Electrical Installation
Lecture No.11
Dr.Mohammed Tawfeeq Alzuhairi
The reflection coefficients ρ can be used to determine the utilization factor UF for any luminaire from the manufacturers catalogues when the room index is calculated. For example, Table -2 gives the utilization factor UF for a fluorescent luminaire with single 40W lamp and prismatic diffuser0011
mm length for different values of the room reflection
coefficients: C – ceiling reflection, W- wall reflection, F- floor reflection. If these values are: (0.5, 0.5, 0.2) and the room index is calculated to be 1.50, then the UF = 0.52. Table -2 Utilisation factor for fluorescent luminare with single 40W lamp and prismatic diffuser 0011 mm length. Room Reflection
Room Index
C
W
F
.75
1.00 1.25 1.50 2.00 2.50 3.00 4.00 5.00
.70
.50
.20
.44
.50
.56
.60
.65
.69
.72
.75
.77
.30
.38
.44
.50
.54
.60
.64
.68
.72
.74
.10
.33
.40
.46
.50
.56
.61
.64
.69
.72
.39
.44
.49
.52
.57
.60
.62
.65
.67
.30
.34
.40
.44
.48
.53
.56
.59
.62
.64
.10
.30
.36
.41
.44
.50
.53
.56
.60
.62
.34
.39
.42
.45
.49
.51
.53
.55
.57
.30
.30
.35
.39
.42
.46
.49
.51
.53
.55
.10
.27
.32
.36
.39
.44
.47
.49
.52
.54
.22
.26
.29
.31
.34
.36
.38
.40
.41
.50
.30
.00
.50
.50
.00
.20
.20
.00
UF Note: The reflection coefficients for a standard room are: (0.7, 0.5, 0.2)