Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0900
APPLICATION NOTE
Metasys Integrator AFP-200 Fire Panel Application Notifier
Introduction
Page
*3
•
Application Details
*3
•
Component Requirements
*5
•
Vendor Contact Information
*6
•
Design Considerations
*6
Cable Connections
9
•
Cable Pinouts
*9
•
Connecting the Cable
*9
Metasys Integrator Setup
*11
Point Mapping Tables
13
•
Detector Points
*13
•
Module Points
*13
•
Bell/System Trouble Points
*14
Metasys Network Setup
*17
•
*17
Mapping to a CS Object
Custom Integration
*19
*Indicates those sections where changes have occurred since the last printing.
© 2000 Johnson Controls, Inc. Code No. LIT-6295402
1 www.johnsoncontrols.com
2
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Introduction This document explains the Metasys Integrator Notifier AFP-200 Fire Alarm Panel application. Use this document with the Metasys Integrator technical bulletins that provide information on installing and commissioning the Metasys Integrator unit. For information on the AFP-200 Fire Panel, see the Notifier documentation. Please note that this application will also work with the Johnson Controls IFC-200 Fire Panel. Note: If you are using a Universal Packaging Module (UPM), you must install the Metasys Integrator 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note. Application Details
The Metasys Integrator unit allows the Notifier AFP-200 Fire Alarm Panel to communicate with the Metasys and Metasys Companion Networks. Once a Notifier AFP-200 Fire Panel is connected to a Metasys or Companion Network via the Metasys Integrator unit, its data is available to the full complement of Metasys Building Automation System (BAS) features, including Change-of-State (COS) monitoring, secondary reporting, alarm and trouble notification, trend, and totalization. Each Metasys Integrator vendor port can connect to one AFP-200 Fire Panel. The AFP-200 Fire Panel has a single Signaling Line Circuit (SLC) that supports up to 99 detectors and 99 modules, plus four Notification Appliance Circuits (NACs) designated “Bell Circuits” on the panel. When the AFP-200 Fire Panel is reset, all Binary Input (BI) points are reset to an open or 0 value and any trouble status is cleared.
!
CAUTION: The Metasys Integrator unit is not Underwriters Laboratories (UL) 864 Listed as a fire alarm control unit. It is designed to provide only secondary ancillary monitoring, while the AFP-200 Fire Control Panel provides UL 864 Listed notification and control functions.
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
3
N1LAN
Standard NCU RS-232
AFP-200 Fire Panel
Metasys Integrator
UNT
afp1
Note:
If you are using a UPM, you must install the Metasys Integrator 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note.
Figure 1: AFP-200 Fire Panel and Metasys Integration Panel Unit
Workstation
RS-232 (50 ft maximum)
AFP-200 Fire Panel
Metasys Integrator
UNT N2 Bus Note: A PC version and converter may be substituted for the Panel unit. afp200comp
Note: If you are using a UPM, you must install the Metasys Integrator 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note.
Figure 2: AFP-200 Fire Panel and Metasys Companion Integration 4
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Component Requirements
To integrate the AFP-200 Fire Panel, you need the following: •
properly installed AFP-200 Fire Panel with firmware Version 2.4
•
RS-232 cable (for connecting the AFP-200 Fire Panel’s RS-232 port to the Metasys Integrator unit)
•
Metasys Integrator unit
•
B&B Optical Isolator, Model RS232 OP4
•
N2 Bus (for connecting the Metasys Integrator unit to the Metasys Network Control Module [NCM] or Companion Network)
•
portable Personal Computer (PC) for downloading vendor communication tables (.VCT files) and network setup information into the Metasys Integrator unit, and for running diagnostics
•
cable for connecting the portable PC to the Metasys Integrator unit
•
cables for connecting AFP-200 Fire Panel to the Metasys Integrator unit (see pin requirements in the Cable Connections section of this document)
•
standard duplex 120 VAC outlet, required within one foot of the B&B Optical Isolator, Model RS232 OP4 to power this device. This device has two plug-in power supply transformers.
This document describes the RS-232 cable and vendor communication tables. Notifier documentation describes their equipment. The remaining components are described in the Metasys Integrator technical bulletins. Metasys Release Requirements
Metasys Companion Release Requirements
To integrate the AFP-200 panel into the Metasys Network, you need: •
Metasys Operator Workstation (OWS) software Release 7.0 or higher
•
Metasys Integrator software/firmware Release 9.0 or higher
To integrate the AFP-200 panel into the Metasys Companion Network, you need: •
Metasys Companion Release 6.0 or higher
•
Metasys Integrator software/firmware Release 9.0 or higher
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
5
Vendor Component Requirements
Integration between the Metasys Integrator unit and Notifier AFP-200 Fire Panel application has been tested with Notifier AFP-200 Firmware Release Version 2.4 and B&B Optical Isolator Model RD232 OP4. B&B Optical Isolator Model RS232 OP4 is required between AFP-200 panel RS-232 port and Metasys Integrator vendor port to eliminate the ground fault. Changes to this equipment or integration of either Notifier or B&B products not discussed in this document require additional software development and testing by Johnson Controls Systems Products. For information on integrating other products, refer to the Custom Integration section of this application note.
Vendor Contact Information
Notifier One Fire-Lite Place Northford, CT 06472 Phone: FAX:
(203) 484-7161 (203) 484-7118
B&B Electronics Company 707 Dayton Road P. O. Box 1040 Ottawa, IL 61350 Phone: FAX: Design Considerations
6
(815) 433-5100 (815) 434-7094
When integrating the AFP-200 Fire Panel, consider the following: •
Make sure that the AFP-200 Fire Panel is set up and running properly with Version 2.4 firmware before integrating with a Metasys or Companion system. This includes configuring the AFP-200 Fire Panel’s RS-232 printer port in remote terminal mode. (The Notifier representative is responsible for the configuration and operation of Notifier equipment.)
•
The Metasys Integrator unit is not UL 864 Listed as a fire alarm control unit. It is designed to provide secondary ancillary monitoring only, while the AFP-200 Fire Panel provides notification and control functions.
•
When the AFP-200 Fire Panel is reset, all BI points are set to open state and the trouble status is reset.
•
The AFP-200 Fire Panel must be reset to clear alarms.
•
RS-232 cable distance between the Metasys Integrator unit and the AFP-200 Fire Panel cannot exceed 50 feet.
•
The trouble status is cleared when a device reports a normal or off state.
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
•
Programming at the AFP-200 Fire Panel will cause the Notifier AFP-200 Fire Panel to go offline. Also, continuous pressing of the panel keys (e.g., Ack/Step) may cause the AFP-200 Fire Panel to go offline at the Metasys Integrator unit.
•
The AFP-200 Fire Panel, when used alone without the Metasys Integrator unit, has a feature that scrolls through trouble messages when multiple messages exist on the system. This feature is not present when the Metasys Integrator unit is connected to the AFP-200 Fire Panel. If multiple messages exist on the system, the Ack/Step key must be pressed to view each individual message.
!
WARNING:
Some change-of-state messages may be missed while running the Diagnostic Analyzer on the Metasys Integrator commissioning PC. Do not run the Metasys Integrator Diagnostic Analyzer after commissioning is complete. Disconnect the Metasys Integrator unit from the AFP-200 printer port while programming the Fire Panel, then reset the AFP-200 panel after reconnecting the Metasys Integrator unit.
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
7
8
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Cable Connections Cable Pinouts
Use the following cable pinouts for the RS-232 connection between the Metasys Integrator unit and the AFP-200 Fire Panel. You must connect the male end of the converter to the Metasys Integrator unit. 12 VDC/ 120 VAC
Vendor Port A or B of Metasys Integrator
Duplex Outlet RS-232 Printer Port on APF-200 (TB4)
DB-9 Female Signal
Pin
RD TD GND
2 3 5
Male (25 Pin) 3 2 7
Female (25 Pin) TX RX RF
Optical Isolator 3 2 Model 2320 P4 7
(50 ft maximum)
afp3
Figure 3: Cable Pinouts Connecting the Cable
Connect the female end of RS-232 cable to either Vendor Port A or Vendor Port B on the Metasys Integrator unit. Connect the other open end (no connector) of the cable to terminal TB4 of the panel as specified in AFP-200 Fire Panel installation documentation.
AFP-200 Fire Panel
Metasys Integrator
Vendor Port A or B
Optical Isolator
RS-232 Printer Terminal Port TBA (EIA-232)
afp4
Figure 4: Port-to-Port Connection
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
9
10
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Metasys Integrator Setup To set up the Metasys Integrator unit, use a portable PC connected to Metasys Integrator Terminal Port. Metasys Integrator setup involves: •
downloading the correct vendor communication tab (.VCT files)
•
setting up the ports
•
setting up the network addressing
The following table provides information specific to the AFP-200 Fire Panel application. For detailed procedures, see the Metasys Integrator technical bulletins. Table 1: Metasys Integrator Setup for AFP-200 Fire Panel Vendor Communication Table (.VCT File) Detector Points
IFC2_DET.VCT
Module Points
IFC2_MOD.VCT
Bell (NAC) and System Trouble Points
IFC2_BEL.VCT
Port Setup Baud Rate
2400
Word Length
7
Stop Bit
1
Parity
Even
Interface
RS-232
Network Setup Vendor Address Detectors Modules Bell (NAC) and System Trouble Points
B*
Timeout Value
3000 ms
Poll Delay
0 ms
Retries
5
Approximate Scan Time (for an N2 address) Detectors Modules Bell (NAC) and System Trouble Points
60 seconds 60 seconds
Time to Receive Alarm/Trouble (after the message generated at the panel) *
D* M*
10 seconds 2 seconds
Be sure to use uppercase characters.
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
11
12
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Point Mapping Tables The following tables show the points available for mapping on the AFP-200 Fire Panel: Detector Points
BI points for each sensor have corresponding Binary Data (BD) points, which are used to map the pre-alarm status of the sensor. These BI points also indicate the trouble status of the detector. Table 2: Detector Points NPT1
NPA2
Description
BI
1-99
Detector SLC Address-LPA
0-Normal, 1-Alarm
BD
1-99
Pre-alarm status of detector at LPA
0-Normal, 1-Alarm
1 2
Value Mapped
Network Point Type Network Point Address
When any detector point goes in or out of trouble, its value remains as it was before the trouble occurred. Module Points
BI points also indicate the trouble status. These BI points also indicate the trouble status of the module. Table 3: Module Points NPT1
NPA2
Description
Value Mapped
BI
1-99
Module SLC Address-LPA
0-Normal, 1-Alarm (Monitor Modules) 0-Off, 1-On (Control Modules)
1 2
Network Point Type Network Point Address
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
13
Bell/System Trouble Points
When any system trouble occurs, you must reset the IFC-200 Fire Panel manually after clearing the trouble. Table 4 is a list of all the bell circuits and system trouble status points. Table 4: Bell/System Trouble Points NPT1
NPA2
Description
Value Mapped
BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Bell Circuit 1 Bell Circuit 2 Bell Circuit 3 Bell Circuit 4 Ground Fault AC Fail Battery Style 6 Option Module Term. Supervisory Annunciator 1 No Answer Annunciator 1 Trouble Annunciator 2 No Answer Annunciator 2 Trouble EPROM Error Internal RAM Error External RAM Error Program Corrupted No Device Installed AVPS. Trouble
0-Off, 0-Off, 0-Off, 0-Off, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal,
1 2
1-On 1-On 1-On 1-On 1-N/A 1-N/A 1-N/A 1-N/A 1-N/A 1-N/A 1-N/A 1-N/A 1-N/A 1-N/A 1-N/A 1-N/A 1-N/A 1-N/A 1-N/A 1-N/A
Network Point Type Network Point Address
Note: All system trouble points remain unreliable once a device goes offline/online, until the panel is reset using the system-reset button. Individual points report online when a trouble status is reported for that point.
14
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Getting Point Summary Information from AFP-200 Fire Panel to Map Points with the Metasys Network
The commissioning person should have the details of point summary at the time of commissioning. If they are not available, collect the status summary from the panel using the following steps: 1.
Disconnect the Metasys Integrator unit from the AFP-200 Fire Panel.
2.
Connect a serial printer at printer port (the same serial port which is used for Metasys Integrator interface).
3.
Press the Enter key at the panel.
4.
Select 2 - read status.
5.
To print all points, press 1 (print points), then Enter. A summary will be printed for all programmed points with their current status. The last three characters in each line of the message are the actual point SLC address.
(For example: D01 is detector at SLC address 01, which is BI-1 in vendor table file IFC2_DET.VCT. M01 is module at SLC address 01, which is BI-1 in vendor table file IFC2_MOD.VCT. B01 is Bell Circuit 1, which is BI-1 in vendor table file IFC2_BEL.VCT.) See Table 2 for detector points, see Table 3 for module points, and see Table 4 for bell/system trouble points.
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
15
16
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Metasys Network Setup Metasys Network setup is described in the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN 629.5). This section contains details specific to the AFP-200 Fire Panel. We recommend that all points that report an alarm or trouble status be directly mapped to BI objects. Mapping to a CS Object
Table 5: Software Model and CS Object Definition Application
Software Model Display (on Tables and Attributes Models CD-ROM)
NT Command Attributes
(recommended) BI1 Status of Detector 1
BI1 Status of Detector 1
IF2_MLOP.DDL
NI1 Status of Module 1
BI1 Status of Module 1
IF2_SYST.DDL
BI17 Network Fail
BI17 Network Fail
AFP-200 Detector SLC
IF2_DLOP.DDL
AFP-200 Module SLC AFP-200 Bell (NAC) and System Trouble Points
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
17
18
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
Custom Integration For information on integrating products which are not discussed in this document, first refer to the Metasys Compatible Global Catalog, an online list of released Connectivity products. If this list does not provide the information you require, consider using the System Integration Project Data Sheet to request a custom contract from the System Integration Team. Both the Metasys Compatible Global Catalog and the System Integration Project Data Sheet can be accessed from The Advisor by performing the following steps: 1.
Click on the Systems Products button located on the left side of The Advisor home page.
2.
Click on the Product Literature link.
3.
Click on the Manuals-FANS link.
4.
Click on the 629.0 Metasys Connectivity Sales Resource Manual link.
5.
Find the System Integration Project Data Sheet link in the Table of Contents. Click on this link to view an online copy of the System Integration Project Data Sheet, or click on the Metasys Compatible Global Catalog link below it to view a list of released Connectivity products.
The System Integration Project Data Sheet (LIT-6290052) can also be found in the Metasys Connectivity Sales Resource Manual (FAN 629). If you need further assistance, contact the Johnson Controls Field Support Center.
Metasys Integrator—Metasys Integrator Notifier AFP-200 Fire Panel Application
19
Notes
Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201
20
www.johnsoncontrols.com FAN 629.5 Metasys Connectivity Technical Manual Metasys Integrator Release 9.0 Printed in U.S.A.