A Model For Induction Motor Aggregation For Power System Studies

  • May 2020
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View A Model For Induction Motor Aggregation For Power System Studies as PDF for free.

More details

  • Words: 1,943
  • Pages: 4
ELECTAIC

ELSEVIER

Electric

Power Systems Research

~aWEA IWITEml AEIE~ACH

42 (1997) 225-228

A model for induction motor aggregation for power system studies P. Pillay a

a,*,

S.M.A. Sabur

b,

M.M. Haq

b

Department of Electrical and Computer Engineering, Clarkson University, Box 5720, Potsdam, NY 13699-5720, USA b Department

of Electrical Engineering,

University

Received

of New Orleans, New Orleans, LA 70148, USA

8 November

1996

Abstract

This paper proposes a new model for aggregating a group of induction motors for system studies. The aggregation method developed here is based on the transformer-type variation of the equivalent circuit. A grouping criteria is used to classify homogeneous motors into different groups. The validity of the proposed method is verified by comparing the results obtained from the aggregate motor with the sum of the individual motors. @ 1997 Elsevier Science S.A. Keywords: Induction

motors;

Aggregation

methods

1. Introduction The simulation of a large group of induction motors for system studies can be time consuming. In order to reduce the computation time, reduced order modelling is used to represent a group of motors with one or more aggregate motors. The accuracy of the results obtained from the aggregate motors depends in part on the assumptions made in the derivation of the aggregate motor and varies from method to method. This subject of the aggregation of induction machines for system studies has received a fair amount of attention in the literature [1-6]. In [1], to develop an aggregation model the approximate equivalent circuit is used with stator resistance being neglected. In the derivation of the model, the basic assumption is of power invariance between the aggregate motor and the sum of the individual motors. Since the skin-effect has a strong influence on the performance of induction motors, in [2] the equivalent circuit is represented by seven electrical parameters instead of five. In [3], the motor parameters are calculated from standard specifications which, together with network and load data, are incorporated into an admittance matrix. The inertia and running slip are chosen to minimize the error between the transient response of * Corresponding author. Tel.: + I 315 2686509; fax: + I 315 2687600. 0378-7796/97/$17.00 ~ 1997 Elsevier PII 80378-7796(96)01211-4

Science S.A. All rights reserved.

the system and its equivalent. In [4], the unknown parameters of the equivalent motor are estimated through a weighted-least squares procedure. In [5], Thevenins theorem along with selected characteristics of the induction machine are used in the calculation of the parameters of the equivalent machine. In [6], a fictitious impedance is introduced to convert the simple equivalent circuit into a circuit with parallel elements only. In this paper, a transformer-type equivalent circuit [7] is used to represent an induction motor. Five motors are used in the current work to obtain the aggregate motor. Results from the aggregate motor are compared with that obtained from the sum of the individual motors.

2. Development of the transformer-type equivalent circuit model for the induction motor Usually induction motors are represented by the conventional equivalent circuit model in Fig. 1. But in this paper, an alternative type of equivalent circuit, called the transformer-type equivalent circuit, is used as shown in Fig. 2. The two circuits are equivalent to each other. The parameters of the two circuits are related in the followmg way: Zo = Z, + Zm

(2.1)

226

P. Pillay et al. / Electric Power Systems Research 42 (1997) 225-228

nZm K-- (Zl +Zm)

(2.2)

Sn2ZIZm Z3

(2.3)

= (Zl + Zm)

z: (2.4)

Zs = Z2 + Z3

In this paper, s stands for slip of the motor and n is chosen as 1, assuming the rotor parameters of the conventional equivalent circuit model are already referred to the primary. Since K is the ratio of Zm and (ZI + Zm) and Zm» Z1> K is close to unity and LK is close to 0°.

Fig. 3. Multimachine connected to the same bus.

z;gg

Kogg ~Ogg

zo:g

3. Development of aggregation model Consider the aggregation of N induction motors connected to the same bus as shown in Fig. 3. It is assumed that all N motors are represented by the transformertype equivalent circuit model. Since all N motors are connected in parallel, they can be shown as in Fig. 3. As a result, the aggregate motor model and parameters can be obtained as follows (Fig. 4): I zagg -0 -

N

Li

(3.1)

I

Fig. 4. The aggregate induction motor.

fore, in this paper, the values of K and LK were chosen as 0.98 and 0° for the aggregate motor. In this paper, mechanical output power of the aggregate motor is assumed to be equal to the total mechanical output power delivered by the individual motors. Therefore N

i~1 Zo

zagg =S N

Hpagg

1

(3.2)

I

i~l Zs

The values of K and LK were tested for different sizes of motors and it was found that their values range from 0.96 to 0.985 and around 2° respectively. There'I

'2

~

R2

(3.3)

I

agg agg COr -COs -S

VI]

agg COs

= Z2 +

-+

(3.5)

Fig. 1. Conventional

equivalent-circuit

R2 . Z2 =-+JX2 S

SPg

Zs

12

ZJ

Z2 r

K

Fig. 2. Alternative

r

Vs=sKVI

equivalent-circuit

' ' ' , ,

_SPg

model.

Z2 is considered

as (3.6)

Then, using (3.5), Zs is calculated for all the individual machines and z~gg is calculated using (3.2). Again z~gg is calculated using (3.2). Again z~gg is the sum of z~gg and z~gg. Therefore, equating the real parts from the relationship between z~gg and Z2gg and z~gg, the following equation is found:

model.

~ KI2

(3.4)

Z3

For the following calculation

{<

Zo

agg

where co~ggis the synchronous speed of the aggregate motor. It is known from the relationship between the parameters of the transformer-type equivalent circuit and those from the conventional type of equivalent circuit that Zs

r

L (HPY

i~

The rotor speed of the aggregate motor was found to be

Li

I[

=

r

R agg V2

~+SaggK1R= sagg

K 2R

(3.7)

where KIR and K2R are the real parts of z~gg and z~gg respectively. Rearranging (3.7), the solution of sagg is obtained as follows

--

227

P. Pillay et al. / Electric Power Systems Research 42 (1997) 225-228 Table 1 Parameters for five individual and one aggregate motors

3000 2660

HP

Rs 4.86 1.48 0.73 0.42 0.25 0.12

3.0 15.0 30.0 50.0 100.0 198.0

R,

XIs

1.84 0.31 0.16 0.14 0.08 0.035

2.67 0.18 0.16 0.15 0.10 0.043

Xh 2.67 0.18 0.16 0.15 0.10 0.041

J

Xm 84.68 24.89 14.96 9.47 3.97 2.10

2320

rpm

0.09 0.50 1.00 1.66 2.7 5.96

:>

1760.0 1765.0 1765.0 1750.0 1740.0 1749.0

~

1980 1640

.~ 1300

?

960

>-

620

0

280 -60 -400 0.00

sagg

= K2R I J(K2R)2 - 4K1RR2gg

= i~I 1 Ji

Jagg

1.2B 1.60 1.92 Time in Sec

2.24

2.56

2.BB 3.20

3000 2320 :>

( )

19BO

~ 1640

2

OJ i

0.96

2660

Here R2ggis unknown and obtained from the difference between z~gg and Z3gg calculated without considering slip. Considering the conservation of kinetic energy, the following relation is used: N

0.64

Fig. 7. Electromagnetic torque of the aggregate motor.

(3.8)

2KlR

0.32

.~ ~

1300

2' 0 t-

960 620

280

(3.9)

OJa;g r

-60 -400 0.00

In this paper, five different sizes of motors are considered. Conventional equivalent circuit parameters of

0.32

0.64

0.96

1.2B 1.60 1.92 Time in Sec

2.24

2.56

2.88

3.20

Fig. 8. Summation of electromagnetic torque of the individual motors.

2500 2000

all the five motors as well as the aggregate motor obtained are given in the Table 1.

1500 Q. 1000

~

500

c '"

0



4. Grouping criterion

~ :J -500 u -1000 -1500 -2000 -2500 0.00

0.32

0.64

0.96

1.28 1.60 1.92 Time in see

2.24

2.56

2.88

3.20

Fig. 5. Stator phase A current of the aggregate motor.

The purpose of a grouping criterion is to identify and group homogeneous motors. The inertia and open circuit time constant are often used to classify motors. In [2], the authors have developed a grouping criterion that may be expressed as (4.1)

G=HylY. where

2500 2000

(Xl + X2)

1500 c.

~

500



c'" ~

u"

(4.2)

y= (R( +R2)

1000

Xm IY.=R2

0 -500

(4.3)

-1000

The

-1500 - 2000

is homogeneous

I ~ (Gmax/Gmin) ~ 2.5

-2500 0.00

group

0.32

0.64

0.96

1.28 1.60 1.92 Time in Sec

2.24

2.56

2.88

if

(4.4)

3.20

Fig. 6. Summation of stator phase A currents of the individual motors.

Based on the above grouping criterion, the disparate sizes of motors are classified into different groups. Then aggregation is done for different motor groups separately to find aggregate motors from each group.

228

P. Pillay et al. / Electric Power Systems Research 42 (1997) 225-228

5. Results In this section, results have been presented for the aggregate motor as well as the sum of the individual motors to compare the performance of the aggregate motor obtained. Table 1 presents the necessary electrical and mechanical parameters for five individual and one aggregate motor. Here, all the individual and aggregate motors are connected to a 460 V bus and the number of poles of each motor is 4. In the simulation, the motors are first started from standstill to steady-state. Then the source is disconnected from the motors for 134 ms (8 cycles) and reclosed. The action of the circuit breaker in practice is represented by increasing the source resistance from its original value to the value of 500 Q. This change of resistance is carried out at the zero level of each phase current to simulate the extinguishing of the current at a current zero. Fig. 5 shows the stator phase A current of the aggregate motor while Fig. 6 shows the sum of the stator phase A currents of the individual motors. Again, Fig. 7 shows the electromagnetic torque of the aggregate motor while Fig. 8 shows the sum of the electromagnetic torques of the individual motors. A comparison between the two sets of curves shows satisfactory correlation.

6. Conclusions In this paper, a new model has been developed to aggregate induction motors. To develop this model, a transformer-type equivalent circuit of the induction mo-

tor is used. A grouping criterion is used to classify different motors into different groups for better results. The results using the aggregate motor are compared to that obtained from the sum of the individual motors. The results are acceptable.

Acknowledgements

The Authors acknowledge EPRI and Entergy Corporation for funding this work. References [I] M.M. Abdel Hakim and G.J. Berg, Dynamic single-unit representation of induction motor groups, IEEE Trans. Power Appar. Syst., PAS-95 (I) (Jan.jFeb. 1976). [2] M. Akbaba and S.Q. Fakhro, New Model for single-unit representation of induction motor loads, including skin effect, for power system transient stability studies, lEE Proc.-B, 139 (6) (Nov. 1992). [3] G.J. Rogers, J. Di Manno and R.T.H. Alden, An aggregate induction motor model for industrial plants, IEEE Trans. Power Appar. Syst., PAS-103 (4) (April 1984). [4] A.H.M.A. Rahim and A.R. Laldin, Aggregation of induction motor loads for transient stability studies, IEEE Trans. Energy Conv., EC-2 (1) (March 1987). [5] M. Taleb, M. Akbaba and E.A. Abdullah, Aggregation of induction machines for power system dynamic studies, IEEEj PES 1994 Winter Meet., New York, New York, Jan. 30-Feb. 3, 1994. [6] D.C. Franklin and A. Morelato, Improving dynamic aggregation of induction motor models, IEEEjPES 1994 Winter Meet., New York, New York, Jan. 30-Feb. 3, 1994. [7] Pragasen Pillay and Larbi Refoufi, Calculation of slip energy recovery induction motor drive behaviour using the equivalent circuit, IEEE Trans. Ind. Appl., 30 (1) (Jan.jFeb. 1994).

Related Documents