Shunt Active Filter Report

  • Uploaded by: mandar
  • 0
  • 0
  • May 2020
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Shunt Active Filter Report as PDF for free.

More details

  • Words: 2,913
  • Pages: 29
ABSTRACT A Shunt Active Power Filter(APF) is a device that is connected in parallel to group of loads.APF cancels the reactive and harmonic currents drawn by the load so as to make supply current sinusoidal. Active Power Filter play a vital role in present day liberalized energy market. Active Power Filter are explored for executing different power conditioning function simultaneously along with harmonic elimination due to increase in nonlinear and unbalanced load, at the point of common coupling. The aim of present dissertation is to study different control strategies for Active Power Filter. More importantly to study instantaneous power theory based Shunt Active Power Filter which is predominantly used in present scenario. The shunt active power filter is investigated through Matlab/Simulink simulation under different load conditions. Simulation results are discussed in depth. Then the design issues of Active Power Filter for different load conditions are also discussed.

1 COEP

CHAPTER 6 SIMULATION DESIGN The p-q theory based shunt APF is implemented for Harmonic compensation and power factor correction. Logic utilized for shunt APF is discussed in chapter 5 and is summarized in fig.5.2 6.1 Specification of the design: Simulation is performed on 2 types of Three phase Balanced Non –Linear Load as fallows: System Parameters Source Voltage System Frequency

VSa,VSb,VSc f

220 Vrms(line- line) 60 Hz

Vdc

800V 1100μF 3.75mH 0.01 Ω

APF Dc-link voltage Dc side capacitance Ac side inductance Ac side resistance

C Lc Rc

(Rating of APF is generally decided by peak voltage and RMS Current) Load 1 Thyristor Rectifier (of rating 4 KVA)supplying to DC motor equivalent of 2.5KW AC side inductance AC side resistance DC side Resistance DC side Inductance

LLac RLac RLdc LLdc

1mH 0.01 Ω 18 Ω 85mH

Load2 Diode rectifier (of rating around 3KVA) supplying to purely resistive load AC side inductance AC side resistance DC side Resistance DC side Inductance

LLac RLac RLdc LLdc

NA NA 18 Ω NA

2 COEP

(NOTE: Rating of APF is generally decided by peak voltage and RMS Current[14] APF rating for Load1 is Vpeak=312v and Irms=3A will result in rating of 12 ×312×3= 0.661 KVA .Thus in practical cases can be assumed to be around 1-1.5KVA}.

3 COEP

Fig 6.1 p-q theory based control block diagram of three-phase shunt APF system. Continuous pow ergui

Va +

[isa]

i -

i -

+

Vb

[isb]

i + -

i -

+

Vc

A

B

[isc]

+ -

+ -

+ -

v

v

220 V rms L-L 3-phase Source

v

+

i -

+

i -

C

Lc

non-linear load g11

Rc

g12 g21

[Vsa]

[Vsb]

+

g32

+

g31

i -

g22

i -

i -

Voltage measurement

+

Load Current measurement

Vdc

a

[Vsc]

b

Goto7 [Vdc]

c

Current measurement [Vsa]

Compensator

Vsa Valpha

[Vsb]

Valpha

Vsb

Isalf a

Isalpha

A1

Isb*

A2

Isc*

B1

Inverse Transformation

Isa

B2

[isa]

Isb

C1

Isc

C2

Vsc Vbeta

[isa]

800

Isa

In1

[Vdc]

Isb

Isbeta Isbeta

Out1

[isb]

Ib*

pdc

ploss

In2

p

[isc]

[isb]

PI controller

Isc

butter

Clarke Transformation

[isc] Low Pass FIlter

4 COEP

current measurement1 Isa*

Vbeta

[Vsc]

Ia*

Ic*

Hysterisis Band Current Controller

Capacitor voltage

6.2 Clark Transformation: is done in accordance with section 4.2.2

1

a

Vsa 2

b

Vsb 3

c

Vsc

alpha Vbeta

beta

Ibeta

Subsystem1

3

p

Valpha

p

Ialpha

Subsystem5 4

a

Isa 5

b

Isb 6

c

Isc

alpha

1 Valpha

beta

Subsystem2 2 Vbeta

Fig 6.2 Block Diagram for Clark Transformation and p calculation

1

1

a

2

-K-

b

-K-

K=-1/2 3 c

Sum of Elements

K=sqrt(2/3)

1 alpha

-KK=-1/2

1 -KSum of K=sqrt(2/3) Elements1

-1

2 beta

Fig 6.3 Clark transformation block diagram for both V∝,Vβ,Iαand Iβ 5 COEP

6.3 Calculation of p According p-q theory real and imaginary power can be separated into two parts: Real power:

p=p+p

Imaginary power:

q=q+q

(from eq)

where p and q are average power due to component iapand iaq respectively p and q are oscillating power due to components iapand iaq respectively.

And

i-(iap+iaq) will produces a purely sinusoidal waveform. But in order to

achieve unity power factor APF must compensate for q from component iaq. Thus, i(iap+iaq+iaq) will produce purely sinusoidal waveform with unity power factor.

Thus, inverse transformation iap will produce reference current iS* for each phase. iap can deduced from p which is filtered out using low pass filter from p.

1 1

Vbeta

p

2 Ibeta

Product

3 Valpha 4 Ialpha

Product1

Fig 6.4 Block diagram for calculation of p

p

p

Fig 6.5 p from p using Low Pass filter 6 COEP

6.4 DC-Bus Voltage Control Under a loss free situation, the shunt APF need not provide any active power to cancel the reactive and harmonic currents from the load. These currents show up as reactive power. Thus, it is indeed possible to make the DC-bus capacitor delivers the reactive power demanded by the proposed shunt APF. As the reactive power comes from the DC-bus capacitor and this reactive energy transfers between the load and the DC-bus capacitor (charging anddischarging of the DC-bus capacitor), the average DC-bus voltage can be maintained at a prescribed value. However, due to switching loss, capacitor leakage current, etc., the distribution source must provide not only the active power required by the load but also the additional power required by the VSI to maintain the DC-bus voltage constant. Unless these losses are regulated, the DC-bus voltage will drop steadily. A PI controller used to control the DC-bus voltage is shown in Figure6.6. Its transfer function can be represented as Hs=Kp+KIs where Kp is the proportional constant that determines the dynamic

response of the DC-bus voltage control, and KI is the integration constant that determines its settling time. 1 PID

Vdc 2 constant

Subtract

PID Controller

1 ploss

Fig 6.6 PI controller for DC-bus voltage control (Note: Kd=0 in above PID cotroller) It can be noted that if Kp and KI are large, the DC-bus voltage regulation is dominant, and the steady-state DC-bus voltage error is low. On the hand, if Kp and KI are small, the real power unbalance give little effect to the transient performance. Therefore, the proper selection of Kp and KI is essentially important to satisfy above mentioned two control performances.

6.5Reference Current Calculation: Reference Currents are calculated from inverse clark transformation.

7 COEP

3

1

pdc

Isalfa

Divide

Product 4 1

ploss

Valpha Product1 2 Vbeta Product2

2 Product3

Divide1

Fig 6.7 Block diagram for calculation of Is∝and Isβ

1 Isalpha

-KGain

1 Ia* -KGain1

2 Ib*

2 Isbeta

-K-

-K-

Gain2

Gain3

3 Subtract

Ic*

Fig 6.8 Reference Current calculation Ia*,Ib *and Ic*

6.6 Hysteresis Band Current Controller: It is introduced in chapter 3 section 3.5.2

8 COEP

Isbeta

4

1

Isa Subtract2

A1

Relay3

1

NOT

Isa*

Logical Operator 5

3

Isb Subtract1

2

2 A2

Relay1

B1

Isb* NOT Logical Operator1 6

4 B2

5

Isc Subtract3

Relay2

3

C1

NOT

Isc*

Logical Operator2

6 C2

Fig 6.9 Hysteresis Band Current Controller Actual source currents ( iSa,iSb,ISc) are compared with the reference currents iSa*,iSb*,ISc*generated by the control algorithm in the hysteresis-band current controller. Three hysteresis-band current controllers generate the switching pattern of the VSI. The switching logic is formulated as follows If iSa< (iSa*HB) higher switch is OFF and lower switch is ON for leg “A” (QA=1) If iSa> (iSa*+ HB) higher switch is ON and lower switch is OFF for leg “A” (QA=0). The switching functions of QB and QC for legs ‘‘B’’ and ‘‘C’’ are determined similarly, using corresponding reference and measured currents and hysteresis bandwidth (HB). The hysteresis-band current control is the fastest control method with minimum hardware and software but variable switching frequency is its main drawback

6.7 Compensator: Switching is done according to gating signals from Hysteresis Band Current Controller. Capacitor Voltage is continuously measured and fed to PI controller as explained earlier.

9 COEP

g12

m

2

m

2

g

1

g

1

c

2

3

b

m

2

g31

1

2 1

2

5

g

m g

a

4

g22

+ v -

C

2

1

g21

m

2 1

3

1

m g

g11

g

1

6

Voltage Measurement3

g32

Fig 6.10 Compensator

6.8 Non-Linear Loads Case:1

Thyristor Converter Supplying to DC motor equivalent

10 COEP

1 Vdc

Rlac Llac

g A B C

DC motor equivalent circuit +

+

i -

Id -

Thyristor Converter Synchronization Voltages

1

A

2

B

+ v -

alpha_deg

Vab

AB

+ v -

BC

Vbc

CA

+ v -

3

C

Vca

0

pulses

Block

Synchronized 6-Pulse Generator

PI Curent Regulator 5 1 s

100 90

Id_Refence

Fig6.11 Block Diagram for Thyristor Converter controlled DC motor Using PI controller DC motor current value is maintained at 20 Amps. PI controller varies alpha of thyristor until motor current matches reference current. Pulse width is takes as 15° .

11 COEP

case2:Diode Rectifier supplying to pure resistive load

1

Diode

Diode2

Diode4

Diode1

Diode3

Diode5

A

2

B

3

C

Fig 6.12 Block diagram for Diode rectifier supplying to pure Resistive Load A pure resistive load is taken in order to APF performance. As in this load phase current varies in abrupt manner on the contrary to RL load where load phase current is smooth varying curve.

12 COEP

CHAPTER 7 SIMULATION RESULTS 7.1 Case 1: Thyristor converter supplying to DC motor Equivalent(R-L Type Load) VSa

ILa

VSb

ILb

VSc

ILc

FiFig 7.1 Source Voltages and Load Currents with APF(Case 1)

13 COEP

Fig 7.2 Harmonic Analysis of Load Current with APF(Case 1)

ISa*

Fig 7.3 Reference Current ISa* (Case 1) 14 COEP

ISa

Fig 7.4 Source Current with APF(Case 1)

ILa

Fig 7.5 Compensating Current and Load Current(Case 1)

15 COEP

ICa

VSa

ISa

VSb

ISb

VSc

ISc

Fig 7.6 Source Voltage and Source Current with APF(Case 1)

16 COEP

Fig7.7 Harmonic Analysis of Source Current (Case 1)

17 COEP

Vc

Fig7.8 DC Capacitor Voltage for three-phase APF(Case 1)

18 COEP

7.2 Case 2: Diode Rectifier supplying to pure resistive

VSa

ILa VSb

ILb

VSc

ILc

Fig 7.9 load Source Voltage & Load Current with APF

19 COEP

Fig 7.10 Harmonic Analysis of Load Current

20 COEP

ISa

Fig 7.11 Source Current after Compensation(Case 2)

ICa

ILa

Fig 7.12 Compensating Current and Load Current(Case 2)

21 COEP

VSa

ISa

VSb

ISb

VSc

ISc

Fig 7.13 Source Voltages and Source Current(Case 2)

22 COEP

Fig 7.14 Harmonic analysis of Source Current(Case 2)

23 COEP

Fig 7.15 DC Capacitor voltage for three-phase APF(Case 2)

7.3 Simulation Result Discussion: 24 COEP

As the source current and voltage are in phase,also the source current is almost sinusoidal(very low THD) it can be said that source is providing only active power required by the circuit. In instantaneous power theory view, source current is providing only average real power component(p) while remaining components i.e real oscillating power(p), imaginary average power(q) and imaginary oscillating power(q), is being provided by Shunt APF.(see Discussion in section 6.3 ) From source currents and THD in case1 (RL load) and case 2 (purely resistive load ) it can be said that the effectiveness of the active filter in compensating for harmonic components of the load current depends on the specific load current waveform involved. Two different waveforms may have the same rms harmonic content but the active filter may do a better job of compensating for one of the waveforms because of the waveshapes involved. Source current has very less THD in case of RL load compared to purely resistive one. Thus it can be inferred performance of shunt APF with RL load is much better than purely resistive load. In general, the current waveform of an ac regulator with resistive load is an example of the waveshape that poses the severest challenge for an active filter. The problem is the high di/dt that is required of the filter to compensate for the high di/dt at turn on of the regulator. The problem is most severe when the regulator is turned on with a firing angle close to 90 degrees because this is when the available driving voltage stored on the dc capacitor is at a minimum. The output di/dt capability can be raised either by increasing the dc voltage setting or by reducing the size of the interfacing inductance. The limiting factor for increasing the dc voltage is the voltage withstand capability of the IGBT devices. The limiting factors for reducing the interfacing inductance include the IGBT di/dt withstand capability, control requirements, the interface passive filter requirement, and overall system stability. If the interfacing inductance becomes too small, the dc voltage cannot be kept constant for normal operation. From harmonics analysis of Source Current it can be seen due to uneven switching of compensator large number of interharmonics are introduced. But,it should be noted that those components have very less magnitude.(Maximum magnitude of interharmonic is 0.11 % in case 1) 25 COEP

Using PI Controller DC capacitor is maintained at reference value. It was seen that Settling time improved drastically using PI controller. It is worth to also to note that p-q based APF can be used for complete harmonic elimination not selective harmonic elimination. 7.4 Future Scope As p-q theory can be implemented in three-phase with excellent results in terms of THD, transient response, reference current generation. The work on extending use of p-q theory in single phase APF is being done[13]. Switching required in APF is very high in order of 10 kHz. Resulting in appreciable amount of power. Thus, one can further work on to reduce switching frequency and to switching losses. One can also work on linear control technique to replace hysteresis band controller .So, that irregular switching in compensator can be removed. Study of Control system of APF is also a possibility n order to get lesser steady state error and improved settling time. Most importantly to study various APF techniques and comparing them in terms of dynamic response, performance under various type of load, total harmonic compensation is to be done.

CHAPTER 8 CONCLUSION

26 COEP

The validity in terms of eliminating p-q theory in terms of eliminating harmonics and power factor improvement is confirmed from low THD source current which is in phase with source voltage. But p-q theory utilizes large number of sensors and reference current calculation block. Large number of calculation in p-q theory demands higher processing power. Resulting in utility to be complex and expensive. The p-q theory base APF is predominantly utilized in three phase circuits thus can not be used at remote single phase customer. As a result, Harmonics are present in large part of system. From source currents of the both cases (i.e. RL Load and purely resistive load) it can be inferred that APF is most effective when the load current waveform does not have abrupt changes. The overall filtering effectiveness depends significantly on the types of loads being compensated. As a result, it is very effective for most voltage source inverter-type loads, even when the distortion is high. From comparing reference current and source waveforms it can be concluded that hysteresis band current controller done the compensation at the cost of high switching frequency. Which can result in high switching losses in practical high power APF applications. PI controller performance is also validated from the DC-bus capacitor voltage which shows decreased settling time. In theoretical view p-q theory has some shortcomings which need to be addressed. Like mathematical expression of instantaneous power does not fallow power conservation and real and imaginary power needed to be more accurately defined as zero sequence instantaneous power can not be defined by the theory. In practical approach also it can be noted that p-q theory is incapable of providing selective harmonic elimination and specific power factor compensation.

References 1.H. Akagi, Y. Kanazawa and A. Nabae, "Generalized Theory of Instantaneous Reactive Power and Its Applications," Transactions of he lEE-Japan, Part B, vol. 103, no.7, 1983, pp. 483-490 2.Power Quality C.Sankaran 27 COEP

3.H. Akagi. “New trends in active filters for power conditioning”, IEEE Trans. on Industry Applications, vol. 32, pp. 1312-1322, (1996). 4. Das, J. C. Passive Filters – Potentialities and Limitations. IEEE Trans. On Industry Applications. 2004. 40(1): 232-241. 5. Power Electronics Handbook CRC PRESS 6. El-Habrouk, M., Darwish, M. K., and Mehta, P. Active Power Filters: A Review. Proc. IEE Electric Power Applications. 2000. 147(5): 403-413. 7. Characteristics of Three Phase Active Power Filter using Extension pq Theory. Proceedings of the IEEE International Symposium on Industrial Electronics (ISIE). July 7-11, 1997. Guimaraes, Portugal: IEEE. 1997. 302-307. 8.Chen, C. L., Chen, E. L., and Huang, C. L. An Active Filter for Unbalanced Three-Phase System using Synchronous Detection Method. Proceedings of the Power Electronics Specialist Conference (PESC). June 20-25, 1994. Taipei, Taiwan: IEEE. 1994. 1451-1455. 9.Chen, D. –H. and Xie, S. –J. Review of Control Strategies Applied to Active Power Filters. Proceedings of the IEEE International Conference on Electric Utility Deregulation, Restructuring and Power Technologies (DRPT). April 5-8, 2004. Hong Kong: IEEE. 2004. 666-670. 10.Textook of “Modern Power Electronics and AC Drives”, B.K.Bose 11.Instantaneous p-q Power Theory for Compensating Non-sinusoidal Systems E. H. Watanabe, Senior Member, IEEE, H. Akagi, Fellow, IEEE and M. Aredes, Member, IEEE 12.Instanteneous Power Theory and applications to power conditioning, IEEE Press, H. Akagi, E. H. Watanabe, M. Aredes. 13. M. Tarafdar Haque “SINGLE-PHASE PQ THEORY”, IEEE Trans. 14 “Active filter design and specification for control of harmonics in industrial and commercial facilities”, Mark McGranaghan Electrotek Concepts, Inc.

28 COEP

29 COEP

Related Documents


More Documents from "David.R.Gilson"