Pump Calculation

  • November 2019
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Pump Calculation as PDF for free.

More details

  • Words: 201
  • Pages: 2
SIZING CALCULATIONS FOR SUMP PUMP AT SUMP PIT FOR PROPOSED ERECTION OF A 2 STOREY DETACHED DWELLING HOUSE WITH BASEMENT AND SWIMMING POOL ON LOT 1663T PARCEL B6A-5 MK 34 AT OCEAN DRIVE, SENTOSA COVE CALCULATION OF DESIGN FLOW Discharge Unit Flow from reflective pool & rain water in basement

= 2.0 lit/sec(estimated)

Design flow rate

= 2.0 lit/sec

CALCULATION OF STATIC HEAD Discharge level at open drain Sump pit level

= =

103.35 99.97

Static Head

=

3.38

CALCULATION OF TOTAL HEAD No. of dia. 50mm fittings

Equivalent length (m)

Length of dia. 50mm pipe (approx) 90 deg. Elbow 6 nos. (6 x 2.3) Gate valve 2 nos. (2 x 22) Check valve 2 nos. (2 x 11.5) Tee piece 1 no

= = = = =

Total equivalent length of 50 dia. mm pipe

Flow Rate (lit/min)

5.56 13.80 44.00 23.00 3.50 89.86

50

100

150

200

Static Head (m) Friction Head 50mm dia.

3.38 0.49

3.38 1.62

3.38 2.70

3.38 5.39

Total Head (m)

3.87

5.00

6.08

8.77

Pump selection From the plot of system curve against pump performance curve:Pump selected : Nocchi submersible pump model Priox 300/9 M Aut Capacity Operating Head

: :

2.0 lit/sec 6m