TEACHING NOTES ON NEAL’S SINGLE LINE BALL TOKEN BLOCK INSTRUMENT
SIGNAL & TELECOMMUNICATION TRAINING CENTRE, BYCULLA, MUMBAI ( I S O 9001-2000 CERTIFIED )
.
SINGLE LINE BLOCK.
CONTENTS
2
PAGE NO.
1. INTRODUCTION
03
2. VARIOUS PARTS OF NEALE’S INSTRUMENT AND THEIR USES.
06
3. POLARITY OF BALL TOKEN B/INSTRUMENTS
11
4. CIRCUITRY EXPLANATIONS
11
5. MODIFICATIONS IN R.E. AREA
13
6. TESTING OF BLOCK INSTRUMENTS
14
7. FAULT FINDING
16
8. BLOCK EARTH
17
9. TOKEN BALANCING
18
10.CIRCUMSTANCES WHERE B/INSTT. KEPT SUSPENDED
19
11.DO’S AND DON’TS, MAINTENANCE
20
12.MAINTENANCE SCHEDULE FOR NEALS B/INSTT.
21
13.TROUBLE SHOOTING
23
.
SINGLE LINE BLOCK.
3
LESSON: ONE SINGLE LINE TOKEN BLOCK INSTRUMENT A. INTRODUCTION: Block instrument is used for controlling the trains in between two stations. The object of providing block instruments is to prevent more than one train in the block section at a time, and when the block section is clear it should be possible to admit one train in to the section from either of the two ends, thus guaranteeing absolute Safety in the running of trains at all time, maintaining space interval between two trains. To achieve this two block instruments are inter connected electrically and provided one at each end of the block section. Authority to proceed in to block section is a token in single line section. Thus block instrument is called TOKEN BLOCK INSTRUMENT. This instrument is designed to have conscious co-operation of the two Stationmasters at either end of the block section for electrically releasing a Token from any one of them. Mechanism & system are provided in such a way to ensure that only one token can be released at a time from either of the instrument connected electrically. This block instrument is used in single line section where number of trains is less. B. ESSENTIAL OF ABSOLUTE BLOCK SYSTEM (GR 8.01): (1). Where trains are worked on the Absolute Block System: a) No train shall be allowed to leave a block station unless Line Clear has been received from the block station in advance. And b) On double lines such line clear shall not be given unless the line is clear, not only up to the first stop signal at the block station at which such line clear is given, but also for an adequate distance beyond it: c) On single lines such line clear shall not be given unless the line is clear of trains running in the same direction, not only up to the first stop signal at the block station at which such line clear is given, but also for an adequate distance beyond it, and is clear of trains running in the direction towards the block station to which such line clear is given. (2). Unless otherwise directed by approved special instructions, the adequate distance referred to in clauses (b) & (c) of sub-rule (1) shall not be less than: a) 400 meters in case of two-aspect lower quadrant signaling or two-aspect colour light signaling, and b) 180 meters in case of multiple-aspect signaling or modified lower quadrant signaling.
.
SINGLE LINE BLOCK.
4
C. GENERAL REQUIREMENT OF BLOCK INSTRUMENTS: 1) CONSTRUCTION & TYPE: All block instruments must be robust type construction and of a type approved by the Commissioner of safety. 2) LIGHTENING PROTECTOR: All instruments must be provided with an efficient lightening protector. 3) PREVENTION OF IRREGULAR OPERATION: There must not be any opening giving access to the interior of the instrument, through which it is possible to operate the mechanism by any irregular means. 4) LOCKING & SEALING FACILITIES: Both locking & sealing facilities must be provided on the instruments. 5) ISOLATION OF TELEPHONE CIRCUIT: Telephone or telegraph instruments must be provided in conjunction with block instruments. It is desirable that the condenser or other means provided for isolating the telephone circuit from the instrument circuit is located within the instrument. 6) PREVENTION OF UNAUTHORISED OPERATION: A lock or other device should preferably be provided to enable the station master to prevent unauthorized manipulation of the instrument during his absence. SM’s key prevents the unauthorized operation. D. SPECIAL REQUIREMENTS (FEATURES) OF SINGLE LINE TOKEN INSTRUMENTS: GENERAL: This block Instrument is of robust construction and of a type approved by the Commissioner of Railway Safety to with-stand rough handling by non technical staff, not only at the Block Stations, but also at out laying siding controlled by the token of the block Section. a) OPERATION BEFORE GIVING LINE CLEAR: The instrument is so designed that the SM has to go through definite moving operations on the instrument in addition to the working of bell, key or plunger. (1) Before he can give Line clear to the S.M. at the other end of the section to release a token and (2) Before he can obtain a token, even with the permission of the S.M. at the other end of the section (SEM para 207). b) FIXED INDICATIONS: The instrument receiving Line clear show a definite fixed indication that a token has presumably been extracted and similarly the instrument giving Line clear also shows a definite fixed indication that permission has been given for the extraction of token. Such indications are locked immediately a token is extracted and so remain until the token is replaced in one of the instruments (SEM Para 208). c) EXTRACTION OF TOKENS: Both Instruments must be restored to normal before a further operation of extracting a token can be carried out. It should not be possible to restore the instruments to normal without the co-operation of the S.M. of the other end. (SEM Para 210). .
SINGLE LINE BLOCK.
5
d) INTERLOCKING LAST STOP SIGNAL: Provision shall be made for interlocking the L.S.S. with the “line clear Indication” of the block instruments. (SEM Para 213)
e) CURRENT INDICATOR: An indicator, operated by incoming and outgoing line currents must be provided (SEM Para 209).
f) OPERATION OF LINE CLEAR RECEIVING AND GIVING MECHANISM: It must not be possible for the mechanism which permits a line clear to be received and that which permits a line clear to be given to be in operation at the same time. (SEM Para 211)
g) DESIGN OF INSTRUMENTS:
(a)
The instruments must be so designed that a token of one block section can not be placed in the instrument of an adjacent section.
(b)
The token for each section must be engraved with code initials of the stations at both ends of the block section and with a serial number (SEM Para 212).
TYPES OF NEALE’S TOKEN INSTRUMENTS:
.
(i)
Block Instrument Single Line, Neale’s Ball Token, Type ‘A’(SA 20701) fig.1
(ii)
Block Instrument, single Line, Neale’s Tablet Token, Type ‘B’(SA 21701) (not used in C.Rly.).Fig. 15.
SINGLE LINE BLOCK.
6
LESSON: TWO NEALE’S BALL TOKEN BLOCK INSTRUMENTS: A. PARTS: 1. BELL UNIT: This is used to communicate the prescribed bell code to the Station at the other end. The bell is of single stroke type. It works in the local circuit in series with one of the two locks coils viz. ’TCF’ or ‘TGT’ through the contact of the polarized relay, which operates with line current. Its coil resistance is 28 Ohms & minimum-working current is 80 mA. 2. POLARISED RELAY: This is a three-position relay, which works on the line current. The movement of the contact spring depends on the polarity of the line current. It has a resistance of 77 ohms and has a pick up value of 15 to 18mA and rated current of 25mA. 3. NEEDLE INDICATOR (GALVO): This an electromagnet coil of 150 ohms and requires a working current of 15 to 25 mA. A Needle is attached to the front of an axle, which moves between two permanent magnets situated inside. The needle is free to move either side depending on the direction of current. It is used to detect the presence of incoming & out going current. An anti-clock wise deflection of needle always indicates the operating handle is in one of the two turned positions namely TCF or TGT. The clock wise deflection indicates that the operating handle is in the vertical (line closed) position except when a token is inserted in to the instrument with the operating handle in either TCF or TGT positions & plunger is pressed. 4. FORCE DROP ARRANGEMENT: It is a mechanical arrangements adopted to ensure that the lock controlled by an electro magnet becomes effective (i.e. equipments get locked) after the de-energisation of the lock coil. NEED: any lock control/operated by an electro magnet gets released whenever the lock coil is energized and the lock becomes effective (equipments get locked) once the lock coil is de-energized. But if due to residual magnetism or mechanical friction, the armature of the electro magnet remains stuck up in energized position even after the supply to the coil is cut off, the lock will become permanently free and will not effective for future operation, which is unsafe. So to prevent this unsafe condition, force drop arrangement is provided. In Neale’s Block Instruments, force drop arrangement for TCF/TGT lock is very important from safety point of view. It is achieved through the bent lever and projection made on lock replacer disc. TCF&TGT LOCKS WITH FORCED DROP ARRAGNEMENT: These two locks are identical and their coils are wound to a total resistance of 28 ohms and require an operating current of 160 mA at a minimum working voltage of 4.5V. The units with the armature and rocker arm in position are not interchangeable between the two. The rocker arm is fixed to the base of the lock coil assembly, the armature, which is free to move, carries a lock on a spindle at one end. The .
SINGLE LINE BLOCK.
7
pawl (TCF/TGT) normally rests on the cam projection of the lock replacer disc, thus mechanically ensuring the locking of the operating handle through the locking of rack. The pawl (TGT/TCF) drops only when the operating handle is pulled out of the slot. When the lock coil is energized and the operating handle is pulled out, the armature is attracted fully and lifts the locks from the locking notch in the rack. This permits the operating handle to be turned either to ‘TGT’ or ‘TCF’ position depending on whether TGT coil or TCF coil is energized. The TCF coil energizes for three operations i.e. I) For turning the operating handle from line Closed to TCF. II) For turning the operating handle from TCF to Line closed. III) For turning the operating handle from TGT to Line closed. The TGT coil energizes only once for turning the operating handle from Line closed to TGT position. The lock replacer disc has four projections A/B/C/D on its periphery (Fig.2). The three projections A/B//C are of the same size all these projections ensure forced dropping of the locks. The fourth projection ‘D’ is deeper than the other three projections and forces the TGT lock pawl down even when the operating handle is in pulled position. When the operating handle is turned about one third from Line closed position towards TGT, the projection engages with the lever of the TGT lock. This coincides with the momentary interruption of the line current by inter-stoke interrupter (jerking contacts) with the momentary interruption current. TGT coil is de-energized and the TGT lock pawl is forced down by this projection on the rack and thus lock pawl engages in the check lock position. Lock pawl is again released only when the line circuit is completed by the jerking contacts when the operating handle is turned a little further and the other station is continuing to keep the tappet rod pressed thus prolonging the last beat. 5.INTER STROKE INTERRUPTOR (JERKING CONTACTS): Two contact pieces with a gap between the two are provided on a bakelite mounting on the spring clutch shaft. In the line closed position of the operating handle, the line circuit is made through by two springs resting on the bottom contact piece. When the operating handle is turned, the clutch shaft is also rotated by a rod connected to the pinion on the operating handle. Due to operation of the operating /bottom handle, the contact spring moves over from the bottom contact piece to the top piece causing a momentary break in the line circuit. This will cause a deflection in the needle indicators. The deflection indicates to the S..M. at the current sending end that the operating handle is being turned at the other station. 6. CONTACT ARRANGEMENT: This consists of four finger springs mounted on a insulated lever below the commutator. The lever moves in an arc through a connecting rod which moves whenever the plunger is pressed. This will result in the spring making contact with the segments mounted on the commutator. As seen from the back of the instrument, battery terminals are connected to the first and third finger springs and earth to the second spring and line through Galvanometer to the fourth spring, the commutator in line closed position of operating handle puts through springs 1.2 & 3,4 when the plunger is pressed. .
SINGLE LINE BLOCK.
8
When the operating handle is turned to TCF or TGT, Springs 1,4&2,3 are put thorough by commutators thus reversing polarity of applied voltage.(fig.3). 7. SAFETY CATCH (Fig.4): This is a small steel piece in a hook form resting on a small projection on the spring clutch shaft. This catch plays a very important role in preventing the declutching of the commutator shaft when the operating handle is being turned from Line closed position to TGT or TCF position and in the turned position of the handle the projection moves away from the safety catch and this permits the de-clutching of the commuator shaft when the token is inserted and the plunger is pressed. If the safety catch is not provided or if it is not functioning properly and if the cummutator shaft is not free due to jamming or for any other reason then the spring clutch shaft would declutch and turn over with the operating handle, when the operating handle is being turned from Line closed to TCF position, for granting permission to approach, there by leaving to commutator normal. As there is no change in commutator the operator at the dispatching end can turn his handle to TCF position only and cannot go to TGT position. This results in block failure. If, however, the commutator shaft sticks in the instrument receiving “Line clear” then the handle would have been turned to “TGT” thereby obtaining a token but having the commutator in normal position. It would create an unsafe condition as under. After departure of the train, the train receiving station can turn the handle to “Line Closed” since the commutator is normal at the train sending station. Also at the train sending station, the operating Handle can be turned to “Line closed” with the co-operation of the train receiving station. Under these conditions both the instruments would be in line closed position with a train in the Block Section. Hence maintenance staff/Inspectors should take special care regarding the proper functioning of the Safety catch. 8 S.M’s LOCK: S.M. lock is a mechanical locking provided on a block instrument, to prevent an unauthorized operation of the block instrument in the absence of the Station Master. SM’s key when out will mechanically lock the operating/ bottom handle and Top Handle, thus preventing them from manipulation. Operating/Bottom handle can be locked in any of the three positions. SM lock up key when out will also disconnect the line battery and thus unauthorized bell codes cannot be sent to the other station. However incoming bell codes are not affected. 9. TOKEN RACES OF A BALL TOKEN INSTRUMENT: There are four races and a token dropped into the instrument, can get into any of the four races at random. Thus, it is not possible to know in advance the serial number of the token that will come out next. 10 TOKEN INDICATOR (Fig.5) : This is a mechanical indicator gives an indication to the operating staff whether any token is present in the bottom handle or not. It works on the principle of gravity drop. An “S: shaped swinging lever is pivoted on the token selector plate. The top end carries a flag indicator painted red & green and mounted in a such a manner as to be seen through a glass opening in the front of the
.
SINGLE LINE BLOCK.
9
instrument. Its bottom is rounded off & presses against a token in the token drum & displays a green indication. If there is no token, the lever revolves under its own weight & the rounded end enters in to the empty space in the token delivery drum locking the same and prevents the bottom handle being turned to TGT when there is no token in the Instrument and changing the indication to red. This however does not prevent bottom handle from being turned to TCF position. 11. SUPER IMPOSED TELEPHONE: A telephone is superimposed on the line wire by means of an induction coil and a condenser. The condenser isolates the telephone circuit from the Block Instrument Circuit. The Telephone is lying on the bracket which disconnects the Telephone circuit from other circuit. 12. TOP HANDLE (TOKEN RECEIVING DRUM): It is a cylindrical cast iron drum with recess to take one token. The recess opens at the top through an aperture in the drum housing normally covered by a hinged metal cap. In this position the arrow marked on turning handle faces vertically upwards. A token is inserted into the instrument by placing it in this recess by lifting the hinged cap and then turning the handle anticlockwise (by handle provided on the front) through approximately 190 degree. The recess is provided with a small fixture called the “Spigot”. The shape of the Spigot corresponds to the hole configuration on the token used in the block section. The purpose of this Spigot is to prevent insertion of a wrong class of token to clear the section. Two spring operated lock pawls are located one each at approximately 85 & 170 degrees with in the drum housing. These lock pawls normally press against the surface of the drum and do not therefore, interfere with its movement if it is turned with a token of correct dimension in its recess. Should the drum be turned in the anti clock wise direction with its recess partially or completely empty, the first lock pawl at 85 degree from the vertical position gets into the token recess and checks its further rotation. Should the first lock pawl fails to detect the correct token in the recess, the second lock pawl will check rotation beyond 170 degree. The token so consigned is led through chute (which has no bottom) whose sides are carved sufficiently inwards to guide the token. The token enters the recess directly in the line closed position of the Bottom Handle, But in the other positions of the handle it rests on the token receiving jaw. The chute ensures that foreign objects (such as , bolts or nuts) inserted into the token receiver will not run down into recess but will fall right through to the bottom of the instrument. The top handle is provided with a lock, to lock it in the turned position between 75 to 85 degree, by removing the SM’s key. This arrangements prevents the insertion of the token in the absence of the Station Master on duty. 13.BOTTOM HANDLE – OPERATING HANDLE – BLOCK HANDLE WITH TOKEN DELIVERY DRUM: The bottom handle is situated at the front middle bottom of the Instrument. The tappet rod is threaded through the centre of the handle. The handle has three positions which gives the condition of the block Section as indicated below (Fig. No.6). (a)The handle with its arrow pointing vertically upwards indicates Line Closed. This is normal position. (b)The handle with its arrow points to the right, indicates that Line clear for a train, has been given. This is called the “Train coming from (TCF) position.
.
SINGLE LINE BLOCK.
10
(c)The handle with its arrow pointed to the left, indicates that Line clear has been obtained and a token extracted. This position is called ”Train Going To”(TGT). The token delivery drum forms an extension of the operating handle and is a heavy cast iron cylinder with a suitable recess in it to house one token. From this, the token is delivered when it comes out of the opening in the front when handle is turned to the TGT position. A toothed section (Pinion) is mounted on hexagonal extension at the end of the drum which works a rack below it every time the block handle is turned. A rod connecting this sector to the spring clutch shaft and the token selector causes both these to rotate along with the handle. The movement of the rack, when the handle is turned is prevented normally by two locking pawls engaging with notches cut in the rack as shown (fig.2). The movement of the handle from any particular position (Line Closed, TCF or TGT) is possible only when the proper locking pawl has been released from the notch in the rack which can happen only through the co-operation of the distant station. 14. TOKEN POUCHED AND HOOPS: The token extracted from block instrument, to hand over it to the driver to enter into the block section with his train, is protected by token pouch. The pouch is attached to the Line clear hoop/stick. This prevents the token from damage while handing over or receiving the token by a driver of a through running train. The pouch/hoops/Line clear stick are periodically checked and damaged pouches/hoops/Line clear sticks are not allowed to be used. 15.LAST STOP SIGNAL CONTROL: a) MECHANICAL : A separate ‘E’ type lock is attached on the TGT side of the instrument to have a mechanical control over L.S.S. A small extension piece is screwed on to the rack on the TGT side. In the normal and TCF positions of the operating handle, the plunger of this lock will get obstructed by the extension piece of the rack due to which the key of the same can not be taken out . In the TGT position of the operating handle only the rack comes out of the lock enabling it to be locked by taking out the key. This key is utilized to take off the LSS either by inserting it in the mechanical lock on the LSS lever or utilizing it to release the SM’s control Instrument. Once this key is taken out of the lock, the lock plunger will foul the rack and the operating handle cannot be turned from the TGT position unless and until the L.S.S. control key is brought back, put back into the lock and turned. (The details are given in figure 11). b) ELECTRICAL: A metallic extension piece attached to the lock replacer disc which is called TGT stud, bridges two contact springs when the block handle is tuned to TGT position. The L.S.S. Reverser feed is taken through this contact, ensuring that the L..S.S. can be taken off only when the block handle is turned to TGT position. On single line sections where Token block Instruments are provided, the following controls must on the L.S.S.
.
(I)
One slot, one train.
(II)
Provision for automatic replacement of L.S.S. with the passage of train.
SINGLE LINE BLOCK.
11
16. CLASS OF BALL TOKENS: The tokens used in Neales Ball token Instruments are hollow round steel balls. They have a through groove cut on a diametric axis which have one of the following configuration. (A)Round hole. (B)Rectangular hole. (C)Triangular hole (D)Four sides hole. (E)Five sides hole. Different hole configurations are provided to distinguish the tokens belonging to block Instruments of different block sections. It ensure that a token belonging to instrument of one block section can not be inserted into an instrument belonging to an adjacent block section thus preventing wrong normalization of Block. The different hole configurations viz. Classes A,B,C,D,&E are as shown in the figure(7)
. Polarity
B In a pair of instruments used for a block section, one instrument is wired for normal polarity and the other for reverse polarity(Fig.8) In normal polarity instrument, the positive of the Battery is connected to the line, when the tappet rod is pressed in the “Line Closed” position of the bottom operating handle. Further a positive polarity on the line is required to turn the operating handle to TGT position. In reverse polarity instrument, the Negative of the battery is connected to line when the tappet rod is pressed in the “Line Closed” position. A negative polarity on the line is required to turn the operating handle to TGT position. The reasons for providing a pair of different polarity instruments is to prevent the possibility of obtaining two tokens simultaneously one at each end of the section in the event of the block line coming in contact with another conductor of favorable polarity. A normal polarity block instrument can be converted into reverse polarity or vice-versa if necessary by reversing the connections of (1) Galvo (2) polarized relay and (3) line battery and altering the terminal designations. The Block Instrument has a capacity of 36 tokens. Normally 32 or less tokens only are used in a pair of instruments.
C. CIRCUITRY EXPLANATION: Working of the block instruments: (To dispatch a train from station A to station B) ‘A’&’B’ are two adjoining Stations (fig 8) provided with normal and reverse polarity Instruments respectively connected by overhead line wire with earth or Metallic return. SM at ‘A’ has to dispatch a train to ‘B’. ‘A’ asks ’B’ for “Line clear” on telephone and then by sending the authorized bell code signals and prolongs the last beat. The prolonged beat energizes the TCF lock coil at ‘B’ and lock pawl clears the rack for moving the block handle from line closed to TCF position. On seeing the needle deflection A releases the plunger. The Ckt. is shown in fig.9 Needle indicator at ‘A’ & ‘B’ deflects to the right . The tongue of the polarized Relay at ‘B’ deflects to ‘R’ completing a local series circuit of block bell and TCF lock coil. When .
SINGLE LINE BLOCK.
12
the handle is being turned at ‘B’, there will be a jerk in the indicator needle, both at ‘A’ and ‘B’ due to jerking contacts momentarily breaking and again making. The block handle having been turned at station ‘B’ to TCF position the commutator is reversed at that station. Plunger at ‘B’ is pressed will now send a +ve current on line. ‘B’ now sends authorized bell code signals to ‘A’ and prolongs the last beat. ‘A’ having a steady deflection of the top of the needle to the left turns his block handle from Line closed’ to ‘TGT” position and obtains a token. The Ckt is shown in fig.10. The tongue of the polarized relay at ‘A’ is attracted towards ‘N’ completing local circuit for the block bell and TGT lock coil in series. There is one bell beat at ’A’ and the TGT coil being energized and armature is attracted. TGT lock pawl is lifted when block handle at “A” is pulled for operation, and the handle is free to be turned to TGT position While the block handle is being turned to TGT position, if the train receiving station releases the plunger, the block handle at the dispatching station gets locked in the check lock position and can not be fully turned to TGT position. So continuous co-operation by pressing plunger is given by the train receiving station to turn when the handle to full TGT position at ‘A’ and a Token is delivered. In this condition of the block handle, either the LSS control key can be extracted (fig.11) or the LSS electrical control contact is made. In the case of mechanical control, the key extracted from the block Instrument is used either in the SM’s control apparatus or in the signal lever controlling the LSS. Once the train clears the LSS, the signal is put back to ON position. Train entering section code is sent to the stations in advance. The LSS control key is inserted into the block instrument at ’A’. Driver on arrival at ’B” hands over the token to SM. S.M. at B calls attention of SM at ‘A’ and on being acknowledged inserts the token into his Instrument. And gives bell signals for ‘train out of Section’. This changes his commutator to Normal “B” prolongs the last beat and SM at ‘A’ observing the indicator needle deflection turns the handle from TGT to ‘Line closed’ position. This changes his commutator also to normal. The Ckt. shown in fig. 12 . ‘A’ now acknowledges the “train out of Section” signal prolonging the last beat, Commutator at ‘A’ having been changed to normal, the prolonged beat energizes the TCF coil at ‘B’ enabling him to turn his block handle from TCF to ‘Line closed’ position both instruments are now in ‘Line closed position.” CANCELLING OF LINE CLEAR: After obtaining line clear and extracting a token, if SM at ‘A” does not dispatch a train for any reason, he can cancel the “Line clear”. ‘A’ informs ‘B” about his intention of not dispatching the train and inserts the token into his Instrument. ‘A’ sends bell signals to ‘B’ for cancelling line clear, prolonging the last beat. The insertion of token and plunging changes his commutator. The polarized relay at ‘B’ is energized to release the TCF lock which enables him to turn his block handle to line closed from TCF position. The station B acknowledges the cancelling signal prolonging the last beat. This enables A to turn the block handle from TGT to Line Closed position. NOTE : Station having token should turn the block handle to normal at last. .
SINGLE LINE BLOCK.
D.
13
Modification in RE area:
Additional requirements in 25 KV 50 Hz electrified areas :Any circuit in the vicinity of 25 KV AC electrified section is likely to be influenced by electrostatic and electromagnetic induction. These induced voltages may cause undesirable and unsafe conditions on signal and Telecommunication equipment. So protective measures are adopted to minimize unsafe condition due to induced voltage. When these instruments are to be used in 25 KV AC electrified areas, a filter circuit in conjunction with a Train wire and Block Bell Equipment is used and the circuit is modified as shown in fig. 13. X & Y relays are introduced to prevent the operation of the polarized relay by the condenser of the filter unit discharging through it after plunger is released. X being slow to release puts through the shunt resistance of 5,000 ohms across the condenser when plunger is released thereby discharging the condenser through the resistance and protecting the polarized relay. FSS PROVING CIRCUIT: As per GR 8.03(2-B) at a class B station on single line , the line shall not be considered cleared and line clear shall not be given unless. All necessary signals had been put back to ON behind the said train. To fulfill this requirements a GPR relay (receiving signal normal proving relay is used. Front contact of this relay is proved in the energisation circuit of TCF coil. GPR in energized condition proves that first stoop signal is at ON position.(as shown in fig. No. 8).
.
SINGLE LINE BLOCK.
14
LESSON: THREE TESTING OF INSTRUMENTS: Test to be conducted after installation and before commissioning the instrument. Check that the correct polarities are connected to the instrument at both ends. This can be checked as follows. (a) With the commutator in normal position when the plunger is pressed, the feed on the line must be positive and earth negative for a N P instrument. To check this connect the volt meter positive lead on line terminal and negative to the earth terminal. The volt meter should give a forward deflection for the correct connection when plunger is pressed. Similarly for R.P .instrument check that the feed on Line is negative and earth +ve. (b) With incoming positive polarity on line, in a N P Instrument polarized relay should deflect towards left/(TGT side) & with (-)ve incoming polarity on line a R. P Instrument the polarized Relay should deflect towards left (TGT side). (c) Where earth return is used, check the earth resistance If it is more than 10 ohms suitable measures should be taken to reduce this. (d) Check that all mechanical parts are free to move without undue friction and that there is no jamming of moving parts. (e) Connect the two block Instrument in the block section. Do not energize any of the lock coils, try to forcibly turn the operating handle to “Train going to” and “Train coming from “ positions. It shall not be possible to turn the handle, of either of the instrument either to TGT or TCF positions. This ensures that the TGT & TCF locks are properly functioning. (f) Energize momentarily the TGT lock coil of either instrument as in the normal operation. Turn the operating handle slowly towards TGT, when the lock pawls is out of notch in the rack, de-energize the lock coil and turn the handle. Ensure that the lock and pawl engages the check lock notch in the rack, and the handle can not be turned further, till the lock coil is re-energized. (g) Energize momentarily the TCF lock coil of either of the instruments. Turn the block handle to TCF. There is no check lock in the TCF side. (h) With the bottom/operating handle in TGT position and without energizing the TCF lock, try to force the block/operating /bottom handle to line closed position. It shall not be possible to do so unless the coil is energized. Repeat the test with the handle in the TCF position. (i) Extract tokens in the normal sequence of operation and restore the instrument to the line closed position. (j) Extract a token and replace it in the same Instrument as is done in the case of canceling “Line clear” and see that the commutator changes when the token is plunged in. Repeat the above operations ten to twelve times. .
SINGLE LINE BLOCK.
15
(k) Check the commutator does not changes unless the token gets into the races in the case of ball token instrument and slides down the rail beyond the tablet receiver in the case of tablet token instrument. Also ensure that the token does not enter the recess or slides down the beyond the tablet receiver unless the commutator changes. Repeat this ten to twelve times. (l) Check that operating handle remain locked when the instruments are out of phase i.e. when the token is out of any of the block instrument. (m) With operating handle in the line closed positions when the bell plunger of the Normal polarity instruments is pressed, check that the needle indicator at both the stations deflects towards the right. If it does not, battery terminals are not properly connected. (n) Put all the 36 tokens in either block instrument and ensure that there is no jamming of token. (o) Remove all tokens from the instrument and ensure that the token indicator functions properly and prevents the block handle from being turned to “Train going to” position from “Line closed” position. It shall not prevent the handle from going to “Train coming from” position. (p) Turn the handle to ”TGT” positions slowly and see that the Token is not released from the instrument before reaching the “TGT ”position. (q) Check that even after the handle is turned to “TGT” position the token is not delivered until the block handle is locked in the notches on the body. This test is required to ensure that “TGT” lock is forced dropped before the delivery of a token from the Instrument. Otherwise it would be possible to return the handle to normal and come to “TGT” again with a second token in case of TCF lock sticking up of lock armature due to residual magnetism or Mechanical faults. (r) Extract a token in the sequence of operation and check the cancellation of “Line Clear” for its’ proper functioning. (s) Check and ensure the full deflection of the needle indicator. (t) Check that the safety catch is functioning properly and prevents the declutching of the spring clutch shaft from the commutator shaft whenever the operating Handle is turned from “Line Closed” to “TCF” or “TGT” position.
.
SINGLE LINE BLOCK.
16
FAULT FINDING: CREATE THE FOLLOWING FAULTS & CHECK RESULTS: (a) Both the instrument in ”Line closed” position. ________________________________________________________________________ Nature of faults Whether token can be Whether token can Obtained at to be obtained at (Normal Polarity) (Reverse Polarity) Station ‘A’ Station ‘B’ ________________________________________________________________________ (i) Positive of foreign source on line & negative on earth YES NO (ii) Negative of foreign source on line & positive earth
NO
YES
(b) With instrument ‘A’ in ”TGT” and at ‘B’ in “TCF” position.
(i) Positive of Foreign source NO NO ‘B’ can turn his on line & negative on earth handle to line Closed _______________________________________________________________________ (ii) Negative of foreign source No NO. A can turn his handle to on line & positive on earth. line closed
.
SINGLE LINE BLOCK.
17
LESSON: FOUR BLOCK EARTH Instructions in various manuals (Maintenance / construction) (a) All Block earth and their connection must be examined at intervals of not less than one month. (b) All block earths must be tested for resistance at intervals of not more than 12 months and where the resistance exceeds 10 ohms action should be taken to reduce the resistance. Where it is not possible to reduce the resistance of earth within the maximum value, additional earths may be provided in parallel (Para 944) all earths installed for protection circuits should be simultaneously tested at least once a year. Metallic Return wire is to be provided in electric traction area.
Metallic and earth returns: (a) Earth wire should be as short as possible. It should be of a cross-section not less than the size of the line wire and should not be smaller than 4mm dia. It should be adequately secured or supported and must not have any spiral or bend. (b) Earth wire should be adequately protected from mechanical injury and be efficiently connected to Earth. (c) All connections to an earth must be well-soldered. (d) It is desirable to have a metallic return to take care of multiple failure as recommended in block manual. (e) The block wire should be placed on top of the alignment so as to preclude the possibility of foreign feed injunction in to the block line. (f) Lightening discharger of striking voltage greater than normal working voltage may be provided at both ends of the block line. Measuring of block earth resistance, out going and incoming current: 1) Block earth must be tested within 12 months. 2) Earth resistance shall not be more than 10 ohms. 3) Method of finding out Resistance of Earth. a) earth should be measured by means of whetstone bridge or G.P. O. detector or megger or earth tester. Two iron bars with terminals fixed on them and suitable length of wire should be used as temporary earths. b)to test an earth two iron bars should be driven about 6 meters apart from the earth to be tested. The bars should be used as temporary earth and driven in the .
SINGLE LINE BLOCK.
18
ground for 1 meter at a time then worked backwards and forwards so as to leave as pace forwarding 0.2 meter. Salt water should be used to ensure that the bars make a good connection with the earth. If salt water not available a weak solution of Salammoniac in water may be used. E1 Earth under test. E2 Temporary earth. E3 Temporary earth R1 Resistance between E1& E2 R2 Resistance between E1& E3 R3 Resistance between E2 & E3. Resistance E1 = R1+R2-R3 2
Measuring of outgoing and incoming current: For measuring outgoing & Incoming current disconnect line wire from line terminal and connect amp. Meter between line wire and line terminal.. Press the bell plunger of the same instrument. Ensure that the outgoing current does not exceed the rated current of polarized relay. This is meant to ensure that in no circumstances the polarized relay is over energized.
Token Balancing: (a) Maintainer must , whenever necessary transfer tokens from the instrument in which these have accumulated to the Instrument at the other end of the Section. Each Maintainer in charge of single line token Instrument must be provided with a “Token Balance Book” consisting of Form No.1 S&T / TB annexure ‘G” serially numbered. Each book before issuing must be endorsed by the issuing inspector as under : “Pages ______________________________to ______________ checked and found correct” b) Maintainers should extract an even No. of Tokens for transferring. c) Maintainers must fill up portion ‘A’ & ‘B’ of token Balance Book form and take the signature of i) SM of the Station from where tokens have been extracted to verify that the token number as mentioned were extracted from the instrument with his permission. ii) The receiving SM to verify that token numbers mentioned in the book have been correctly deposited in the relevant instrument. d) SM must have instructions to advise the Maintainer by Wire/Control message as soon as the balance of Tokens in their token balance register falls to ‘Six” except where token balances are in use (Para 741). e) tokens which are deformed or have worn out under size or cracked or damaged in any other way should be removed. Advice of removed tokens should be given to all concerned by wire. f) A lost token should be replaced with a Token of the next higher number in continuation of the series in use on the Section in accordance with instructions .
SINGLE LINE BLOCK.
19
Balancing of Tokens: Signal Maintainers (Electrical) must comply with instructions regarding balancing of tokens laid down in Para 741 Entries in the Token Balance Book must be made legibly In ink”.(Para-1408). The Neale’s Token Instrument shall be considered as having failed and working of the Block Instrument shall be suspended in the following circumstances: 1) When bell signals are received indistinctly or fail altogether. 2) If the needle of the galvanoscope fails to move, when bell signals are given or received or shows a wrong indication viz. to the right instead of left and viceversa. 3) When a token is broken or damaged in any way during or after extraction. 4) If a token can not be taken out from the instrument after proper signals have been exchanged and no token is out from either instrument of a section. 5) When a token can be taken out from the instrument without proper signals being exchanged with the station at the other end of the section. NOTE : This test shall be made when the operators take change of the block instrument. 6) If a Token can not be put back into instrument or jams when being put back into the instrument. 7) If a train arrives at a station without a token referring to the block section over which the train has passed. 8) When the Token belonging to a block section has been over carried to another station or is lost and can not be found. 9) When there is no token in the Instrument at the station from which a trains ready to start. 10) When there is reason to believe that there is contact between the block wire and any other circuit (Permanent or intermittent deflection in Galvo or irregular bell beats heard without pressing the plunger on either end.) 11) If the operating handle can not be turned to any one of the three positions with a prolonged beat from the distant station. 12) If the operating handle can be turned to any one of the three positions without prolonged beat from the station at the other end. 13) If the dial glass of galvanoscope is broken. 14) If the instrument or is battery counter is found unlocked. 15) When the key of the token receiver drum is lost or the lock is out of order. 16) When the key of the clamp locked on the token handed over to the proceedings train, is returned to the station in rear by the officer in charge of the motor trolley following that train. 17) When a private number can not be obtained from the Station Master at the other end of the Section through the Block telephone. 18) If it is known that the Instrument is defective in any way not specified above.
.
SINGLE LINE BLOCK.
20
LESSON: FIVE DO’s and Don’ts: a) Do not bend the contact spring specially the finger contacts, unless absolutely necessary to obtain contact pressure. b) Do not bend the TGT and TCF Pawl unless absolutely necessary to adjust the force dropping action. c) Do not allow the Block Instrument to be in the circuit, if the safety catch on commutator shaft is either broken or not functioning properly. d) Do not file the rack notch or lock pawls, if they are not properly engaging, remove them and re-adjust. e) Do not open the polarized relay; if the seal is broken for any reason, it must be removed from the circuit. f) Do not make the SM’s lock up contact through under any circumstances. g) Check the tablet releaser actuating link screw is intact. If these screws are not in the position the tablet token can be released before operating the handle is locked in the TGT position.
LOCKING AND SEALING ARRANGMENTS: A sealing screw is provided in the back of the instruments which can be used for sealing. In addition to this sealing facilities locking arrangements also is provided to lock the instrument by maintainer (SM’s lock and Maintainer’s lock
MAINTENANCE OF TOKEN INSTRUMENTS: 1. Check that ball tokens are correct size otherwise it will get jam in the races of block Instrument. 2. The Needle Indicator ( Galvo ) must be maintained properly so that they operate and return to normal position correctly when released. The direction of the needle must correspond to the polarity of the current flowing through. 3. Care must be taken to see that the token indicator on the ball token instrument is free to move . The pin must be oiled once in a fortnight with axial iron medium grade IS 1628 for the movement of the indicator. 4. Check the forced dropping arrangement of TCF & TGT lock. Care must be taken to check that the rocker arm is free about its fulcrum pins. The edge of the lock must be squire if not the lock must be immediately changed to avoid any possible jumping off from the notch in the rack. Similar care must be taken to see that the lock not be forced .
SINGLE LINE BLOCK.
21
out of the notch in the check lock position and thus allowing the operating handle to be turned to TGT position. 5. See that the polarized relay armature is free and it returns to its normal position i.e. neutral position, when the current is not flowing. If it does not return to its normal position it indicates that either there is some residual magnetism or there is fiction in the bearing. Replace the polarized relay immediately. 6. All batteries must be kept clean, terminals must be free from dust and corrosion. Battery must be kept sealed check and ensure that lightening and power protective devices earth and earth connections are effective and good condition. Care must be taken to see that the correct polarity is maintained at the time of battery renewal. 7. Block Instrument telephone, telephone flexible cord and condenser or other means provided for isolating the telephone from Block instrument circuit must be in good condition for safe working of the instrument. 8. During routine maintenance, care must be taken to see that the safety catch provided near the spring clutch type is in position and is free to move about its fulcrum pins without any friction. 9. (a) Check that locking pawls are correctly safe squire end. (b) Check that the notch in the rack are correctly safe and are squire where necessary. © Check that spigot riveting is not loosed. (d) Check that maintainer’s key and SM’s key can not be extracted in unlock condition. (e) Check that if screws bolts and nuts are loosed tightened them.
MAINTENANCE SCHEDULE FOR NEALE’S ‘A’ TYPE TOKEN BLOCK INSTRUMENT: Sr.No. Maintenance work to be done.
ESM F
SI M
CSI Q
F
M
Q
-
HY
Y
CHECK THE DISTINCTIVENESS OF THE TONE OF THE BELL. CHECK THE LEVEL OF INSTRUMENT. M
HY
Y
HY
Y
Q
HY
1.
CHECK LOCKING AND SEALING
2.
CHECK THE SM’S LOCKUP KEY WORKING CHECK THE OVERHAULED DATE.
3. 4. 5. 6.
.
PERIODICITY
CHECK THE POLARITY OF THE INSTRUMENT
-
SINGLE LINE BLOCK.
7.
22
CHECK AND ENSURE THE FULL DEFLECTIONS OF THE NEEDLE INDICATORS CHECK THE TOKEN FOR DAMAGE
8.
9.
F
M
Q
F
M
Q
F
M
Q
F
M
Q
F
M
Q
F
M
Q
F
M
Q
--
Q
F
M
Q
17.
CHECK THE TOKEN INDICATOR IS WORKING FREELY. CHECK THE FORCED DROP ARRANGEMENT OF TCF & TGT AND THE EDGE OF LOCK CHECK THE POLARISED RELAY FUNCTION CHECK THE FUNCTIONING OF SAFETY CATCH. CHECK THE SPIGOT FOR ITS TIGHTNESS CHECK THE TOKEN RECEIVER FOR CORRECT TOKEN CONFIGURATION CLEAN THE RACK AND PINION TEETH & LUBRICATE WITH AXLE OIL MEDIUM GRADE 1628. INSPECT CONTACT SURFACES
F
M
Q
18.
CHECK EARTH CONNECTIONS
F
M
Q
19.
CHECK THE TELPHONE AND TELEPHONE CORDS CHECK THE BLOCK AND TELEPHONE BATTERIES FOR CLEANLINESS & RECORD VOLTAGE RECORD CHECK ALL WIRINGS OF THE INSTRUMENTS. MEASURE THE LINE CURRENT
F
M
Q
F
M
Q
--
M
Q
F
M
Q
10.
11. 12. 13. 14. 15.
20.
21. 22.
*F - FORTHNIGHTLY.
*M – MONTHLY.
Periodicity of Overhauling:
--
*Q -QUARTERLY
Single line Token (Ball & tablet) Instruments are required to be overhauled once in 10 years.
.
SINGLE LINE BLOCK.
23
LESSON: SIX TROUBLE SHOOTING: TROUBLE
REASON
. AT SENDING STATION. 1. No deflection in 1. Line battery weak or any GALVO when bell cell in group has become plunger is pressed at reverse polarity. sending station. 2. Finger Spring contact broken, jerking contact not making 3. Wire disconnection 4. Galvo coil open /Galvo defective 5. Earth wire broken , line fuse may be blown up AT RECEIVING STATION 1. Rest contact not making. 2. Jerking contact open 3. High resistance on line 4. BPR relay coil open.
2. Galvo deflects but bell beat is not received at receiving station.
1. Check battery voltage and current. 2. Check the spring contact assembly. 3. check wire connection. 4. Check Galvo coil 5. Check earth resistance
1 & 2. . Check rest & jerking contact pressure . 3. Clean the jumper wire and tight the connection. 4. Check working current of BPR and coil resistance 1. Local battery may weak. 1. Check local battery 2. TCF/TGT coil open. voltage and current. 3. Bell coil may defective 2. Check the TCF/TGT coil 4. Bell armature may jam. resistance, voltage and current 3. Check bell coil resistance & bell assembly. 1. SM’s key may be out 1. Check SM’s key. It 2. Block handle jammed due to should be In. jamming token in the races 2. Check the block and token thoroughly Line contact fault. Check the line by foot and rectify it.
3. Bell beat is received but block handle is not turned to TCF/TGT position. 4. Bell beats is received without pressing the bell plunger at sending / receiving station. 5. when Bell plunger Earth contact fault in section. pressed galvo deflects .
REMEDY
Check the block line from sending to receiving station
SINGLE LINE BLOCK.
24
but no response at either of station.
6.SM’s key not extracted, when required by SM. 7. Token is not going into block instrument.
and rectify it.
1. SM lock may be defective 2. Token receiving drum is not turned fully. 1. Token hole shape has damaged. 2. Token jammed with spigot in token receiving drum. 8. Token is inserted 1. Commutator shaft has not but block is not been changed after insertion of getting normalized. token and pressing the bell plunger. 9. Block handle is not going from line closed to TCF.
.
1.Check SM’s .lock position. 2. Check the movement of receiving drum. 1. Check the shape of token hole if damaged remove it. 2. See that token should be free in token receiving drum 1. Check the spiral spring condition between commutator shaft and spring clutch shaft. 2. Check that commutator shaft is not jammed. 1. GNR relay may drop. 1.Check the power supply, 2. Normal band of circuit fuse and GNR. controller of outer signal may 2.Check the circuit not make. controller band. If required 3. NTR may drop. adjust it . 3. Check the track circuit & attend it.
SINGLE LINE BLOCK.
25
NEALES BLOCK INSTRUMENT TROUBLE SHOOTING CHART: No out going from X & No incoming to X Short L1 & L2 at test Panel at X. check Galvo Deflection
Short L1 & L2 at Block counter And Ensure Galvo deflection.
Short L1 & L2 At instrument Terminal
Check for continuity of Incoming circuit at X Check earth connection, if earth return.
Break in line Wire between Block counter To test panel
Break in line Wire between Block counter To instrument.
Trace the incoming Circuit, Check Polarized Relay & rest contact & rectify coil.
Proceed to Y station by Observing the Aerial line.
Short L1 & L2 at Y station at test panel & ensure Galvo Deflection.
Check the continuity of incoming circuit from L1 & L2. Check earth connections.
Inform Lineman to rectify line fault.
.
Trace the incoming circuit, rest contact, polarized relay coil & rectify.
Check the outgoing circuit from Battery to L1&L2 & Rectify
SINGLE LINE BLOCK.
.
26
SINGLE LINE BLOCK.
.
27
SINGLE LINE BLOCK.
.
28
SINGLE LINE BLOCK.
.
29
SINGLE LINE BLOCK.
.
30
SINGLE LINE BLOCK.
.
31
SINGLE LINE BLOCK.
.
32
SINGLE LINE BLOCK.
.
33
SINGLE LINE BLOCK.
.
34
SINGLE LINE BLOCK.
.
35
SINGLE LINE BLOCK.
.
36
SINGLE LINE BLOCK.
.
37
SINGLE LINE BLOCK.
.
38
SINGLE LINE BLOCK.
.
39