, valve packing and actuator seals. Dynamic friction is smaller than static friction (Ref 2).
ratio for seismic considerations n
2
Stroke Speeds
Linear Piston Actuators | 521
©2002 CCI. All rights reserved.
How does the “resolution” translate into better controllability? The
The elastic system is simply as spring mass system that can be modeled using the equation of motion for a Single Degree Of Freedom (SDOF) system. The “spring” has a pneumatic component (trapped air in actuator) and a mechanical component (compression spring). So the smallest change in a control valve position is: Fstatic - Fdynamic ∆X = Ksystem
determining the slope of the Valve Capacity “Cv” versus Lift curve at the point of interest (i.e., Lift). ∆Cv =
( ooCv )
∆X
x
(3)
By substituting the resolution of the actuator from equation into = Summation of static friction forces, such as, packing, seals
and piston rings
equation , the fractional change in valve capacity ∆Cv is determined. Next, by using the ISA sizing equations one can calculate the actual flow change possible with a given actuator.
Fdynamic = Summation of dynamic friction forces, such as, packing, seals and piston rings Ksystem
in position that the actuator can accomplish can be determined by
(1)
where, Fstatic
step change in the flow capacity corresponding to the smallest change
In Appendix B, we have presented a calculation showing how to perform resolution calculations in a typical feedwater regulator
= Summation of pneumatic and mechanical stiffness at the
valve travel of interest
application. Poor control, high vibration and pressure swings are endemic of this application. In this application, high rangeability and fine resolution are required to maximize control. Long stroke lengths
For a valve stroke with total stroke “H”, in terms of percentage
and a stiff actuator is the key to performance enhancements. The
resolution equation may be rewritten as follows:
authors use such calculations to diagnose control problems in actual
∆X =
Fstatic - Fdynamic Ksystem
1 H
plant applications. 100% (2)
The pneumatic stiffness of a typical double-acting piston actuator easily allows positioning accuracy’s of 0.5% where required; in comparison, positioning accuracy’s of a diaphragm actuator ranges from 2% to 5%.
It is clear from equation that larger the “stiffness” of the actuator, smaller its resolution. With smaller resolution better process control is possible. Similarly, longer the stroke smaller the resolution.
Controllability under Transient Conditions Operability under transient conditions, whether they are fluid
Appendix A, derives the expression for the stiffness of a pneumatic
flow related buffeting forces or a system related pressure transient
spring diaphragm actuator and a piston actuator.
phenomenon - a piston actuator would be better able to resist such
For a spring diaphragm actuator it is
magnitude and waveform of the transient pressures, it is possible to
forces due to its inherent high stiffness. If one could estimate the study its effect on the controllability of the valve.
Kd = γ A
PL LL
+Kspring
(14)
Environmental Qualification Environmentally qualified actuators must withstand high ambient temperatures, radiation, high mechanical stresses due to vibration or
And the lowest stiffness at a given supply pressure occurs when LL = H. For a double acting piston actuator the stiffness is
Kp = γ A
PU PL LU + LL
fast actuation, seismic loads and finally any Design Basis Events. Piston actuators feature a high thrust to weight ratio because they can operate at higher supply pressures. This also helps to keep the
+ Kspring
design compact without much overhanging mass, which will reduce (15)
the natural frequency of the actuator-yoke system. Higher natural frequency system is desired when the valve is designed to withstand seismic loads.
The lowest stiffness generally occurs when LU = LL. Refer, to the Appendix A for the nomenclature and figures. The piston actuator is definitely stiffer when compared to a equivalent spring diaphragm actuator.
©2002 CCI. All rights reserved.
The only elastomers in a piston actuator are o-rings, which are robust because the stresses on the o-rings are quite low. Diaphragm actuators with fabric reinforced diaphragms are under higher stresses and typically fail at the bolt holes due to high stress concentrations. 521 | Linear Piston Actuators
3
transmission of the force to the load and instead tend to excite the
ENHANCING SYSTEM PERFORMANCE
“spring-mass” system.
A pneumatic actuator’s performance can improve by the simple addition of a positioner. But in valves with high seal friction a positioner would only exacerbate control problems. An important element for improved control stability is actuator stiffness. Actuators with insufficient stiffness can be adversely affected by process
The advantage of a piston actuator with its higher Stiffness, consequently larger natural frequency or smaller time constant becomes evident.
dynamics, which will tend to contribute to control instability,
Even slow processes such as level control will benefit from better
especially in fast response systems such as pressure control. This
stability, shortened settling time and better control stability when
is best understood by looking at the natural frequency of a SDOF
positioners are used. If a diaphragm actuator is used without a
system.
positioner, it must use a specific range spring and bench-set for the fn = 1 2
application. Any change in the application parameters will require
Ksystem g
re-calibration of the bench set. Due to bench set an actuator without
F (4)
Where,
psig, hence reducing its effectiveness in controlling the process. Diaphragm actuators are widely used in nuclear power plants. While
fn
= Natural frequency of the system, Hz
g
= Acceleration due to gravity, 386 in/sec2
F
= External Load moved by the actuator, lbf
Ksystem
a positioner may not use all of its signal range of 3-15 signal or 6-30
= Stiffness of the actuator pneumatic + spring system, lbf/in
If an actuator with a low natural frequency, is trying to respond fast it will become unstable as its velocity ramp rate gets closer to its Time Period. In other words, if an actuator tries to reach its final velocity from rest within its Time Period, it will become unstable. The Time Period of a system is defined as Ts = 1/fn seconds.
they provide good performance in many applications, there are some critical applications where they have shortcomings. One of the major concerns is the non-linear change in effective area of a simple flat diaphragm. This has in some cases resulted in over estimation of the available actuator thrust, which can be a serious problem in safety significant applications. The simple flat diaphragms are not capable of providing long strokes, but this is somewhat remedied by using a “rolling” or molded diaphragm with a large fold. Still they do not come close to what a piston actuator can offer in large stroke lengths. The wall thickness of the stamped housings and the strength of the diaphragm itself limit the supply pressure to the diaphragm actuators. The upper bound for diaphragm actuators is around 60-80 psig on the average, while the piston actuators are routinely designed to operate at 150 psig. Misapplications of linear actuators to Gate valves are significant because quantifying the required force accurately, problems due to pressure locking thermal binding are significant as is evidenced by NRC Generic Letter 89-10 and Information Notice 96-08 respectively. The large seating and un-seating forces require special dampening devices to prevent damage to the backseats. These gate valves retrofitted with the system media operated actuators now offer the most reliable solution. They use piston actuators except the power source is the system media itself. They provide such a large
Figure 1: Ramp Velocity Profile The velocity profile of a actuator is shown in figure 1. The system ramps up to a final velocity then travel at the constant final velocity and ramps down as the actuator reaches its final position. A first order
thrust margin that all concerns for accurately estimating wedging and un-wedging forces under a variety of scenarios become unnecessary. REFERENCES Borden G., Friedmann P. Editors, 1998, “Control Valves
system reaches 99.8% of its final value in six Time Periods. So the
1)
ideal time required to reach the final velocity desired should about 6
– Practical Guide of Measurement and Control”, Instrument Society
times the Time Period of system, i.e., Tr > 6Ts
of America, Research Triangle Park, North Carolina, USA
Actuators with lower stiffness and equipped with volume boosters
2)
for fast stroke speeds are prone to oscillatory problems. Any attempts
Tribology” CRC Press, Boca Raton, FL, USA
Ludema K., 1996, “Friction, Wear, Lubrication – A Textbook in
to speed up a system makes the system Time Period impede the
4
Linear Piston Actuators | 521
©2002 CCI. All rights reserved.
©2002 CCI. All rights reserved.
521 | Linear Piston Actuators
5
PNEUMATIC PISTON Throttling, On-Off Medium to High Medium Medium Medium
Medium to High Spring or Volume Tank Medium Fast with accessories Low to Moderate Simple Low Low
Medium
ATTRIBUTE
Service Type
Thrust Capability
Thrust to Weight Ratio
Economy for built in Thrust Output Margin
Overall Dimensional Envelope
Stiffness
Fail Safe
Cleanliness of Power Source
Stroking Speed
Purchase Cost
Construction Complexity
Cost for Maintenance
Required Technical Expertise for Maintenance
Supplier Choice
Very Large
Low
Medium
Simple
Low
Fast with accessories
Medium
Spring supplemented by Volume Tank if necessary
Low to Medium
Large
Low
Low
Small to Medium
Throttling, On-Off
SPRING DIAPHRAGM
Small
High
High
High
High
Slow
N/A
Standby Power Source required
Very High
Compact
High
High
Very High
Low Duty Throttling, On-Off
ELECTRIC MOV
Comparison of Actuator Types
Small
Specialized
Very High
Very High
Very High
Very Fast
Very High
Accumulator
High to Very High
Large
High
High
Medium to Very High
Throttling, On-Off
ELECTROHYDRAULIC
Small
Specialized
Moderate
High
Very High
Very Fast
Medium
As available system media
Very High
Compact
Very High
High
Very High
On-Off
SYSTEM MEDIA OPERATED
Using the Taylor Series expansion and keeping just the first two terms
APPENDIX A
in the series gives,
PNEUMATIC ACTUATOR STIFFNESS To compute the pneumatic stiffness of an actuator, assume that the changes in stem position occur so rapidly that there is no air supplied
P1V1 γ =
or exhausted from the actuator. Such a process is adiabatic in nature.
(
P1V1 γ +
V1 γkx A
)(
1−
)
γAx V1
(9)
Let the initial volume of the actuator chamber under consideration be “V1” and the initial pressure be “P1” in absolute units. Now let
Expanding the above equation
the volume of the actuator chamber suddenly change to a lower volume “V2” and the pressure increase to “P2”in absolute units. The relationship that defines the change is given by the following equation.
P1V1 γ= P2V2γ
P1V1 γ = P1V1 γ −
γAx V1
P1V1 γ +
V1 γkx V1 γkx γAx A A V1
(10)
(5) And dropping out the term containing x2 , since x2 << 0 and
Where,
simplifying gives the expression for pneumatic “spring rate”.
γ = Ratio of the specific Heats
k=
Let the infinitesimal change in the piston stroke be “x”, and the surface
P1γA2 V1
(11)
area of the piston “A”. Then the new pressure and volume can be rewritten as follows: P2 = P1 + kx A
ACTUATOR STIFFNESS (6)
This section derives the expression for the spring constant of a double acting actuator with a return spring (Figure A1) and a diaphragm with
Where, “k” is the pneumatic stiffness (or Spring Rate) that is to
a return spring (Figure A2).
calculated. The change in volume can be re-written as follows:
In a double acting actuator both sides of the piston are filled with V2 = V1 - Ax
(7)
air. In a diaphragm actuator one side is filled with air and the spring side is connected to the atmosphere. Notice the large volume of air that would be trapped in the bottom of the spring diaphragm actuator even when the valve is closed. In a piston actuator this volume is minimized to a small value. When this fact is applied to equation it is clear that smaller the volume, higher the stiffness. This makes the
Substituting (6) and (7) into (8) and re-arranging:
spring diaphragm operator to have a lower stiffness when compared to a piston actuator. Further, this has one other important consequence P1V1 γ = P1V1 γ =
( (
P1+ P1+
kx A kx A
) ) (
(8)
(V1 - Ax)γ V1γ
1−
Ax V1
)
γ
when throttling at low plug lifts. Commonly, known as the “Bath Stopper Effect”, spring diaphragm operators with flow over the plug and throttling at low lifts can slam into the seat causing severe water hammer. So most of the time they are specified as flow under the plug. This problem does not occur with well designed piston actuators which can have stiffness approaching very large values and can be used in flow over the plug applications. Depending on the bias of the positioner, the maximum pressure in the cylinder is 2/3 to 3/4 of the supply pressure. The maximum pressure is set by the positioner manufacturer and is usually controlled by the clearances in spool machining. Hence it is fixed for a given model of positioner. Some smart positioners have a value as low as 1/2 of the supply pressure.
6
Linear Piston Actuators | 521
©2002 CCI. All rights reserved.
The systems all behave as though they are springs connected in
For a piston actuator the equivalent spring is
parallel. Hence, their stiffness can be simply summed to come up with equivalent spring stiffness for the actuator. For convenience it is possible to define air “equivalent air-volume lengths” as follows, VU
LU =
A
(12)
PU LU
+
PL LL
+ Kspring
(15)
Comparing equations and it can be seen a piston actuator that operates at a higher supply pressure would be much stiffer when compared to a diaphragm actuator.
VL
LL =
Kp = γA
A
(13)
for the upper and lower chambers respectively For a diaphragm actuator the equivalent spring is
Kd= γA
PL LL
+ Kspring
(14)
Since, the upper chamber is connected to the atmosphere it does not act as a spring and is not included in the above equation.
Figure A2: Fail extend piston actuator
Figure A1: Fail extend spring diaphragm actuator
©2002 CCI. All rights reserved.
521 | Linear Piston Actuators
7
8
Linear Piston Actuators | 521
©2002 CCI. All rights reserved.
©2002 CCI. All rights reserved.
521 | Linear Piston Actuators
9
10
Linear Piston Actuators | 521
©2002 CCI. All rights reserved.
©2002 CCI. All rights reserved.
521 | Linear Piston Actuators
11
12
Linear Piston Actuators | 521
©2002 CCI. All rights reserved.
uses
1003
©2002 CCI. All rights reserved.
521 | Linear Piston Actuators
13
14
Linear Piston Actuators | 521
©2002 CCI. All rights reserved.
©2002 CCI. All rights reserved.
521 | Linear Piston Actuators
15
16
Linear Piston Actuators | 521
©2002 CCI. All rights reserved.
©2002 CCI. All rights reserved.
521 | Linear Piston Actuators
17
18
Linear Piston Actuators | 521
©2002 CCI. All rights reserved.