PROYECTO: HOSPITAL PACASMAYO INSTALACIONES ELÉCTRICAS

BAJA TENSIÓN

INFORME DE CALCULO DE BANDEJA PARA ALIMENTADORES SECTOR “A”

ENCARGADO: Amiel Ricardo Bautista Quispe

DISTRIBUCION DE ALIMENTADORES TABLEROS

DUCTOS TIPO

DUCTOS DE CONCRETO

1 3 4 5 6 7 8 9 10

ALIMENTADORES

TABLEROS VOLTAJE

TD-1 TEST-1 TAA-2 TE-3 TD-4 TEST-4 TAA-DC TEST-3 TD-3 TEST-2 TE-2 TAA-1 TD-2 TE-1 TE-4 TAA-N TAA-E TE-4 TAA-N TAA-E

380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380

NUMERO DE CONDUCTORES 5 5 5 5 5 5 5 5 5 5 5 5 5 5 3 3 3 2 2 2

FASE (mm2) 95 50 70 70 70 70 16 50 35 35 120 35 25 120 150 150 150 0 0 0

NEUTRO

95 50 70 70 70 70 16 50 35 35 120 35 25 120 0 0 0 150 150 150

DIAMETRO seccion DIAMETRO EXTERIOR interior EXTERIOR TIERRA DE de ducto CONDUCTOR CONDUCTOR comercial DE FASE TIERRA (mm) 16 6.9 90 ducto de concreto 15.6 10 11.9 6.3 90 ducto de concreto 10 13.7 6.3 90 ducto de concreto 10 13.7 6.3 90 ducto de concreto 10 13.7 6.3 90 ducto de concreto 10 13.7 6.3 90 ducto de concreto 10 8 6.3 106 ducto PVC-P 4" 10 11.9 6.3 10 10.6 6.3 106 ducto PVC-P 4" 10 10.6 6.3 16 17.4 6.9 106 ducto PVC-P 4" 10 10.6 6.3 106 ducto PVC-P 4" 10 9.6 6.3 16 17.4 6.9 106 ducto PVC-P 4" 0 19.4 6.9 106 ducto PVC-P 4" 0 19.4 6.9 106 ducto PVC-P 4" 0 19.4 6.9 106 ducto PVC-P 4" 16 19.4 6.9 16 19.4 6.9 106 ducto PVC-P 4" 16 19.4 6.9

CALCULO DE SECCION DE LOS CONDUCTORES:

TIPO DE CONDUCTOR

N2XOH

LSOHX TOTAL

SUB-TOTAL # PESO DE DE CALIBRE DE DIAMETRO CADA CONDUCTORES CONDUCTORES EXTERIOR CONDUCTOR POR TIPO (kg/m) 4 4 12 8 16 4 8 12 11 6 85

16 25 35 50 70 95 120 150 10 16

8 9.6 10.6 11.9 13.7 15.6 17.4 19.4 6.3 6.9

0.185 0.282 0.373 0.495 0.694 0.953 1.184 1.444 0.116 0.17

PESO SUBTOTAL POR TIPO DE CONDUCTOR (kg/m) 0.74 1.128 4.476 3.96 11.104 3.812 9.472 17.328 1.276 1.02 54.316

SECCION DE CONDUCTOR (mm2) 50.265 72.382 88.247 111.22 147.411 191.134 237.787 295.592 31.172 37.392

SECCION SUBTOTAL POR TIPO DE CONDUCTOR (mm2) 201.06 289.528 1058.964 889.76 2358.576 764.536 1902.296 3547.104 342.892 224.352 11579.068

CALCULO DE BANDEJA:

K: coeficiente de apilamiento de los cables < a 2.5mm2: 1.2 > a 2.5mm2:1.4 e: reserva de espacio en % para futuras ampliaciones ∑n: sumatoria de las secciones de los cables a instalar en la bandeja SEC: seccion util en mm2 de la bandeja K: coeficiente de apilamiento de los cables < a 2.5mm2: 1.2 > a 2.5mm2:1.4 e: reserva de espacio en % para futuras ampliaciones

∑n: sumatoria de las secciones de los cables a instalar en la bandeja