Data sheet
EliminatorTM Liquid line filter driers, type DCL and DML
Introduction
EliminatorTM liquid line filter driers protect refrigeration and air-conditioning systems from moisture, acids, and solid particles. With these contaminants eliminated, systems are safer from harmful chemical reactions and from abrasive impurities. There are two types of EliminatorTM cores. Type DML driers have a core composition of 100% molecular sieves, while type DCL contain 80% molecular sieves with 20% activated alumina. All EliminatorTM driers have a solid core with binding material held to an absolute minimum. Core selection is primarily based on the refrigerant oil used in the system.
Features
EliminatorTM type DML, with a solid core of 100% molecular sieves, are optimized for use with HFC refrigerants and polyolester (POE) or polyalkyl glycol (PAG) oils. Type DML driers are designed for applications requiring high water adsorption, and can be used with any manufacturer’s compressor. Because type DML driers contain no activated alumina, oil additives will not be depleted.
EliminatorTM type DCL, with a solid core of 80% molecular sieves and 20% activated alumina, is the drier of choice for systems with HCFC and CFC refrigerants and mineral or alkyl benzene oils. Type DCL driers are particularly suited for systems that operate at high condensing temperatures and require high drying capacity.
The Core Type DML · 100% 3Å molecular sieves core. · High drying capacity minimizing the risk of acid formation (hydrolysis). · Optimized for HFC refrigerants (R 134a, R 404A, R 410A, etc.) with POE and PAG oils. Compatible with R 22. · Will not deplete oil additives.
The Shell · UL approved for MWP up to 42 bar. · Available with solder (solid copper), flare, or O-ring face seal connections. · Corrosion resistant powder-painted finish. Can be used in all environments including marine applications.
Type DCL · 80% 3Å molecular sieves with 20% activated alumina. · Perfect core blend for systems that operate at high condensing temperatures and require high drying capacity. · Optimized for CFC and HCFC refrigerants (R 22, R 502, etc.) with mineral and alkyl benzene oils. Compatible with HFC’s and refrigerant blends.
The Filter · 25 mm filter provides high retention with minimal pressure drop. · Thermally stable up to 120°C.
Allows installation with any orientation provided the arrow is in the flow direction. Available in 8 sizes from 3 to 75 cubic inches. Approvals
S UL file no. SA 6398
ã Danfoss A/S, 09 - 1999
RD.6A.K1.02
1
Data sheet
EliminatorTM Liquid line filter driers, type DCL and DML
Technical data and capacities
DML
R 134a, R 507, R 404A, R 407C, R 410A
Drying and liquid capacity - Type DML
Drying capacity [kg refrigerant] 1) Type
DML 032/032s DML 033/033s DML 052/052s DML 052.5s DML 053/053s DML 082/082s DML 082.5s DML 083/083s DML 084/084s DML 162/162s DML 162.5s DML 163/163s DML 164/164s DML 165/165s DML 167s DML 303/303s DML 304/304s DML 305/305s DML 306s DML 307s DML 309s DML 413 DML 414/414s DML 415/415s DML 417s DML 419s DML 607s DML 609s DML 757s DML 759s
R 134a R 507 24 °C 7 7 8.5 8.5 8.5 12.5 12.5 12.5 12.5 27 27 27 27 27 27 57 57 57 57 57 57 80 80 80 80 80 113 113 160 160
52 °C 6.5 6.5 8 8 8 12 12 12 12 25.5 25.5 25.5 25.5 25.5 25.5 54 54 54 54 54 54 75 75 75 75 75 107 107 150 150
R 404A 24 °C 11 11 13 13 13 20 20 20 20 43.5 43.5 43.5 43.5 43.5 43.5 92.5 92.5 92.5 92.5 92.5 92.5 130 130 130 130 130 185 185 260 260
Liquid capacity [kW] 2)
R 407C R 410A 52 °C 6 6 7.5 7.5 7.5 11.5 11.5 11.5 11.5 24 24 24 24 24 24 51 51 51 51 51 51 70 70 70 70 70 101 101 140 140
24 °C 6.5 6.5 8 8 8 12.5 12.5 12.5 12.5 27 27 27 27 27 27 57 57 57 57 57 57 80 80 80 80 80 114 114 160 160
52 °C 6 6 7 7 7 11 11 11 11 23 23 23 23 23 23 48.5 48.5 48.5 48.5 48.5 48.5 74 74 74 74 74 97 97 148 148
Max Working Pressure R 134a R 404A R 407C PB R 507 R 410A [bar] 7 5 7 42 17 13 19 42 7 5 8 42 9 7 10 42 18 14 19 42 7 5 8 42 9 7 10 42 19 14 21 42 26 20 29 42 7 5 8 42 11 9 12 42 22 16 24 42 30 22 33 42 43 30 47 42 49 36 54 35 21 15 23 42 31 22 34 42 45 33 49 42 62 45 68 35 59 43 65 35 59 43 65 35 25 18 27 42 32 23 35 42 53 37 58 42 91 65 100 35 91 65 100 35 75 54 82 35 87 64 95 35 82 60 90 35 94 68 102 35
1)
Drying capacity is based on following moisture content test standards before and after drying: R 134a: From 1050 ppm W to 75 ppm W. If drying to 50 ppm W is required, reduce stated capacities by15%. R 404A, R 507: From 1020 ppm W to 30 ppm W. R 407C: From 1020 ppm W to 30 ppm W. R 410A: From 1050 ppm W to 60 ppm W. 2 ) Given in accordance with ARI 710-86 for te = –15°C, tc = 30°C and Dp = 0.07 bar. For R 22 you may use R 407C/R 410A capacities.
2
RD.6A.K1.02
ã Danfoss A/S, 09 - 1999
Data sheet
EliminatorTM Liquid line filter driers, type DCL and DML
Technical data and capacities (continued)
DCL
R 22, R 12, R 502
Drying and liquid capacity - Type DCL Drying capacity [kg refrigerant] 1) Type
DCL 032/032s DCL 033/033s DCL 052/052s DCL 052.5s DCL 053/053s DCL 082/082s DCL 082.5s DCL 083/083s DCL 084/084s DCL 162/162s DCL 162.5s DCL 163/163s DCL 164/164s DCL 165/165s DCL 167s DCL 303/303s DCL 304/304s DCL 305/305s DCL 306s DCL 307s DCL 309s DCL 413 DCL 414/414s DCL 415/415s DCL 417s DCL 419s DCL 607s DCL 609s DCL 757s DCL 759s
R 22 24 °C 4.5 4.5 5.5 5.5 5.5 9 9 9 9 20 20 20 20 20 20 42 42 42 42 42 42 59 59 59 59 59 84 84 120 120
52°C 4 4 5 5 5 8 8 8 8 19 19 19 19 19 19 41 41 41 41 41 41 56 56 56 56 56 80 80 110 110
R 12 24 °C 15 15 20 20 20 30 30 30 30 70 70 70 70 70 70 140 140 140 140 140 140 200 200 200 200 200 250 250 300 300
Liquid capacity [kW] 2)
R 502 52 °C 15 15 20 20 20 30 30 30 30 70 70 70 70 70 70 140 140 140 140 140 140 200 200 200 200 200 250 250 300 300
24 °C 7.5 7.5 10 10 10 15 15 15 15 35 35 35 35 35 35 75 75 75 75 75 75 100 100 100 100 100 150 150 200 200
52 °C 4 4 5 5 5 8 8 8 8 18 18 18 18 18 18 37.5 37.5 37.5 37.5 37.5 37.5 50 50 50 50 50 75 75 100 100
R 22
R 12
R 502
Max Working Pressure [bar]
7 19 8 10 19 8 10 21 29 8 12 24 33 47 54 23 34 49 68 65 65 26 35 58 100 100 83 97 91 104
6 14 6 8 15 6 8 15 22 6 9 18 24 35 40 17 25 37 51 49 49 20 26 43 74 74 63 73 69 79
5 13 5 7 14 5 7 14 20 5 9 16 22 30 36 15 22 33 45 43 43 18 23 37 65 65 54 63 59 68
42 42 42 42 42 42 42 42 42 42 42 42 42 42 35 42 42 42 35 35 35 42 42 42 35 35 35 35 35 35
1)
Drying capacity is based on following moisture content test standards before and after drying: R 22: From 1050 ppm W to 60 ppm W in accordance with ARI 710-86. R 12: From 565 ppm W to 15 ppm W in accordance with ARI 710-86. R 502: From 1020 ppm W to 30 ppm W in accordance with ARI 710-86. 2) Given in accordance with ARI 710-86 for t = –15°C, t = 30°C and Dp = 0.07 bar. e c
ã Danfoss A/S, 09 - 1999
RD.6A.K1.02
3
Data sheet
Ordering
EliminatorTM Liquid line filter driers, type DCL and DML
DCL
Flare Type
Connection in.
Code no.
Type
Connection in.
/4 /8
023Z0001 023Z0002
DML 032 DML 033
1
/4 /8
023Z0003 023Z0004
DML 052 DML 053
1
DCL 032 DCL 033
1
DCL 052 DCL 053
1
DCL 082 DCL 083 DCL 084
1
/4 /8 1 /2
023Z0005 023Z0006 023Z0007
DML 082 DML 083 DML 084
1
DCL 162 DCL 163 DCL 164 DCL 165
1
/4 /8 1 /2 5 /8
023Z0008 023Z0009 023Z0010 023Z0011
DCL 303 DCL 304 DCL 305
3
/8 /2 5 /8
DCL 413 DCL 414 DCL 415
3
3
3
3
3
1
/8 /2 5 /8 1
Type DCL 032s DCL 033s DCL 052s DCL 052.5s DCL 053s DCL 082s DCL 082.5s DCL 083s DCL 084s DCL 162s DCL 162.5s DCL 163s DCL 164s DCL 165s DCL 167s DCL 303s DCL 304s DCL 305s DCL 306s DCL 307s DCL 309s
Connection in.
023Z0038 023Z0039
/4 /8
023Z0040 023Z0041
/4 /8 1 /2
023Z0042 023Z0043 023Z0044
DML 162 DML 163 DML 164 DML 165
1
/4 /8 1 /2 5 /8
023Z0045 023Z0046 023Z0047 023Z0048
023Z0012 023Z0013 023Z0014
DML 303 DML 304 DML 305
3
/8 /2 5 /8
023Z0049 023Z0050 023Z0051
023Z0101 023Z0102 023Z0103
DML 413 DML 414 DML 415
3
023Z0108 023Z0109 023Z0110
Type
/4 /8
023Z0015 023Z0016
DML 032s DML 033s
/4 /16 3 /8
023Z0017 023Z0018 023Z0019
DML 052s DML 052.5s DML 053s
1
/4 /16 3 /8 1 /2
023Z0020 023Z0021 023Z0022 023Z0023
DML 082s DML 082.5s DML 083s DML 084s
1
/4 /16 3 /8 1 /2 5 /8 7 /8
023Z0024 023Z0025 023Z0026 023Z0027 023Z0028 023Z0029
DML 162s DML 162.5s DML 163s DML 164s DML 165s DML 167s
3
023Z0030 023Z0031 023Z0032 023Z0033 023Z0034 023Z0035
DML 303s DML 304s DML 305s DML 306s DML 307s DML 309s
3 1 5
5
5
/8 /2 5 /8 3 /4 7 /8 11/8 1
1
3
3
3
3
1
/8 /2 5 /8 1
DML
Solder
Code no.
1
Code no.
/4 /8
DCL
Solder
4
DML
Flare
Connection in.
Code no.
/4 /8
023Z0052 023Z0053
/4 /16 3 /8
023Z0054 023Z0055 023Z0056
1
/4 /16 3 /8 1 /2
023Z0057 023Z0058 023Z0059 023Z0060
1
/4 /16 3 /8 1 /2 5 /8 7 /8
023Z0061 023Z0062 023Z0063 023Z0064 023Z0065 023Z0066
3
023Z0067 023Z0068 023Z0069 023Z0070 023Z0071 023Z0072
1 3 1 5
5
5
/8 /2 5 /8 3 /4 7 /8 11/8 1
DCL 414s DCL 415s DCL 417s DCL 419s
/2 /8 7 /8 11/8
023Z0104 023Z0105 023Z0106 023Z0107
DML 414s DML 415s DML 417s DML 419s
/2 /8 7 /8 11/8
023Z0111 023Z0112 023Z0113 023Z0114
DCL 607s DCL 609s
7 /8 11/8
023Z0036 023Z0037
DML 607s DML 609s
7 /8 11/8
023Z0073 023Z0074
DCL 757s DCL 759s
7 /8 11/8
023Z0115 023Z0116
DML 757s DML 759s
7 /8 11/8
023Z0117 023Z0118
RD.6A.K1.02
5
1 5
ã Danfoss A/S, 09 - 1999
Data sheet
EliminatorTM Liquid line filter driers, type DCL and DML
Identification
Type codes Filter drier Solide core
Example for type codes D
C
L
05
3
D C M L S 03 05 08 16 30 41 60 75
s Application Size (volume)
Connection (filter connection in 1/8 of an inch increments)
2 2.5 3 4 5 6 7 9 (blank) s FS
Connection type
Selection
80/20% composite core 100% molecular sieves core Liquid line Suction line 3 cu.in. 5 cu.in. 8 cu.in. 16 cu.in. 30 cu.in. 41 cu.in. 60 cu.in. 75 cu.in. 1
/4 in. /16 in. 3 /8 in. 1 /2 in. 5 /8 in. 3 /4 in. 7 /8 in. 11/8 in. Flare connection Solder connection Face seal (O-ring seal) 5
Type selection is made considering the application
Refrigerant
Oil
DCL Can be used Recommended Recommended Recommended Can be used Not recommended 2)
HFC HCFC CFC Mineral or AB POE or PAG, pure POE or PAG, with additives
DML Recommended Can be used Not recommended 1) Can be used Recommended Recommended
1
) For CFC systems, DCL filter driers are recommended. In these systems, circumstances may require the use of a filter drier with acid adsorbing properties. 2 ) Use of filter driers containing activated alumina are not recommended in systems with oils containing additives.
Selection example
Select the appropriate type (DML or DCL) based on refrigerant and oil type. Then select the drier size based on the adsorption and liquid capacity required. a. Amount of charge: 25 kg R 134a at tL = 24°C To dry 25 kg R 134a at 24°C from 1050 to 60 ppm moisture, a DML 16 is necessary. b. Cooling capacity: Qe = 20 kW To obtain a mass flow corresponding to 20 kW cooling capacity with a DML 16 filter drier, a
3
/8 inch connection must be chosen. Larger connections can be chosen in accordance with the liquid line dimension. c. Result A DML 163 or DML 163s can be used. If the initial moisture content is very small or a planned change of the filter drier is considered, a smaller filter drier size can be chosen.
Drying capacity [kg refrigerant] 1) Type
DML 032/032s DML 033/033s DML 162/162s DML 162.5s DML 163/163s DML 164/164s DML 165/165s DML 167s
ã Danfoss A/S, 09 - 1999
RD.6A.K1.02
R 134a R 507 24 C 7 7 27 27 27 27 27 27
52 C 6.5 6.5 25.5 25.5 25.5 25.5 25.5 25.5
R 404A
24 C 11 11 43.5 43.5 43.5 43.5 43.5 43.5
Liquid capacity [kW] 2)
R 407C R 410A 52 C 6 6 24 24 24 24 24 24
24 C 6.5 6.5 27 27 27 27 27 27
52 C 6 6 23 23 23 23 23 23
Max Working R 134a R 404A R 407C Pressure R 507 R 410A [bar] 7 17 7 11 22 30 43 49
5 13 5 9 16 22 30 36
7 19 8 12 24 33 47 54
42 42 42 42 42 42 42 42
5
Data sheet
EliminatorTM Liquid line filter driers, type DCL and DML
Design and function
1. 2. 3. 4. 5. 6. 7.
Inlet Spring Solid core Polyester mat Perforated plate Seal cap, flare connection Seal cap, solder connection
The relatively large diameter of the filter drier means that the liquid flow velocity is suitably low and the pressure drop minimal.
Powder formation is eliminated because the solid core grains are bonded and cannot move against each other.
Dimensions and weights Flare connections
6
RD.6A.K1.02
DCL/DML 032 DCL/DML 033
A mm 66 66
L mm 110 123
D1 mm 58 58
D2 mm 54 54
Weight kg. 0.35 0.38
DCL/DML 052 DCL/DML 053 DCL/DML 082 DCL/DML 083 DCL/DML 084
75 75 101 101 101
119 132 145 158 166
58 58 58 58 58
54 54 54 54 54
0.39 0.42 0.48 0.51 0.56
DCL/DML 162 DCL/DML 163 DCL/DML 164 DCL/DML 165 DCL/DML 303 DCL/DML 304 DCL/DML 305 DCL/DML 413 DCL/DML 414 DCL/DML 415
110 110 110 110 186 186 186 187 187 187
154 167 175 184 243 251 260 244 252 261
80 80 80 80 80 80 80 93 93 93
76 76 76 76 76 76 76 89 89 89
0.83 0.86 0.91 0.95 1.33 1.38 1.42 2.06 2.11 2.15
ã Danfoss A/S, 09 - 1999
Data sheet
EliminatorTM Liquid line filter driers, type DCL and DML
Dimensions and weights Solder connections
DCL/DML 032s DCL/DML 033s DCL/DML 052s DCL/DML 052.5s DCL/DML 053s DCL/DML 082s DCL/DML 082.5s DCL/DML 083s DCL/DML 084s DCL/DML 162s DCL/DML 162.5s DCL/DML 163s DCL/DML 164s DCL/DML 165s DCL/DML 167s DCL/DML 303s DCL/DML 304s DCL/DML 305s DCL/DML 306s DCL/DML 307s DCL/DML 309s DCL/DML 414s DCL/DML 415s DCL/DML 417s DCL/DML 419s DCL/DML 607s DCL/DML 609s DCL/DML 757s DCL/DML 759s
ã Danfoss A/S, 09 - 1999
RD.6A.K1.02
A mm
B mm
L mm
D1 mm
D2 mm
Weight kg.
66 66 75 75 75 101 101 101 101 110 110 110 110 110 110 186 186 186 186 186 186 187 187 187 187 340 340 338 338
71 72 80 80 81 106 106 107 109 115 115 116 118 118 120 192 194 194 194 196 196 195 195 197 197 350 350 348 348
98 104 107 111 113 133 137 139 143 142 146 148 152 158 172 224 228 234 246 248 249 229 235 249 250 402 403 400 401
58 58 58 58 58 58 58 58 58 80 80 80 80 80 80 80 80 80 80 80 80 93 93 93 93 80 80 93 93
54 54 54 54 54 54 54 54 54 76 76 76 76 76 76 76 76 76 76 76 76 89 89 89 89 76 76 89 89
0.33 0.34 0.37 0.38 0.38 0.46 0.47 0.47 0.48 0.81 0.82 0.82 0.83 0.84 0.86 1.29 1.30 1.31 1.33 1.35 1.36 2.03 2.04 2.08 2.09 2.39 2.40 3.38 3.39
7
Data sheet
EliminatorTM Liquid line filter driers, type DCL and DML
8
RD.6A.K1.02
ã Danfoss A/S, 09 - 1999