Suggestion on How to Use • Industry Trainers are encouraged to use this material in their sessions • Download both the PowerPoint file (.ppt) and script file (.pdf) • Print the script file (.pdf) and read the script as you view the PowerPoint presentation in the “Slide Show” view. In this way you see the slides in large format and have animation (if there is any) • Must have PowerPoint and Adobe Reader application software on your system.
© 2001 Cooper Bussmann, Inc.
Selective Coordination
Selective Coordination • For 600 Volts & less • Easy concept to understand • Hard to verify, if you do not know what to look for • Misinterpretations or lack of understanding is very prevalent • People review curves (hand drawn or computer generated) and they do not know how to interpret
© 2001 Cooper Bussmann, Inc.
Selective Coordination Definition: The act of isolating a faulted circuit from the remainder of the electrical system, thereby eliminating unnecessary power outages. The faulted circuit is isolated by the selective operation of only the overcurrent protective device closest to the overcurrent condition.
© 2001 Cooper Bussmann, Inc.
Selective Coordination: Avoids Blackouts Without Selective Coordination
With Selective Coordination
OPENS NOT AFFECTED
OPENS
UNNECESSARY POWER LOSS
NOT AFFECTED
Fault
Faul t
Selective Coordination: NEC
®
240.2 Definitions Coordination. The proper localization of a fault condition to restrict outages to the equipment affected, accomplished by the choice of selective fault-protective devices.
© 2001 Cooper Bussmann, Inc.
Selective Coordination: NEC
®
240.12 Electrical System Coordination where orderly shutdown required to minimize hazards 620.62 Selective Coordination required where more than one elevator is supplied by single feeder. 517.17 Selective coordination between main and feeder required for health care facilities where main has GFP (feeder also required to have GFP).
© 2001 Cooper Bussmann, Inc.
Selective Coordination
Chapter 2 Video Selective Coordination
© 2001 Cooper Bussmann, Inc.
Selective Coordination
Coordination Circuit Breakers
© 2001 Cooper Bussmann, Inc.
Magnetic Element Bimetal Trip Bar
Circuit Breaker Operation
Load Line Latch
Spring Loaded Contacts © 2001 Cooper Bussmann, Inc.
Bimetal Trip Bar
Thermal Overload Operation Normal State
Load Line Latch
Spring Loaded Contacts © 2001 Cooper Bussmann, Inc.
Bimetal Trip Bar
Thermal Overload Operation Unlatch & Open
Load Line Latch
Spring Loaded Contacts © 2001 Cooper Bussmann, Inc.
Magnetic Element
Trip Bar
Short Circuit Operation Normal State
Load Line Latch
Spring Loaded Contacts © 2001 Cooper Bussmann, Inc.
Magnetic Element
Trip Bar
Short Circuit Operation Unlatching
Load Line Unlatch
Spring Loaded Contacts © 2001 Cooper Bussmann, Inc.
Magnetic Element
Trip Bar
Short Circuit Operation Opening
Load Line Latch
Spring Loaded Contacts © 2001 Cooper Bussmann, Inc.
Magnetic Element
Trip Bar
Short Circuit Operation Cleared
Load Line Latch
Spring Loaded Contacts © 2001 Cooper Bussmann, Inc.
Coordination Thermal-Mag Circuit Breakers Thermal Magnetic Molded Case Circuit Breaker TimeCurrent Curve ◆
Overload Region
◆Instantaneous
Region ◆Interrupting Time ◆Unlatching Time
◆Interrupting Rating © 2001 Cooper Bussmann, Inc.
Coordination Thermal-Mag Circuit Breakers (See SPD)
© 2001 Cooper Bussmann, Inc.
Selective Coordination D
Time
C
B A
4000A Fault
Current © 2001 Cooper Bussmann, Inc.
Lacking Coordination
OPENS NOT AFFECTED UNNECESSARY POWER LOSS
Fault
© 2001 Cooper Bussmann, Inc.
Selective Coordination Insulated Case Circuit Breakers (See SPD) 2000A Insulated Case Circuit Breaker ◆ STD Is an Option - Allows breaker to delay opening ◆ Instantaneous Override built-in: may be as low as 12X the breaker rating ◆ Will often result in lack of coordination ◆
© 2001 Cooper Bussmann, Inc.
Selective Coordination Insulated Case Circuit Breakers (See SPD) 2000A Insulated Case with STD and Instantaneous Override and 100A Molded Case Thermal Magnetic Circuit breaker - NO Coordination in Short-Circuit Region (above 21,000A) ◆
© 2001 Cooper Bussmann, Inc.
Selective Coordination LV Air Power Circuit Breakers (See SPD) ◆Short
Time Delay - Allows the fault current to flow for up to 30 cycles. ◆Used
to coordinate with downstream
◆Subjects
equipment to high mechanical and thermal stresses, often violating 110.10 ◆Arc
Flash/ Blast Risks Much Higher
◆High
Cost, Larger Equipment © 2001 Cooper Bussmann, Inc.
Selective Coordination: Fuses
© 2001 Cooper Bussmann, Inc.
© 2001 Cooper Bussmann, Inc.
Selective Coordination:Fuses (See SPD)
Time Current Curves
© 2001 Cooper Bussmann, Inc.
Selective Coordination:Fuses (See SPD) Selectivity Ratio Guide Based on Thermal Principle Based on I2t
Not Melt
Clear
I2t melting > I2t Clearing 1200 A 600 A © 2001 Cooper Bussmann, Inc.
Selective Coordination (See SPD ) Line Side Fuse
Load Side Fuse
LOW-PEAK® : LOW-PEAK® 2:1 Line:Load Ratio Selectivity Ratio Table Assures Coordination! No Plotting required! © 2001 Cooper Bussmann, Inc.
Selective Coordination Fuses 480V, 3 phase
Example: Main: KRP-C 1200 SP Feeder: LPS-RK 200 SP Branch: LPS-RK-30 SP
1200 A MSB
GFP
200 A
MCC
30 A © 2001 Cooper Bussmann, Inc.
Selective Coordination - Fuses Use Selectivity Table Main
KRP-C 1200 SP
Feeder
LPS-RK 200 SP
Branch
LPS-RK 30 SP
What happens: Branch Circuit Isca = 5000 A or 50,000A or 300,000A ?
© 2001 Cooper Bussmann, Inc.
Selective Coordination- Fuses
Lineside KRP-C 1200SP to Loadside LPS-RK 200SP 1200/200 = 6:1 Table only need 2:1 Selective Coordination Lineside LPS-RK 200SP to Loadside LPS-RK 30SP 200/30= 6.67:1 Table only need 2:1 Selective Coordination
© 2001 Cooper Bussmann, Inc.
Selective Coordination
NOT AFFECTED OPENS
Fault
© 2001 Cooper Bussmann, Inc.
Selective Coordination Simple Rules for Checking • Circuit Breakers • Fuses
(instantaneous trip)
© 2001 Cooper Bussmann, Inc.
Can you look at this and assess whether coordinated? You do not even need to draw curve!
Simple Rule: (Amp rating) x (I.T. setting) = Isca @ which CB will unlatch:
CB IT IT Amp Set Amp Pickup 100 5X 500 200 5X 1,000 400 10X 4,000 1600 12X 19,000
See SPD
1600 A 400 A 200 A 100 A
Selective Coordination • You already know the simple rule for fuses. • Simply use amp rating ratios • Typically 2:1 for Low Peak Fuses to Low Peak Fuses
© 2001 Cooper Bussmann, Inc.
Selective Coordination • Do coordination exercise using simple rules – Fusible system – Circuit breaker system
• It’s simple!
© 2001 Cooper Bussmann, Inc.
Are These Selectively Coordinated? Low Peak KRP-C 1000 SP Low Peak LPJ 200 SP Low Peak LPJ 20 SP Fault 10000 Amps © 2001 Cooper Bussmann, Inc.
Are These Selectively Coordinated?
Selectively Coordinated
Low Peak KRP-C 1000 SP
Low Peak KRP-C 1000 SP
Low Peak LPJ 200 SP Low Peak LPJ 20 SP Fault 10000 Amps
Low Peak LPJ 200 SP NOT AFFECTED OPEN S
Low Peak LPJ 20 SP Fault 10000 Amps © 2001 Cooper Bussmann, Inc.
Are These Selectively Coordinated? 1000 A. CB IT @ 10 X 200 A. CB IT @ 10 X 20 A. CB IT @ 10X Fault 10000 Amps © 2001 Cooper Bussmann, Inc.
Are These Selectively Coordinated?
Not Coordinated
1000 A. CB IT @ 10 X
1000 A. CB IT @ 10 X
200 A. CB IT @ 10 X
200 A. CB IT @ 10 X
20 A. CB IT @ 10X Fault 10000 Amps
NOT AFFECTED OPEN S
20 A. CB IT @ 10X Fault 10000 Amps © 2001 Cooper Bussmann, Inc.
The Issue: Lack of coordination takes out other loads
1000 A. CB IT @ 10 X 200 A. CB IT @ 10 X
Unnecessary Blackout OPEN S
20 A. CB IT @ 10X Fault 10000 Amps © 2001 Cooper Bussmann, Inc.
Ground Fault Protection 230-95
© 2001 Cooper Bussmann, Inc.
See SPD
© 2001 Cooper Bussmann, Inc.
GFP Health Care 517-17
Where one level of GFP is provided per 230.95 or 215.10 an additional step of GFP on feeders required. The Ground Fault Protection for service and feeder shall be fully Selectively Coordinated
What does this mean ?
© 2001 Cooper Bussmann, Inc.
517-17 Health Care GFP
Main Feeder
1200 A CB 200 A CB
GFP on Main & Feeder Does this meet 517-17?
© 2001 Cooper Bussmann, Inc.
517-17 Health Care GFP
Main Feeder
1200 A Fuse 200 A Fuse
GFP on Main & Feeder Does this meet 517-17?
© 2001 Cooper Bussmann, Inc.
Following Excerpts from IEEE Standards
© 2001 Cooper Bussmann, Inc.
IEEE 242-1986 “BUFF BOOK” Protection and Coordination of Industrial and Commercial Power Systems Page 263 6.4.1 Protection (Series Connection). It should be noted that selectivity will not be provided at any current level where the breaker trip characteristic curves overlap when this protection scheme is used, that is, both circuit breakers will trip.
© 2001 Cooper Bussmann, Inc.
IEEE 242-1986 “BUFF BOOK” Protection and Coordination of Industrial and Commercial Power Systems Page 528 Coordination 14.2.2 Coordination can easily be achieved with low voltage current-limiting fuses that have fast response times. Manufacturer’s time current curves and selectivity ratio guides are used for both overload and short-circuit conditions, precluding the need for calculating time intervals.
© 2001 Cooper Bussmann, Inc.
IEEE 141-1993 “RED BOOK” Electrical Power Distribution for Industrial Plants Page 256 5.7.2.3 Low-voltage circuit breakers. To achieve this level of selectivity, power circuit breakers utilize short-time delay trips. The equipment protected by this breaker must be designed to handle the available short-circuit current for the duration of the short-time delay.
© 2001 Cooper Bussmann, Inc.
IEEE 242-1986 “BUFF BOOK” Protection and Coordination of Industrial and Commercial Power Systems
Page 528 Coordination 14.1 A coordination study should be made when the available short-circuit current of the source to the plant is increased.
© 2001 Cooper Bussmann, Inc.
IEEE 242-1986 “BUFF BOOK” Protection and Coordination of Industrial and Commercial Power Systems Page 528 Coordination 14.1 A coordination study or revision of a previous study may be needed for an existing plant when new loads are added to the system or when existing equipment is replaced with higher rated equipment.
© 2001 Cooper Bussmann, Inc.
IEEE 602-1996 “WHITE BOOK” Electrical Systems in Health Care Facilities Page 57/58 3.7.1.1 Protection requirements. As total selectivity and maximum safety to personnel are critical, a total short-circuit coordination, and component protection study shall be performed.
© 2001 Cooper Bussmann, Inc.
IEEE 141-1993 “RED BOOK” Electrical Power Distribution for Industrial Plants Page 256 5.7.2.3 Low-voltage circuit breakers. It should be recognized that providing selectivity to the load-side devices may result in equipment bus structures being underprotected. The Standards for such equipment, ANSI/UL 891-1984 [B21] for switchboards, ANSI/UL 845-1987 [B20] for motor control centers,
© 2001 Cooper Bussmann, Inc.
IEEE 1015-1997 “BLUE BOOK” Applying Low-Voltage Circuit Breakers Used in Industrial and Commercial Power Systems Page 135 5.5.4 Short-time delay All MCCBs and most ICCBs with a short time delay have an instantaneous override. If selective coordination is required for fault currents above the instantaneous override level, a power circuit breaker defined as an LVPCB with a short-time delay option, as shown in Figure 5-16, should be considered.
© 2001 Cooper Bussmann, Inc.
IEEE 242-1986 “BUFF BOOK” Protection and Coordination of Industrial and Commercial Power Systems Page 252 6.3 Trip Unit The resulting combination of long-time delay and short-time delay characteristics provides delayed tripping for all levels of overcurrent below the instantaneous response. This provides time for downstream circuit breakers to operate and clear the fault. The withstand of other electrical components in the current path should be checked to be certain they can handle the additional stress associated with the longer clearing time.
© 2001 Cooper Bussmann, Inc.
IEEE 1015-1997 “BLUE BOOK” Applying Low-Voltage Circuit Breakers Used in Industrial and Commercial Power Systems Page 62 3.38 Series-connected rating. Sometimes it is erroneously thought that series combinations are at a disadvantage with regard to coordination as compared to fully rated systems. The fact is that even fully rated circuit breakers with instantaneous trips will not “coordinate” once the fault level exceeds both circuit breakers’ instantaneous trip levels.
© 2001 Cooper Bussmann, Inc.
IEEE 1015-1997 “BLUE BOOK” Applying Low-Voltage Circuit Breakers Used in Industrial and Commercial Power Systems Page 134 5.5.3 Series MCCBs Selective coordination is limited to currents below the instantaneous pickup of the lineside circuit breaker. For any fault downstream of the load-side MCCB having a current greater than the instantaneous pickup of the line-side MCCB, both circuit breakers trip, and power is interrupted to unfaulted circuits fed by the line-side circuit breaker. © 2001 Cooper Bussmann, Inc.