Pipe Friction Loss Calculation

  • November 2019
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Pipe Friction Loss Calculation as PDF for free.

More details

  • Words: 1,256
  • Pages: 5
THICKNESS OF INSULATION Room Temperature Heat transfer coefficient of air Heat transfer coefficient of insulation material Temperature of chilled water (surface of pipe) Dew point of room temperature

40.0 °C 8.0 kcal/m².h.°C 0.03 kcal/m².h.°C 7.0 °C 33.5 °C

d0 d1 Ln (d1/d0) θ0 θs θrd NPS Insulation (mm) (mm) thick. (mm) (mm) (mm) (°C) (°C) (°C) 20 27 25 77 1.048 7.0 37.63 33.5 25 33 25 83 0.922 7.0 37.51 33.5 32 42 30 102 0.887 7.0 37.87 33.5 50 60 30 120 0.693 7.0 37.69 33.5 65 73 40 153 0.740 7.0 38.27 33.5 80 89 40 169 0.641 7.0 38.20 33.5 100 114 40 194 0.532 7.0 38.11 33.5 125 139 40 219 0.455 7.0 38.05 33.5 150 168 40 248 0.389 7.0 37.99 33.5 200 219 40 299 0.311 7.0 37.92 33.5 250 273 40 353 0.257 7.0 37.87 33.5 300 324 40 404 0.221 7.0 37.84 33.5 350 356 40 436 0.203 7.0 37.82 33.5 400 406 40 486 0.180 7.0 37.80 33.5 450 457 40 537 0.161 7.0 37.78 33.5 500 508 40 588 0.146 7.0 37.76 33.5 550 559 40 639 0.134 7.0 37.75 33.5 600 610 50 710 0.152 7.0 38.19 33.5 650 660 50 760 0.141 7.0 38.18 33.5 700 711 50 811 0.132 7.0 38.17 33.5 750 762 50 862 0.123 7.0 38.17 33.5 800 813 50 913 0.116 7.0 38.16 33.5 850 864 50 964 0.110 7.0 38.16 33.5 900 914 50 1014 0.104 7.0 38.15 33.5 950 965 50 1065 0.099 7.0 38.15 33.5 1000 1016 50 1116 0.094 7.0 38.14 33.5 1100 1118 50 1218 0.086 7.0 38.14 33.5 1200 1219 50 1319 0.079 7.0 38.13 33.5 The condition of relative humidity & dew point is set by using the Psychrometric Chart.

Result No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation No condensation

Where ; α λ d0 d1 θ0 θr θs θrd t

Formula :

: : : : : : : : :

Heat transfer coefficient of air (normally = 8 kcal/m².h.°C) Heat transfer coefficient of insulation material (kcal/m.h.°C) Outside diameter of pipe (m) Outside diameter of insulation material (m) Temperature of chilled water (surface of pipe ) (°C) Temperature of room (surrounding) (°C) Temperature of surface insulation material (°C) Dew point of temperature (°C) Insulation thickness (m)

θs

=

θr

-

( θr



θο )

Pipe Insulation

d0 d1

Section

Type

Outside Diameter Same Flow Rate D1 D2 pipe thk. Q1 Q2 (mm) (mm) (mm) (m3/h) (m3/h)

From Thermal Storage Tank Chilled Water 100.0 45° S.E. 100.0 90° S.E. 100.0 Diversion Tee (M-B) 100.0

Sectional Area A1 A2 (m2) (m2)

Length Friction Velocity (m or Loss V1 V2 Qty.) (mmAq/m) (m/sec) (m/sec)

Dynamic Pressure (mmAq)

Coefficient of Resistance

Pressure loss (mmAq)

Remarks

100.0

5.0 5.0 5.0 5.0

20.0 20.0 20.0 20.0

20.0

0.0064 0.0064 0.0064 0.0064

0.0064

0.1 0.1 0.1 0.1

9.92 -

0.87 0.87 0.87 0.87

0.87

38.87 λ = 38.87 std. = 38.87 std. = 38.87 ζ 12 =

0.0230 0.1000 0.2460 1.2800

0.99 3.89 9.56 49.75 m = 1.00

Diversion Tee(M)

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 13 = 0.9600

37.31 m = 1.00

Diversion Tee(B-M)

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 23 = 1.0600

41.20 m = 1.00

Convern.Tee(B-M)

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 23 = 1.0600

41.20 m = 1.00

Convern.Tee(M)

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 13 = 0.5000

19.43 m = 1.00

Tee / w. blind end

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 21 = 1.0000

38.87

Tee / w. blind end

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 12 = 1.0000

38.87

Tee / w. Valve

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 13 = 0.0500

1.94

R.(convern.flow)

100.0

80.0

5.0

20.0

20.0

0.0064

0.0038

0.1

-

0.87

1.44

16.58 ζ 12 = 0.0000

0.00 Coeff. negligible

Flow Meter

80.0

-

5.0

20.0

-

0.0038

-

0.1

51.42

1.44

-

R (Divern.flow) B.F.V. Control Valve Control Valve Y-type Strainer Check Valve

80.0 100.0 100.0 100.0 100.0 100.0

100.0 -

5.0 5.0 5.0 5.0 5.0 5.0

20.0 20.0 20.0 20.0 20.0 40.0

20.0 -

0.0038 0.0064 0.0064

0.0064 -

-

1.44 0.87 0.87

0.87 -

-

0.0064 0.0064

-

0.1 0.1 0.1 0.1 0.1 0.1

-

1.75

-

-

106.21

λ = 0.0339

106.21 ζ 12 = 0.1014 38.87 std. = 0.2400 38.87 std. = 0.2400

155.48

K = 2.0000

5.14 10.78 ξ = 0.65 9.33 9.33 XCV 3,000.00 TCV 3,000.00 466.43 Swing Type

KV2 / 2g K Factor have to refer to catalog (2 to 4) Plus Safety Factor 50%

Section

Type

Outside Diameter Same Flow Rate D1 D2 pipe thk. Q1 Q2 (mm) (mm) (mm) (m3/h) (m3/h)

From Thermal Storage Tank Cooling Water 100.0 45° S.E. 100.0 90° S.E. 100.0 Diversion Tee (M-B) 100.0

Sectional Area A1 A2 (m2) (m2)

Length Friction Velocity (m or Loss V1 V2 Qty.) (mmAq/m) (m/sec) (m/sec)

Dynamic Pressure (mmAq)

Coefficient of Resistance

Pressure loss (mmAq)

Remarks

100.0

5.0 5.0 5.0 5.0

20.0 20.0 20.0 20.0

20.0

0.0064 0.0064 0.0064 0.0064

0.0064

0.1 0.1 0.1 0.1

13.69 -

0.87 0.87 0.87 0.87

0.87

38.87 λ = 38.87 std. = 38.87 std. = 38.87 ζ 12 =

0.0318 0.1000 0.2460 1.2800

1.37 3.89 9.56 49.75 m = 1.00

Diversion Tee(M)

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 13 = 0.9600

37.31 m = 1.00

Diversion Tee(B-M)

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 23 = 1.0600

41.20 m = 1.00

Convern.Tee(B-M)

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 23 = 1.0600

41.20 m = 1.00

Convern.Tee(M)

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 13 = 0.5000

19.43 m = 1.00

Tee / w. blind end

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 21 = 1.0000

38.87

Tee / w. blind end

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 12 = 1.0000

38.87

Tee / w. Valve

100.0

100.0

5.0

20.0

20.0

0.0064

0.0064

0.1

-

0.87

0.87

38.87 ζ 13 = 0.0500

1.94

R.(convern.flow)

100.0

80.0

5.0

20.0

20.0

0.0064

0.0038

0.1

-

0.87

1.44

16.58 ζ 12 = 0.0000

0.00 Coeff. negligible

Flow Meter

80.0

-

5.0

20.0

-

0.0038

-

0.1

51.22

1.44

-

R (Divern.flow) B.F.V. Control Valve Control Valve Y-type Strainer Check Valve

80.0 100.0 100.0 100.0 100.0 100.0

100.0 -

5.0 5.0 5.0 5.0 5.0 5.0

20.0 20.0 20.0 20.0 20.0 40.0

20.0 -

0.0038 0.0064 0.0064

0.0064 -

-

1.44 0.87 0.87

0.87 -

-

0.0064 0.0064

-

0.1 0.1 0.1 0.1 0.1 0.1

-

1.75

-

-

106.21

λ = 0.0339

106.21 ζ 12 = 0.1014 38.87 std. = 0.2400 38.87 std. = 0.2400

155.48

K = 2.0000

5.12 10.78 ξ = 0.65 9.33 9.33 XCV 3,000.00 TCV 3,000.00 466.43 Swing Type

KV2 / 2g K Factor have to refer to catalog (2 to 4) Plus Safety Factor 50%