Max Fault Current -generator

  • Uploaded by: Neetha Lakshman
  • 0
  • 0
  • June 2020
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Max Fault Current -generator as PDF for free.

More details

  • Words: 211
  • Pages: 1
Max Fault Level of Generator Diesel Generating set comprises of diesel engine as the prime mover. When a short circuit occurs on the system powered by a generator, the generator continues to produce voltage at the generator terminals as the field excitation is maintained and the prime mover drives the generator at normal speed. The generated voltage causes a large magnitude fault current flow from the generator to the short circuit. The flow of fault current is limited only by the generator impedance and the impedance of circuit between the generator and short circuit. In case of a short circuit at the generator terminals, the fault current is limited by generator impedance only

Objective – To calculate the fault current of the generator Generator Rating – 2000KVA Rated Voltage -415V Sub Transient Reactance Xd “ - 0.11 ( Reference Technical Data Sheet of Alternator ) Fault Current If = Fault MVA / √3 x kV Fault MVA = MVA / Xd” Fault MVA = 2/0.11 = 18.1818 Fault Current = 18.1818/ √3 x 0.415 = 25.295 kA Full Load Current of the Generator = MVA / √3 x kV =2.782kA or 2782 A This means that the fault current is (25.295/2782 ) times i.e approximately 9times the full load current .

Related Documents

Fault
November 2019 31
Generator
May 2020 20
Generator
November 2019 39
Generator
November 2019 32
Generator
July 2020 15

More Documents from ""

Heart Lock Technique
October 2019 23
We Are For Peace
October 2019 22
Swot Analysis
October 2019 41
10 Words
April 2020 15