## apcupsd.conf v1.1 ## # # for apcupsd release 3.14.2 (15 September 2007) - debian # # "apcupsd" POSIX config file # # ========= General configuration parameters ============ # # UPSNAME xxx # Use this to give your UPS a name in log files and such. This # is particulary useful if you have multiple UPSes. This does not # set the EEPROM. It should be 8 characters or less. #UPSNAME # UPSCABLE # Defines the type of cable connecting the UPS to your computer. # # Possible generic choices for are: # simple, smart, ether, usb # # Or a specific cable model number may be used: # 940-0119A, 940-0127A, 940-0128A, 940-0020B, # 940-0020C, 940-0023A, 940-0024B, 940-0024C, # 940-1524C, 940-0024G, 940-0095A, 940-0095B, # 940-0095C, M-04-02-2000 # UPSCABLE usb # # # # # # # # # # # # # # # # # # # # # # # # # # # #

To get apcupsd to work, in addition to defining the cable above, you must also define a UPSTYPE, which corresponds to the type of UPS you have (see the Description for more details). You must also specify a DEVICE, sometimes referred to as a port. For USB UPSes, please leave the DEVICE directive blank. For other UPS types, you must specify an appropriate port or address. UPSTYPE apcsmart

DEVICE /dev/tty**

Description Newer serial character device, appropriate for SmartUPS models using a serial cable (not USB).

usb



Most new UPSes are USB. A blank DEVICE setting enables autodetection, which is the best choice for most installations.

net

hostname:port

Network link to a master apcupsd through apcupsd's Network Information Server. This is used if you don't have a UPS directly connected to your computer.

snmp

hostname:port:vendor:community SNMP Network link to an SNMP-enabled UPS device. Vendor is the MIB used by the UPS device: can be "APC", "APC_NOTRAP" or "RFC" where APC is the powernet MIB, "APC_NOTRAP" is powernet with SNMP trap catching disabled, and RFC is the IETF's

# rfc1628 UPS-MIB. You usually want "APC". # Port is usually 161. Community is usually # "private". # # dumb /dev/tty** Old serial character device for use # with simple-signaling UPSes. # # pcnet ipaddr:username:passphrase # PowerChute Network Shutdown protocol # which can be used as an alternative to SNMP # with AP9617 family of smart slot cards. # ipaddr is the IP address of the UPS mgmt # card. username and passphrase are the # credentials for which the card has been # configured. # UPSTYPE usb DEVICE # LOCKFILE <path to lockfile> # Path for device lock file. Not used on Win32. LOCKFILE /var/lock # SCRIPTDIR <path to script directory> # Directory in which apccontrol and event scripts are located. SCRIPTDIR /etc/apcupsd # PWRFAILDIR <path to powerfail directory> # Directory in which to write the powerfail flag file. This file # is created when apcupsd initiates a system shutdown and is # checked in the OS halt scripts to determine if a killpower # (turning off UPS output power) is required. PWRFAILDIR /etc/apcupsd # NOLOGINDIR <path to nologin directory> # Directory in which to write the nologin file. The existence # of this flag file tells the OS to disallow new logins. NOLOGINDIR /etc # # ======== Configuration parameters used during power failures ========== # # The ONBATTERYDELAY is the time in seconds from when a power failure # is detected until we react to it with an onbattery event. # # This means that, apccontrol will be called with the powerout argument # immediately when a power failure is detected. However, the # onbattery argument is passed to apccontrol only after the # ONBATTERYDELAY time. If you don't want to be annoyed by short # powerfailures, make sure that apccontrol powerout does nothing # i.e. comment out the wall. ONBATTERYDELAY 6 # # Note: BATTERYLEVEL, MINUTES, and TIMEOUT work in conjunction, so

# the first that occurs will cause the initation of a shutdown. # # If during a power failure, the remaining battery percentage # (as reported by the UPS) is below or equal to BATTERYLEVEL, # apcupsd will initiate a system shutdown. BATTERYLEVEL 8 # If during a power failure, the remaining runtime in minutes # (as calculated internally by the UPS) is below or equal to MINUTES, # apcupsd, will initiate a system shutdown. MINUTES 5 # If during a power failure, the UPS has run on batteries for TIMEOUT # many seconds or longer, apcupsd will initiate a system shutdown. # A value of 0 disables this timer. # # Note, if you have a Smart UPS, you will most likely want to disable # this timer by setting it to zero. That way, you UPS will continue # on batteries until either the % charge remaing drops to or below BATTERYLEVEL, # or the remaining battery runtime drops to or below MINUTES. Of course, # if you are testing, setting this to 60 causes a quick system shutdown # if you pull the power plug. # If you have an older dumb UPS, you will want to set this to less than # the time you know you can run on batteries. TIMEOUT 0 # Time in seconds between annoying users to signoff prior to # system shutdown. 0 disables. ANNOY 300 # Initial delay after power failure before warning users to get # off the system. ANNOYDELAY 60 # The condition which determines when users are prevented from # logging in during a power failure. # NOLOGON <string> [ disable | timeout | percent | minutes | always ] NOLOGON disable # If KILLDELAY is non-zero, apcupsd will continue running after a # shutdown has been requested, and after the specified time in # seconds attempt to kill the power. This is for use on systems # where apcupsd cannot regain control after a shutdown. # KILLDELAY <seconds> 0 disables KILLDELAY 0 # # ==== Configuration statements for Network Information Server ==== # # NETSERVER [ on | off # information server. # server process will # EVENT data over the NETSERVER on

] on enables, off disables the network If netstatus is on, a network information be started for serving the STATUS and network (used by CGI programs).

# NISIP <dotted notation ip address> # IP address on which NIS server will listen for incoming connections. # This is useful if your server is multi-homed (has more than one # network interface and IP address). Default value is 0.0.0.0 which # means any incoming request will be serviced. Alternatively, you can # configure this setting to any specific IP address of your server and # NIS will listen for connections only on that interface. Use the # loopback address (127.0.0.1) to accept connections only from the # local machine. NISIP 127.0.0.1 # NISPORT <port> default is 3551 as registered with the IANA # port to use for sending STATUS and EVENTS data over the network. # It is not used unless NETSERVER is on. If you change this port, # you will need to change the corresponding value in the cgi directory # and rebuild the cgi programs. NISPORT 3551 # If you want the last few EVENTS to be available over the network # by the network information server, you must define an EVENTSFILE. EVENTSFILE /var/log/apcupsd.events # EVENTSFILEMAX # By default, the size of the EVENTSFILE will be not be allowed to exceed # 10 kilobytes. When the file grows beyond this limit, older EVENTS will # be removed from the beginning of the file (first in first out). The # parameter EVENTSFILEMAX can be set to a different kilobyte value, or set # to zero to allow the EVENTSFILE to grow without limit. EVENTSFILEMAX 10 # # ========== Configuration statements used if sharing ============= # a UPS with more than one machine # NETTIME # Interval (in seconds) at which the NIS client polls the server. # Used only when this apcupsd is a network client (UPSTYPE net). #NETTIME 60 # # Remaining items are for ShareUPS (APC expansion card) ONLY # # UPSCLASS [ standalone | shareslave | sharemaster ] # Normally standalone unless you share an UPS using an APC ShareUPS # card. UPSCLASS standalone # UPSMODE [ disable | share ] # Normally disable unless you share an UPS using an APC ShareUPS card. UPSMODE disable # # ===== Configuration statements to control apcupsd system logging ======== # # Time interval in seconds between writing the STATUS file; 0 disables STATTIME 0

# Location of STATUS file (written to only if STATTIME is non-zero) STATFILE /var/log/apcupsd.status # LOGSTATS [ on | off ] on enables, off disables # Note! This generates a lot of output, so if # you turn this on, be sure that the # file defined in syslog.conf for LOG_NOTICE is a named pipe. # You probably do not want this on. LOGSTATS off # Time interval in seconds between writing the DATA records to # the log file. 0 disables. DATATIME 0 # FACILITY defines the logging facility (class) for logging to syslog. # If not specified, it defaults to "daemon". This is useful # if you want to separate the data logged by apcupsd from other # programs. #FACILITY DAEMON # # ========== Configuration statements used in updating the UPS EPROM ========= # # # These statements are used only by apctest when choosing "Set EEPROM with conf # file values" from the EEPROM menu. THESE STATEMENTS HAVE NO EFFECT ON APCUPSD. # # UPS name, max 8 characters #UPSNAME UPS_IDEN # Battery date - 8 characters #BATTDATE mm/dd/yy # Sensitivity to line voltage quality (H cause faster transfer to batteries) # SENSITIVITY H M L (default = H) #SENSITIVITY H # UPS delay after power return (seconds) # WAKEUP 000 060 180 300 (default = 0) #WAKEUP 60 # UPS Grace period after request to power off (seconds) # SLEEP 020 180 300 600 (default = 20) #SLEEP 180 # Low line voltage causing transfer to batteries # The permitted values depend on your model as defined by last letter # of FIRMWARE or APCMODEL. Some representative values are: # D 106 103 100 097 # M 177 172 168 182 # A 092 090 088 086 # I 208 204 200 196 (default = 0 => not valid) #LOTRANSFER 208 # High line voltage causing transfer to batteries

# The permitted values depend on your model as defined by last letter # of FIRMWARE or APCMODEL. Some representative values are: # D 127 130 133 136 # M 229 234 239 224 # A 108 110 112 114 # I 253 257 261 265 (default = 0 => not valid) #HITRANSFER 253 # Battery charge needed to restore power # RETURNCHARGE 00 15 50 90 (default = 15) #RETURNCHARGE 15 # Alarm delay # 0 = zero delay after pwr fail, T = power fail + 30 sec, L = low battery, N = never # BEEPSTATE 0 T L N (default = 0) #BEEPSTATE T # Low battery warning delay in minutes # LOWBATT 02 05 07 10 (default = 02) #LOWBATT 2 # UPS Output voltage when running on batteries # The permitted values depend on your model as defined by last letter # of FIRMWARE or APCMODEL. Some representative values are: # D 115 # M 208 # A 100 # I 230 240 220 225 (default = 0 => not valid) #OUTPUTVOLTS 230 # Self test interval in hours 336=2 weeks, 168=1 week, ON=at power on # SELFTEST 336 168 ON OFF (default = 336) #SELFTEST 336