Flakiness & Elongation Index

  • June 2020
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Flakiness & Elongation Index as PDF for free.

More details

  • Words: 1,284
  • Pages: 3
Edited by Foxit Reader Copyright(C) by Foxit Software Company,2005-2007 For Evaluation Only.HM-925 Flakiness Index

HM-926 Elongation Index

Operating Instructions Instructions— as per BS 812 Determination of Flakiness Index & Elongation Index Gilson Models HM-925 & HM-926 B. Apparatus: The following apparatus is required. 1. A metal thickness gauge of the pattern shown in Figure 5 or special sieves having elongated apertures. The width of the apertures and the thickness of the sheet used in the gauge or sieve shall be as specified in Figure 5. 2. BS test sieves as shown in Table 9 as appropriate.

HM-925 I. Determination of Flakiness Index (Thickness) A. General: This method is based on the classification of aggregate particles as flaky when they have a thickness (smallest dimension) of less than 0.6 of their nominal size, this size being taken as the mean of the limiting sieve apertures used for determining the size fraction in which the particle occurs. The flakiness Index of an aggregate sample is found by separating the flaky particles and expressing their mass as a percentage of the mass of the sample tested. The test is not applicable to material passing a 6.30 mm BS test sieve or retained on a 63.0 mm BS test sieve.

3. A balance accurate to 0.5% of mass of the test sample. C. Sample for test: The sample for this test shall be taken in accordance with BS 812. It shall comply with the appropriate minimum mass, for sieve analysis with due allowance for 63.0 mm BS test sieve and passing a 6.30 mm BS test sieve. The sample shall be taken from the laboratory sample by quartering or by means of a sample divider. Before testing it shall be brought to a dry condition by standard methods. D. Procedure: Carry out a sieve analysis using the sieves given in Table 9.

These sizes marked on gauge

Figure 5­– HM-925 Thickness Gauge (Flakiness Index) 1.5mm Steel Sheet Rolled over an 8mm diameter bar. PHONE: 800-444-1508 740-548-7298

P.O. Box 200, Lewis Center, Ohio 43035-0200 Email: [email protected] Website: www.globalgilson.com

FAX: 800-255-5314 740-548-5314

Edited by Foxit Reader Copyright(C) by Foxit Software Company,2005-2007 For Evaluation Only.Gauges Table 9. Dimensions of Thickness and Length Aggregate Size-fraction BS Test Sieve Nominal Aperture Size 100% Passing 100% Retained mm 63.0 50.0 37.5 28.0 20.0 14.0 10.0

mm 50.0 37.5 28.0 20.0 14.0 10.0 6.30

Thickness Gauge*

Length Gauge †

Width of Slot

Gap between Pins

Minimum Mass for Subdivision

mm 33.9 ± 0.3 26.3 ± 0.3 19.7 ± 0.3 14.4 ± 0.15 10.2 ± 0.15 7.2 ± 0.1 4.9 ± 0.1

mm — 78.7 ± 0.3 59.0 ± 0.3 43.2 ± 0.3 30.6 ± 0.3 21.6 ± 0.2 14.7 ± 0.2

kg 50 35 15 5 2 1 0.5

Discard all aggregate retained on the 63.0 mm BS test sieve and all aggregate passing the 6.30 mm BS test sieve. Then weigh each of the individual size-fractions retained on the sieves, other than the 63 mm BS test sieve, and store them in separate trays with their size marked on the trays.

HM-926

Where the number of particles in any size fraction is considered to be excessive i.e. more than the appropriate mass given in Table 9, the fraction may be subdivided by standard methods. Under such circumstances the rest of the procedure should be suitably modified, and the appropriate correction factor applied to determine the mass of flaky particles that would have been obtained had the whole of the original size-fraction been gauged. From the sums of the masses of the fractions in the trays (M1), calculate the individual percentage retained on each of the various sieves. Discard any fraction of which the mass is 5% or less of mass M1. Record the mass remaining (M2). Gauge each fraction by one of these procedures: 1. Using the gauge: Select the thickness gauge appropriate to the size-fraction under test (see Table 9) and gauge each particle separately by hand or 2. Using the special sieves: Select the special sieve appropriate for the size-fraction under test. Place the whole of the size-fraction into the sieve which shall then be shaken until the majority of flaky particles have passed through the slots. The gauge the particles retained individually by hand. Combine and weigh all the particles passing the gauges or special sieves (M3).

E. Calculating & Reporting (Flakiness Index): The Flakiness Index shall be reported to the nearest whole number. The sieve analysis obtained in the test shall also be reported. Flakiness =

II.

M3 x 100 M2

Determination of Elongation IndeX (LENGTH) A. General: This method is based on the classification of aggregate particles as elongated when they have a length (greatest dimension) of more than 1.8 of their nominal size, this size being taken as the mean of the limiting sieve apertures used for determining the size-fraction in which the particle occurs. The Elongation Index of an aggregate sample is found by separating the elongated particles and expressing their mass as a percentage of the mass of the sample tested. The test is not applicable to material passing a 6.30 mm BS test sieve or retained on a 50.0 mm BS test sieve. B. Apparatus: The following apparatus is required. 1. A metal length gauge of the pattern shown in

Edited by Foxit Reader Copyright(C) by Foxit Software Company,2005-2007 be subdivided. Under such circumstances the rest Only. The gauge lengths shall be those For Evaluation

Figure 6. specified in the 'length gauge' column of Table 9.

2. BS test sieves as shown in Table 9 as appropriate 3. A balance accurate to 0.5% of mass of test sample. C. Sample for test: The sample for this test shall be taken in accordance with Clause 5 of this Part of this standard. It shall comply with the appropriate minimum mass for sieve analysis, with due allowance for later rejection of particles retained on a 50.0 mm BS test sieve and passing a 6.30 mm BS test sieve. The sample shall be taken from the laboratory sample by quartering or by means of a sample divider. Before testing it shall be brought to a dry condition by standard methods. D. Procedure: Carry out a sieve analysis using the sieves shown in Table 9. Discard all aggregate retained on the 50.0 mm BS test sieve and all aggregate passing the 6.30 mm BS test sieves. Weigh and store each of the individual size-fractions retained on the other sieves in separate trays with their size marked on the tray. Where the number of particles in any size-fraction is considered to be excessive, i.e. more than the appropriate mass given in table 9, the fraction may

of the procedure should be suitably modified and the appropriate correction factor applied to determine the mass of flaky particles that would have been obtained had the whole of the original size-fraction been gauged. From the sum of masses of the fractions in the trays (M1), calculate the individual percentages retained on each of the various sieves. Discard any fraction whose mass is 5% or less of mass M1. Record the mass remaining (M2).

Gauge each fraction as follows. Select the length gauge appropriate to the sizefraction under test (see Table 9) and gauge each particle separately by hand. Elongated particles are those whose greatest dimension prevents them from passing through the gauge. Combine and weigh all Elongated particles (M3). E. Calculating & Reporting (Elongation Index): The Elongation Index shall be reported to the nearest whole number. The sieve analysis obtained in this test shall also be reported. Elongation Index =

M3 x 100 M2

These sizes marked on gauge Dimensions are in millimeters.

Figure 6 – HM-926 Length Gauge (Elongation Index)

cm 9/05

Related Documents