GAS NATURAL Densidad: 0.6 Hs (PCS): 11.86

(relativa) kWh/Nm3

Hi (PCI):

kWh/Nm3

10.67

POTENCIA INSTALADA DEL PUNTO DE SUMINISTRO:

TRAMO A-B

Nº Puntos de Consumo

S2

P (kW)

Q (Nm3/h)

Lr (m)

1

1.00

500.0

42.2

30.0

Descripción: TRAMO Denominación del tramo Nº Puntos de Consumo Cantidad de puntos de consumo a los que dará suministro el tramo S2 Coeficiente de Simultaneidad P (kW) Potencia total para el tramo analizado (Kw) 3 Q (Nm /h) Caudal total del tramo analizado Lr (m) Longitud real del tramo (metros) P. entrada (mbar) Presión de entrada al tramo (mmbar.) P2min (mbar) Presión mínima que querremos a la salida del tramo (mmbar) Dt (mm) Diámetro teórico para la presión mínima que hemos marcado (mm.) Tubería Elección de la tubería comercial P. salida (mbar) Presión de salida del tramo para la tubería elegida Velocidad del gas a la salida del tramo (debe ser menor de 20 m/seg.) V (m/s)

Celdas para introducir datos

500

kWh

P. entrada (mbar) P2min (mbar) Dt (mm) 55.0

30.0

32.4

Tubería

P. salida (mbar)

V (m/s)

Cu 33/35

32.1

14.0

que dará suministro el tramo

alida del tramo (mmbar) ma que hemos marcado (mm.)

bería elegida (debe ser menor de 20 m/seg.)

Cu 8/10 Cu 10/12 Cu 13/15 Cu 16/18 Cu 20/22 Cu 19/22

Cu 26/28 Cu 25/28 Cu 33/35 Cu 32/35 Cu 40/42 Cu 39/42 Cu 51/54 Cu 61/64 Cu 60/64 Cu 73/76 Cu 72/76 Cu 85/89

GAS GAS NATURAL PROPANO

D. RELATIVA 0.6 1.6 kw/kg kcal/kg

COBRE Cu 8/10 Cu 10/12 Cu 13/15 Cu 16/18 Cu 20/22 Cu 19/22 Cu 26/28 Cu 25/28 Cu 33/35 Cu 32/35 Cu 40/42 Cu 39/42 Cu 51/54 Cu 61/64 Cu 60/64 Cu 73/76 Cu 72/76 Cu 85/89 Cu 104/108

Hs (kWh/Nm3) 11.9 28.6 13.8 11,891.0

Diám. Interior mm 8.0 10.0 13.0 16.0 20.0 19.0 26.0 25.0 33.0 32.0 40.0 39.0 51.0 61.0 60.0 73.0 72.0 85.0 104.0

APARATO CALDERA MURAL MIXTA 24 kW CALDERA MURAL MIXTA 32 kW CALENTADOR 14 litros/min CALENTADOR 11 litros/min COCINA 4 FUEGOS COCINA 4 FUEGOS + HORNO GAS SECADORA

ACERO Ac 1/8" DN 6 Ac 1/4" DN 8 Ac 3/8" DN 10 Ac 1/2" DN 15 Ac 3/4" DN 20 Ac 1" DN 25 Ac 1 1/4" DN 32 Ac 1 1/2" DN 40 Ac 2" DN 50 Ac 2 1/2" DN 65 Ac 3" DN 80 Ac 4" DN 100 Ac 5" DN 125 Ac 6" DN 150

Putil (kW) 24.0 32.0 24.4 19.2 7.5 11.0 4.0

Diám. Interior mm 6.2 8.9 12.6 16.1 21.7 27.3 36.0 41.9 53.1 68.9 80.9 105.3 129.7 155.1

Rendimiento 93% 93% 87% 87% 100% 100% 100%

G.C. (PCI) kW 25.8 34.4 28.0 22.1 7.5 11.0 4.0

POLIETILENO

MOP (bar) 5 5 5 5 5 5 5 5 5 10 10 10 10 10 10 10 10 10

PE-100 SDR 17,6 DN 32 PE-100 SDR 17,6 DN 40 PE-100 SDR 17,6 DN 63 PE-100 SDR 17,6 DN 90 PE-100 SDR 17,6 DN 110 PE-100 SDR 17,6 DN 160 PE-100 SDR 17,6 DN 200 PE-100 SDR 17,6 DN 250 PE-100 SDR 17,6 DN 315 PE-100 SDR 11 DN 32 PE-100 SDR 11 DN 40 PE-100 SDR 11 DN 63 PE-100 SDR 11 DN 90 PE-100 SDR 11 DN 110 PE-100 SDR 11 DN 160 PE-100 SDR 11 DN 200 PE-100 SDR 11 DN 250 PE-100 SDR 11 DN 315

Diam. Espesor Diam. Ext. mm Int. 32 1.8 28.4 40 2.3 35.5 63 3.6 55.8 90 5.1 79.8 110 6.3 97.5 160 9.1 141.8 200 11.4 177.3 250 14.2 221.6 315 17.9 279.2 32 2.9 26.2 40 3.6 32.7 63 5.7 51.5 90 8.2 73.6 110 10.0 90.0 160 14.5 130.9 200 18.2 163.6 250 22.7 204.5 315 28.6 257.7

FÓRMULAS PARA EL CÁLCULO DE INSTALACIONES DE GAS

PÉRDIDA DE CARGA

VELOCIDAD

- Fórmula de Renuard

P2A −P2B =51 ,5×ρ× LE ×Q 1,82× D−4, 82 PA: Presión absoluta en el inicio del tramo (bar) PB: Presión absoluta en el final del tramo (bar)

r: densidad relativa del gas Q: Caudal (m3/h) LE: Longitud equivalente (m), (Longitud real x 1,2) D: Diámetro interior de la tubería (mm)

V =378×

Q×Z P×D2

V: Velocidad del gas (m/s) Q: Caudal (m3/h) Z: Factor de compresibilidad (Z=1 para presiones absolutas inferiores a 5 P: Presión absoluta en el final del tramo (bar) D: Diámetro interior de la tubería (mm)

FÓRMULAS PARA EL CÁLCULO DE INSTALACIONES DE GAS

PÉRDIDA DE CARGA - Fórmula de Renuard

2

2

P A −P B =51 ,5× ρ× LE ×Q

1, 82

×D

−4, 82

PA: Presión absoluta en el inicio del tramo (bar) PB: Presión absoluta en el final del tramo (bar)

r : densidad relativa del gas Q: Caudal (m3/h) LE: Longitud equivalente (m), (Longitud real x 1,2) D: Diámetro interior de la tubería (mm)

- Fórmula de Renuard simplificada válida para presión inferior a 0,5 bar

P A −P B =232. 000×ρ×LE ×Q

1, 82

×D

PA: Presión absoluta en el inicio del tramo (mm c.d.a.) PB: Presión absoluta en el final del tramo (mm c.d.a.)

r: densidad relativa del gas Q: Caudal (m3/h) LE: Longitud equivalente (m), (Longitud real x 1,2) D: Diámetro interior de la tubería (mm)

−4, 82

S DE GAS

VELOCIDAD

V =378×

Q×Z P×D 2

V: Velocidad del gas (m/s) Q: Caudal (m3/h) Z: Factor de compresibilidad (Z=1 para presiones absolutas inferiores a 5 bar) P: Presión absoluta en el final del tramo (bar) D: Diámetro interior de la tubería (mm)