Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

location: West Eugene design conditions: DB

89 F

MDR

31 F

program: 16 person office space 4700 SF passively heated

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

zoning

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

North Elevation

South Elevation Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

total area of thermal mass : 5900 SF

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

original diagrams of cooling strategy

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

original diagrams of cooling strategy

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

original diagrams of cooling strategy

cool breezes from the north

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

psychrometric chart

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

band of sun analysis

winter

summer

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

heat gain - lighting

Zone A

0.5 BTU/hSF

Zone B

5.1

Zone C

5.1

Zone D

0.5

Zone E

5.1

Zone F

5.1

D

A

F

E

C

B

daylighting zones

heat gain weighted average subtotal : 2.6 BTU/hSF

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

heat gain - people + equipment

office equipment

1.1 BTU/hSF

16 people

2.3 BTU/hSF

heat gain subtotal : 3.4 BTU/hSF

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

heat gain - envelope

externally shaded windows

4.2 BTU/hSF

opaque walls roof

(cmu, straw bale)

0.2 BTU/hSF

(wood framed)

1.0 BTU/hSF

heat gain subtotal : 5.4 BTU/hSF

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

heat gain - ventilation

ventilation for 16 people at 17 cfm/person

heat gain subtotal : 0.92 BTU/hSF

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

heat gain - ventilation or infiltration

total heat gain for thermally “open” building

12.3 BTU/hSF

total heat gain for thermally “closed” building

11.4 BTU/hSF

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

rule of thumb - cross ventilation

window inlet area 124 SF

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

rule of thumb - cross ventilation

inlet area

3%

wind velocity

7.7 mph

cross ventilation capacity = 30 BTU/hSF

open building heat gain = 12.1 BTU/hSF

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

rule of thumb - stack ventilation

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

rule of thumb - stack ventilation

stack height

28’

stack area (throat)

100 SF

floor area

4756 SF

stack ventilation capacity = 8 BTU/hSF

open building heat gain = 12.1 BTU/hSF

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

detailed calculations - stack ventilation

stack height

28’-9’=19’

stack area (throat)

100 SF

T in

80 F

T out

68 F

Conclusion: Stack vent works at T out < 77 F

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

rule of thumb - cool tower

DB of 89 F MCB of 66 F exit air temp = 71 F average exit airflow = 1500 cfm

cool tower capacity = 18,000 BTU/h open building heat gain = 57,600 BTU/h

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

rule of thumb - night flush

mass area

5900 SF

floor area

4756 SF

DB

89 F

MDR

31 F

storage capacity = 100 BTU/d SF heat gain for “closed” building: 9 hours occupied @ 12.3 BTU/d SF 15 hours unoccupied @ 1.2 BTU/d SF total heat gain @ 129 BTU/d SF Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

detailed calculations - night flush line A - mass surface area

5900 SF

line B - mass heat capacity

66,400 BTU/F

line C - floor area

4756 SF

line D - total mass cooling

795,700 BTU

line E - final mass temperature

70 F

line F - n/a

-----------

line G - total cooling

795,700 BTU

line H - total heat gain

635,200 BTU

line I - air flow required for flush

6 ACH

Total cooling capacity exceeds total heat gain - NIGHT FLUSH WORKS Night flush of thermal mass works from 9 pm till 9 am

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon

conclusion

for outside temperatures below 77 F use stack ventilation when outside temperatures exceed 77 F employ night flush

Passive Cooling - Redesign of the West Eugene Wetlands Resident Staff Building - Tracy Bacon