PER UNIT SYSTEM
Per unit system A key problem in analyzing power systems is the large number of transformers. – It would be very difficult to continually have to refer impedances to the different sides of the transformers
This problem is avoided by a normalization of all variables. This normalization is known as per unit analysis In power system analysis, it is common practice to use per-unit quantities for analyzing and communicating voltages, current, power, and impedance values.
Per unit system These per-unit quantities are normalized or scaled on a selected base, allowing engineers to simplify power system calculations with multiple voltage transformations Therefore; actual quantity quantity in per unit = base value of quantity
Per Unit Conversion Procedure Pick a 1f VA base for the entire system, SB Pick a voltage base for each different voltage level, VB. Voltage bases are related by transformer turns ratios. Voltages are line to neutral. Calculate the impedance base, ZB= (VB)2/SB Calculate the current base, IB = VB/ZB Convert actual values to per unit
Per unit system Note: Per unit conversion affects magnitudes, Angles are not affected If the nominal value is chosen as the base voltage, a “normal” voltage value will be close to 1.0 p.u Also, per unit quantities no longer have units (i.e., a voltage is 1.0 p.u. volts) except under certain conditions
Advantages of per unit system ordinary parameters vary considerably with variation of physical size,
terminal voltage and power rating etc. while per unit parameters are independent of these quantities over a wide range of the same type of apparatus. In other words, the per unit impedance values for the apparatus of like ratings lie within a narrow range
It provide more meaningful information. The chance of confusion between line and phase values in a three-phase
balanced system is reduced. A per unit phase quantity has the same numerical value as the corresponding per unit line quantity regardless of the three-phase connection whether star or delta.
Advantages of per unit system cont’d Impedances of machines are specified by the manufacturer in terms of
per unit values. The per unit impedance referred to either side of a single-phase transformer is the same. The per unit impedance referred to either side of a three -phase transformer is the same regardless of the connection whether they are ∆-∆, Y-Y or ∆-Y. The computation effort in power system is very much reduced with the use of per unit quantities. Usually, the per unit quantities being of the order of unity or less can easily be handled with a digital computer. Manual calculation are also simplified. Per unit quantities simply theoretical deduction and give them more generalizes forms.
example •Example: nominal voltage at bus bar A is 132 kV and actual voltage at A is 127 kV. The per unit voltage at A is:
Rules for Choosing Base Values Choose ONE base power for the entire system Arbitrary choice Commensurate with the system e.g. 400V use 100kVA or 1MVA, 11kV use 10MVA, 132KV use 100MVA, 400kV use 1000MVA Choice also depends on rating of generators/transformers e.g. commercial/industrial building = mainly 400V use 100kVA distribution utility = mainly 11kV use 10MVA
Rules for Choosing Base Values cont’d Choose ONE base voltage for voltage level “of most interest” Choose the nominal voltage, Each voltage level must have one base voltage, between two base voltages the connecting transformer turns ratio must be maintained
Other base values chosen to get the same relations between per unit quantities as between actual quantities – electrical laws (ohms law,….) will not be broken under per unit system With the base power and base Voltage determined, the base current and base impedance can be calculated
Rules for Choosing Base Values cont’d • That is;
• For a three phase system,
Per unit example • Solve for the current, load voltage and load power in the circuit shown below using per unit analysis with an SB of 100 MVA, and voltage bases of 8 kV, 80 kV and 16 kV, respectively.
Per unit example cont’d Z BLeft
82 (kV) 2 = = 0.64W 100MVA
Z BMiddle Z BRight
802 (kV) 2 = = 64W 100MVA
162 (kV) 2 = = 2.56W 100MVA
Same circuit, with values expressed in per unit
Per unit example cont’d 1.0а 0 I = = 0.22�- 30.8�p.u. (not amps) 3.91 + j 2.327 VL =а1.0 �-0��0.22 2.327�30.8 90� = 0.859�- 30.8�p.u. 2
VL SL = = = 0.189 p.u. Z SG =а�а 1.0 =0.22 0 0.22 а 30.8 VL I L*
30.8 p.u.
Per unit example cont’d To convert back to actual values just multiply the per unit values by their per unit base V LActual = 0.859�- 30.8� �16 kV = 13.7�- 30.8�kV S LActual =а� 0.189 =а 0 SGActual =а� 0.22=а30.8
100 MVA 18.9 0 MVA 100 MVA
22.0 30.8 MVA
I BMiddle
100 MVA = = 1250 Amps 80 kV
Actual I Middle
= 0.22�- 30.8� �1250 = 275�- 30.8�A
Calculation in 3 phase “Homework” Solve for the current, load voltage and load power in the previous circuit, assuming:
–a 3f power base of 300 MVA, –and line to line voltage bases of 13.8 kV, 138 kV and 27.6 kV –the generator is Yconnected so its line to line voltage is 13.8 kV.
Change of MVA Base in per unit Parameters
for equipment are often given using power rating of equipment as the MVA base To analyze a system all per unit data must be on a common power base OriginalBase Z pu
Hence
NewBase � Z actual � Z pu
OriginalBase Z pu
2 Vbase
2 Vbase
� OriginalBase / NewBase = S Base S Base
NewBase S Base
NewBase ZOriginalBase � = Z pu pu OriginalBase S Base
NewBase Z pu
example
Example: A 350 MVA, 230/20 kV transformer has leakage reactance of 10%. What is p.u. value on 100 MVA base? What is value in ohms (230 kV)? 100 X e = 0.10 � = 0.0286 p.u. 350 230 2 0.0286 � = 15.1 W 100
• In general for change of MVA base,
• In cases where the new base Voltage equates to the old base voltage, then;
Calculation example questions • A 3phase two winding transformer is rated at 75MVA, 11.8/145kV, 50Hz and the equivalent leakage impedance referred to the 11.8kV • Using the transformer ratings as base values, determine the per-unit leakage impedances referred to the 11.8kV winding and the 145kV winding. • winding is Zeq = 0.22Ω
Example question 2 For the power network shown below calculate using per-unit quantities the voltage in kV, the current in kA and the power in kW received by the load • • • • •
G1 = synchronous generator = 75MVA, 11.8kV, sync reactance Xd = j1.83 p.u. T1 = generator transformer = 75MVA, 11.8kV/145kV X = j0.125 p.u. L1 = 132kV transmission line: Z = 0.18 + j0.40 Ω/km, length = 20km. T2 = step-down transformer = 45MVA, 132kV/11kV, X = j0.125 p.u. ZL = 11kV load = 10MVA, cosɸ = 0.8 (lagging).